Technical Data REG-FR_versionB1_a_English 04.2013 Position Indicator Interface Type REG-FR Codetable input: Rs step. resistor Function The REG-FR resistance interface converts the position of a tap changer with resistor row into a BCD code. A build-in power supply supports the measure transducer, voltage outputs and 6 relay. Tap changer resistors (same values) will be connected to measure input of REG-FR by only 3 or 4 wires.The value Rs of one of this resistors should be adjusted by potentiometer R and will be displayed by a voltmeter on both connectors+, (range DC 5V,Rin >500k/V, with 0,1V/ -in position 'R1; and 1V/100 -in position R3 with feature 'R13 or 0,5V/, -feature 'R2 on display) 6 relay contacts (NO contacts) and 6 current outputs make the BCD code available for further use. + - R REG-F without BCD offset output signal Dez BCD code 20 10 8 4 2 1 0 Ohm 1 x Rs 2 x Rs . 9 x Rs 10 x Rs . 28 x Rs 29 x Rs 30 x Rs 1 2 3 0 0 0 0 0 1 0 0 0 0 1 0 0 0 0 0 1 1 10 11 0 1 0 0 0 0 0 1 0 0 0 1 29 30 31 1 0 1 0 0 1 1 1 0 0 0 0 1 1 0 0 0 1 broken wire 39 1 1 1 0 0 1 Transfer behaviour The BCD code signal at the output will change +1 each time the input is increased by 1 resistor Rs of the tap changer. By default the REG-FR is set to 3-wire connection and the tap-changer resistor with 10 /step in position 'R1 or 100/step in position ‘R3 with feature ‘R13 (2,0 /step for feature 'R2) . Select row resistor range ‘R1 or ‘R3 with two jumpers on PCB. Up to 37 uniform resistor tap-change positions are converted into a BCD code. programmable input with 3- or 4-wire connection up to 100m distance between tap changer and REG-FR contacts with AC 250V 2A, DC 220V 150W Large auxiliary voltage range of the power supply Cutting a (red green insulated) wire on pc board and the wire between connector F1/2d and F2/4d activates the 4 wire resistance compensation. No measure current flows thru the tap switch and short disconnections will be surpressed. Technical specifications Regulations and standards IEC1010, IEC801-1 to 6; VDE0110, VDE0160 Interference immunity EN50082-2 Emitted interference EN50081-2, EN55011 Safety Safety class / Overvoltage category I / II Degree of pollution / Test voltage 2 / 2.3kV AC Supply voltage to auxiliary voltage, to relay contacts, Auxiliary voltage to relay contacts Current supply Galv. separated Feature H1 AC 85..240V /DC100..264V Feature H2 AC 20.. 60 V / DC 18..72 V Power consumption < 6 VA / 6W H1; 1A/T H2; 2A/T Temperature Operation 0 ... +65°C Storage, transport -25 ... +85°C Mechanical data Design Circuit board Front panel Configuration Plug-in connector 19” plug-in modules (8T, 3H) 100 x 160mm Aluminium, RAL 7035 grey according to DIN 41494 Part 5 2 units, 'F1': DIN 41612 MH 24+7pole 'F2': DIN 41612 F 48-pole 19” mounting ‘F1’ at Positions ‘n’ and ‘F2’ plus 5T Degree of protection IP00 Weight Plug-in modules 0.3 kg Input row resistor 5 .. 50 each step and 100 ..500 each step -feature R13 1.5 .. 10 each step -feature R2 number of tap changer resistors < 37 resistor tolerance Rs < 2 % from adjusted value wire resistance RL < 20 3-or 4-wire connection (compensates wire resistance RL) measure current Ik 0,2 ..10 mA through resistor row AC voltage on input <0,5V, >45Hz; BCD ‘39’ error code Output BCD 1 ... BCD 20/Vz, to the BCD input (50 V) of the REG-D Voltage at 10kOhm ON (1) > 10V DC OFF (0) < 5V DC U+ voltage output DC 15 V DC; reference BCD GND ; 1.2 kOhm internal resistance Relays with one working contact each for outputting the BCD codes1..20/Vz-; Contact closed / open (1) / (0) Electrical isolation of the relays from each other and from all other circuits Contact load AC 250V 2A DC 220V 150W Number of switching operations < 105 Contact assignment Socket connector ‘F1’ “MH” 24+7-p. 2 4 8 10 