Record Plus Thermal Magnetic Trip Units FE frame Trip Units The breakers are availble as a complete entity or in kit form where a Breaker Frame and an interchangaeble trip unit are the basic components. The interchangeability feature covers the electromechanical trip units described here and the electronic devices described on page B12. Each Trip Unit is equipped with an Interchange Interlock that prevents the inadvertent use of a trip unit designed for the FE250 model in an FE160 or vice versa. The standard Electromechanical Trip Units are equipped with a GE patented fault type indicator. The device has Intro A The following versions are available: LTM (line thermal magnetic protection) (FE...TA sub type) A trip unit designed for the protection of generic loads, the device is available as 3 and 4p model for the FE160 and FE 250 frame sizes. This sub type has an adjustable thermal and magnetic setting. The thermal setting range is 0.8 to 1 x In and the magnetic relay is adjustable from 5-10 x In. (Fixed at 8 x In for Ratings < 80A). LTMD (Selective thermal magnetic protection) (FE...TD sub type) A trip unit designed for the selective protection of generic loads, it is available as 3 and 4p model for the FE160 and FE250 N, H & L breaker types. Making full use of the FE frames unique propeties this device offers both full and enhanced selectivity with downstream devices as the Record Plus FD160, the ElfaPlus, Red Line MCB's and the Surion Motor Starter. This sub type has an adjustable thermal and magnetic setting. The thermal setting range is 0.8 to 1 x In and the magnetic relay is adjustable from 5-10 x In. B C D GTM (generator thermal magnetic) (FE...TG sub type) Suitable for the protection of generator circuits and or long cable runs, the device is available as 3 and 4p model for the Standard (FE160N & FE250N) and Hi-Break (FE160H & FE250H) breaker types. This sub type has an adjustable thermal and magnetic setting. The thermal setting range is 0.8 to 1 x In and the magnetic relay is adjustable from 3-5 x In. E F G Mag Break™ (magnetic only) (FE...MO sub type) A trip unit designed to offer short circuit protection for, use in motor protection circuits in coordination with a contactor and thermal overload relay in accordance with the EN 60 947-4 standard. The device is available as 3 and 4p model for the FE160 & FE250 N, H & L breaker types This sub type has NO thermal protection and an magnetic relay that is adjustable from 10 to 15 x In. X Y (non automatic - switch disconnector) A 'dummy 'trip unit available in a 160A and 250A variant. Has no protection elements. Designed as switch disconnector. B.6 two indicator flags, one indicating an overload event (coloured brown) and a second, coured blue, indicating a short circuit or an event triggered by an RCD . (If the indicated protection devices are present). Thermal protection devices are normally calibrated at an ambient temperature of 40 degrees centigrade. Some executions are also available in a verison calibrated at 55 degrees. The time current curves published here are valid for both executions. Record Plus FE160 and FE250 breakers - trip unit overview (electromechanical) Electro-mechanical trip unit overview TA N H L FE160 FE250 V FE160 LTMD TD N H L FE160 GTM TG N H L FE250 FE160 Mag. Break™ MO N H L FE250 Y Y FE160 FE250 25 32 40 50 63 80 100 125 160 125 160 200 250 100 125 160 125 160 200 250 100 125 160 125 160 200 250 3.5 7 12.5 20 30 50 80 100 125 160 160 200 250 160 250 adjustable 0.8÷1xIn adjustable 0.8÷1xIn adjustable 0.8÷1xIn adjustable 0.8÷1xIn adjustable 0.8÷1xIn adjustable 0.8÷1xIn 20 26 32 40 50 64 80 100 128 100 128 160 200 80 100 128 100 128 160 200 60 100 128 100 128 160 200 ! 