CH306, CR386 Nonreversing Magnetic Motor Starters

advertisement
GE NEMA Rated Full Voltage Starters
CH306, CR386 Nonreversing Magnetic Motor Starters
1600 Horsepower Maximum
NEMA Sizes 00-9
600 Volts Maximum
50/60 Hertz
GE Fastrac™ Program items are printed in red type.
CR306, CR386 Three-Phase, Three-Pole Forms,
NEMA Types Open, 1,3R, 12 and 4/4X, Three-Leg Protection, 60 Hertz©
List price includes a holding interlock, pressure terminals for the
line and load connections, plus a 3-leg block type overload relay
(manual reset).
One NO isolated contact on the overlpad relay is available as an
option at $24.00, GO-10G. To order, add suffix LAA to Catalog
NEMA
Size
Max mum
Horsepower®
Continuous
Rating
Voltage®
(60 Hertz)
Separate Control— 1 1 5-1 20 V
00
9
200-208
230-240
460-480
575-600
Separate Con rol— 1 1 5-1 20 V
18
0
3
3
5
5
Separate Con rol— 1 1 5-1 20 V
1
27
200-208
230-240
460-480
575-600
714
714
10
10
Separate Control— 1 1 5-1 20 V
2
45
10
200-208
230-240
460-480
575-600
15
25
25
Separate Control — 1 1 5-1 20 V
3
90
25
30
50 .
50
200-208
230-240
460-480
575-600
Separate Control— 1 1 5 - 1 2 0 V
4
135
40
50
100
100
200-208
230-240
460-480
575-600
Separate Control— 1 1 5-1 20 V
5
270
75
100
200
200
200-208
230-240
460-480
575-600
Separate Control— 1 15-120 V
6
540
810
9
162.00
162.00
162.00
162.00
162.00
B102
216.00
B602
216.00
216.00
216.00
216.00
B623
B603
13604
B605
List
Price,
GO-10G
C002
234.00
C102
246.00
C023
COOS
C004
G005
234.00
234.00
234.00
234.00
C123
C103U)
C104
C105
246.00
246.00
246.00
246.00
D002
426.00
D102
486.00
D023
D003
D004
D005
426.00
426.00
426.00
426.00
D123
D103
D104
D105
486.00
486.00
486.00
486.00
E002
690.00
E102
E023
E003
E004
E005
690.00
690.00
690.00
690.00
E123
E103
E104
E105
F002
1578.00
F023
F003
F004
F005
1578.00
1578.00
1578.00
1578.00
G002
G023
G003
G004
G005
Use NEMA Size 0
C602
C623
C603
C604
C605
D602
618.00
D2:i '
618.00
D402
918.00
D604
D605
618.00
618.00
618.00
618.00
D223
D203
D204
D205
618.00
618.00
618.00
618.00
D423
D403
D404
D405
918.00
918.00
918.00
918.00
810.00
E602
966.00
E202
966.00
E402
1422.00
810.00
810.00
810.00
810.00
E623
E603
tb'B
966.00
966.00
966.00
966.00
E223
E203
E204
E205
966.00
966.00
966.00
966.00
E423 . '
E403
E404
E405
1422.00
1422.00
1422.00
1422.00
F102
1830.00
F602
2346.00
F202
2346.00
F402
2874.00
F123
F103
F623
F603
F604
2346.00
2346.00
2346.00
2346.00
F223
F203
2346.00
2346.00
2346.00
2346.00
F423
F403
F104
F105
1830.00
1830.00
1830.00
1830.00
F404
't-405
2874.00
2874.00
2874.00
2874.00
3855.00
G102
4317.00
G60'j
5637.00
G2U2
5637.00
G402
5637.00
3855.00
3855.00
3855.00
3855.00
G123
G103
G104
G105
4317.00
4317.00
4317.00
4317.00
G623
G603
G604
G605
5637.00
5637.00
5637.00
5637.00
G223
G203
G204
G205
5637.00
5637.00
5637.00
5637.00
G423
G403
G404
G405
5637.00
5637.00
5637.00
5637.00
HH002
9165.00
HH102
12165.00
HH602
13785.00
— 202
13785.00
HH402
15165.00
HH023
HH003
HH004
HH005
9165.00
9165.00
9165.00
9165.00
HH123
HH103
HH104
HH105
12165.00
12165.00
12165.00
12165.00
HH623
HH603
HH604
HH605
13785.00
13785.00
13785.00
13785.00
— 223
HHP03
HH204
HH205
13785.00
13785.00
13785.00
13785.00
HH423
HH403
HH404
HH405
15165.00
15165.00
15165.00
15165.00
19455.00
19455.00
19455.00
19455.00
Separate Con rol— 1 1 5-1 20 V
L002AA1A
31983.00
800
1600
1600
L003AA1A
L004AA1 A
L005AA1A
31983.00
31983.00
31983.00
-..'tJU.
