WIRING MATTERS Winter 07 Issue 25 FAIRGROUNDS, AMUSEMENT PARKS AND CIRCUSES The impact of the17th Edition of the Wiring Regulations Solar Photovoltaic Power Supply Systems Protective Conductor Currents 17th EDITION 1 public supply is given in ESQCR 2002. For sets above 16A the requirements of the distributor must be ascertained. The 17th Edition recognises that there are two connection options: (i) connection into a separate dedicated circuit. (ii) connection into an existing final circuit. Connection into a dedicated circuit is preferred. Regulation 551.7.2 sets out the requirements for the two options. The Regulation requires that a generating set used as an additional source of supply in parallel with another source shall either be installed on the supply side of all protective devices for the final circuits of the installation (connection into a separate dedicated circuit) or if connected on the load side of all protective devices for the final circuits must fulfil a number of additional requirements. THE IMPACT OF THE 17TH EDITION OF THE WIRING REGULATIONS by Geoff Cronshaw IN THIS second article we look at more of the changes expected in the 17th Edition of the IEE Wiring Regulations and the impact these will have on the design, erection and verification of electrical installations. This article is generally based on the Draft for Public Comment and therefore the actual requirements may change. Chapter 55 – other equipment. Regulation 551 – Low voltage generating sets This set of Regulations now includes additional requirements contained in Regulation 551.2 to ensure the safe connection of low-voltage generating sets including small scale embedded generators. A new Regulation 551.4.2, regarding the use of RCDs, has been added. Regulation 551.4.2 states: the generating set shall be connected so that any provision within the installation for protection by RCDs in accordance with Chapter 41 remains effective for every intended combination of sources of supply. Notes have been added including one to Regulation 551.1 stating that the procedure for connecting generating sets up to 16A in parallel with the These additional requirements are: (i) the current carrying capacity of the final circuit conductors shall be greater than or equal to the rated current of the protective device plus the rated output of the generating set and (ii) A generating set shall not be connected to a final circuit by a plug and socket and (iii) A residual current device providing additional protection of the final circuit in accordance with Regulation 415.1 shall disconnect all live conductors including the neutral conductor and (iv) The line and neutral conductors of the final circuit and of the generating set shall not be connected to earth and (v) Unless the device providing automatic disconnection of the final circuit in accordance with Regulation 411.3.2 disconnects the line and neutral conductors, it shall be verified that the combination of the disconnection time of the protective device for 왘 IEE Wiring Matters | Winter 07 | www.theiet.org 17th EDITION 2 왗 the final circuit and the time taken for the output voltage of the generating set to reduce to 50V or less is not greater than the disconnection time required by Regulation 411.3.2 for a final circuit. Section 559 luminaries and lighting installations Section 559 luminaries and lighting installations is a new series of Regulations giving particular requirements for fixed outdoor lighting installations, extra-low voltage lighting installations, and lighting for display stands. Section 559 includes requirements from Regulations 553-03 (lampholders) and 553-04 (lighting points) in the 16th Edition. This new section also includes requirements from Section 611 (Highway Power Supplies and Street Furniture) of the 16th Edition. The impact of this new section is that additional requirements are now included in the Regulations for general lighting including requirements for protection against fire, connection of luminaires to the fixed wiring, fixing of the luminaires, requirements for through wiring in a luminaire, requirements for control gear eg ballasts, and compensation capacitors. A further new requirement is the need to give consideration to stroboscopic effects. The Regulations for outdoor lighting installations has been expanded compared to Section 611 in the 16th Edition, to cover, car parks, gardens, parks, places open to the public, illumination of monuments and floodlighting. Other lighting arrangements specifically mentioned include telephone kiosks, bus shelters, advertising panels and town plans, which it is recommended are provided with additional protection by a 30mA RCD. Regulation group 559.11 is a completely new series of Regulations that were not included in the 16th edition covering requirements for extra-low voltage lighting installations. The particular requirements of these Regulations apply to extra-low voltage lighting installations supplied from sources with a maximum rated voltage of 50 V ac rms or 120 V dc The Regulations include requirements for protection against electric shock (SELV), protection against the risk of fire due to short circuit, types of wiring systems including special requirements where bare conductors are used, the types of transformers and converters, and requirements for suspended systems. New sections on special locations The 17th Edition includes additional sections on special locations not currently included in the 16th Edition as follows: Marinas Photovoltaic power systems Exhibitions, shows and stands Floor and ceiling heating systems Mobile and transportable units Fairgrounds, amusement parks and circuses Marinas: There are particular risks associated with electrical installations in marinas. The environment of a marina or yachting harbour is harsh for electrical equipment. The water, salt and movement of structures accelerate deterioration of the installation. The presence of salt water, dissimilar metals and a potential for leakage currents increases the rate of corrosion. There are also increased electric shock risks associated with a wet environment, by reduction in body resistance and contact with earth potential. Site investigations should be carried out at an early stage to determine likely maximum wave heights. This is of particular importance in exposed coastal sites. Where marinas have breakwater type pontoons, it is likely that under certain conditions waves will pass over the structure. The risks specifically associated with craft supplied from marinas include: i) Open circuit faults of the PEN 왘 Wiring Matters is produced by IET Services Limited, a subsidiary of The Institution of Engineering and Technology (IET), for the IET. Michael Faraday House, Six Hills Way, Stevenage, Herts, SG1 2AY, United Kingdom Tel: +44 (0)1438 313311 Fax: +44 (0)1438 313465 Advertising Sales D Smith +44 (0)1438 767224 daniellesmith@theiet.org | Editor G D Cronshaw +44 (0)1438 767384 gcronshaw@theiet.org | Contributing Editors M Coles, J Elliott, J Ware | Design Sable Media Solutions IEE Wiring Matters is a quarterly publication from the Institution of Engineering and Technology (IET). The IET is not as a body responsible for the opinions expressed. ©2007: The Institution of Engineering and Technology. