GE NEMA Rated Full Voltage Starters CH306, CR386 Nonreversing Magnetic Motor Starters 1600 Horsepower Maximum NEMA Sizes 00-9 600 Volts Maximum 50/60 Hertz GE Fastrac™ Program items are printed in red type. CR306, CR386 Three-Phase, Three-Pole Forms, NEMA Types Open, 1,3R, 12 and 4/4X, Three-Leg Protection, 60 Hertz© List price includes a holding interlock, pressure terminals for the line and load connections, plus a 3-leg block type overload relay (manual reset). One NO isolated contact on the overlpad relay is available as an option at $24.00, GO-10G. To order, add suffix LAA to Catalog NEMA Size Max mum Horsepower® Continuous Rating Voltage® (60 Hertz) Separate Control— 1 1 5-1 20 V 00 9 200-208 230-240 460-480 575-600 Separate Con rol— 1 1 5-1 20 V 18 0 3 3 5 5 Separate Con rol— 1 1 5-1 20 V 1 27 200-208 230-240 460-480 575-600 714 714 10 10 Separate Control— 1 1 5-1 20 V 2 45 10 200-208 230-240 460-480 575-600 15 25 25 Separate Control — 1 1 5-1 20 V 3 90 25 30 50 . 50 200-208 230-240 460-480 575-600 Separate Control— 1 1 5 - 1 2 0 V 4 135 40 50 100 100 200-208 230-240 460-480 575-600 Separate Control— 1 1 5-1 20 V 5 270 75 100 200 200 200-208 230-240 460-480 575-600 Separate Control— 1 15-120 V 6 540 810 9 162.00 162.00 162.00 162.00 162.00 B102 216.00 B602 216.00 216.00 216.00 216.00 B623 B603 13604 B605 List Price, GO-10G C002 234.00 C102 246.00 C023 COOS C004 G005 234.00 234.00 234.00 234.00 C123 C103U) C104 C105 246.00 246.00 246.00 246.00 D002 426.00 D102 486.00 D023 D003 D004 D005 426.00 426.00 426.00 426.00 D123 D103 D104 D105 486.00 486.00 486.00 486.00 E002 690.00 E102 E023 E003 E004 E005 690.00 690.00 690.00 690.00 E123 E103 E104 E105 F002 1578.00 F023 F003 F004 F005 1578.00 1578.00 1578.00 1578.00 G002 G023 G003 G004 G005 Use NEMA Size 0 C602 C623 C603 C604 C605 D602 618.00 D2:i ' 618.00 D402 918.00 D604 D605 618.00 618.00 618.00 618.00 D223 D203 D204 D205 618.00 618.00 618.00 618.00 D423 D403 D404 D405 918.00 918.00 918.00 918.00 810.00 E602 966.00 E202 966.00 E402 1422.00 810.00 810.00 810.00 810.00 E623 E603 tb'B 966.00 966.00 966.00 966.00 E223 E203 E204 E205 966.00 966.00 966.00 966.00 E423 . ' E403 E404 E405 1422.00 1422.00 1422.00 1422.00 F102 1830.00 F602 2346.00 F202 2346.00 F402 2874.00 F123 F103 F623 F603 F604 2346.00 2346.00 2346.00 2346.00 F223 F203 2346.00 2346.00 2346.00 2346.00 F423 F403 F104 F105 1830.00 1830.00 1830.00 1830.00 F404 't-405 2874.00 2874.00 2874.00 2874.00 3855.00 G102 4317.00 G60'j 5637.00 G2U2 5637.00 G402 5637.00 3855.00 3855.00 3855.00 3855.00 G123 G103 G104 G105 4317.00 4317.00 4317.00 4317.00 G623 G603 G604 G605 5637.00 5637.00 5637.00 5637.00 G223 G203 G204 G205 5637.00 5637.00 5637.00 5637.00 G423 G403 G404 G405 5637.00 5637.00 5637.00 5637.00 HH002 9165.00 HH102 12165.00 HH602 13785.00 — 202 13785.00 HH402 15165.00 HH023 HH003 HH004 HH005 9165.00 9165.00 9165.00 9165.00 HH123 HH103 HH104 HH105 12165.00 12165.00 12165.00 12165.00 HH623 HH603 HH604 HH605 13785.00 13785.00 13785.00 13785.00 — 223 HHP03 HH204 HH205 13785.00 13785.00 13785.00 13785.00 HH423 HH403 HH404 HH405 15165.00 15165.00 15165.00 15165.00 19455.00 19455.00 19455.00 19455.00 Separate Con rol— 1 1 5-1 20 V L002AA1A 31983.00 800 1600 1600 L003AA1A L004AA1 A L005AA1A 31983.00 31983.00 31983.00 -..'tJU. $ $ Use NEMA Size 0 B202 K002AA1A 2250 Catalog Number CR306 B223 K003AA1A K004AA1A K005AA1A 230 460 575 List Price, GO-10G 288.00 230 460 575 220-240 440-480 550-600 Catalog Number CR306 NEMA Type 4/4X Watertight, Dust-tight (Stainless Steel) <3> 288.00 288.00 