$
$
Use NEMA Size 0
B202
K002AA1A
2250
Catalog
Number
CR306
B223
K003AA1A
K004AA1A
K005AA1A
230
460
575
List
Price,
GO-10G
288.00
230
460
575
220-240
440-480
550-600
Catalog
Number
CR306
NEMA Type 4/4X
Watertight, Dust-tight
(Stainless Steel) <3>
288.00
288.00
288.00
288.00
13167.00
13167.00
13167.00
1215
Use NEMA Size 0
B123
B103
B104
B105
J003AA1A
J004AA1A
J005AA1A
450
900
900
NEMA Type 12U>8>
Dust-tight, Driptight
Industrial Use
174.00
174.00
174.00
174.00
174.00
204.00
230
460
220-240
440-480
550-600
A 105
$
List
Price,
GO-10G
Catalog
Number
CR306
204.00
204.00
204.00
204.00
13167.00
575
A102
List
Price,
GO-10G
B002
J002AA1A
300
600
600
Catalog
Number
CR306
NEMA Type 3R
Rainproof
Sleet-Res slant
B023
B003
B004
B005
Separate Control— 1 15-120 V
220-240
440-480
550-600
Control
Circuit
Voltage©
$
List
Price,
GO-10G
Horsepower
Separate Con rol— 1 1 5-1 20 V
8
A002
List
Price,
GO-10G
Catalog
Number
CR386
Motor
Voltage
7
150
200
400
400
200-208
230-240
460-480
575-600
Catalog
Number
CR306
A023
A003
A004
A005
114
2
2
200-208
230-240
460-480
575-600
NEMA Type 1
General-Purpose
Open Type
Horsepower
Numbers (Size 00-5) listed in table.
Three heaters should be ordered as separate items. List Price
$9.00 each, GO-10H. Packaged in quantities of three; must be
ordered in multiples of three. Select heaters by using tables on
pages 1-71 to 1-75.
288.00
B402
B2U 1
B205
288.00
288.00
288.00
288.00
B423
B403
B404
B405
318.00
C202
318.00
C402
462.00
318.00
318.00
318.00
318.00
C223
C203
C204
C205
318.00
318.00
318.00
318.00
C423
C403
C404
C405
462.00
462.00
462.00
462.00
$
426.00
426.00
426.00
426.00
426.00
Note: See page 1-7 for single-phase forms.
© Pricing for 50-Hertz forms (at standard voltages) is the same as shown in table
for 60 Hertz. Listed prices for 460-480 Volt also apply to 380-415 Volt, 50 Hertz.
See page 1-2 for 380-415 Volt horsepower ratings.
© Motor full-load current should not exceed continuous ampere rating of starter.
® NEMA Types 4/4X and 12 starters are UL listed to include Class II Groups F and
G, Division 2 only, and Class III hazardous locations.
® External reset not included on standard listed forms.
© Refer to Coil Table, page 1-3 for other available starter coils and suffixes (sizes
00-6). For sizes 7-9 starters with other control circuit voltages, contact nearest
GE Industrial Systems — Electrical Distribution and Control Representative.
® Units are individually boxed and "Poly-Packed" six per carton as standard.
Reference:
See page 1-5.
1-6
r
1999 Issue
Prices and data subject to change without notice
GE NEMA Rated Full Voltage Starters
Section 7
GE Fastrac™ Program Service
Full Voltage Noncombination Starters
GE Fastrac Program covers nonreversing magnetic motor starters
(3-phase, 3-pole) in NEMA sizes 0-4 with a full range of options. It
also includes standard catalog torms of many other nonreversing
magnetic motor starters, magnetic reversing controllers, magnetic
two-speed controllers and magnetic contactors.