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means without the permission in writing of the publisher. Copying of articles is not permitted except for personal and internal use. Multiple copying of the content of this publication without permission is always illegal. Web-offset printing by Wyndeham Heron, The Bentall Complex, Colchester Road, Heybridge, Maldon, Essex, UK Co-operating Organisations The Institution of Engineering & Technology acknowledges the contribution made by the following organisations in the preparation of this publication: British Electrotechnical & Allied Manufacturers Association Ltd – R Lewington, P D Galbraith, M H Mullins | Department for Communities and Local Government – I Drummond | Electrical Contractors Association – D Locke, S Burchell | City & Guilds of London Institute – H R Lovegrove | Energy Networks Association – D J Start | Electrical Contractors Association of Scotland SELECT – D Millar, N McGuiness | Health & Safety Executive – K Morton | Electrical Safety Council | ERA Technology Limited – M Coates | British Cables Association – C Reed | Scottish Building Standards Agency | DTI – D Tee | CORGI – P Collins | GAMBICA – K Morris. ISSN 1749-978-X IEE Wiring Matters | Winter 07 | www.theiet.org PWRRFP73 17th EDITION 4 conductor of PME supplies raising the potential to true earth of all metalwork (including that of the craft, if connected) to dangerous levels ii) Inability to establish an equipotential zone external to the craft iii) Possible loss of earthing due to long supply cable runs, connecting devices exposed to weather and flexible cord connections liable to mechanical damage. Particular requirements to reduce the above risks include: i ) Prohibition of a TN-C-S system for the supply to a boat. (Regulation 709.411.4) ii ) Additional protection by 30 mA RCDs in both the craft and the marina installation. (Regulation 709.531.2) iii) outlets to be installed at not less than 1m above the highest water level. (Regulation 709.553.1.13 does give certain exceptions.) There are also additional requirements to meet the conditions of external influences. PV supply systems This section applies to the electrical installations of PV power supply systems including systems with ac modules. Stand alone systems are still under consideration. This section includes the following additional measures: Regulation 712.410.3 – PV equipment on the dc side shall be considered to be energised, even when the system is disconnected from the ac side. Regulation 712.410.3.6 – The protective measures of non conducting location and earth free local equipotential bonding are not permitted on the dc side. Regulation 712.411.3.2.1.1 – On the ac side, the PV supply cable shall be connected to the supply side of the device supplying current using equipment. IEE Wiring Matters | Winter 07 | www.theiet.org Regulation 712. 537. 2.1.1 – To allow for maintenance, means of isolating the ac and dc sides of the PV convertor shall be provided. There are also additional requirements for accessibility, external influences, routing of protective conductors, selection and erection of cables to avoid the risk of lightning strike, short-circuit and earth faults, overcurrent protection, compliance with standards, protection against electromagnetic interference and devices for isolation. For detailed requirements of this section please refer to the specific article concerning PV systems in this edition of Wiring Matters. Exhibitions, shows and stands The risks associated with exhibitions, shows and stands are those of electric shock and fire. These arise from: 1. the temporary nature of the installation 2. lack of permanent structures 3. severe mechanical stresses 4. access to the general public. Because of these increased risks additional measures are required. Regulation 711.410.3.4 – A cable intended to supply temporary structures shall be protected at its origin by an RCD with maximum residual operating current 300mA. Regulation 711.3.1.2 – Bonding of all metallic structural parts which are accessible within the stand etc. Regulation 711.3.3 – Additional protection is required for all final circuits and sockets-outlets up to 32A by RCD to 415.1.1. Regulation 711.411.4 – TN-C-S shall not be used. Regulation 711.537.2.3 – every temporary structure, such as a vehicle, stand or unit, intended to be occupied by one specific user and each distribution circuit supplying outdoor installations shall be provided with its own readily accessible and properly identifiable means of isolation. Floor and Ceiling Heating Systems This Section applies to the installation of electric floor and ceiling heating systems; it does not apply to wall heating or outdoor heating systems. The risks associated with ceiling heating systems are generally that of penetration of the heating element by nails, drawing pins, etc pushed through the ceiling surface. For this reason Regulation 753.411.3.2 requires RCDs with a maximum rated residual operating current of 30mA shall be used for automatic disconnection of supply. Similarly, there are concerns that under-floor heating installations can be damaged by carpet gripper nails, etc and for similar reasons protection by a 30 mA RCD is required. To protect the building structure and provide precautions against fire, there are requirements to avoid overheating of the floor or ceiling heating system. Heating units manufactured without exposed conductive parts shall be provided on site with a grid with spacing of not more than 30mm, or other suitable conductive covering above the floor heating or below the ceiling heating and connected to the protective conductor of the installation. Mobile and transportable units The particular requirements of this Section apply to mobile or transportable units. These may be selfpropelled, towed or transportable containers or cabins. Examples of the units include technical and facilities vehicles for the entertainment industry, medical services, advertising, fire fighting, workshops, offices, transportable catering units etc. The risks associated with mobile and transportable units include: Risk of loss of connection to earth due to use of temporary cable connections, risks arising from the connection to different national and local electricity 17th EDITION 5 distribution networks, impracticality of establishing an equipotential zone external to the unit, open-circuit faults of the PEN conductor of PME supplies raising the potential of all metalwork (including that of the unit) to dangerous levels, risk of shock arising from high functional currents flowing in protective conductors, and vibration while the vehicle or trailer is in motion, or while a transportable unit is being moved – causing faults within the unit installation. Some of the requirements to reduce these risks include: Regulation 717.411.1 Automatic disconnection shall be by RCD. Regulation 717.411.3.1.2 Accessible conductive parts of the unit to be connected through the main equipotential bonding to the main earth terminal within the unit. Regulation 717.514 Identification adjacent to the supply inlet: (i) The type of supply which may be connected. (ii) The voltage rating of the unit. (iii) The number of phases and their configuration. (iv) The on board earthing arrangements. (v) The maximum power required by the unit. Persons involved in mobile or transportable units will need to refer to section 717 of the 17th edition of the Wiring Regulations. Fairgrounds, amusement parks and circuses This Section specifies the minimum electrical installation requirements to facilitate the safe design, installation and operation of temporary erected mobile or transportable electrical machines and structures which incorporate electrical equipment. The machines and structures are intended to be installed repeatedly, without loss of safety, temporary, at fairgrounds, amusement parks, circuses or similar places. The permanent electrical installation is excluded from the scope. This section does not apply to the internal electrical wiring of the machines. For detailed requirements of this section please refer to the specific article concerning fairgrounds, amusement parks and circuses in this edition of Wiring Matters. More information. Important: this article only considers a small number of changes expected in the 17th Edition. For more information refer to IET website, www.theiet.org Trade in your old installation or portable appliance tester for selected Fluke models and receive a free Fluke 117 Multimeter or £125!