Accessories for Protective Devices Auxiliary Switch Z-HK, Z-AHK; Tripping Signal Switch Z-NHK • Design according to IEC/EN 60947-5-1, IEC/EN 62019 • Can be mounted subsequently (screws) • The specified minimum voltages are per contact Take into account particularly in case of series connection! • Z-AHK, Z-NHK: Contact function with relative movement (self-cleaning contacts) • Contact material and design particularly suitable for extra low voltage • Z-NHK: The function of one of the two change-over contacts can be switched from “auxiliary switch” to “tripping signal switch” • Tripping signal contact transmits message of electric tripping, not mechanical switch-off • Test key for contact function “electrical tripping” Connection diagrams Z-HK Z-AHK Z-NHK 13 21 22 14 Technical Data Electrical Can be mounted from the left onto Can be mounted from the right onto Contact function Rated voltage Frequency Rated current Rated thermal current Ith Utilisation category AC13 Rated operational current Ie Utilisation category AC15 Rated operational current Ie Utilisation category DC12 Rated operational current Ie Utilisation category DC13 Rated operational current Ie Rated insulation voltage UI Minimum operational voltage per contact Umin Minimum operational current Imin Rated peak withstand voltage Uimp (1.2/50µ) Conditional short circuit current Ik with back-up fuse 6A or PLSM-B4-HS Max. back-up fuse, overload and short circuit Mechanical Tripping indicator “electrical tripping” Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws Z-AHK Z-AHK Z-NHK PFIM, PFR CFI6, PFHM-4p – 1NO + 1NC 250 V 50/60 Hz 8A 8A CLS, L71, PFHM-2p CKN, PKDM – 1NO + 1NC 250 V 50/60 Hz 4A 4A CLS, L71, CKN, PKDM PFIM, PFR, CFI6, PFHM 2CO 250 V 50/60 Hz 4A 4A 6A/250V AC 2A/440V AC 3A/250V AC – 3A/250V AC – – 2A/250V AC 2A/250V AC – 0.5A/110V DC 0.5A/110V DC 0.5A/230V DC 2A/110V DC 4A/60V DC 250 V AC 24 V AC/DC 50 mA AC/DC 2.5 kV – – – 250 V AC 5 V DC 10 mA DC 2.5 kV – – – 250 V AC 5 V DC 10 mA DC 2.5 kV – 8 A gL / PLSM-B4-HS 1 kA 6 A gL / PLSM-B4-HS 1 kA 6 A gL / PLSM-B4-HS – – blue/white 45 mm 45 mm 45 mm 80 mm 80 mm 80 mm 8.8 mm (0.5MU) 8.8 mm (0.5MU) 8.8 mm (0.5MU) onto switching dev. onto switching dev. onto switching dev. IP40 IP40 IP40 finger and hand touch safe according to BGV A3, ÖVE-EN 6 lift terminals lift terminals lift terminals 0.5-2.5 mm2 0.5-2.5 mm2 0.5-2.5 mm2 M3 (Pozidrive Z0) M3 (Pozidrive Z0) M3 (Pozidrive Z0) max. 0.8-1.0 Nm max. 0.8-1.0 Nm max. 0.8-1.0 Nm Dimensions (mm) Z-HK Z-HK Z-NHK 329 Accessories for Protective Devices Example: Z-HK + PFIM Example: Z-AHK + PLS. 1NO+1NC 24V 50mA min. 1NO+1NC 5V 10mA min. Example: Z-NHK + PLS. PFIM + Z-NHK 2CO 5V 10mA min. 330 Accessories for Protective Devices Auxiliary Switch ZP-IHK, ZP-WHK; Tripping Signal Switch ZP-NHK • • • • • • • • Design according to IEC/EN 62019 No screws required. Can be snapped onto PLS and PKNM subsequently ZP-IHK, ZP-WHK: can be snapped on additionally 1 time onto itself The specified minimum voltages are per contact. Take into account particularly in case of series connection! Contact material and design particularly suitable for extra low voltage. Contact function with relative movement (self-cleaning contacts)e) ZP-NHK: The function of one of the two change-over contacts can be switched from “auxiliary switch” to "tripping signal switch" Tripping signal contact transmits message of electric tripping, not mechanical switch-off Test key for contact function “electrical tripping” Connection diagrams ZP-IHK ZP-WHK ZP-NHK • ZP-NHK: The “Service button” is used to check whether or not the auxiliary switch is correctly wired in the tripping-signal-switch position. Activating the “service button” will mechanically simulate an electrical switch-off, so the mechanism for the electrical switchoff will disengage and can be checked. The main switchgear (MCB, combined MCB/RCD or RCD …) connected to the ZP-NHK auxiliary switch does not need to trip as well during an inspection through the service button. Technical