Combination Starters
Eighty percent of all the combination starters that GE sells are
available on a GE Fastrac Program basis.
Standard cycle: 2 weeks
GE Fastrac Program: 1 day
To order GE Fastrac starters, select and price items required that
are printed with red catalog numbers. Clearly indicate on the order
that Fastrac service is required.
Refer? nces:
DEP-C15 Fastrac Application & Selection Guide for NEMA Controls
DEP-078 Fastrac Now™—the motor starter you need is only
minutes away.
GE's 300-Line of NEMA rated controls has a complete offering of
full voltage nonreversing, reversing, two-speed and combination
motor starters, plus magnetic contactors.
They are available in NEMA Sizes 00-9; 600 Volts maximum, 1600
horsepower maximum. Open forms are available in sizes 00-9.
Type 1 enclosures are available in sizes 00-6. Types 3R, 12, 4, and
4X enclosures are available in sizes 0-6. The 300-Line has
standard specification approval by many major manufacturers for
the toughest industrial applications.
FASTRAC
Nonreversing Magnetic Motor Starters
(CR306, CR386 Series) . . . . . . . . . . .
Take Control With GE
Magnetic Reversing Controllers
(CR309 S e r i e s ) . . . . . . . . . . . . .
Fastrac Now™
Distributor-assembled kits for various enclosed starter
combinations. No point-to-point wiring required. Assembly
possible by anyone while retaining full UL listing. See pages 1-78
to 1-84 for Fastrac Now™ distributor-assembled starters.
.1-4 to 1-11
.1-12to1-17
Magnetic Two-Speed C o n t r o l l e r s . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18 to 1-23
Nonreversing Combination Magnetic Starters
(CR307, CR308, CR310, CR311, CR387,
CR390, CR385 Series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-24 to 1-38
Combination Magnetic Safety Starters
(CR307, CR308, CR310, CR311 Series). . . . . . . . . . . . . . . . . . .1-39 to 1-41
Magnetic Contactors
(CR305, CR385 S e r i e s ) . . . . . . . . . . . . . . . . . . . . . . . . . . .
.1-42to1-49
Supplementary Information For All Full Voltage Starters:
technical D a t a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2,1-3
Factory-Installed Modifications And
Modification K i t s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.1-50 to 1-61
Motor Current Ratings . . . . . . . . . . . . . . . . . . . . . . . . . .
..1-69,1-70
Heater Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . .
.1-71(01-75
Solid-State Overload R e l a y s . . . . . . . . . . . . . . .
Starter Selection......
Panel Mount Overload Relays . . . . . . . . . . . . . . .
NEMA Type Enclosures Only
. . .1-62to1-64
. 1-65
.1-66 to 1-68
. .1-76,1-77
Fastrac Now Distributor-Assembled S t a r t e r s . . . . . . . . . . . . . . . . 1-78 to 1-84
References:
See Publication Index, Section 18.
Data subject to change without notice
1999 Issue
1-1
GE NEMA Rated Full Voltage Starters
300-Line
Application Information and Technical Data
NEMA Size
0
1
2
3
4
5
6
7
8
9
1
2
2
3
3
714
7%
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
3
3
5
5
5
7V4
7V4
10
10
10
10
15
25
25
25
25
30
50
50
50
40
50
75
100
75
100
100
150
200
200
150
200
300
400
400
300
500
600
600
450
750
900
900
800
1350
1600
1600
1
^
1
1
2
2
5
5
10
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Vk
3
3
5
5
5
Th
10
15
15
15
15
20
30
30
30
25
30
50
60
60
60
75
125
150
150
125
150
250
NA
1Vz
2
2
250
250
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Continuous Current Max
Starters and Enclosed
Contactors
Open Contactors
9
10
18
20
27
30
45
50
90
100
135
150
270
300
540
600
810
900
1215
1350
2250
2500
Coil Burden (VA)
Inrush 2-Pole
Holding 2-Pole
Inrush 3-Pole
Holding 3-Pole
Inrush 4- and 5-Pote
Holding 4- and 5-Pole
151
24
151
24
151
24
151
24
151
24
151
24
151
24
151
24
151
24
528
60
528
60
576
75
1152
83
1152
83
1248
87
1248