288.00 288.00 13167.00 13167.00 13167.00 1215 Use NEMA Size 0 B123 B103 B104 B105 J003AA1A J004AA1A J005AA1A 450 900 900 NEMA Type 12U>8> Dust-tight, Driptight Industrial Use 174.00 174.00 174.00 174.00 174.00 204.00 230 460 220-240 440-480 550-600 A 105 $ List Price, GO-10G Catalog Number CR306 204.00 204.00 204.00 204.00 13167.00 575 A102 List Price, GO-10G B002 J002AA1A 300 600 600 Catalog Number CR306 NEMA Type 3R Rainproof Sleet-Res slant B023 B003 B004 B005 Separate Control— 1 15-120 V 220-240 440-480 550-600 Control Circuit Voltage© $ List Price, GO-10G Horsepower Separate Con rol— 1 1 5-1 20 V 8 A002 List Price, GO-10G Catalog Number CR386 Motor Voltage 7 150 200 400 400 200-208 230-240 460-480 575-600 Catalog Number CR306 A023 A003 A004 A005 114 2 2 200-208 230-240 460-480 575-600 NEMA Type 1 General-Purpose Open Type Horsepower Numbers (Size 00-5) listed in table. Three heaters should be ordered as separate items. List Price $9.00 each, GO-10H. Packaged in quantities of three; must be ordered in multiples of three. Select heaters by using tables on pages 1-71 to 1-75. 288.00 B402 B2U 1 B205 288.00 288.00 288.00 288.00 B423 B403 B404 B405 318.00 C202 318.00 C402 462.00 318.00 318.00 318.00 318.00 C223 C203 C204 C205 318.00 318.00 318.00 318.00 C423 C403 C404 C405 462.00 462.00 462.00 462.00 $ 426.00 426.00 426.00 426.00 426.00 Note: See page 1-7 for single-phase forms. © Pricing for 50-Hertz forms (at standard voltages) is the same as shown in table for 60 Hertz. Listed prices for 460-480 Volt also apply to 380-415 Volt, 50 Hertz. See page 1-2 for 380-415 Volt horsepower ratings. © Motor full-load current should not exceed continuous ampere rating of starter. ® NEMA Types 4/4X and 12 starters are UL listed to include Class II Groups F and G, Division 2 only, and Class III hazardous locations. ® External reset not included on standard listed forms. © Refer to Coil Table, page 1-3 for other available starter coils and suffixes (sizes 00-6). For sizes 7-9 starters with other control circuit voltages, contact nearest GE Industrial Systems — Electrical Distribution and Control Representative. ® Units are individually boxed and "Poly-Packed" six per carton as standard. Reference: See page 1-5. 1-6 r 1999 Issue Prices and data subject to change without notice GE NEMA Rated Full Voltage Starters Section 7 GE Fastrac™ Program Service Full Voltage Noncombination Starters GE Fastrac Program covers nonreversing magnetic motor starters (3-phase, 3-pole) in NEMA sizes 0-4 with a full range of options. It also includes standard catalog torms of many other nonreversing magnetic motor starters, magnetic reversing controllers, magnetic two-speed controllers and magnetic contactors. Combination Starters Eighty percent of all the combination starters that GE sells are available on a GE Fastrac Program basis. Standard cycle: 2 weeks GE Fastrac Program: 1 day To order GE Fastrac starters, select and price items required that are printed with red catalog numbers. Clearly indicate on the order that Fastrac service is required. Refer? nces: DEP-C15 Fastrac Application & Selection Guide for NEMA Controls DEP-078 Fastrac Now™—the motor starter you need is only minutes away. GE's 300-Line of NEMA rated controls has a complete offering of full voltage nonreversing, reversing, two-speed and combination motor starters, plus magnetic contactors. They are available in NEMA Sizes 00-9; 600 Volts maximum, 1600 horsepower maximum. Open forms are available in sizes 00-9. Type 1 enclosures are available