Record Plus MCCB-Trip units_Curves FE

advertisement
Record Plus
Thermal Magnetic Trip Units
FE frame
Trip Units
The breakers are availble as a complete entity or in kit
form where a Breaker Frame and an interchangaeble trip
unit are the basic components. The interchangeability
feature covers the electromechanical trip units described
here and the electronic devices described on page B12.
Each Trip Unit is equipped with an Interchange Interlock
that prevents the inadvertent use of a trip unit designed
for the FE250 model in an FE160 or vice versa.
The standard Electromechanical Trip Units are equipped
with a GE patented fault type indicator. The device has
Intro
A
The following versions are available:
LTM (line thermal magnetic protection)
(FE...TA sub type)
A trip unit designed for the protection of generic loads, the
device is available as 3 and 4p model for the FE160 and FE
250 frame sizes.
This sub type has an adjustable thermal and magnetic
setting. The thermal setting range is 0.8 to 1 x In and the
magnetic relay is adjustable from 5-10 x In. (Fixed at 8 x In
for Ratings < 80A).
LTMD (Selective thermal magnetic protection)
(FE...TD sub type)
A trip unit designed for the selective protection of generic
loads, it is available as 3 and 4p model for the FE160 and
FE250 N, H & L breaker types.
Making full use of the FE frames unique propeties this
device offers both full and enhanced selectivity with
downstream devices as the Record Plus FD160, the
ElfaPlus, Red Line MCB's and the Surion Motor Starter.
This sub type has an adjustable thermal and magnetic
setting. The thermal setting range is 0.8 to 1 x In and the
magnetic relay is adjustable from 5-10 x In.
B
C
D
GTM (generator thermal magnetic)
(FE...TG sub type)
Suitable for the protection of generator circuits and or long
cable runs, the device is available as 3 and 4p model for
the Standard (FE160N & FE250N) and Hi-Break (FE160H &
FE250H) breaker types.
This sub type has an adjustable thermal and magnetic
setting. The thermal setting range is 0.8 to 1 x In and the
magnetic relay is adjustable from 3-5 x In.
E
F
G
Mag Break™ (magnetic only)
(FE...MO sub type)
A trip unit designed to offer short circuit protection for, use
in motor protection circuits in coordination with a
contactor and thermal overload relay in accordance with
the EN 60 947-4 standard. The device is available as 3 and
4p model for the FE160 & FE250 N, H & L breaker types
This sub type has NO thermal protection and an magnetic
relay that is adjustable from 10 to 15 x In.
X
Y (non automatic - switch disconnector)
A 'dummy 'trip unit available in a 160A and 250A variant.
Has no protection elements.
Designed as switch disconnector.
B.6
two indicator flags, one indicating an overload event
(coloured brown) and a second, coured blue, indicating
a short circuit or an event triggered by an RCD .
(If the indicated protection devices are present).
Thermal protection devices are normally calibrated at an
ambient temperature of 40 degrees centigrade. Some
executions are also available in a verison calibrated at 55
degrees. The time current curves published here are valid
for both executions.
Record Plus
FE160 and FE250 breakers - trip unit overview (electromechanical)
Electro-mechanical trip unit overview
TA
N
H
L
FE160
FE250
V
FE160
LTMD
TD
N
H
L
FE160
GTM
TG
N
H
L
FE250
FE160
Mag.
Break™
MO
N
H
L
FE250
Y
Y
FE160
FE250
25
32
40
50
63
80
100
125
160
125
160
200
250
100
125
160
125
160
200
250
100
125
160
125
160
200
250
3.5
7
12.5
20
30
50
80
100
125
160
160
200
250
160
250
adjustable
0.8÷1xIn
adjustable
0.8÷1xIn
adjustable
0.8÷1xIn
adjustable
0.8÷1xIn
adjustable
0.8÷1xIn
adjustable
0.8÷1xIn
20
26
32
40
50
64
80
100
128
100
128
160
200
80
100
128
100
128
160
200
60
100
128
100
128
160
200
!
25
32
40
50
63
80
100
125
160
125
160
200
250
100
125
160
125
160
200
250
100
125
160
125
160
200
250
Fixed
8 x In
adjustable
5÷10 In
adjustable
5÷10 In
adjustable
5÷10 In
adjustable
3-5 In
adjustable
7÷15In
No protection
200
256
320
400
504
adjustable
10÷15In
400
500
625
800
625
800
1000
1250
500
625
800
625
800
1000
1250
300
375
480
375
480
600
750
24.5
49
87.5
140
210
500
800
1000
1250
1600
1600
2000
2500
800
1000
1250
1600
1250
1600
2000
2500
1000
1250
1600
1250
1600
2000
2500
400
625
800
625
800
1000
1250
52.5
105
188
300
450
750
1200
1500
1875
2400
2400
3000
3750
4P4T
4P 3.5T
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
=Ir/2
4P3T
FE frame
FE250
(A)
Neutral protection
not protected
LTM
Applicable for breaker types
Magnetic Im
pick-up band ± 20% Im
min (A)
max (A)
not protected
Type Subtype
Thermal Ir
pick-up band 1.05 ÷ 1.3 Ir
min (A)
max (A)
not protected
In
Intro
A
not protected
FE frame
B
No protection
C
D
!
