For Your Information... EcoSystem® Ballasts and Emergency Wiring

advertisement
®
For Your Information...
EcoSystem® Ballasts and Emergency Wiring
APPLICATION
NOTE
#140
Overview
EcoSystem Lighting Networks are easily used with Emergency (essential) lighting systems.
EcoSystem ballasts may be used for Emergency and egress lighting. EcoSystem ballasts
used for Emergency lighting must be separated physically and electrically from utility (normal/
non-emergency) power devices; however, the EcoSystem Bus may be wired to both normal/
non-emergency fixtures and Emergency fixtures as well.
This application note details emergency fixture wiring for EcoSystem ballasts.
For information on using emergency ballasts and dimming ballasts see Lutron Application
Note #50.
Wiring Details: EcoSystem Bus wired NEC® Class 2
Use the following wiring guide when the EcoSystem Bus wires (E1 & E2) are wired according
to NEC® Class 2 wiring codes.
Wiring to EcoSystem Ballasts in Emergency and Normal Fixtures
(EcoSystem Bus NEC® Class 2)
NEU
Emergency Feed
(from transfer switch)
HOT
Conduit
EcoSystem
Ballast
E1
E2
Emergency Fixture
Utility Power
(normal/nonemergency)
NEU
HOT
Conduit
EcoSystem
Ballast
E1
E2
Normal Fixture
EcoSystem Bus
(to additional ballasts
and Bus Supply)
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
1
Wiring Details: EcoSystem® Bus Wired NEC® Class 1
Use the following wiring guide when the EcoSystem Bus (E1 & E2) wires are wired according
follow NEC® Class 1 wiring codes.
Wiring to EcoSystem Ballasts in Emergency and Normal Fixtures
(EcoSystem Bus NEC® Class 1)
Emergency Feed
(from transfer switch)
NEU
HOT
Conduit
EcoSystem
Ballast
E1
E2
Emergency Fixture
Conduit
Utility Power
(normal/nonemergency)
EcoSystem Bus
(to additional
ballasts and Bus
Supply)
NEU
HOT
Conduit
EcoSystem
Ballast
E1
E2
Normal Fixture
Additional Information
During normal operation (utility power is present), all EcoSystem ballasts will operate as
programmed. When utility power fails, the EcoSystem ballast, powered with an Emergency
feed, will turn on to its programmed Emergency light level (100% by default) and ignore all
other inputs.
Notes
• In all examples shown, the EcoSystem Bus Supply or EcoSystem Energi Savr NodeTM unit
must be powered via normal/non-emergency power ONLY.
• When using a ballast module (ie: C5-BMF-2A), wire the device like the EcoSystem ballasts
shown. The ballast module will power the ballast(s) to which it is wired in an emergency
condition.
• Emergency lighting codes vary by locale and may require more stringent separation of
normal and essential lighting circuits. Always consult local code prior to completing an
EcoSystem installation.
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
2
UL924 Compliance with EcoSystem®
Using a LUT-ELI-3PH with a EcoSystem Bus Supply or EcoSystem Energi Savr NodeTM unit
ensures that the system is compliant with UL924. Follow the wiring diagram in the LUT-ELI3PH for mains wiring. Use the diagram below to complete the installation. There can be up to
20 Bus Supplies or 32 or EcoSystem Energi Savr Node units connected to one LUT-ELI-3PH.
Example 1: LUT-ELI-3PH with EcoSystem Bus Supply
LUT-ELI-3PH
24 VCommon
PP-120-H
or
PP-277-H
Power
Pack
t
Ho
100-347 V~
50/60 Hz
3 Phase
Normal
Supply
Neutral
11
10
9
8
7
6
5
4
CLASS 2 LOW VO LTAGE WIRING
3
2
mo
Com )
(Pin 5
12
From Normal/
Emergency Supply
1
24 V-
n
Common
.
e rg
Em nse
S e n 6)
(Pi
Su Bus
pp
ly
Su Bus
pp
ly
120-277 V~
Normal/
Emergency
Supply
Connect up to 20
Bus Supplies
Wiring Summary:
• Wire Power Pack Red Wire (+24 V-) to LUT-ELI-3PH terminal 8 (V+)
• Wire Power Pack Black Wire (Common) to LUT-ELI-3PH terminal 7 (Circuit Common) and to
EcoSystem Bus Supply Terminal 5 (Common)
• Wire Signal wire from LUT-ELI-3PH (terminal 1) to EcoSystem Bus Supply terminal 6
(CCI-Emergency)
Note: When normal power fails and the LUT-ELI trips, the EcoSystem Bus Supply stops
powering the EcoSystem bus, and all emergency ballasts will turn on to their emergency
light level.
Note: The LUT-ELI-3PH includes panic closure inputs as well. Consult the LUT-ELI-3PH
instructions for wiring details.