in sizes 00-6. Types 3R, 12, 4, and 4X enclosures are available in sizes 0-6. The 300-Line has standard specification approval by many major manufacturers for the toughest industrial applications. FASTRAC Nonreversing Magnetic Motor Starters (CR306, CR386 Series) . . . . . . . . . . . Take Control With GE Magnetic Reversing Controllers (CR309 S e r i e s ) . . . . . . . . . . . . . Fastrac Now™ Distributor-assembled kits for various enclosed starter combinations. No point-to-point wiring required. Assembly possible by anyone while retaining full UL listing. See pages 1-78 to 1-84 for Fastrac Now™ distributor-assembled starters. .1-4 to 1-11 .1-12to1-17 Magnetic Two-Speed C o n t r o l l e r s . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18 to 1-23 Nonreversing Combination Magnetic Starters (CR307, CR308, CR310, CR311, CR387, CR390, CR385 Series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-24 to 1-38 Combination Magnetic Safety Starters (CR307, CR308, CR310, CR311 Series). . . . . . . . . . . . . . . . . . .1-39 to 1-41 Magnetic Contactors (CR305, CR385 S e r i e s ) . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-42to1-49 Supplementary Information For All Full Voltage Starters: technical D a t a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2,1-3 Factory-Installed Modifications And Modification K i t s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-50 to 1-61 Motor Current Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . ..1-69,1-70 Heater Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . .1-71(01-75 Solid-State Overload R e l a y s . . . . . . . . . . . . . . . Starter Selection...... Panel Mount Overload Relays . . . . . . . . . . . . . . . NEMA Type Enclosures Only . . .1-62to1-64 . 1-65 .1-66 to 1-68 . .1-76,1-77 Fastrac Now Distributor-Assembled S t a r t e r s . . . . . . . . . . . . . . . . 1-78 to 1-84 References: See Publication Index, Section 18. Data subject to change without notice 1999 Issue 1-1 GE NEMA Rated Full Voltage Starters 300-Line Application Information and Technical Data NEMA Size 0 1 2 3 4 5 6 7 8 9 1 2 2 3 3 714 7% NA NA NA NA NA NA NA NA NA NA NA NA 3 3 5 5 5 7V4 7V4 10 10 10 10 15 25 25 25 25 30 50 50 50 40 50 75 100 75 100 100 150 200 200 150 200 300 400 400 300 500 600 600 450 750 900 900 800 1350 1600 1600 1 ^ 1 1 2 2 5 5 10 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA Vk 3 3 5 5 5 Th 10 15 15 15 15 20 30 30 30 25 30 50 60 60 60 75 125 150 150 125 150 250 NA 1Vz 2 2 250 250 NA NA NA NA NA NA NA NA NA NA NA NA NA NA Continuous Current Max Starters and Enclosed Contactors Open Contactors 9 10 18 20 27 30 45 50 90 100 135 150 270 300 540 600 810 900 1215 1350 2250 2500 Coil Burden (VA) Inrush 2-Pole Holding 2-Pole Inrush 3-Pole Holding 3-Pole Inrush 4- and 5-Pote Holding 4- and 5-Pole 151 24 151 24 151 24 151 24 151 24 151 24 151 24 151 24 151 24 528 60 528 60 576 75 1152 83 1152 83 1248 87 1248 2580 3360 1600 210 1600 210 NA NA 1500 140 2900 300 NA NA 2900 300 3600 400 NA NA Control Power Transformer VA (Min) 50 50 50 100 Coil Operating Voltage % Minimum Pickup % Maximum Dropout 85 63 85 63 85 63 Switching Delay 3-Pole Pickup Typical (Milliseconds) Dropout Typical (Milliseconds) 15-30 7-15 15-30 7-15 Mechanical Lite Millions Nominal 20 3 00 Normal Starting Duty HP Rating® Single Phase 115V60H2 230V 60Hz Three Phase 200V 60Hz 230V 60Hz 380-41 5V 50Hz 460V 60Hz 575V 60Hz Plugging or Jogging HP Rating© SinglePhase 115V60Hz 230V 60Hz Three Phase 200V 60Hz 230V 60Hz 380-415V50HZ 460V 60Hz 575V 