2580
3360
1600
210
1600
210
NA
NA
1500
140
2900
300
NA
NA
2900
300
3600
400
NA
NA
Control Power Transformer
VA (Min)
50
50
50
100
Coil Operating Voltage
% Minimum Pickup
% Maximum Dropout
85
63
85
63
85
63
Switching Delay 3-Pole
Pickup Typical (Milliseconds)
Dropout Typical (Milliseconds)
15-30
7-15
15-30
7-15
Mechanical Lite Millions Nominal
20
3
00
Normal Starting Duty HP Rating®
Single Phase
115V60H2
230V 60Hz
Three Phase
200V 60Hz
230V 60Hz
380-41 5V 50Hz
460V 60Hz
575V 60Hz
Plugging or Jogging HP Rating©
SinglePhase
115V60Hz
230V 60Hz
Three Phase
200V 60Hz
230V 60Hz
380-415V50HZ
460V 60Hz
575V 60Hz
1
/3
1
VA
1V4
Vh
2
2
NA
NA
"
1'/2
15
87
1248
87
191
255
95
2580
191
3600
276
3360
255
NA
NA
200
250
500®
500®
1000®
1500®
1501®
85
68
85
65
85
85
85
85
65
65
65
50
85
50
85
50
15-30
7-15
20-40
20-45
7-15
20-45
7-15
30-50
7-15
15-25
30-50
15-25
60-90
100-150
80-125
25-100
80-125
25-100
20
20
10
5
5
5
1
1
1
0.5
15
17%
14%
48
53
48
75
79
106
203
263
302
17V4
1356
Weight (Less Carton)
Contactor (Pounds)
Starter (Pounds)
2A
3%
2%
33/4
2%
61/2
3V,
7%
Power Terminals
Wire Size Range
(75 DEG) AWG
Torque (Pounds-Inches)
14-8
20
14-8
20
14-8
20
14-4
50
10-1/0
8-3/0
200
1/0-500kcmil
300
2 2/0-500kcmil
3 2-600kcmil
150
375
500
4 2-600kcmil
500
NA
NA
50
50
50
50
50
50
65
65
65
65
65
Max. Noise (DBA)
365
© When operation of the controller requires jogging (inching) or plug stopping or when normal operation requires continued operation in excess of 5
operations per minute or 10 operations in a 10-minute period, the plugging or jogging horsepower ratings must be followed.
® In lieu of a 500 to 1500 VA control transformer, a 50 VA unit in conjunction with a control relay can be used as follows:
1. Wire control relay coil in control circuit on secondary side of control transformer.
2. Wire two poles of control relay in series with contactor coil at line voltage.
Mounting Position
Devices must be mounted to a sturdy vertical surface with the line
side terminals up. No other orientations are permitted.
Operating Temperature
Equipment is designed for ambient temperature outside of
equipment enclosures to be -25° to 40°C. When contactor is
energized, temperatures will be above outside ambient in
equipment enclosures. Temperature rises inside the enclosures
should be limited so that internal air temperature does not exceed
65° for sizes 00 to 6 and 60°C for sizes 7 to 9. If condensing
moisture is present, space heater kits should be used to prevent
condensation when contactor is not energized.
Storage temperature should be -30° to 65°C. If equipment is
stored over 1 week, it may be necessary to cover the equipment
and provide a source of heat to prevent condensation.
1-2
1999 Issue
Data subject to change without notice
GE NEMA Rated Full Voltage Starters
300-Line\
Application Information and Technical Data \
Short-Circuit Ratings
Control Transformers
Fusible forms of combination magnetic starters equipped with UL
labeled, nonrenewable, NEC-type fuses listed in the table below,
are adequate for installation on motor branch circuits where the
available short-circuit current at the incoming line terminals of the
starter does not exceed the value shown.
Circuit breaker-type combination magnetic starters equipped with
the circuit breakers listed in the table at right are adequate for
installation on motor branch circuits where the available shortcircuit current at the incoming line terminals of the starter does not
exceed the value shown.
For either type, it is recognized that maintenance of some
components may be required after a branch circuit fault and in
some cases a device may require replacement.
Where to Use
It is often desirable to use a control transformer in conjunction with
a magnetic starter or controller to provide low voltage control.
