Technically Speaking No. 0011 Industrial Products Division Capacitors for Power Factor Correction 4-20-2012 1. Basic Power In any power system, there are three components that effect connected equipment: real, reactive, and active power. Active power is the most commonly understood, and is measured in watts (W) or kilowatts (kW). Real power is given in volt-amps (kVA), and represents the power that is actually doing work. Reactive power (kVAR) represents the portion of power flow that is temporarily stored in the form of electric or magnetic fields, due to inductive and capacitive network elements, and returned to power source. The power factor (PF) of an AC electrical system is given as a percentage of the actual power drawn. That percentage represents how much of the total power being drawn is real power, and how much is reactive power. 2. Why Correct Power Factor The goal of power factor correction is to get the percentage of power used as close to 100% active power as possible. There are several reasons for trying to improve power factor, the main reason being that utilities can charge fees if power factor is below a certain value. Also, if there is a lot of reactive current traveling on the distribution system, it may cause voltage drops which can cause electrical equipment to abruptly shut down or overheat. In order to prevent these situations, the industry often tries to correct the power factor to approximately 95%. This correction is achieved by connecting capacitors in parallel with the connected motor circuits. This configuration results in a capacitive current that leads the lagging current from the supply. This leading current cancels the lagging current, and brings the percentage of active power closer to 100%, usually between 92% and 95%. 3. Power Factor Correction Capacitors The standard power factor correction system includes three capacitors in a bank, which are rated by the manufacturer using the total kVAR of the system, rather than the capacitance of the individual capacitors. The system also includes current limiting fuses, as well as discharge resistors that will reduce voltage to 50 Volts or less in one minute on motors rated at a voltage below 2400V. On machines with a voltage higher than 2400V, the resistors can drop the voltage within 5 minutes, which is in compliance with the NEC. These capacitors are depicted below in Figure 1, showing the three units in parallel, with 2 current limiting fuses. TS0011 Reference D.S. 10.3.7 Technically Speaking [3] Power Factor [2] Current Correction Capacitors Limiting Fuses Figure 1 Figure 2 below shows the connection of these capacitors to the motor leads. The capacitor leads are simply connected directly in parallel with the main motor leads. Figure 2 TS0011 Reference D.S. 10.3.7 Technically Speaking 4. Equations for Selecting Capacitors A standard power factor correction system is selected based on the no load kVA of the motor. To determine the correct kVAR value of the capacitor to be used for PF correction, the following calculations can be applied. All of the data required to perform these calculations is provided in the standard software package, i.e. the motor datasheets. It is therefore advisable to perform all calculations and use the lower calculated kVAR for capacitor selection. Equation 1: 0.9 1000 Where: 1.73 1 = No load current at rated voltage. = Rated Voltage. = Maximum expected percent overspeed. An industry standard capacitor is selected with a value equal to or less than the kVAR calculated above. The goal is to select a capacitor that is as close to this calculated kVAR as possible without exceeding it. This ensures the best power factor correction without risking damage to the motor or anything else connected to the capacitor. Example 1: For a motor that runs at 4000V, has a no load current of 30A, and will be running at 15% overspeed, a kVAR value would be calculated as: 0.9 30 1000 4000 1.73 1 .15 186840 1322.5 141.278 From this value, a capacitor would be selected with a kVAR of 125 because the next higher capacitor is rated at 150 kVAR, which would exceed the calculated value. Some other basic calculations are listed below, including how to calculate line power factor, as well as an alternate method for calculating a kVAR for the capacitors that are to be used. TS0011 Reference D.S. 10.3.7 Technically Speaking Equation 2: To determine the value of a capacitor in kVAR that will correct power factor to 95%: tan cos 1 tan cos 1 . 95 Where: = Input power in kilowatts with rated output horsepower or rated output power of a generator. This value is calculated as: 746 1000 . . = Full load efficiency in per unit notation (from datasheet) = Uncorrected full load power factor in per unit notation If a power factor of 95% is requested, the value of the necessary capacitor can be calculated using the above equations. This calculation will give a different kVAR value from that calculated in Equation 1. The lesser of the two values is always taken to ensure that the motor is not damaged by the addition of the capacitors in the circuit. For this calculation, the same procedure is used as above, i.e. an in industry standard capacitor with kVAR value less than or equal to the calculated value. Also, the value of 0.95 in the above equation can be substituted with another value to correct to a different power factor. For example, to correct to a power factor of 85%, one could write: tan cos 1 tan cos 1 . 85 Example 2: To correct the power factor on a motor that runs at 1500 HP, 4000V, 91% power factor, and 95.6% efficiency, up above 95%, plug these values into equation 2, and write: tan cos 1. 91 . 4556 1500 1000 tan cos 1 . 95 .3287 746 .4556 .3287 .956 1119000 .1269 956 148.5 TS0011 Reference D.S. 10.3.7 Technically Speaking For this power factor correction, use a 125 kVAR capacitor because the next higher rating is 150 kVAR and that exceeds the calculated value. The difference between Equation 2 and Equation 1 is that Equation 2 is based on the horsepower, efficiency, and uncorrected power factor of the motor. However, Equation 1 gives a kVAR value equal to 90% of the no load kVA of the motor. Equation 3: To determine the line PF of a system with known capacitive reactance: PFL Cos Tan‐1 Tan . ‐ .746 Where: and PF is the uncorrected PF of the system. Example 3: Given a machine that is 1500 HP, using a 125 kVAR capacitor, has an uncorrected power factor of 91% and which is 95.6% efficient, write: PFL Cos Tan‐1 Tan ‐ 125 .956 1500 .746 Cos Tan‐1 . 45 ‐ . 11 Cos . 34 .94 PFL Giving a corrected line power factor of 94% 5. Precautions The kVAR calculated in all of the above examples is the total three phase kVAR for the motor. Additionally, precautions should be taken when connecting capacitors to motors that are multispeed, wye-delta start, or used with autotransformers. In cases like these, any fast switching will parallel the incoming line voltage with whatever voltage was stored in the capacitors. The resulting transient voltage is unpredictable and can generate transient currents and torques that could be high enough to damage the machine. When connecting power factor correction capacitors in conjunction with other equipment, the manufacturer of said equipment should be consulted to be sure that the equipment is compatible with the capacitors. TS0011 Reference D.S. 10.3.7