60Hz 1 /3 1 VA 1V4 Vh 2 2 NA NA " 1'/2 15 87 1248 87 191 255 95 2580 191 3600 276 3360 255 NA NA 200 250 500® 500® 1000® 1500® 1501® 85 68 85 65 85 85 85 85 65 65 65 50 85 50 85 50 15-30 7-15 20-40 20-45 7-15 20-45 7-15 30-50 7-15 15-25 30-50 15-25 60-90 100-150 80-125 25-100 80-125 25-100 20 20 10 5 5 5 1 1 1 0.5 15 17% 14% 48 53 48 75 79 106 203 263 302 17V4 1356 Weight (Less Carton) Contactor (Pounds) Starter (Pounds) 2A 3% 2% 33/4 2% 61/2 3V, 7% Power Terminals Wire Size Range (75 DEG) AWG Torque (Pounds-Inches) 14-8 20 14-8 20 14-8 20 14-4 50 10-1/0 8-3/0 200 1/0-500kcmil 300 2 2/0-500kcmil 3 2-600kcmil 150 375 500 4 2-600kcmil 500 NA NA 50 50 50 50 50 50 65 65 65 65 65 Max. Noise (DBA) 365 © When operation of the controller requires jogging (inching) or plug stopping or when normal operation requires continued operation in excess of 5 operations per minute or 10 operations in a 10-minute period, the plugging or jogging horsepower ratings must be followed. ® In lieu of a 500 to 1500 VA control transformer, a 50 VA unit in conjunction with a control relay can be used as follows: 1. Wire control relay coil in control circuit on secondary side of control transformer. 2. Wire two poles of control relay in series with contactor coil at line voltage. Mounting Position Devices must be mounted to a sturdy vertical surface with the line side terminals up. No other orientations are permitted. Operating Temperature Equipment is designed for ambient temperature outside of equipment enclosures to be -25° to 40°C. When contactor is energized, temperatures will be above outside ambient in equipment enclosures. Temperature rises inside the enclosures should be limited so that internal air temperature does not exceed 65° for sizes 00 to 6 and 60°C for sizes 7 to 9. If condensing moisture is present, space heater kits should be used to prevent condensation when contactor is not energized. Storage temperature should be -30° to 65°C. If equipment is stored over 1 week, it may be necessary to cover the equipment and provide a source of heat to prevent condensation. 1-2 1999 Issue Data subject to change without notice GE NEMA Rated Full Voltage Starters 300-Line\ Application Information and Technical Data \ Short-Circuit Ratings Control Transformers Fusible forms of combination magnetic starters equipped with UL labeled, nonrenewable, NEC-type fuses listed in the table below, are adequate for installation on motor branch circuits where the available short-circuit current at the incoming line terminals of the starter does not exceed the value shown. Circuit breaker-type combination magnetic starters equipped with the circuit breakers listed in the table at right are adequate for installation on motor branch circuits where the available shortcircuit current at the incoming line terminals of the starter does not exceed the value shown. For either type, it is recognized that maintenance of some components may be required after a branch circuit fault and in some cases a device may require replacement. Where to Use It is often desirable to use a control transformer in conjunction with a magnetic starter or controller to provide low voltage control. Fusible Combination Starters NEMA Size Fuse Type Maximum Symmetrical rms Amperes H, K 0-3 4,5 0-5 J, RK-1.RK-5 100,000 6 J, L, RK-1.RK-5 100,000 Coil Suffix (THIS TABLE IS TO BE USED FOR STARTER FORMS WITHOUT CONTROL TRANSFORMERS.) Indicates voltage and frequency of operating coils. For use in ordering full voltage starters and contactors, Sizes 00-6, with other coil ratings than those shown in listing on pages 1-6 to 1-49. Frequency 24V (Hertz) 5,000 10,000 H, K Description—Factory Wired A transformer, with sufficient capacity for the control circuit, mounted with the starter can be supplied by the factory for the majority of transformer ratings and types of enclosures. 