Fusible Combination Starters
NEMA
Size
Fuse Type
Maximum Symmetrical rms Amperes
H, K
0-3
4,5
0-5
J, RK-1.RK-5
100,000
6
J, L, RK-1.RK-5
100,000
Coil Suffix
(THIS TABLE IS TO BE USED FOR STARTER FORMS WITHOUT
CONTROL TRANSFORMERS.)
Indicates voltage and frequency of operating coils. For use in
ordering full voltage starters and contactors, Sizes 00-6, with other
coil ratings than those shown in listing on pages 1-6 to 1-49.
Frequency 24V
(Hertz)
5,000
10,000
H, K
Description—Factory Wired
A transformer, with sufficient capacity for the control circuit,
mounted with the starter can be supplied by the factory for the
majority of transformer ratings and types of enclosures.
60
Breaker
Type
Rating
Amperes
NEMA
Size
TEB
15-50
15-70
TEC®
TED
THED
TFJ&
600 Volt
5,000
5,000
5,000
5,000
~
3-30
3-50
15-50
30-100
50-150
0
1
25,000
25,000
25,000
25,000
25,000
25,000
25,000
25,000
25,000
25,000
5,000
5,000
5,000
5,000
5,000
3-30
3-50
15-50
30-100
50-150
0
1
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
r
i
r
1
5,000
25,000
5,000
25,000
5,000
r
25,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
15-100
25-150
TEC®
480 Volt
0
1
2
3
15-50
15-30
35-70
15-50
60-100
25-100
110-150
15-50
15-50
60-70
15-50
60-100
25-100
110-150
2
3
4
2
3
4®
0
i
/
-i
/
-,
/
T
1
-i
I
-i
1
1
2
3
0
1
2
3
-
i
5,000
5,000
25,000
5,000
25,000
5,000
25,000
5,000
r
1
r
i
r
i
65,000
65,000
65,000
65,000
65,000
65,000
42,000
14,000
25,000
14,000
25,000
25,000
25,000
25,000
5,000
25,000
5,000
25,000
5,000
25,000
5,000
TFK
70-225
4
22,000
22,000
22,000
THFK
70-225
4
25,000
25,000
10,000
TJK
THJK
TKM, TKC
THKM8
TB6, TBC
225-600
5
225-400 -i
450-600 /
5
300-800
300-800
300-800
6
r
t
10,000
10,000
10,000
35,000
10,000
35,000
10,000
25,000
10,000
42,000
65,000
65,000
30,000
35,000
65,000
22,000
25,000
42,000
© Open continuous Ampere ratings are for contactors only.
© Mag-Break® motor circuit protector with adjustable magnetic trip
(Amperes).
® Mag-Break motor circuit protector with adjustable magnetic trip
(Amperes) and current limiter.
® 100 Amperes and smaller current limiters are UL listed.
Data subject to change without notice
®
265-277V
02
23
03
110V
-
02
-
-
460-480V
575-600V
®
®
13
04
05
220V
380-41 5V
440V
550V
03
64
04
05
Note: The 02 coil suffix (115-120V, 60 Hz/110V, 50 Hz) supersedes the 22
coil suffix (120V, 60 Hz).
© Suffix shown for this voltage is part of Catalog Number in magnetic
starter-contactor listings.
Auxiliary Contact Ratings
NEMA Size 0-9
Amperes
AC Volts
s
Continuous
Make
Break
10
10
10
10
60
30
6.0
3.0
1.5
10
10
.—
115
230
460
575
15
12
1.2
DC Volts
125
250
1.1
0,5
Contactor DC Ratings
Interrupting Ratings
NEMA
Size
No. of
Poles in
Series
Continuous
Current
Rating
Inductive Amps
125 Volts
Noninductive Amps
250 Volts
250 Volts
125 Volts
N.O.
N.C.
N.O.
N.C,
N.O.
N.C.
N.O,
1
0.8
5
15
50
4
15
50
N.C.
1
2
3
4
9
9
9
9
2.5
7
14
25
2.5
7
14
25
0,6
1.2
3.5
7
0.5
1.2
3.5
7 '
5
4
25
35
50
25
35
• 50
1
2
3
4
18
18
18
18
2.8
7
14
25
2.5
7
14
25
0.7
1.5
3.5
7
0.5
1.2
3.5
7
6
35
50
90
4.5
25
35
60
1.1
6
25
60
0.9
4.5
25
55
1 .