* Fluke Fluke 1653 1653 Installation Installation Tester Tester For a limited period, purchase a new Fluke 1652/1653 multifunction installation tester or a Fluke 6500 PAT, send your old tester, a claim voucher and proof-of-purchase to Fluke and claim £125 or a free Fluke 117 Digital Multimeter. The Fluke 1652 and 1653 installation testers comply with the latest standards such as EN61557, are simple to operate and are rugged and reliable. The Fluke 6500 Automatic PAT is optimised to give maximum performance for demanding portable appliance testing applications. For details on how to move up to the latest Fluke testers visit: www.fluke.co.uk/electrical, or contact Fluke directly on 020 7942 0700. *Terms and conditions apply Fluke Fluke 6500 6500 PAT PAT Fluke. Keeping your world up and running. TM Trade-in and move up – to a new Fluke tester! For more information, visit www.fluke.co.uk/electrical 020 7942 0700 FAIRGROUNDS 6 internal electrical wiring of machines (see BS EN 60204-1). Electrical Supplies The nominal supply voltage of temporary electrical installations in booths, stands and amusement devices should not exceed 230/400 V ac or 440 V dc. Supplies can be obtained from a number of sources: from the public network, i.e. the DNO generators, i.e. those mounted on trucks owned by the touring event from privately owned supplies, i.e. a local factory with sufficient sparecapacity FAIRGROUNDS, AMUSEMENT PARKS AND CIRCUSES by Mark Coles THIS ARTICLE looks at Temporary Electrical Installations for Structures, Amusement Devices and Booths at Fairgrounds, Amusement Parks and Circuses – a proposed new Section for BS 7671:2008, 17th Edition of the IEE Wiring Regulations. Currently, there is no Part or Section of BS 7671:2001(2004) covering such installations but information can be found in IEC 60364-7-740 and HD 60364-7-740. The proposed Section 740 of BS 7671:2008 is based on the CENELEC Harmonised Document HD 60364-7-740, of which, the UK is to incorporate the technical intent of that standard. (Please note that Regulations and Sections quoted within this article are from the proposed BS 7671:2008 and may be subject to change). IET Wiring Matters | Winter 07 | www.theiet.org The Scope of Section 740 Section 740 recognises that some installations are exposed to many differing and onerous circumstances, as they are frequently installed, dismantled, moved to a new location then installed and operated again. To compound problems, such installations can be exposed to the elements, open to the general public, house animals and livestock and be operated as a place of work. The equipment must function without compromising safety, therefore, the installation has to be fit for purpose and be designed to cope with ever-changing conditions. The permanent electrical installation, from which the temporary system is supplied, or the building in which the temporary system is housed, is excluded from the scope, nor does the scope apply to the There can be any number of electrical sources supplying the temporary system and it is of paramount importance that line-andneutral conductors from different sources are not interconnected. Where the supply is obtained from the DNO any instructions given must be adhered to. Supplies obtained from the DNO would preferably be TN-S but this isn’t always possible. A TN-S system has the neutral of the source of energy connected with earth at one point only, at, or as near as is reasonably practicable, to the source of supply. The consumer’s main earthing terminal is typically connected to the metallic sheath of the distributor’s SWA service cable. Where the available supply is TN-C-S, the supply should not be used in that form, i.e. a TT system should be created. The reason is that the ESQCR prohibits the use of a TN-C-S system for the supply of a caravan or similar construction. Where continuity of service is important, IT systems may be used for dc applications only. Protection against electric shock At the origin of each electrical supply, to all or part of the installation, an RCD, with a rated residual operating 왘 FAIRGROUNDS 8 왗 current not exceeding 300 mA, is to be installed to provide automatic disconnection of supply. As there will be further RCDs downstream of this point, this RCD should be of the S-type, complying with the requirements of BS EN 61008-1 or BS EN 61009-1 and incorporate a time delay in accordance with BS EN 60947-2, to provide discrimination with further RCDs protecting final circuits. For supplies to ac motors, RCDs should be the time-delayed or the S-type where necessary to prevent unwanted tripping. The protective measure of protection by obstacles is not permitted on this type of installation, however, placing out of arm’s reach is acceptable for electric dodgems – more of which later. Additional protection All final circuits in the installation, e.g. lighting, socket-outlets rated up to 32 A, mobile equipment connected by a flexible cable and rated up to 32 A are to be protected by an RCD having a rated residual operating current not exceeding 30 mA. The requirement for additional protection relates to the increased risk of damage to cables within an installation of this nature. Lighting circuits incorporating emergency luminaires, with selfcontained batteries for example, should be protected by the same RCD protecting that lighting circuit. This requirement for additional protection does not apply to: SELV or PELV circuits – this measure alone is deemed to be a protective measure in all situations circuits protected by electrical separation lighting circuits placed out of arm’s reach – provided they are not supplied by socket-outlets, i.e. those manufactured to BS 1363 or BS EN 60309-1; luminaire supporting couplers or plug-in lighting distribution units excepted IET Wiring Matters | Winter 07 | www.theiet.org BS EN 60332-1-2. Cables of type H07RNF or H07BN4-F (BS 7919) together with conduits complying with BS EN 61386-23 are deemed to satisfy this requirement. Cables should have a minimum rated voltage of 450/750 V, except that, within amusement devices, cables and cords having a minimum rated voltage of 300/500 V may be used. Where cables are buried in the ground, the route should be marked at suitable intervals and be protected against mechanical damage. Supplementary bonding Particular care must be taken in areas where livestock are housed as they are sensitive to small potential differences. To minimise potentials, supplementary bonding should be installed to connect all exposedconductive-parts and extraneousconductive-parts that can be touched