Data Electrical Can be mounted from the left onto MCB: RCD/MCB: Accessories: Contact function Rated voltage Frequency Rated current Rated thermal current Ith Utilisation category AC13 Rated operational current Ie Utilisation category AC15 Rated operational current Ie Utilisation category DC12 Rated operational current Ie Rated insulation voltage UI Minimum operational voltage per contact Umin Minimum operational current Imin Rated peak withstand voltage Uimp (1.2/50µ) Conditional short circuit current Ik with back-up fuse 6A or PLSM-B4-HS Max. back-up fuse, overload and short circuit Mechanical Tripping indicator “electrical tripping” Frame size Device height Device width Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws Dimensions (mm) ZP-IHK, ZP-WHK ZP-IHK ZP-WHK ZP-NHK PLS, PLZ PKNM ZP-A40, ZP-ASA, Z-MS 1xZP-IHK, 1xZP-WHK 1NO + 1NC 250 V 50/60 Hz 6A 6A PLS, PLZ PKNM ZP-A40, ZP-ASA, Z-MS 1xZP-IHK, 1xZP-WHK 1CO 250 V 50/60 Hz 6A 6A PLS, PLZ PKNM ZP-A40, ZP-ASA, Z-MS – 2CO 250 V 50/60 Hz 4A 4A 3A/250V AC 3A/250V AC 3A/250V AC 2A/250V AC 2A/250V AC 2A/250V AC 0.5A/110V DC 250 V AC 5 V DC 10 mA DC 2.5 kV 0.5A/110V DC 250 V AC 5 V DC 10 mA DC 2.5 kV 0.5A/110V DC 250 V AC 5 V DC 10 mA DC 2.5 kV 1 kA 1 kA 1 kA 6 A gL / PLSM-B4-HS 6 A gL / PLSM-B4-HS 6 A gL / PLSM-B4-HS – – blue/white 45 mm 45 mm 45 mm 80 mm 80 mm 80 mm 8.8 mm (0.5MU) 8.8 mm (0.5MU) 8.8 mm (0.5MU) IP40 IP40 IP40 finger and hand touch safe according to BGV A3, ÖVE-EN 6 lift terminals lift terminals lift terminals 0.5-2.5 mm2 0.5-2.5 mm2 0.5-2.5 mm2 M4 (Pozidrive Z2) M4 (Pozidrive Z2) M3 (Pozidrive Z0) max. 1.2 Nm max. 1.2 Nm max. 0.8-1.0 Nm Example: ZP-IHK (ZP-WHK) + PLS. ZP-NHK Example: ZP-NHK + PLS. 331 Accessories for Protective Devices Shunt Trip Release Z-ASA, ZP-ASA • Remote release for subsequent mounting onto PLS, CLS6, PKN, PKDM, Z-A40, Z-MS • Module width 1MU • Additional installation of standard auxiliary switch is possible • Position indicator red - green • Type ZP-ASA for snap-on mounting Connection diagram 1 2 Technical Data Electrical Can be mounted onto RCDs, combined RCD/MCBs: Accessories: Operational voltage range Frequency Possible standard auxiliary switch Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity ZP-ASA24 ZP-ASA230 PLS, PKN ZP-A40, Z-MS 12-110V AC 12-60V DC 50/60 Hz ZP-NHK PLS, PKN ZP-A40, Z-MS 110-415V AC 110-220V DC 50/60 Hz ZP-NHK 45 mm 45 mm 80 mm 80 mm 17.5 mm (1MU) 17.5 mm (1MU) quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 IP40 IP40 finger and hand touch safe according to BGV A3, ÖVE-EN 6 open mouthed/lift open mouthed/lift + guide + guide 1-25 mm2 1-25 mm2 Dimensions (mm) Z-ASA ZP-ASA Connection Example 230 V Connection Example 24 V Example: Z-ASA + PLS Example: ZP-ASA + PLS 333 Accessories for Protective Devices Undervoltage Release Z-USA, Z-USD • Tripping: Instantaneous Z-USA Delayed Z-USD, typ. 0,4 s • Voltage control indicator blue/white • Service key for zero voltage switch-on for testing purposes • Can be used with PLS, CLS, Z-A40 and Z-MS Connection diagram 0,4 s Technical Data Z-US./115 Z-US./230 Z-US./400 Electrical Rated voltage Un Frequency Making threshold Tripping threshold 115 V AC 50-60 Hz 80% of Un 50% of Un 230 V AC 50-60 Hz 80% of Un 50% of Un 400 V AC 50-60 Hz 80% of Un 50% of Un Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Terminals Terminal capacity Terminal protection 45 mm 45 mm 45 mm 80 mm 80 mm 80 mm 17.5 mm (1MU) 17.5 mm (1MU) 17.5 mm (1MU) quick fastening on DIN rail IEC/EN 60715 IP40 IP40 IP40 open mouthed/lift open mouthed/lift open mouthed/lift 1 - 2x2.5 mm2 1 - 2x2.5 mm2 1 - 2x2.5 mm2 finger and hand touch safe, according to BGV A3, ÖVE-EN 6 Dimensions (mm) Connection Example Release Connection Examplees 400V and 230V Connection example Z-USA/400 + Z-MS 334 Connection example Z-USA/230 + CLS Protective Devices Accessories for Manual Motor Starters • Accessories for manual motor starters are the same as for PFIM, CLS etc. (releases, auxiliary switches, and busbars • Shunt trip release