60 Breaker Type Rating Amperes NEMA Size TEB 15-50 15-70 TEC® TED THED TFJ& 600 Volt 5,000 5,000 5,000 5,000 ~ 3-30 3-50 15-50 30-100 50-150 0 1 25,000 25,000 25,000 25,000 25,000 25,000 25,000 25,000 25,000 25,000 5,000 5,000 5,000 5,000 5,000 3-30 3-50 15-50 30-100 50-150 0 1 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 r i r 1 5,000 25,000 5,000 25,000 5,000 r 25,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000 15-100 25-150 TEC® 480 Volt 0 1 2 3 15-50 15-30 35-70 15-50 60-100 25-100 110-150 15-50 15-50 60-70 15-50 60-100 25-100 110-150 2 3 4 2 3 4® 0 i / -i / -, / T 1 -i I -i 1 1 2 3 0 1 2 3 - i 5,000 5,000 25,000 5,000 25,000 5,000 25,000 5,000 r 1 r i r i 65,000 65,000 65,000 65,000 65,000 65,000 42,000 14,000 25,000 14,000 25,000 25,000 25,000 25,000 5,000 25,000 5,000 25,000 5,000 25,000 5,000 TFK 70-225 4 22,000 22,000 22,000 THFK 70-225 4 25,000 25,000 10,000 TJK THJK TKM, TKC THKM8 TB6, TBC 225-600 5 225-400 -i 450-600 / 5 300-800 300-800 300-800 6 r t 10,000 10,000 10,000 35,000 10,000 35,000 10,000 25,000 10,000 42,000 65,000 65,000 30,000 35,000 65,000 22,000 25,000 42,000 © Open continuous Ampere ratings are for contactors only. © Mag-Break® motor circuit protector with adjustable magnetic trip (Amperes). ® Mag-Break motor circuit protector with adjustable magnetic trip (Amperes) and current limiter. ® 100 Amperes and smaller current limiters are UL listed. Data subject to change without notice ® 265-277V 02 23 03 110V - 02 - - 460-480V 575-600V ® ® 13 04 05 220V 380-41 5V 440V 550V 03 64 04 05 Note: The 02 coil suffix (115-120V, 60 Hz/110V, 50 Hz) supersedes the 22 coil suffix (120V, 60 Hz). © Suffix shown for this voltage is part of Catalog Number in magnetic starter-contactor listings. Auxiliary Contact Ratings NEMA Size 0-9 Amperes AC Volts s Continuous Make Break 10 10 10 10 60 30 6.0 3.0 1.5 10 10 .— 115 230 460 575 15 12 1.2 DC Volts 125 250 1.1 0,5 Contactor DC Ratings Interrupting Ratings NEMA Size No. of Poles in Series Continuous Current Rating Inductive Amps 125 Volts Noninductive Amps 250 Volts 250 Volts 125 Volts N.O. N.C. N.O. N.C, N.O. N.C. N.O, 1 0.8 5 15 50 4 15 50 N.C. 1 2 3 4 9 9 9 9 2.5 7 14 25 2.5 7 14 25 0,6 1.2 3.5 7 0.5 1.2 3.5 7 ' 5 4 25 35 50 25 35 • 50 1 2 3 4 18 18 18 18 2.8 7 14 25 2.5 7 14 25 0.7 1.5 3.5 7 0.5 1.2 3.5 7 6 35 50 90 4.5 25 35 60 1.1 6 25 60 0.9 4.5 25 55 1 . 1 2 3 4 27 27 27 27 3 7 14 25 2.5 7 14 25 0,7 1.5 3.5 7 0.5 1.2 3.5 7 6.5 50 70 120 4.5 25 35 60 1 .2 7 35 70 0.9 4.5 25 55 2 2 3 4 45 45 45 7 14 25 1.5 3.5 7 60 120 160 3 2 3 4 90 90 90 7 14 25 2.2 4.5 9 • 600 600 600 300 600 600 4 2 3 4 135 135 135 7 14 25 2.2 4.5 9 600 600 600 300 600 600 00 0 TJJ& 230-240V ® - ' 50 Maximum Symmetrical rms Amperes 240 Volt 200-208V 24 Frequency (Hertz) Circuit Breaker Combination Starters 11 5-1 20V ® 1999 Issue 9 40 80 1-3 GE NEMA Rated Full Voltage Starters CH306, CR386 Nonreversing Magnetic Motor Starters 1600 Horsepower Maximum NEMA Sizes 00-9 600 Volts Maximum 50/60 Hertz Basic 300-Line Features CONTACTOR Captive saddle clamps Staggered terminals (optional above size 1) Encapsulated coil OVERLOAD RELAY Manual Weld Check Coil retainers ±10% trip adjustment Armature retaining clip Overload