25 32 40 50 63 80 100 125 160 125 160 200 250 100 125 160 125 160 200 250 100 125 160 125 160 200 250 Fixed 8 x In adjustable 5÷10 In adjustable 5÷10 In adjustable 5÷10 In adjustable 3-5 In adjustable 7÷15In No protection 200 256 320 400 504 adjustable 10÷15In 400 500 625 800 625 800 1000 1250 500 625 800 625 800 1000 1250 300 375 480 375 480 600 750 24.5 49 87.5 140 210 500 800 1000 1250 1600 1600 2000 2500 800 1000 1250 1600 1250 1600 2000 2500 1000 1250 1600 1250 1600 2000 2500 400 625 800 625 800 1000 1250 52.5 105 188 300 450 750 1200 1500 1875 2400 2400 3000 3750 4P4T 4P 3.5T =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 =Ir/2 4P3T FE frame FE250 (A) Neutral protection not protected LTM Applicable for breaker types Magnetic Im pick-up band ± 20% Im min (A) max (A) not protected Type Subtype Thermal Ir pick-up band 1.05 ÷ 1.3 Ir min (A) max (A) not protected In Intro A not protected FE frame B No protection C D ! E Depicted is the LTMD type F G X B.7 Record Plus Time Current Curves FE frame Breaker FE160 LTM 40, 50 & 63A Breaker FE160 LTM 25 & 32A 10000 10000 Influence of current limitation on maximum tripping time Influence of current limitation on maximum tripping time 100 Set at 0.8 x In 10 1000 1 10 Millisec (mS) 1000 Millisec (mS) 100 Set at 0.8 x In Ir=40, 50 or 63A 10 1 10 100 Set at 1 x In Ir=32, 40 or 50A 100 10 10 1 1 A 0,01 Seconds (S) 0,1 B LTM type Fixed at 8 x In LTM type Fixed at 8 x In 0,1 0,01 Seconds (S) Trip Units 100 Intro 0,001 0,10 1,00 X Nominal Current In 10,00 100,00 0,001 0,10 1,00 X Nominal Current In Breaker FE160 LTM 80, 100, 125 & 160A C 10,00 10000 Influence of current limitation on maximum tripping time Influence of current limitation on maximum tripping time 100 10 1000 1 10 Set at 0.8 x In Ir=100, 125 or 160A Millisec (mS) Set at 0.8 x In Ir=80, 100, 125 or 160A Millisec (mS) 100 1000 100 100 X Nominal Current In 100 100 F 10 10 G 1 1 LTM type Adjustable 5 - 10 x In 0,1 0,1 0,01 0,01 0,001 0,10 1,00 X Nominal Current In Time current curves are depicted in cold state. Seconds (S) Seconds (S) 1 Set at 1 x In Ir=80, 100 or 128A E B.8 10 10 X Nominal Current In Set at 1 x In Ir=63, 80, 100 or 128A X 100,00 Breaker FE160 GTM 100, 125 & 160A 10000 D 100 X Nominal Current In X Nominal Current In Set at 1 x In Ir=20 or 25A 10,00 100,00 0,001 0,10 1,00 X Nominal Current In GTM type Adjustable 3 - 5 x In 10,00 100,00 Record Plus Time Current Curves Breaker FE250 LTMD 125, 160, 200 & 250A Breaker FE160 LTMD 100, 125 & 160A 10000 10000 Influence of current limitation on maximum tripping time Influence of current limitation on maximum tripping time Set at 0.8 x In Ir=80, 100 or 128A Millisec (mS) 1000 10 1000 1 10 Set at 0.8 x In Ir=100,125,160 or 200A Millisec (mS) 100 100 10 1 10 100 100 X Nominal Current In X Nominal Current In Set at 1 x In Ir=125,160,200 or 250A Set at 1 x In Ir=100, 125 or 160A 100 10 10 1 1 LTMD type Adjustable 5 - 10 x In 0,1 LTMD type Adjustable 5 - 10 x In 0,1 Seconds (S) 0,001 0,10 1,00 X Nominal Current In 10,00 100,00 A 0,001 0,10 1,00 X Nominal Current In Breaker FE250 GTM 125, 160, 200 & 250A 10,00 C 10000 Influence of current limitation on maximum tripping time Influence of current limitation on maximum tripping time 100 10 1000 1 10 Set at 0.8 x In Ir=100,125,160 or 200A 100 Millisec (mS) Set at 0.8 x In Ir=100,125,160 or 200A Millisec (mS) 100 10 D 1 10 X Nominal Current In 100 X Nominal Current In Set at 1 x In Ir=125,160,200 or 250A Set at 1 x In Ir=125,160,200 or 250A 100 100 E 10 10 F 1 1 G 0,1 GTM type Adjustable 3 - 5 x In 0,1 0,001 0,10 1,00 X Nominal Current In LTMD type Adjustable 5 - 10 x In X 0,01 Seconds (S) 0,01 Seconds (S) B 100,00 Breaker FE250 LTM 125, 160, 200 & 250A 10000 1000 Intro 0,01 0,01 Seconds (S) FE frame 100 10,00 100,00 0,001 0,10 1,00 X Nominal Current In 10,00 100,00 Time current curves are depicted in cold state. B.9 Record Plus Time Current Curves FE frame Breaker FE160 Mag Break 8, 12.5, 20, 50, 80, 100, 125 and 160A Breaker FE250 Mag Break 160, 200 & 250A 10000 10000 Influence of current limitation on maximum tripping time Influence of current limitation on maximum tripping time 1000 100 10 Millisec (mS) Millisec (mS) 100 1000 1 10 100 10 1 1 Seconds (S) Mag Breaker type Adjustable 10 - 15 x In 0,001 7.2 10,00 1,00 X Nominal Current In 125A type depicted C D E F G X Time current curves are depicted in cold state. B.10 0,1 Thermal Withstand Line Allowing up to Class 30 protection Mag Breaker type Adjustable 10 - 15 x In 0,01 Seconds (S) Trip Units 10 0,01 B 100 Thermal Withstand Line Allowing up to Class 30 protection A 100 X Nominal Current In (200A type depicted) 100 Intro 1 10 X Nominal Current In (125A type depicted) 0,1 10 100,00 0,001 1,00 7.2 10,00 X Nominal Current In (200A type depicted) 100,00