by livestock. Where a metal grid is laid in the floor, or extraneous-conductive-parts are accessible, they should be included within the supplementary bonding of the location. It is important to note that animal excrement and urine is very corrosive and so all supplementary bonding connections should be enclosed in a suitable enclosure. THE INSTALLATION Wiring systems Conduit, cable trunking and ducting, tray and ladder systems can be used but must, of course comply with the manufacturer's instructions; the following standards apply: conduit systems BS EN 61386 series cable trunking systems/cable ducting systems BS EN 50085 (particular parts only) tray and ladder systems BS EN 61537 Cables All cables should be fire rated and meet the requirements of Electrical connections Joints should not be made in cables except where necessary as a connection into a circuit. Where joints are made, these should be either using connectors in accordance with the BS 7671, the manufacturer’s instructions or the connection should be made in an enclosure with a degree of protection of at least IP4X or IPXXD. Where strain can be transmitted to terminals the connection should incorporate cable anchorage(s). External influences Electrical equipment should have a degree of protection of at least IP44. Switchgear and controlgear Switchgear and controlgear should be placed in cabinets which can be opened only by the use of a key or a tool, except for those parts designed and intended to be operated by ordinary persons. Isolation It is a requirement that every electrical installation of a booth, stand or amusement device has its own means of isolation, switching and overcurrent protection, these devices should be readily accessible. There are similar requirements for supplies to amusement devices. Additionally, each distribution circuit should be provided with its own readily accessible and properly identified means of isolation. A device for isolation should FAIRGROUNDS 9 disconnect all live conductors – line(s) and neutral conductors. Examples of devices used for isolation are: circuit-breaker RCD plug and socket arrangement Luminaires Every luminaire and decorative lighting festoon-chain should have a suitable IP rating and be securely attached to the structure or support intended to carry it. Its weight should not be carried by the supply cable, unless it has been selected and erected for this purpose. Luminaires and decorative lighting festoon-chains mounted less than 2.5 m, i.e. arm’s reach, above floor level or could be otherwise accessible to incidental contact, should be firmly fixed, sited and guarded to prevent risk of injury to persons or ignition of materials. Access to the fixed light source should only be possible after removing a barrier or an enclosure, which should only be possible by the use of a tool. Lighting festoon-chains should use H05RN-F (BS 7919) cable or equivalent, they may be used in any length provided the overcurrent protective device in the circuit is correctly rated. Luminous tube, sign or lamps with an operating voltage higher than 230 V/400 V a.c., e.g. neon signs, are to be installed out of arm’s reach or be adequately protected from accidental or deliberate damage. A separate circuit should be used which should be controlled by an emergency switch. The switch should be easily visible, accessible and marked in accordance with the requirements of the local authority. Luminaires in shooting galleries and other sideshows where projectiles are used should be suitably protected against accidental or deliberate damage. When transportable floodlights are used, they should be mounted so that the luminaire is inaccessible to noninstructed persons. Supply cables should be flexible and have adequate protection against mechanical damage. Safety isolating transformers and electronic converters Safety isolating transformers should comply with BS EN 61558-2-6 or provide an equivalent degree of safety. Each transformer or electronic converter should incorporate a protective device which can be manually reset only; this device should protect the secondary circuit. Safety isolating transformers should be mounted out of arm’s reach or be mounted in a location that provides equal protection, e.g. in a panel or room that can only be accessed by a skilled or instructed person, and should have adequate ventilation. Access by competent persons for testing or by a skilled person competent in such work for protective device maintenance should be provided. Electronic converters should conform to BS EN 61347-2-2. Enclosures containing rectifiers and transformers should be adequately ventilated and the vents should not be obstructed when in use. Plugs and socket-outlets An adequate number of socket-outlets should be installed to allow the user's requirements to be met safely. In booths, stands and for fixed installations, one socket-outlet for each square metre or linear metre of wall is generally considered adequate. Socketoutlets dedicated to lighting circuits placed out of arm’s reach should be labelled according to their purpose. When used outdoors, plugs, socketoutlets and couplers should comply with BS EN 60309-2, or where interchangeability is not required, BS EN 60309-1. FIRE RISK Luminaires and floodlights Luminaires and floodlights should are to be fixed so that a focusing or concentration of heat is not likely to cause ignition of any material. Electric motors An electric motor which is automatically or remotely controlled and which is not continually supervised should be fitted with a manual reset protective device against excess temperature. ELECTRICAL EQUIPMENT Electrical supply to devices At each amusement device, there should be a connection point readily accessible and permanently marked to indicate the following essential characteristics: rated voltage rated current rated frequency Electric dodgems Electric dodgems should only be operated at voltages not exceeding 50 V a.c. or 120 V d.c. The circuit should have an electrical separation from the electrical supply by means of a safety isolating transformer in accordance with BS EN 61558-2-4 or a motor-generator set. Low voltage generating sets It is very important that all generators are located to prevent danger and injury to people through inadvertent contact with hot surfaces and dangerous parts. The electrical equipment associated with the 왘 IET Wiring Matters | Winter 07 | www.theiet.org FAIRGROUNDS 10 generator should be mounted securely and, if necessary, on anti-vibration mountings. Where a generator supplies a temporary installation, forming part of a TN, TT or IT system, care should be taken to ensure that the earthing arrangements are adequate and, in cases where earth electrodes are used, they are considered to be continuously effective. In reality this means that the drying of the ground, in summer, or freezing of the ground, in winter, should not adversely affect the value of earth fault loop impedance for the installation. The neutral conductor of the starpoint of the generator should, except for IT systems, be connected to the exposed-conductive-parts of the generator. INSPECTION AND TESTING The temporary installation The electrical installation between its origin and any electrical equipment should be inspected and tested after each assembly on site. Internal electrical wiring of roller coasters, electric dodgems, etc., are not considered as part of the verification of the electrical installation. In