1
2
3
4
27
27
27
27
3
7
14
25
2.5
7
14
25
0,7
1.5
3.5
7
0.5
1.2
3.5
7
6.5
50
70
120
4.5
25
35
60
1 .2
7
35
70
0.9
4.5
25
55
2
2
3
4
45
45
45
7
14
25
1.5
3.5
7
60
120
160
3
2
3
4
90
90
90
7
14
25
2.2
4.5
9
• 600
600
600
300
600
600
4
2
3
4
135
135
135
7
14
25
2.2
4.5
9
600
600
600
300
600
600
00
0
TJJ&
230-240V
®
- '
50
Maximum Symmetrical rms Amperes
240 Volt
200-208V
24
Frequency
(Hertz)
Circuit Breaker Combination Starters
11 5-1 20V
®
1999 Issue
9
40
80
1-3
GE NEMA Rated Full Voltage Starters
CH306, CR386 Nonreversing Magnetic Motor Starters
1600 Horsepower Maximum
NEMA Sizes 00-9
600 Volts Maximum
50/60 Hertz
Basic 300-Line Features
CONTACTOR
Captive saddle clamps
Staggered terminals
(optional above size 1)
Encapsulated coil
OVERLOAD RELAY
Manual Weld Check
Coil retainers
±10% trip adjustment
Armature retaining clip
Overload relay heaters,
(not shown)
Long-life armature
Visual trip indicator
Manual reset arm
Captive saddle clamps
Typical Size 1 Motor Starter
GE's full voltage (600-Volt maximum) magnetic motor starter has
an encapsulated coil and a 3-leg overload relay to protect against
overloads in all phases. It is on standard specifications of major
manufacturers. The line offers features and benefits most asked
for by users.
Forms available include reversing and nonreversing, two-speed,
and combination, sizes 00-9.
• Toolless contactor disassembly (Sizes 00-4)—allows
quick access for inspection and maintenance. Just release two
retainers and pull a clip to get at magnet, coil, and contacts.
CR306 Size 1 Motor Starter with Solid-State Overload Relay Installed
• Saddle clamp terminals (Sizes 00-1)—accommodate ring,
• Largest selection of modifications and accessory kitsspade, and stripped wire leads and carry permanent stampedin identification. Staggered arrangement makes wiring easier
includes auxiliary contacts, coils, fifth-pole addition, vertical and
and helps prevent shorting between phases.
horizontal mechanical interlocks, surge suppressors, control
circuit fusing, NEMA Type enclosures, push buttons, selector
• Current-carrying components—contact tips are weldswitches, indicating lights, control transformers, space heaters,
resistant silver cadmium oxide (fine silver on sizes 00 and 0
and more.
only). Contacts are installed in a wedge configuration for
positive make with minimum bounce.
Technical Features—Solid-State Overload
• Optional PF capacitor terminals—permit easy connection
• 2:1 Adjustable full load amps with tactile feedback dial
of power factor correction capacitors between contactor and
• Selectable 10/20/30 protection class
overload relay for energy conservation.
• Ambient insensitive within the stated operating temperature
• Class 20 overload protection.
range of -20° to +70°C
• Built-in thermal memory to prevent hot motor restarts
• Visual trip indicator with manual reset—to avoid surprise
• Protection against complete phase current loss
restarts. Reset occurs on arm upstroke so a tripped condition
• Phase current unbalance: Adjustable 20-50%
can't be overridden by holding the arm down.
• Manual reset (standard) and remote reset (optional) 24 Vdc or
• Manual weld check—provides a convenient test against
120 Vac
welding of overload relay contacts. Just depress the weld
• Accuracy: ±2%
check operator to trip the relay, run a simple continuity test
• Repeatability: ±2%
across the relay contacts, then depress the manual reset to
• Self-powered @ 50% of minimum current range
return the starter to service.
• Size: 1-6 (0.40A-540A, 600 V, 50/60 Hz)
• Unbalance trip signal for PLC operation
• Optional isolated NO contact on the overload relay• Manual trip
provides means of direct interface with programmable controller
• Visual trip indication
or computer to monitor performance and diagnose faults.