relay heaters, (not shown) Long-life armature Visual trip indicator Manual reset arm Captive saddle clamps Typical Size 1 Motor Starter GE's full voltage (600-Volt maximum) magnetic motor starter has an encapsulated coil and a 3-leg overload relay to protect against overloads in all phases. It is on standard specifications of major manufacturers. The line offers features and benefits most asked for by users. Forms available include reversing and nonreversing, two-speed, and combination, sizes 00-9. • Toolless contactor disassembly (Sizes 00-4)—allows quick access for inspection and maintenance. Just release two retainers and pull a clip to get at magnet, coil, and contacts. CR306 Size 1 Motor Starter with Solid-State Overload Relay Installed • Saddle clamp terminals (Sizes 00-1)—accommodate ring, • Largest selection of modifications and accessory kitsspade, and stripped wire leads and carry permanent stampedin identification. Staggered arrangement makes wiring easier includes auxiliary contacts, coils, fifth-pole addition, vertical and and helps prevent shorting between phases. horizontal mechanical interlocks, surge suppressors, control circuit fusing, NEMA Type enclosures, push buttons, selector • Current-carrying components—contact tips are weldswitches, indicating lights, control transformers, space heaters, resistant silver cadmium oxide (fine silver on sizes 00 and 0 and more. only). Contacts are installed in a wedge configuration for positive make with minimum bounce. Technical Features—Solid-State Overload • Optional PF capacitor terminals—permit easy connection • 2:1 Adjustable full load amps with tactile feedback dial of power factor correction capacitors between contactor and • Selectable 10/20/30 protection class overload relay for energy conservation. • Ambient insensitive within the stated operating temperature • Class 20 overload protection. range of -20° to +70°C • Built-in thermal memory to prevent hot motor restarts • Visual trip indicator with manual reset—to avoid surprise • Protection against complete phase current loss restarts. Reset occurs on arm upstroke so a tripped condition • Phase current unbalance: Adjustable 20-50% can't be overridden by holding the arm down. • Manual reset (standard) and remote reset (optional) 24 Vdc or • Manual weld check—provides a convenient test against 120 Vac welding of overload relay contacts. Just depress the weld • Accuracy: ±2% check operator to trip the relay, run a simple continuity test • Repeatability: ±2% across the relay contacts, then depress the manual reset to • Self-powered @ 50% of minimum current range return the starter to service. • Size: 1-6 (0.40A-540A, 600 V, 50/60 Hz) • Unbalance trip signal for PLC operation • Optional isolated NO contact on the overload relay• Manual trip provides means of direct interface with programmable controller • Visual trip indication or computer to monitor performance and diagnose faults. • Standard isolated 1 NO and 1 NC aux. contact (A600, Q600) • Dual bimetals—anticipate overloads, responding to rising • Built-in line/load straps current and temperature with faster tripping on severe overloads • Fits with existing 300-Line Starters for better motor protection. Trip points are factory-calibrated • Power factor correction terminals (sizes 1-4) for accuracy. • DIN rail mountable sizes 1 & 2 • ±10% trip adjustment—by turning a dial in the overload relay face allows "tuning" the protection to the motor on the spot. 1-4 1999 Issue Data subject to change without notice GENEMA