special cases the number of the tests may be modified according to the type of temporary electrical installation. The HSE offers guidance on the inspection and testing of the temporary electrical installation in the publication HSG 175 – Fairgrounds and Amusement Parks: Guidance on Safe Practice. The document is the result of work carried out by the Fairgrounds and Amusement Parks Joint Advisory Committee (FJAC) which has worked for over 25 years to continually improve standards and the exchange of information. Fairgrounds and amusement parks have been shown to be relatively safe compared to such activities as driving a car or riding a bicycle but there have been a small number of serious accidents involving the general public and employees. IET Wiring Matters | Winter 07 | www.theiet.org Amusement devices The Scope of Section 740 does not cover amusement devices but, in law, there is still a requirement to ensure that the devices are fit for use. The Amusement Device Safety Council (ADSC) is the policy making body for safety, self regulation and technical guidance in the UK amusement industry. This committee, in partnership with HSE, develops the policy for, and oversees the Amusement Device Inspection Procedures Scheme (ADIPS). ADIPS is the fairground and amusement park industry’s self regulated safety inspection scheme which registers competent ride inspectors and the rides they inspect. The purpose of the scheme is to promote and improve fairground and amusement park safety through rules and procedures relating to the annual inspection of the amusement devices. It is supported by industry associations who require that their members use ADIPS. ADIPS is also available to any operator of amusement devices as it demonstrates ‘best practice’ and their compliance with the Health and Safety at Work (etc) Act. Further information The following standards and publications have been referenced in this article or will provide further reading on the subject: BS 1363 – 13 A plugs, socket-outlets and adaptors BS 7919 – Electric cables. Flexible cables rated up to 450/750V, for use with appliances and equipment intended for industrial and similar environments BS EN 50085 – Cable trunking and cable ducting systems for electrical installations BS EN 60204-1 – Safety of machinery. Electrical equipment of machines. Specification for general requirements BS EN 60309-1 – Plugs, socket-outlets and couplers for industrial purposes. General requirements BS EN 60309-2 - Plugs, socket-outlets and couplers for industrial purposes. Dimensional interchangeability requirements for pin and contact-tube accessories BS EN 60332-1-2 – Tests on electric and optical fibre cables under fire conditions. Test for vertical flame propagation for a single insulated wire or cable. Procedure for 1 kW pre-mixed flame BS EN 60947-2 – Low-voltage switchgear and control gear. Circuit-breakers BS EN 61008-1 – Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs). General rules BS EN 61009-1 – Residual current operated circuitbreakers with integral overcurrent protection for household and similar uses (RCBOs). General rules BS EN 61347-2-2 – Lamp controlgear. Particular requirements for d.c or a.c. supplied electronic step-down convertors for filament lamps BS EN 61386 – Conduit systems for cable management. General requirements BS EN 61537 – Cable management. Cable tray systems and cable ladder systems BS EN 61558-2-6 – Safety of power transformers, power supply units and similar. Particular requirements for safety isolating transformers for general use IEC/HD 60364-7-740 – Electrical installations of buildings – Part 7-740: Requirements for special installations or locations – Temporary electrical installations for structures, amusement devices and booths at fairgrounds, amusement parks and circuses HSG 175 – Fairgrounds and Amusement Parks: Guidance on Safe Practice ISBN 978-0-7176-6249-4 ADIPS – www.adips.co.uk Thanks to Ken Morton of the HSE. PV POWER SUPPLY SYSTEMS 12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems. The additional requirements planned for inclusion in BS 7671:2008 along with some explanations are discussed in this article. As with any low voltage installation, the general requirements in Parts 1 to 6 of BS 7671:2008 have also to be met which include in Part 5, Section 551, requirements for low voltage generating sets. Please note that a list of definitions is included at the end of this article. The risks The particular risks associated with solar photovoltaic systems are: PV systems cannot be switched off. Modules produce electricity when exposed to daylight. Hence, unlike most other electrical installation work, the installation of a PV system typically involves working on a live system. Regulation 14 of the Electricity at Work Regulations gives requirements that must be met. Special precautions should be made to ensure live terminals are either not accessible or cannot be readily touched during installation and maintenance. Such terminals will be live at all times during daylight hours. It is important that anyone opening an enclosure is aware of this. An electrician who has come to work on the electrical installation needs to be aware that there is a second source of energy which will also need to be isolated. IET Wiring Matters | Winter 07 | www.theiet.org PV modules are current-limiting devices which require a nonstandard approach when designing fault protection systems for the dc side, as fuses are not likely to operate under short-circuit conditions. A different approach to fault protection is often needed, such as sizing the conductors for the maximum fault current that can flow at any given point in the circuit. PV systems include dc wiring, with which few electrical installers are familiar. PV presents a unique combination of hazards – due to risk of electric shock, falling and simultaneous manual handling difficulties. All of these hazards are encountered as a matter of course on a building site, but rarely all at once. While roofers may be accustomed to minimising risks of falling or injury due to manual handling problems, they may not be used to dealing with the risk of electric shock. Similarly, electricians would be familiar with electric shock hazards but not with handling large objects at heights. The particular requirements of Section 712 of BS 7671:2008 apply to electrical installations of PV power supply systems which will only work when connected in parallel with an electricity supply. The requirements in this section are not intended for PV systems for standalone operation. The requirements are for PV systems assembled from items of equipment, not supplied as a complete unit. PV modules junction box DC side AC side inverter meter consumer unit Figure 1: Block diagram of a PV system The Electricity Safety, Quality and Continuity Regulations 2002 A solar photovoltaic (PV) power supply systems described in Section 712 is required to meet the requirements of the Electricity Safety, Quality and Continuity Regulations 2002 as it is an embedded generator. Where the output does not exceed 16 A per phase the PV system is considered as a small-scale embedded generator (SSEG) that is exempted from certain of the requirements provided that: the equipment should be type 왘 PV POWER SUPPLY SYSTEMS 14 tested and approved by a recognised body, the consumer’s installation should comply with the requirements of BS 7671, the equipment must disconnect itself from the