• Standard isolated 1 NO and 1 NC aux. contact (A600, Q600)
• Dual bimetals—anticipate overloads, responding to rising
• Built-in line/load straps
current and temperature with faster tripping on severe overloads
• Fits with existing 300-Line Starters
for better motor protection. Trip points are factory-calibrated
• Power factor correction terminals (sizes 1-4)
for accuracy.
• DIN rail mountable sizes 1 & 2
• ±10% trip adjustment—by turning a dial in the overload relay
face allows "tuning" the protection to the motor on the spot.
1-4
1999 Issue
Data subject to change without notice
GENEMA Rated Full Voltage Starter
CR306, CR386 Nonreversing Magnetic Motor Starter,
1600 Horsepower Maximurr
NEMA Sizes GO600 Volts Maximurr
50/60 Hert
Schematic Diagram
STOP
r
START
_d
Typical CR306 Size 4
magnetic motor starter
Application
^xlx
y-
te
\
"
———o-^NrOOL
GE's magnetic motor starters listed here may be used for starting
full-voltage, nonreversing, single-speed ac motors up tp 1600
horsepower, 600 Volts maximum, providing protection to the
motor against running or stalled overloads.
Their compact size and ease of wiring make them especially
suitable for motor control centers, custom-type control panels,
and switchgear equipment. Refer to page 1-4 for features of basic
starter.
1
a
>
{OL
i
OL
>
Typical Schematic Diagram for CR306 Starter
(NEMA Sizes 00-6)
Ordering Directions
1. Specify starter by complete Catalog Number.
Example: CR306C103 is a Size 1 starter with 230-240-Volt,
60-Hertz coil and in Type 1 general-purpose enclosure @
$246.00, GO-10G.
2. The final letter of the Catalog Number denotes extra auxiliary
contacts (sometimes referred to as auxiliary interlocks). Order
the desired extra auxiliary contacts by replacing the final letter
with one from first column of auxiliary interlock table (see page
1-58).
Example: CR306C103AAB is Size 1 starter with one extra
normally open, auxiliary contact @ $312.00, GO-10G.
3. Starter forms are available with coils of other ratings than those
shown on pages 1-6 to 1-7. Refer to coil suffix table, page 1-3
for information. To order forms with other coil ratings, insert
suffix from coil table in place of fifth and sixth numbers of
listed starter Catalog Number shown on pages 1-6 to 1-7.
Example: A CR306C102 NEMA Size 1, three-pole starter in
Type 1 enclosure with 24-Volt, 60-Hertz coil becomes a
CR306C124 Catalog Number.
4. For continuous rated motors with a service factor of 1.15 to 1.25
select the heater with maximum motor Amperes equal to or
immediately greater than the actual full-load current taken
directly from the nameplate of motor. Order heaters by
complete Catalog Number from appropriate heater tables on
pages 1-71 to 1-75. List Price $9.00 each, GO-10H. Packaged
in quantities of three; must be ordered in multiples of three.
References:
Instructions
IT
NEMA Size
Publication Number
00,0,1
2
3
4
5
6
7-9
GEH-5190
GEH-4774
GEH-4806
GEH-4807
GEH-4839
GEH-5198
GEH-5108
Prices and data subject to change without notice
5. Order special modifications or forms not listed by complete
description using a listed Catalog Number as reference.
Example: Similar to CR306C104 except with 480/120-Volt
control transformer and red indicating light in cover.
Total List P r i c e . . . . . . . . . . . . . . . . . . . . . . . . $483.00, GO-10G.
6. Two-phase, four-wire forms are available. Contact nearest
GE Industrial Systems—Electrical Distribution and Control
Representative for pricing and ordering information.
Standard Coil Ratings
Standard Voltages (60 Hertz):
24,115-120, 200-208, 230-240, 265-277, 460-480 and 575-600
Standard Voltages (50 Hertz):
110, 220,380, 440 and 550
For price adders on special voltage and/or frequency coils, refer
to page 1-52.
50-Hertz Starters
Pricing of starters for use on 50 Hertz at standard voltages is the
same as shown in table for 60 Hertz. Refer to page 1-2 for threephase horsepower ratings at 380 Volts, 50 Hertz.
Factory-Installed
Modifications.......... pages 1-50 to 1-56
Field-Installed
Modification Kits....... pages 1-57 to 1-61
Heater Selection
Tables ................ pages 1-71 to 1-75
f 999 Issue