Rated Full Voltage Starter CR306, CR386 Nonreversing Magnetic Motor Starter, 1600 Horsepower Maximurr NEMA Sizes GO600 Volts Maximurr 50/60 Hert Schematic Diagram STOP r START _d Typical CR306 Size 4 magnetic motor starter Application ^xlx y- te \ " ———o-^NrOOL GE's magnetic motor starters listed here may be used for starting full-voltage, nonreversing, single-speed ac motors up tp 1600 horsepower, 600 Volts maximum, providing protection to the motor against running or stalled overloads. Their compact size and ease of wiring make them especially suitable for motor control centers, custom-type control panels, and switchgear equipment. Refer to page 1-4 for features of basic starter. 1 a > {OL i OL > Typical Schematic Diagram for CR306 Starter (NEMA Sizes 00-6) Ordering Directions 1. Specify starter by complete Catalog Number. Example: CR306C103 is a Size 1 starter with 230-240-Volt, 60-Hertz coil and in Type 1 general-purpose enclosure @ $246.00, GO-10G. 2. The final letter of the Catalog Number denotes extra auxiliary contacts (sometimes referred to as auxiliary interlocks). Order the desired extra auxiliary contacts by replacing the final letter with one from first column of auxiliary interlock table (see page 1-58). Example: CR306C103AAB is Size 1 starter with one extra normally open, auxiliary contact @ $312.00, GO-10G. 3. Starter forms are available with coils of other ratings than those shown on pages 1-6 to 1-7. Refer to coil suffix table, page 1-3 for information. To order forms with other coil ratings, insert suffix from coil table in place of fifth and sixth numbers of listed starter Catalog Number shown on pages 1-6 to 1-7. Example: A CR306C102 NEMA Size 1, three-pole starter in Type 1 enclosure with 24-Volt, 60-Hertz coil becomes a CR306C124 Catalog Number. 4. For continuous rated motors with a service factor of 1.15 to 1.25 select the heater with maximum motor Amperes equal to or immediately greater than the actual full-load current taken directly from the nameplate of motor. Order heaters by complete Catalog Number from appropriate heater tables on pages 1-71 to 1-75. List Price $9.00 each, GO-10H. Packaged in quantities of three; must be ordered in multiples of three. References: Instructions IT NEMA Size Publication Number 00,0,1 2 3 4 5 6 7-9 GEH-5190 GEH-4774 GEH-4806 GEH-4807 GEH-4839 GEH-5198 GEH-5108 Prices and data subject to change without notice 5. Order special modifications or forms not listed by complete description using a listed Catalog Number as reference. Example: Similar to CR306C104 except with 480/120-Volt control transformer and red indicating light in cover. Total List P r i c e . . . . . . . . . . . . . . . . . . . . . . . . $483.00, GO-10G. 6. Two-phase, four-wire forms are available. Contact nearest GE Industrial Systems—Electrical Distribution and Control Representative for pricing and ordering information. Standard Coil Ratings Standard Voltages (60 Hertz): 24,115-120, 200-208, 230-240, 265-277, 460-480 and 575-600 Standard Voltages (50 Hertz): 110, 220,380, 440 and 550 For price adders on special voltage and/or frequency coils, refer to page 1-52. 50-Hertz Starters Pricing of starters for use on 50 Hertz at standard voltages is the same as shown in table for 60 Hertz. Refer to page 1-2 for threephase horsepower ratings at 380 Volts, 50 Hertz. Factory-Installed Modifications.......... pages 1-50 to 1-56 Field-Installed Modification Kits....... pages 1-57 to 1-61 Heater Selection Tables ................ pages 1-71 to 1-75 f 999 Issue 1-5