distributor’s network in the event of a network fault, and the distributor must be advised of the installation before or at the time of commissioning. Connection of a PV system to the electrical installation A PV system used as an additional source of supply in parallel with another source should preferably be connected on the supply side of all the protective devices for the final circuits of the installation. If a PV system is to be connected on the load side of all the protective devices for a final circuit of the installation additional requirements given in Regulation 551.7 of BS 7671: 2008 must be met. PROTECTION FOR SAFETY Protection against electric shock PV equipment on the dc side must be considered energized, even when the system is disconnected from the ac side. Protection by the use of Class II or equivalent insulation should preferably be adopted on the dc side. Protection by non-conducting location or earth-free local equipotential bonding is not permitted on the dc side. On the ac side, the PV supply cable should be connected to the supply side of the protective device for automatic disconnection of circuits supplying current-using equipment. Where an electrical installation includes a PV power supply system without at least simple separation between the ac side and the dc side, an RCD installed to provide fault protection by automatic disconnection IET Wiring Matters | Winter 07 | www.theiet.org string cables N strings (connected in parallel) main DC cable M modules per string (connected in series) Figure 2: Simplified circuit of dc side of supply should be type B. B type residual current circuit-breakers provide specific protection of single and three-phase installations and people even in the presence of dc fault currents on the network generated by controllers and variable speed drives, battery chargers and inverters and power supplies They are a requirement for single and three-phase supplied applications, where Class l equipment installed downstream from the RCCB is likely to produce dc component fault currents (pure dc fault). Type B RCDs also provide protection against sinusoidal ac residual currents (AC type) and pulsed dc residual currents (A type). However, where the PV convertor is, by construction, not able to feed dc fault currents into the electrical installation, a type B RCD is not needed. Protection by extra-low voltage: SELV and PELV For SELV and PELV systems, UOC STC replaces Uo and must not exceed 120 V dc Protection against overload on the dc side Overload protection may be omitted to PV string and PV array cables when the continuous current-carrying capacity of the cables is equal to or greater than 1.25 times ISC STC at any location. Overload protection may be omitted to PV main cables when the continuous current-carrying capacity of the PV main cable is equal to or greater than 1.25 times ISC STC of the PV generator. Protection against short-circuit current The PV supply cable must be protected against short-circuit current by an overcurrent protective device installed at the connection to the ac mains. Isolation and switching To allow maintenance of the PV converter, means of isolating the PV converter from the ac side and the dc side must be provided. ac side. Means of isolation should be provided on the ac side. A switchdisconnector should be installed adjacent to the inverter. The device should switch all live conductors and should be able to be locked off. A further means of isolation should be provided at the consumer unit or distribution board. At the point of installation of any ac isolator, the public supply should be considered as the source and the PV system should be considered as the load. PV POWER SUPPLY SYSTEMS 15 dc side. A switch disconnector must be provided on the dc side of the PV converter. The dc switch should switch all live conductors and must be suitably rated for the required dc operation. Switching ac is less demanding than switching dc – with an ac supply, the voltage passes through 0 V many times a second. A switch planned to be used on the dc side must be rated to break dc; an equivalent ac-rated switch is not acceptable or safe. dc connectors. Connectors, where used to connect PV modules, PV strings or the inverter should be dc rated and touch safe (i.e. the IP rating should be not less than IP21). They should be of Class II design, shrouded and of a design totally dissimilar in appearance to any other connectors used in the installation. Selection and erection PV modules should comply with the requirements of the relevant equipment standard, e.g. BS EN 61215 for crystalline PV modules. PV modules of class II construction or with equivalent insulation are recommended if UOC STC of the PV strings exceeds 120 V dc The PV array junction box, PV generator junction box and switchgear assemblies should comply with BS EN 60439-1. Electrical equipment on the dc side must be suitable for direct voltage and direct current. PV modules may be connected in series up to the maximum allowed operating voltage of the PV modules (UOC STC of the PV strings) and the PV converter, whichever is lower. Specifications for this equipment shall be obtained from the equipment manufacturer. If blocking diodes are used, their reverse voltage shall be rated for 2 x UOC STC of the PV string. The blocking diodes shall be connected in series with the PV strings. As specified by the manufacturer, the PV modules should be installed in such a way that there is adequate heat dissipation under conditions of maximum solar radiation for the site. Cables routed behind a PV array should be rated for a temperature of at least 80°C. Cable should be installed so as to minimise the risk or earth faults and short circuits. Cables should be sized such theat the voltage drop between the array and inverter is less than 3 per cent. External cables 왘 for skills wred 17th Edition of the IEE Wiring Regulations (BS7671:2008) With a commitment to quality and exceptional service, our flexible qualifications provide a recognised mark of excellence for the building services engineering sector. • • Portfolio of four new qualifications for 17th Edition • Developed through consultation with SummitSkills along with the ECA and NICEIC Allows new entrants and existing electricians to reach national standards of achievement For further information, visit www.eal.org.uk or contact Customer Services on: Tel: +44 (0)870 240 6889 Fax: +44 (0)870 240 6890 Email: customercare@eal.org.uk IET Wiring Matters | Winter 07 | www.theiet.org PV POWER SUPPLY SYSTEMS 16 Distribution board 4 Overcurrent protective device (712.434.1) 3 PEN/PE Main equipotential bonding bar supply point Protective equipotential bonding, if relevant Metering as required Circuits supplying currentusing equipment PV generator Bypass diodes, if relevant AC side DC side I PV string Blocking diode, if relevant (712.512.1.1) PV supply cable switchgear assembly Devices for isolation (712.537.2.1.1 and 712.537.2.2.5) PV DC main cable L+ RCD, if relevant PV invertor Transformer, if relevant DC L- PV module AC Device for isolation (712.537.2.2) U Common enclosure (optional) Overvoltage protective device, if relevant PV generator junction box PV string cable Overcurrent protective device, if necessary Figure 3: PV system – general schematic, one array should be UV stable, water resistant and flexible. For the dc system, it is recommended that Class II equivalent wiring, connections and equipment is used