Victorian Electricity Supply Industry Code of Practice

advertisement
VICTORIAN ELECTRICITY
SUPPLY INDUSTRY
CODE OF PRACTICE
LOW VOLTAGE SERVICE FUSE
REMOVAL & REINSERTION BY LICENSED
ELECTRICIANS and L & G CLASS INSPECTORS
VICTORIAN ELECTRICITY
SUPPLY INDUSTRY
CODE OF PRACTICE
LOW VOLTAGE SERVICE FUSE
REMOVAL & REINSERTION BY LICENSED
ELECTRICIANS and L & G CLASS INSPECTORS
This CODE OF PRACTICE has been developed by key electrical industry
stakeholders to ensure that disconnection and reinstatement of supply by
operation of Electricity Distributor service fuses at the supply interface to specified
Victorian electricity customers installations may be undertaken in a responsible
manner by Licensed Electricians and L & G Class Electrical Inspectors, other than
those working for Electricity Distributors.
Compliance with this Code permits these licensed persons to remove and reinsert
the Electricity Distributors service fuse link normally located in the customer
installations fuse holder under controlled conditions within specified installations
to disconnect and reconnect supply.
Increased electrical safety, efficiencies, reduced costs and maintenance of
responsible management for disconnection and reconnection of electricity to
customers will result from this Code.
1st print and issue - December 2000
2nd print - November 2002
Revision 1 - April 2014
2
FOREWORD
To: All licensed electricians and L & G Class electrical inspectors
CODE OF PRACTICE – LV FUSE REMOVAL AND REINSERTION
This Code of Practice (code) has been developed by key electrical industry stakeholders to facilitate
appropriately licensed persons to disconnect and reconnect the majority of electrical installations by the
removal and reinsertion of low voltage service fuse(s).
The initiative will greatly enhance the electrical safety of licensed persons who need to work on electrical
equipment in electrical installations such as main switchboards, and increase industry efficiencies by
reducing site visits for disconnection and reconnection purposes by electricity distribution companies
(Network Operators).
Service fuse links are assets which are owned by electricity distribution companies. Electricity Safety
Management Schemes made under the Electricity Safety (Management) Regulations 2009 limit the
operation of such assets to persons with qualifications, proficiency and experience to safely perform that
function. While Energy Safe Victoria takes the view that licensed electricians or inspectors should have
these skills, it supports the use of this code to reinforce those skills.
This code relates to fuse removal and reinsertion by licensed electricians and L & G Class electrical
inspectors. These licence holders should comply with the specified conditions, these conditions include:
• The necessity for those licence holders to be competent in fuse removal and reinsertion and use the
appropriate equipment and processes.
• Limitation of service fuse removal and reinsertion to direct metered installations with a maximum
demand of less than 100 Amps per phase.
• The distribution company must be advised of essential details where the licensed person intends to
remove and reinsert a service fuse to these installations. Failure to advise the distributor may result in
the distributor attending to investigate a meter alarm at the particular premises. Attendance by the
distributor under these circumstances may attract a service call charge.
• The licensed person shall contact the relevant distribution company for fuse removal and/or reinsertion
not covered by the code.
• The licensed person’s responsibilities and liabilities associated with this function, electricity distribution
company contact details and other essential information is included in the code.
Further specified conditions are listed and other sections of the code include, typical processes,
equipment, photos of typical equipment the fuse removal and reinsertion process.
Fuse removal outside these conditions should be the subject of negotiation between the distribution
company and the customer.
However, to ensure electrical safety is maintained, it is emphasised that licensed persons must be
competent and use the appropriate equipment and process.
I commend this Code of Practice to you and congratulate those industry organisations involved with the
development of the code.
Yours sincerely
Paul Fearon
DIRECTOR OF ENERGY SAFETY
2.
3
CONTENTS
SECTION
CONTENT
Page
Foreword
2
Definitions
3
1.
Preface
4
2.
Purpose
4
3.
Scope
4
4.
Specified Conditions
5
5.
Processes – typical
6
6.
Equipment – typical
6
7.
Photos – typical fuse removal & insertion
7
DEFINITIONS
Licensed Person – a holder of a current Electrician’s A Class Licence and/or Electrical
Inspector’s Class L or G Licence as issued by Energy Safe Victoria.
Code – Victorian Electricity Supply Industry Code of Practice Low Voltage Service Fuse
Removal & Reinsertion by Licensed Electricians and L & G Class Inspectors
Service Fuse – Means the Supply Protection Device (Fuse Link/Cartridge)
Fuse Assembly – Means Supply Protection Assembly which contains the service fuse
4
1.
PREFACE
This Code has been prepared and endorsed by the following organisations:
•
•
•
•
•
•
•
CitiPower Ltd
Energy Safe Victoria (ESV)
Jemena
Powercor Australia Ltd
SP AusNet
United Energy
NECA - National Electrical & Communications Association (Victorian Chapter)
The Code is managed by a Steering Committee consisting of a representative from each
of these organisations.
2.
PURPOSE
Supply to a customer installation within Victoria is normally controlled by an Electricity
Distributors fuse link located and sometimes sealed within a Fuse Assembly provided by
the customer.