ZP-ASA • Undervoltage releases Z-USA: instantaneous Z-USD: delayed • Auxiliary switch ZP-IHK: 1 NO + 1 NC • Tripping signal switch ZP-NHK: 1 CO + 1 CO • Remote control and automatic switching device Z-FW • Moisture-proof enclosure IP54 Z-MFG Z-MFG/NL: with N-led through (solid neutral) Z-MFG/NOT: with N-led through (solid neutral) and EMERGENCY OFF key Installation Example ZP-NHK + Z-MS-2p + Z-FW-LP Dimensions (mm) ZP-IHK ZP-NHK ZP-ASA Z-USA, -USD Moisture-proof Enclosure Z-MFG • According to EN 50298 • Suitable for manual motor starters Z-MS, e.g. 3p (+ Z-USA); miniature circuit breakers CLS, e.g. 3p (+ Z-USA); circuit breakers Z-A40 • Earth conductor connection integrated in all types • Entries for 4 x PG16 cable glands prepared • Operation: Turning handle, can be locked in the OFF-position by means of 3 padlocks, max. Ø 6 mm • Enclosure cover can be sealed with leads in 2 locations • Scope of delivery: 4 entry bushes, 1 mushroom-shaped pushbutton (red) + 1 contact (NC) in Z-MFG/NOT Technical Data Electrical Power Loss of installed devices Mechanical Degree of protection Protection class Neutral connection Max. Device width Terminal capacity N/PE Tightening torque N/PE-terminals cover screws Z-MFG Z-MFG//NL Z-MFG/NOT max. 17 W max. 17 W max. 17 W IP54 II – 4MU max. 16 mm2 IP54 II integrated 4MU max. 16 mm2 IP54 II integrated 4MU max. 16 mm2 max. 2 Nm max. 2 Nm max. 2 Nm max. 2 Nm max. 2 Nm max. 2 Nm Dimensions (mm) Z-MFG Z-MFG/NL Z-MFG/NOT 328 Protective Devices Accessories for PLHT Shunt Trip Release Z-LHASA • • • • • Can be mounted subsequently Contact position indicator red - green Marking labels can be fitted Wide operational voltage range Sufficient power of extra low voltage source must be ensured Z-LHASA/24: min. 90 VA Connection diagram 1 2 Technical Data Electrical Operational voltage range Z-LHASA/230: 110-415 V~ Z-LHASA/24: 12-60 V~ Operational frequency 50-60 Hz Max. current consumption at point of switching on at Un Z-LHASA/230: 2A Z-LHASA/24: 18 A Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Upper and lower terminals 45 mm 90 mm 27 mm quick fastening on DIN rail IEC/EN 60715 IP40 lift terminals Dimensions (mm) Auxiliary Switch Z-LHK • Auxiliary switch according to IEC 947-5-1 • Can be mounted subsequently Connection diagram 13 21 22 14 Technical Data Electrical Rated operational current Minimum operational voltage Rated thermal current Rated insulation voltage Maximum back-up fuse Contacts Utilisation category AC13 Utilisation category DC13 (250 V~) 6A/AC13 24V each line 8A 440 V~ 6 A gL or CLS6-4/./B-HS 1NO+1NC 6A/250VAC 2A/440VAC 4A/60VDC 2A/110VDC 0.5A/230VDC Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Upper and lower terminals Terminal capacity Dimensions (mm) 319 45 mm 90 mm 9 mm mounted onto protective devices IP40 lift terminals 1 x 1mm2 to 2 x 2.5mm2 Protective Devices Accessories for PBHT Shunt Trip Release Z-BHASA • • • • • Can be mounted subsequently Contact position indicator red - green Marking labels can be fitted Wide operational voltage range Sufficient power of extra low voltage source must be ensured PBHT-ASA/24: min. 90 VA • Screws for mounting included PBHT => BHASA => PLHT Connection diagram 1 2 Technical Data Electrical Minimum pulse duration Internal resistance Duty Tripping time Peak withstand voltage (1.2/50µ) Endurance AC voltage range: Responding limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption DC voltage range: Responding limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Upper and lower terminal screws Terminal capacity Fastening torque of terminal screws Z-BHASA/24 Z-BHASA/230 15 ms 2Ω 100% < 20 ms 2 kV >4,000 operating cycles 10 ms 130 Ω 100% < 20 ms 2 kV >4,000 operating cycles 8V 12-60 V 1.4-7 A 4.0 ms 70 V 110-415 V 3.4 A (at 230V) 4.5 ms 11 V 12-60 V 1.7 A typ. 2 ms 90 V 110-230 V 1.7 A typ. 4 ms 45 mm 45 mm 90 mm 90 mm 27 mm 27 mm quick fastening on DIN rail IEC/EN 60715 IP40 IP40 lift terminals lift terminals 2.5-30 mm2 2.5-30 mm2 4 Nm 4 Nm Dimensions (mm) 282