wherever possible as this will reduce fire risk. PV string cables, PV array cables and PV dc main cables must be selected and erected so as to minimise the risk of earth faults and shortcircuits. This may be achieved for example by reinforcing the protection of the wiring against external influences by the use of single-core sheathed cables. The cable connecting the inverter to the consumer unit or distribution board must, as for any circuit, have overcurrent protection which includes both overload and fault protection. Accessibility. The selection and erection of equipment shall facilitate safe maintenance and shall not adversely affect provisions made by the manufacturer of the PV equipment to enable maintenance or service work to be carried out safely. The inverter should carry a current Engineering Recommendation G77/1 Earthing arrangements and protective conductors IET Wiring Matters | Winter 07 | www.theiet.org type test certificate. A key requirement is that the inverter will disconnect the PV system when the distribution system is not energised. This is to prevent the hazardous situation of the photovoltaic system feeding the network or local distribution system during a planned or unscheduled loss of mains. Such an event is termed ‘islanding’ and presents a potential danger to those working on the network/distribution system. Where protective equipotential bonding conductors are installed, they shall be parallel to and in as close contact as possible with dc cables and ac cables and accessories. Lightning protection system Where there is a perceived increase in risk of lightning strike as a consequence of the installation of a PV system advice should be taken from a lightning protection system specialist as to whether a separate lightning protection system should be installed. Additionally, if the PV array has a metal frame which is not required to be earthed because it is of Class II construction, advice should be taken as to whether it should in fact be connected to the Main Earthing Terminal when considering lightning protection implications. Where a lightning protection system is already PV POWER SUPPLY SYSTEMS 17 Figure 4: PV system – general schematic with more than one array present, it is considered best practice to main bond the array frame to the Main Earthing terminal. Where an LPS is installed or is to be installed, PV system components should be mounted away from lightning rods and down leads. Long leads, for example dc main cables connecting the array to the inverter that are over 50m in length, should be installed in earthed metal conduit or trunking. To minimize voltages induced by lightning which could result in electromagnetic interference, the area of all wiring loops should be kept as small as possible. LABELLING Junction boxes. All junction boxes (PV generator and PV array boxes) must carry a warning label indicating that parts inside the boxes may still be live even after isolation from the PV converter. The dc isolator should be labelled as ‘PV array dc isolator’, with the ON and OFF positions clearly marked. Switch enclosures should also be labelled with ‘Danger, contains live parts during daylight’. The ac isolator should be labelled as ‘PV system isolator’ with the ON and OFF positions clearly marked. from the origin At the consumer unit or distribution board to which the generating set is connected At all points of isolation of both sources of supply. The warning notice should have the following wording: _____________________________________ WARNING - DUAL SUPPLY Additional source. As the installation includes a generating set, the PV system, which is used as an additional source of supply in parallel with another source, and warning notices should be affixed at the following locations in the installation: Isolate the mains supply at..................... Isolate the generator at........................... _____________________________________ At the origin of the installation At the meter position, if remote All labels shall be clear, easily visible, constructed and affixed to 왘 Isolate both mains and on-site generation before carrying out work. IET Wiring Matters | Winter 07 | www.theiet.org PV POWER SUPPLY SYSTEMS 20 last and remain legible for the life of the installation. Parallel operation Further requirements with regard to a PV installation operating in parallel with the public supply system are given in Regulation 551.7 of BS 7671. Definitions, and explanations PV – Solar photovoltaic. PV cell – Basic PV device which can generate electricity when exposed to light such as solar radiation. A photovoltaic cell acts as a current source, hence PV modules are current limiting devices – even under short circuit conditions, the output current of a module will not rise above a certain level (Isc). Operating a module in short circuit is in general of little consequence, indeed many charge controllers in battery charging systems routinely short circuit an array output. PV module – Smallest completely environmentally protected assembly of interconnected PV cells. Some modules have an electrical output that is considerably higher during the first weeks of operation. This increase is on top of that produced by temperature/irradiance variation. Typically, operation during this period will take Voc, Isc (and nominal power output) well above any value calculated using a standard multiplication factor. To avoid oversizing for this eventuality the array could be left disconnected for that initial period. Refer to the manufacturer for this information. PV string – Circuit in which PV modules are connected in series, in order for a PV array to generate the required output voltage. PV module string circuits cannot rely on conventional fuse protection for automatic disconnection of supply under fault conditions. This is because the short circuit current is little more than the operating current – a fuse would simply not operate. IET Wiring Matters | Winter 07 | www.theiet.org Figure 5: PV system PV array – Mechanically and electrically integrated assembly of PV modules, and other necessary components, to form a dc power supply unit. PV array junction box – Enclosure where all PV strings of any PV array are electrically connected and where protection devices can be located if necessary. PV generator – Assembly of PV arrays. PV generator junction box – Enclosure where all PV arrays are electrically connected and where devices can be located if necessary. PV string cable – Cable connecting PV modules to form a PV string. PV array cable – Output cable of a PV array. PV dc main cable – Cable connecting the PV generator junction box to the dc terminals of the PV inverter. PV inverter – Device which converts dc voltage and dc current into ac voltage and ac current. PV supply cable – Cable connecting the ac terminals of the PV inverter to a distribution circuit of the electrical installation. PV ac module – Integrated module/ invertor assembly where the electrical interface terminals are ac only. No access is provided to the dc side. PV installation – Erected equipment of a PV power supply system. Standard test conditions (STC) Test conditions specified in IEC 60904-3 for PV cells and modules. Open-circuit voltage under standard test conditions UOC STC Voltage under standard test conditions across an unloaded (open) generator, or on the dc side of the convertor. Short-circuit current under standard test conditions ISC STC Short-circuit current of