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
3
UL924 Compliance with EcoSystem®
Example 2: LUT-ELI-3PH with EcoSystem Energi Savr NodeTM Unit
120-277 V~ Normal/Emergency Feed
H
N
EcoSystem
Energi Savr
Node
G
ECO2
ECO1
RESET
PP-120-H or
PP-277-H
Power Pack
ECO1
ECO1
PWR
TEST
From Normal/
Emergency
Supply
CCI
COM
IR 4
COM
COM
GROUP 4
EMERG
+20V
OCC 4
COM
GROUP 3
PHOTO 4
PHOTO 3
IR 3
IR 2
COM
GROUP 2
+20V
OCC 3
IR 1
+20V
OCC 2
COM
GROUP 1
PHOTO 2
MUX
PHOTO 1
QS LINK
OCC 1
MUX
+24V
+20V
COM
TEST TEMP
CONTACT CLOSURE
ETHERNET
Hot
24 VCommon
Neutral
Power
Pack
COM
COM
EMERG
CCI
120-277 V~
Normal Supply
5
4
3
LED2
LED1
LED3
1
TEST
RADIOTOUCH
6
FACF
NOT USED
2
GND
PHASE
7
´FACP´ N/O
8
CONTACTS
9
´FACP´ N/C
10
COMMON
MUX
11
+24VFW
DRAIN
12
CONTACTS
SENSE
Com – Common
MUX
CONTACT CLOSURE
S1
CLASS 2 LOW VOLTAGE WIRING
LUT-ELI-3PH
Emerg – Emergency
Wiring Summary:
• Wire Power Pack Red Wire (+24 V-) to LUT-ELI-3PH terminal 8 (V+)
• Wire Power Pack Black Wire (Common) to LUT-ELI-3PH terminal 7 (Circuit Common)
• Wire Signal wire from LUT-ELI-3PH (terminal 1) to Energi Savr Node Emerg input
Note: When normal power fails and the LUT-ELI trips, the EcoSystem Energi Savr Node
stops powering the EcoSystem bus, and all emergency ballasts will turn on to their
emergency light level.
Note: The LUT-ELI-3PH includes panic closure inputs as well. Consult the LUT-ELI-3PH
instructions for wiring details.
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
4
UL924 Compliance with Quantum®
Using a LUT-ELI-3PH with a Quantum Bus Supply ensures that the system is compliant with
UL924. Follow the wiring diagram in the LUT-ELI-3PH for mains wiring. Use the diagram
below to complete the installation. Only 1 Bus Supply per hub needs to be connected per
LUT-ELI-3PH. There can be up to 5 Quantum hubs connected to one LUT-ELI-3PH.
Wiring to Quantum Bus Supply
From Normal/
Emergency supply
24 V-
Hot
120-277 V~ Normal/
Emergency Feed
Common
Neutral
100-277 V~
Normal supply
PP-120-H or
PP-277-H
Power Pack
78
56
34
12
Common
5
4
3
LED2
LED1
1
LED3
2
TEST
RADIOTOUCH
6
FACF
NOT USED
´FACP´ N/O
7
CONTACTS
8
GND
PHASE
9
´FACP´ N/C
10
CONTACTS
11
COMMON
12
+24VFW
EM C
MUX
E2
MUX
E1
DRAIN
E2
SENSE
E1
S1
CLASS 2 LOW VOLTAGE WIRING
Emerg.
signal
LUT-ELI-3PH
Wiring Summary:
• Wire Power Pack Red Wire (+24 V-) to LUT-ELI-3PH terminal 8 (V+)
• Wire Power Pack Black Wire (Common) to LUT-ELI-3PH terminal 7 (Circuit Common) and to
Quantum Bus Supply Terminal 5 (Common)
• Wire Signal wire from LUT-ELI-3PH (terminal 1) to Quantum Bus Supply terminal 6
(CCI-Emergency)
Note: When normal power fails and the LUT-ELI-3PH trips, the Quantum Bus Supply stops
powering the EcoSystem bus, and all emergency ballasts will turn on to their emergency
light level.
Note: The LUT-ELI-3PH includes panic closure inputs as well. Consult the LUT-ELI-3PH
instructions for wiring details.
Need additional assistance? Call the Lutron Technical Support Center 1-800-523-9466.
Please provide exact model number when calling.
5
Notes
Contact Information
ASIAN HEADQUARTERS
Singapore
Lutron GL Ltd.
15 Hoe Chiang Road, #07-03 Euro Asia Centre
Singapore 089316
TEL +65.6220.4666
FAX +65.6220.4333
Internet: www.lutron.com
E-mail: product@lutron.com
WORLD HEADQUARTERS
USA
Lutron Electronics Co., Inc.
7200 Suter Road, Coopersburg, PA 18036-1299
TEL +1.610.282.3800
FAX +1.610.282.1243
Toll-Free 1.888.LUTRON1
Technical Support 1.800.523.9466
Asia Technical Hotlines
Northern China: 10.800.712.1536
Southern China: 10.800.120.1536
Hong Kong: 800.901.849
Indonesia: 001.803.011.3994
Japan: +81.3.5575.8411
Macau: 0800.401
Singapore: 800.120.4491
Taiwan: 00.801.137.737
Thailand: 001.800.120.665853
Other countries: +65.6220.4666
North and South America Technical Hotlines
USA, Canada, Caribbean: 1.800.523.9466
Mexico: +1.888.235.2910
Central/South America: +1.610.282.6701
EUROPEAN HEADQUARTERS
United Kingdom
Lutron EA Ltd.
6 Sovereign Close, London, E1W 3JF United Kingdom
TEL +44.(0)20.7702.0657
FAX +44.(0)20.7480.6899
FREEPHONE (UK) 0800.282.107
Technical support +44.(0)20.7680.4481
Printed in U.S.A.
02/2011
P/N 048-140 Rev. E