TS/TS data sheet

advertisement

Data Sheet

TS/TS

Thermistor Room Temperature Sensor

TS/TS Temperature Sensor

Description

The TS/TS Thermistor Temperature Sensor is a wall‑mounted thermistor room temperature sensor in a compact enclosure designed for good thermal response.

Features

▪ Mounts directly onto surface

▪ Operating range 6 to 40°C (43 to 104°F)

CE approved

IP30 housing

Compact

Physical

46 mm (1.81")

19.3 mm (0.76”)

56 mm

(2.2")

TS/TS Thermistor Room Temperature Sensor Data Sheet TA201166 Issue 1, 22/12/2010 1

TS/TS Data Sheet

FuncTionaliTy

Housing: The TS/TS sensor is suitable for mounting on a wall.

It consists of a clip‑on cover and a base unit which contains the

10 kΩ thermistor connected to a terminal block.

3.25 mm

(0.12")

The cover can be easily sprung off by applying simultaneous pressure to the right and left sides at the top and bottom of the front cover.

4.5 mm

(0.18")

32.7 mm

(1.28")

27.8 mm

(1.09") base unit fixing centres

inSTallaTion

Mount the sensor on an inside wall approximately 1.3 m (54") from the floor (or in the specified location) to allow exposure to the average zone temperature.

Maintain a mounting clearance of approx. 10 cm (4") to both sides of the sensor in order to allow free airflow.

Do not mount the sensor on an outside wall, on a wall containing water pipes, or near air ducts. Avoid locations exposed to discharge air or radiation from lights, appliances, or the sun.

Keep wiring at least 305 mm (1 ft.) away from large inductive loads such as motors, line starters, lighting ballasts, and large power distribution panels. Run sensor wiring separately from

50 Vac or greater power wiring.

The sensor can be mounted directly onto walls (see fixing centres diagram above), in which case the type of screws appropriate to the wall material should be used.

Procedure

Choose location

Mount sensor to surface using 3 screws – not supplied

(hole Ø 3.25 mm / 0.12")

Connect terminals

Assemble sensor

Set up strategy

Test

For full installation details see TG201167 TS/TS Installation

Instructions.

2 TS/TS Thermistor Room Temperature Sensor Data Sheet TA201166 Issue 1, 22/12/2010

Data Sheet connecTionS

Sensor IQ1xx/2xx

COM (0V)

IN polarity independent

Sensor

Terminate screen at IQ end only

Analogue input channel linked for thermistor (T)

IQ3

0 (0V)

N (in) N

+ (24 V) polarity independent

TS/TS oRDeR coDeS

TS/TS/BoX5 Box of 5 off TS/TS 10 kΩ thermistor room temperature sensors

DiSPoSal

COSHH (Control of Substances Hazardous to Health ‑

UK Government Regulations 2002) ASSESSMENT FOR

DISPOSAL OF TS/TS Temperature Sensor.

RECYCLING .

All plastic and metal parts are recyclable.

Weee Directive:

At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.

Do not dispose of with normal household waste.

Do not burn.

TS/TS Thermistor Room Temperature Sensor Data Sheet TA201166 Issue 1, 22/12/2010 3

TS/TS Data Sheet

SPeciFicaTionS elecTRical

Thermistor :10 kΩ at 25 °C (77 °F)

(Trend standard thermistor sensor)

Temperature range :0 to 40 °C (32 to 104 °F)

Temperature accuracy :(of sensor) ±0.44 °C, ±0.79 °F

(0 °C to 40 °C, 32 °F to 104 °F)

input channel and Sensor scaling

The input channel should be linked for thermistor, T.

MecHanical

Dimensions

Temperature

Operating

Storage

Relative humidity

Connections

3

4

1

2

P x

5

6 y e u l

The sensor type module must be set up with the correct scaling.

The recommended method of setting the sensor type scaling is to use SET. For all IQ2 series controllers with firmware version

2.1 or greater, or IQ3 series controllers, the SET Unique Sensor

Reference given below should be used:

Thermistor TBTS (°C)

Thermistor TBTS F (°F)

Alternatively, set sensor type scaling mode 5, characterise, and enter scaling manually using table below.

Note that for IQ3 the scaling mode and exponent (E) do not need to be set up.

For all other IQ controllers see the Sensor Scaling Reference

Card, TB100521A.

units

Input type

Exponent

Upper

Lower

Points ix

2.641

3.47

4.46

6.663

7.668

8.102

50

40

30

10

0

‑5

°c

1 (thermistor volts)

3

50

‑5

6

122

23 ox (°c)

°F

122 ox (°F)

104

86

50

32

23

Protection

EMC

System Accuracy (including controller):

±0.9 °C, ±1.62 °F (0 °C to 40 °C, 32 °F to 104 °F)

:56 x 46 x 19.3 mm (2” x 1 9 /

16

” x 3 /

4

”)

:6 to 40 °C (+43 to +104 °F)

:-40 to +65 °C (-40 to +150 °F)

:5% to 95% RH non-condensing

:Sprung terminal terminal block

1.5 to 0.34 mm² cross‑sectional area

(16 to 22 AWG)

:IP30

:EN61326-1:2006

Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com

© 2010 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls

Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend control Systems limited

Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

Trend control System uSa

6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trendcontrols.com

4 TS/TS Thermistor Room Temperature Sensor Data Sheet TA201166 Issue 1, 22/12/2010