a PV module, PV string, PV array or PV generator under standard test conditions. dc side Part of a PV installation from a PV cell to the dc terminals of the PV inverter. ac side Part of a PV installation from the ac terminals of the PV inverter to the point of connection of the PV supply cable to the electrical installation. Simple separation Separation provided between circuits or between a circuit and earth by means of basic insulation. CPC currents 23 Protective conductor current. Electric current which flows in a protective conductor under normal operating conditions. PROTECTIVE CONDUCTOR CURRENTS by Stewart Langdown of TridonicAtco UK Ltd FLUORESCENT LIGHTING or other discharge lighting often incorporates electronic high frequency control gear which provides many advantages, including: energy saving ability to provide dimming, lower weight increased lamp life reduction or elimination of stroboscopic effects instant start A consequence of the use of such control gear is that often electrical filters have to be provided to suppress high frequency noise being superimposed on the mains supply. These filters generally consist of series-connected inductors in each live conductor with capacitors connected between the live conductors and the circuit protective conductor. The small filter capacitors connected between the live conductors and the circuit protective conductor result in a small but non-negligible, protective conductor current. Where a large installation incorporates many luminaires, such as a large office block, the resultant protective conductor current, in the earthing conductor for the installation, can add up to a few amperes. Protective conductor currents can also result from the mains input filters associated with switch-mode powersupplies of IT equipment and other equipment such as photocopiers, fax machines and motorised equipment employing variable speed drives. See figure 1. IEC 598 gives the maximum value for leakage current as < 0.5 mA for Class 0 and II and 1 mA for Class I luminaires. Definitions The current flowing in the protective conductor is often referred to as ‘Earth leakage current’. The definition of protective conductor current, from Part 2 of the 16th Edition of BS 7671, is: The term Earth Leakage current is no longer defined. Interestingly, in the 17th Edition of BS 7671, it is planned that protective conductor current will be defined as: Protective conductor current. Electric current appearing in a protective conductor such as leakage current or electric current resulting from an insulation fault. The definition planned for the 17th Edition represents a clarification, in that both continuous protective conductor current due to normal operation and occasional protective conductor current due to faults are recognized. Protective conductor current is generally thought of as the difference of the currents flowing in the line and neutral conductors. Typically this is between the current carrying conductors and the case or frame of the electrical device, which is almost inevitably connected to earth. However protective conductor current may result from currents flowing in interconnecting cables, such as the outer screen of signal cables, that are connected between different 왘 Figure 1: A typical filter circuit which includes series connected inductors, bypass capacitors and resistors to discharge the capacitors IET Wiring Matters | Winter 07 | www.theiet.org CPC currents 24 왗 items of electrical equipment. See figure 2. The leakage current need not flow via the protective or functional earth. Signal cables coupled to the frame or casing can provide additional routes for protective conductor current flow. There is a risk of electric shock if a protective conductor becomes disconnected because where the circuit supplies Class I equipment under earth fault conditions there will be no path for the fault current to flow to earth causing operation of the protective device. In addition, the metal case of the item of equipment is likely to remain at an elevated potential presenting a latent risk of shock for someone contacting the case and an item of earthed metalwork, such as a metallic water pipe. Furthermore, where an item of equipment has a protective conductor current, should there be a break in the protective conductor, the metal case of the item of equipment will attain an elevated potential posing a risk of electric shock. This shock risk is extended to all the items of equipment on the particular circuit, whether they individually have high protective conductor currents or not. RCD operation. Equipment causing protective conductor currents connected downstream of a residual current device (RCD) can affect the operation of the device. An RCD operates by monitoring the difference between the line and neutral conductor currents and, when the difference – which represents the earth leakage current – exceeds a predetermined limit, it will operate and disconnect the circuit. The RCD detects the difference between phase and neutral conductor currents. The difference in the currents may be due to a fault or due to filters in the equipment supplied. The RCD is generally installed for the purpose of detecting an earth fault, providing the circuit is properly IET Wiring Matters | Winter 07 | www.theiet.org equipment RCD interconnected equipment filter fault protective conductor current due to filter protective conductor current due to a fault protective conductor current due to interconnected equipment Figure 2: Protective conductor currents resulting from a filter, a fault or interconnecting cables. Figure 3: RCD operation under fault conditions. The RCD monitors the difference between phase and neutral currents which represents the fault current. The fault current flows in the protective conductor circuit. When this fault current exceeds a predetermined limit, the RCD operates and disconnects the circuit. designed, as the current resulting from a fault is generally significantly higher than other protective conductor currents. Design considerations. An installation containing a number of luminaires with electronic switchgear, IT equipment or interconnected equipment can be a cause for concern where RCD protection is required for the respective final circuits. The installation designer must ensure that the protective conductor current seen by the RCD in normal, fault-free, operation is kept significantly less than that at which the device will operate. Where it is necessary to specify a residual current device with a residual operating current of 30 mA in order to meet the requirement for additional protection, such as in a socket-outlet circuit, then in order to keep the expected protective conductor currents well below the residual operating current it may be necessary to replace the proposed single circuit by separate circuits each with its own RCD. Less serious, but equally frustrating, is the effect uncontrolled residual current may have on sensitive equipment which could fail, give false information readings or suffer from noise problems; this could be critical in medical applications. Technology as we have discussed in this brief article has bought many benefits but as we move to a greener, more sustainable lighting market then adequate provisions must be made by the electrical designers and installers to give sufficient provision to the potential issues raised by the user of new technology in commercial and residential properties.