E
Depicted is the LTMD type
F
G
X
B.7
Record Plus
Time Current Curves
FE frame
Breaker FE160 LTM 40, 50 & 63A
Breaker FE160 LTM 25 & 32A
10000
10000
Influence of current limitation
on maximum tripping time
Influence of current limitation
on maximum tripping time
100
Set at 0.8 x In
10
1000
1
10
Millisec (mS)
1000
Millisec (mS)
100
Set at 0.8 x In
Ir=40, 50 or 63A
10
1
10
100
Set at 1 x In
Ir=32, 40 or 50A
100
10
10
1
1
A
0,01
Seconds (S)
0,1
B
LTM type
Fixed at
8 x In
LTM type
Fixed at
8 x In
0,1
0,01
Seconds (S)
Trip Units
100
Intro
0,001
0,10
1,00
X Nominal Current In
10,00
100,00
0,001
0,10
1,00
X Nominal Current In
Breaker FE160 LTM 80, 100, 125 & 160A
C
10,00
10000
Influence of current limitation
on maximum tripping time
Influence of current limitation
on maximum tripping time
100
10
1000
1
10
Set at 0.8 x In
Ir=100, 125 or 160A
Millisec (mS)
Set at 0.8 x In
Ir=80, 100, 125 or 160A
Millisec (mS)
100
1000
100
100
X Nominal Current In
100
100
F
10
10
G
1
1
LTM type
Adjustable
5 - 10 x In
0,1
0,1
0,01
0,01
0,001
0,10
1,00
X Nominal Current In
Time current curves are depicted in cold state.
Seconds (S)
Seconds (S)
1
Set at 1 x In
Ir=80, 100 or 128A
E
B.8
10
10
X Nominal Current In
Set at 1 x In
Ir=63, 80, 100 or 128A
X
100,00
Breaker FE160 GTM 100, 125 & 160A
10000
D
100
X Nominal Current In
X Nominal Current In
Set at 1 x In
Ir=20 or 25A
10,00
100,00
0,001
0,10
1,00
X Nominal Current In
GTM type
Adjustable
3 - 5 x In
10,00
100,00
Record Plus
Time Current Curves
Breaker FE250 LTMD 125, 160, 200 & 250A
Breaker FE160 LTMD 100, 125 & 160A
10000
10000
Influence of current limitation
on maximum tripping time
Influence of current limitation
on maximum tripping time
Set at 0.8 x In
Ir=80, 100 or 128A
Millisec (mS)
1000
10
1000
1
10
Set at 0.8 x In
Ir=100,125,160 or 200A
Millisec (mS)
100
100
10
1
10
100
100
X Nominal Current In
X Nominal Current In
Set at 1 x In
Ir=125,160,200 or 250A
Set at 1 x In
Ir=100, 125 or 160A
100
10
10
1
1
LTMD type
Adjustable
5 - 10 x In
0,1
LTMD type
Adjustable
5 - 10 x In
0,1
Seconds (S)
0,001
0,10
1,00
X Nominal Current In
10,00
100,00
A
0,001
0,10
1,00
X Nominal Current In
Breaker FE250 GTM 125, 160, 200 & 250A
10,00
C
10000
Influence of current limitation
on maximum tripping time
Influence of current limitation
on maximum tripping time
100
10
1000
1
10
Set at 0.8 x In
Ir=100,125,160 or 200A
100
Millisec (mS)
Set at 0.8 x In
Ir=100,125,160 or 200A
Millisec (mS)
100
10
D
1
10
X Nominal Current In
100
X Nominal Current In
Set at 1 x In
Ir=125,160,200 or 250A
Set at 1 x In
Ir=125,160,200 or 250A
100
100
E
10
10
F
1
1
G
0,1
GTM type
Adjustable
3 - 5 x In
0,1
0,001
0,10
1,00
X Nominal Current In
LTMD type
Adjustable
5 - 10 x In
X
0,01
Seconds (S)
0,01
Seconds (S)
B
100,00
Breaker FE250 LTM 125, 160, 200 & 250A
10000
1000
Intro
0,01
0,01
Seconds (S)
FE frame
100
10,00
100,00
0,001
0,10
1,00
X Nominal Current In
10,00
100,00
Time current curves are depicted in cold state.
B.9
Record Plus
Time Current Curves
FE frame
Breaker FE160 Mag Break 8, 12.5, 20, 50, 80, 100, 125 and 160A
Breaker FE250 Mag Break 160, 200 & 250A
10000
10000
Influence of current limitation
on maximum tripping time
Influence of current limitation
on maximum tripping time
1000
100
10
Millisec (mS)
Millisec (mS)
100
1000
1
10
100
10
1
1
Seconds (S)
Mag Breaker type
Adjustable
10 - 15 x In
0,001
7.2 10,00
1,00
X Nominal Current In 125A type depicted
C
D
E
F
G
X
Time current curves are depicted in cold state.
B.10
0,1
Thermal Withstand Line
Allowing up to Class 30 protection
Mag Breaker type
Adjustable
10 - 15 x In
0,01
Seconds (S)
Trip Units
10
0,01
B
100
Thermal Withstand Line
Allowing up to Class 30 protection
A
100
X Nominal Current In (200A type depicted)
100
Intro
1
10
X Nominal Current In (125A type depicted)
0,1
10
100,00
0,001
1,00
7.2 10,00
X Nominal Current In (200A type depicted)
100,00