14 16 28 30 32 Socket connector ‘F2’ “F” 48-pole 2 4 6 8 20 26 28 30 32 1 z b d Relay BCD 1 Relay BCD 1 Relay BCD 2 Relay BCD 2 Relay BCD 4 Relay BCD 4 Relay BCD 8 Relay BCD 8 Rel. BCD 10 Rel. BCD 10 Rel.20 or sign Rel.20 or signAC/DC L / + current supply AC/DC N / - current supply PE z U+ GND BCD 1 BCD 4 BCD 10 b U+ GND d Ik Rsi Rsg GND R U+ GND BCD 2 BCD 8 BCD20 or sign - Technical Data REG-FR Features ID REG-FR position indicator interface Galvanically isolated ./. row resistor Rs / step 8T 3H plug-in modules REG-FR AC 85..240 V / DC 100 ..264 V H1 AC 20... 60 V / DC 18 .. 72 V . H2 5 ... 50 / 100 ... 500 . R13 Rs / step 1,5 ... 10 . R2 select row resistor range ‘R1 or ‘R3 by two jumpers . An input for tap-change curremt with 0/4..20mA, per tap-change position range and output codes such as BINARY, AWZ or GRAY are available. The device is also available with a wall-mounting housing. accessoire: control panel 96x48mm with 20mm display size and wide range input DC 12V …150V Application with REG-FR feature 'H1' REG-FR step resistance --> BCD 3 wire connection (same wire resistance R L in wire 'I k' and 'GND') REGSys F1/16d BCD 20 or sign(-) F1/16z F1/14d 10 F1/14z F1/10d 8 F1/10z F1/8d 4 F1/8z F1/4d 2 3-wire connection active by 2 wire shortcuts: on PCD wire redgreen on pin F2/2d to F2/4d Trafo tap changer with connected resistors (same values) F1/4z F1/2d 1 F1/2z F1 F2/2d F2/4d Ik, Rsi Rsg GND Ik Rsi Accessoire : . REG-F BCD B4 F2/6d Rsg F2/8d GNDR 96 x 48mm DIN with 6 inputs for BCD-code DC 12 ...150V; and wide range power supply H1 oder H2 tap display shield BCD 1 BCD F2/28z 2 F2/28d F2/30z 8 F2/30d 10 F2/32z 20 or sign(-) F2/32d 4 cable length l cable length l, AWG GND GND F2/26d,z V 24b BCD1 input LV (50V) V 26b 2 V 28b 4 V 30b 8 V 24z 10 V 26z or 30z 20 V 32b,32z GND GND < 100m 18AWG (0,8mm 2) < 40m 20AWG (0,5mm 2) GND F2/26d,z U+ U+ F2/20d,z 1,2kOhm N (-) L (+) F1/32 F1/30 F1/28 protective earth PE 19" rack Adjust step resistance Rs by frontside potentiometer R to +0,2% accuracy. For unknown row resistance Rs shows a LED in the center of '+' connector the middle of step position with potentiometer turning. With feature ‘R3 and Rs >100/step a 2 wire connection is recommened. Connect pins F2/ 6d – 8d and F2/2d –4d for this case. When there is a large distance between the REG-FR and the resistor row Rs, the maximum cable length depends more on the interference influences of parallel energy cables than on the measure transduce resistance - see example. A superposed AC voltage of up to 0.5 V is permissible at the REG-FR input. Since each application has different earth and voltage conditions, the only general statement that can be made is that longer lines are possible if the parallel cables are shielded and have a larger separation between each other. example cable length l wire with 24AWG (0.5mm 2, 4 copper wires with 0.8mm diameter, shielded) RL = distance to Rs + switch resist. = 12 + 3 l = R x A / rho = 12 x 0.5 / 0.02 = 300 m In standart the first tap (row beginning) shows BCD signal “1”, the tap after the first Rs shows “2” and so on. This could de changed to –1 …-14 for first step by a negative offset for BCD signal. It is selected by 4 solder shortcuts on pc board. example: standart first tap: 0x Rs --> diplay = position 1; max: 37x Rs -->display = position 38 offset –12 positions first tap: 0x Rs -->pos. -12; 12x Rs-->pos. -0; max: 31x RS ->position19 For example, on pc board (find wire redgreen) the S81solder shortcuts 8 + 4 + 1 (=13) should be closed, while1 – (-12) =13. Is negative offset active, the BCD signal output BCD20 changes to sign (-) output and broken wire will be shown as –19. A. Eberle GmbH & Co. KG Frankenstr. 160 D-90461 Nürnberg Germany phone 0049 911/ 62 8108-0 FAX/ 62 8108-96