This Code is to enable removal and reinsertion of LV service fuses for disconnection and
reconnection of specified customer’s installations connected to Victorian Electricity
Distribution Networks to be performed in a structured, orderly and efficient manner by other
than Electricity Distributors where this is deemed necessary by an appropriately licensed
person.
Benefits will include:
•
enhancement of safety while performing work on the parts of the electrical
installation that are not controlled by the main switch
•
reduction of frequency of electrical workers working live, thus providing
increased safety for electrical workers
•
increased industry efficiency and decreased costs by reducing the necessity for
Electricity Distributor personnel site visits.
3.
SCOPE
This Code permits licensed persons who have the competency to remove and reinsert
LV service fuses for the purpose of disconnection and reinstatement of supply. This Code
applies to direct metered Domestic, Commercial and Industrial Electrical Installations up to
100 A maximum demand per phase connected to an Electricity Distribution Network within
Victoria under the specified conditions section of this Code:
5
4.
SPECIFIED CONDITIONS
4.1. The licensed person shall be competent in the removal and reinsertion of LV
service fuses and use appropriate equipment and processes.
4.2. The licensed person shall obtain permission from the customer and any affected
occupier prior to supply removal, except in emergency conditions.
4.3. The licensed person shall not remove and/or re-insert LV service fuses to other
than Domestic, Commercial and Industrial Electrical Installations up to 100 A
maximum demand per phase connected to a Victorian Electricity Distributors
Network:
4.4. The licensed person shall notify the relevant Electricity Distributor on the following
telephone numbers prior* to removal of the service fuses/s and provide the
information listed:
Jemena
CitiPower
Powercor
SP AusNet
United Energy
•
•
•
•
•
•
•
•
131 626
131 280
132 412
131 799
132 099
Name, licence number and contact phone number of the licensed person
Certificate of Electrical Safety Number
Customer Name
Premises Address
Meter Number
Reason for disconnection
Disconnection time
Proposed reconnection time (ensure reference to item 6 for 3 phase
installations)
*In an emergency this information shall be provided at the earliest opportunity following the fuse removal.
4.5. The licensed person shall notify the relevant Electricity Distributor by telephone
following reinsertion of the service fuse/s and provide the following information:
•
•
•
•
•
•
Name and Licence Number (if different to original caller)
Certificate of Electrical Safety Number
Customer Name
Premises Address
Meter Number
Reconnection time
4.6. The licensed person shall arrange for the relevant Electricity Distributor to reinsert
the fuses if any work performed upstream of 3 phase meters affect the meters phase
rotation.
4.7. The licensed person shall maintain records including the time, date and location of
all service fuse removals and reinsertions. and the seal identification number where a
seal is required to be replaced.
4.8. The licensed person shall not interfere with Electricity Distributor assets other than
service fuses and their associated seals.
Note: The licensed person shall not interfere with the Electricity Distributor assets, these include, service cables,
meters, metering communications equipment, time switch, meter panel wiring and their associated seals.
6
4.9. The licensed person shall replace any service fuse seal which has been removed
with a commercially available seal that has a unique number. The seal number shall
be recorded in accordance with clause 4.7.
4.10. The licensed person shall not purport to represent any Electricity Distributor.
4.11. The licensed person shall minimise the time supply is disconnected.
4.12. The licensed person shall notify the relevant Electricity Distributor to arrange repair
where the service fuse or equipment is damaged during fuse removal or reinsertion.
4.13. The licensed person will limit unsupervised access to the live metal parts of a
service fuse assembly while the fuse is removed..
4.14. The licensed person shall perform all work in a manner which complies with good
industry practice and all applicable occupational health and safety laws and
regulations.
4.15. The licensed person shall comply with the conditions of this Code.
4.16. The licensed person accepts responsibility and all liability for any loss,
consequential loss, injury or damage resulting from any work performed under this
Code.
4.17. The licensed person will contact the relevant Electricity Distributor for service fuse
removal and reinsertions which are not covered by this Code.
5.
PROCESSES – TYPICAL
a.
b.
c.
d.
e.
f.
g.
h.
i.
6.
Obtain permission of customer and any affected occupant
Notify Distributor
Install notices, shed load (turn off main switches), remove service fuse and test
to ensure supply is isolated
Perform work and conduct mandatory tests
Limit unsupervised access to live metal parts of the service fuse assembly.
Reinsert service fuse and conduct live tests (voltage, polarity, phase sequence)
and re-seal fuse
Advise customer and any affected occupant
Inform Distributor
Record work details
EQUIPMENT - TYPICAL
a.
b.
c.
LV Fuse sticks
LV gloves
Testing equipment
• Earth Reel/Spike/Trailing Lead
• 3 Tube Neon Tester or approved Voltage Tester
This equipment is available through most Victorian Electrical Wholesalers.
7
7.
Typical Supply Protection Assemblies
Typical supply protection assembly
(overhead supply ≤ 100 amps)
Typical supply protection assembly
(underground supply ≤ 100 amps)
8.
Typical Supply Protection Assembly sealing devices
8.1.
The licensed person shall re-seal the Supply Protection Assembly at time of reinsertion, with an appropriate seal provided by the licensed person.