2.02 GENERATOR SET EXERCISE (TEST) WITH LOAD MODE. THE CONTROL SYSTEM SHALL BE CONFIGURABLE TO TEST THE GENERATOR SET UNDER LOAD. IN THIS MODE, THE TRANSFER SWITCH SHALL CONTROL THE GENERATOR SET IN THE FOLLOWING SEQUENCE: TRANSFER SWITCH SHALL INITIATE THE EXERCISE SEQUENCE AT A TIME INDICATED IN THE EXERCISE TIMER PROGRAM, OR WHEN MANUALLY INITIATED BY THE OPERATOR. WHEN THE CONTROL SYSTEMS SENSE THE GENERATOR SET AT RATED VOLTAGE AND FREQUENCY, IT SHALL OPERATE TO CONNECT THE LOADS TO THE GENERATOR SET BY OPENING THE NORMAL SOURCE CONTACTS, AND CLOSING THE ALTERNATE SOURCE CONTACTS A PREDETERMINED TIME PERIOD LATER. THE TIMING SEQUENCE FOR THE CONTACT OPERATION SHALL BE PROGRAMMABLE IN THE CONTROLLER. THE GENERATOR SET SHALL OPERATE CONNECTED TO THE LOAD FOR THE DURATION OF THE EXERCISE PERIOD. IF THE GENERATOR SET FAILS DURING THIS PERIOD, THE TRANSFER SWITCH SHALL AUTOMATICALLY RECONNECT THE GENERATOR SET TO THE NORMAL ON COMPLETION OF THE EXERCISE PERIOD, THE TRANSFER SWITCH SHALL OPERATE TO CONNECT THE LOADS TO THE NORMAL SOURCE BY OPENING THE ALTERNATE SOURCE CONTACTS, AND CLOSING THE NORMAL SOURCE CONTACTS A PREDETERMINED TIME PERIOD LATER. THE TIMING SEQUENCE FOR THE CONTACT OPERATION SHALL BE PROGRAMMABLE IN THE CONTROLLER. THE TRANSFER SWITCH SHALL OPERATE THE GENERATOR SET UNLOADED FOR A COOL-DOWN PERIOD, AND THEN REMOVE THE START SIGNAL FROM THE GENERATOR SET. IF THE NORMAL POWER FAILS AT ANY TIME WHEN THE GENERATOR SET IS RUNNING, THE TRANSFER SWITCH SHALL IMMEDIATELY CONNECT THE SYSTEM LOADS TO THE GENERATOR SET. 2.03 GENERATOR SET EXERCISE (TEST) WITHOUT LOAD MODE. THE CONTROL SYSTEM SHALL BE CONFIGURABLE TO TEST THE GENERATOR SET WITHOUT TRANSFER SWITCH LOAD CONNECTED. IN THIS MODE, THE TRANSFER SWITCH SHALL CONTROL THE GENERATOR SET IN THE FOLLOWING SEQUENCE: TRANSFER SWITCH SHALL INITIATE THE EXERCISE SEQUENCE AT A TIME INDICATED IN THE EXERCISE TIMER PROGRAM, OR WHEN MANUALLY INITIATED BY THE OPERATOR. WHEN THE CONTROL SYSTEMS SENSE THE GENERATOR SET AT RATED VOLTAGE AND FREQUENCY, IT SHALL OPERATE THE GENERATOR SET UNLOADED FOR THE DURATION OF THE EXERCISE PERIOD. AT THE COMPLETION OF THE EXERCISE PERIOD, THE TRANSFER SWITCH SHALL REMOVE THE START SIGNAL FROM THE GENERATOR SET. IF THE NORMAL POWER FAILS AT ANY TIME WHEN THE GENERATOR SET IS RUNNING, THE TRANSFER SWITCH SHALL IMMEDIATELY CONNECT THE SYSTEM LOADS TO THE GENERATOR SET. 3.0 CONSTRUCTION AND PERFORMANCE 3.01 THE TRANSFER SWITCH MANUFACTURER SHALL SUBMIT TEST DATA FOR EACH SIZE SWITCH, SHOWING IT CAN WITHSTAND FAULT CURRENTS OF THE MAGNITUDE AND THE DURATION NECESSARY TO MAINTAIN SYSTEM INTEGRITY. MINIMUM UL LISTED WITHSTAND AND CLOSING RATINGS SHALL BE AS FOLLOWS: SIZE (AMPS) 100-400 401-600 601-1200 ANY MOLDED BREAKER (RMS SYMMETRICAL) 35,000 50,000 50,000 SIZE (AMPS) 100-400 401-600 601-1200 SPECIFIC COORDINATED MOLDED CASE BREAKER 50,000 65,000 85,000 SIZE (AMPS) 100-4000 CURRENT LIMITING FUSE 200,000 LIGHTOLIER 8037CLW S7142BU BETA-CALCO 63 2441 3A XX 1 DB G 3.08 THE TRANSFER SWITCH SHALL BE PROVIDED WITH 4 HOURS OF FACTORY TRAINED INSTRUCTIONS COORDINATED WITH FACULTY. INSTRUCTION MAY BE VIDEOTAPED AT OWNERS DISCRETION. H BETA-CALCO 63 9802 XX1 COOPER LIGHTING LA8055ML NOTES 1. A 24 VDC SHUNT TRIP OPERATOR MUST BE PROVIDED ON THE GENERATOR FEEDER BREAKER TO OPERATE SHOULD THE TWO SOURCES BE PARALLELED FOR LONGER THAN SPECIFIED PARAMETERS 8021CCL S6132BU LIGHTOLIER I EG1-13-FO81W-D J 2. 24 VDC MUST BE SUPPLIED FROM THE ENGINE BATTERIES FOR USE WITH THE SHUNT TRIP CIRCUIT AND AS A BACKUP FOR ALARM FUNCTIONS. QVS2GSD GC1FT120VBE K 3. TRANSFER SWITCH SHALL BE IN CONFORMANCE WITH THE APPLICABLE PORTIONS OF: UL 1008 NFPA 70 NFPA 110 IEEE 241 IEEE 446 NEMA ICS UL 50/508 ICS 6 NEMA 250 L JESCO M INSIGHT LIGHTING N ---- FUSED DISCONNECT SWITCH, SIZE PER NEC. HUBBELL HBL1221 AC SWITCH SPECIFICATION GRADE, TOGGLE TYPE, SINGLE POLE, 20A, 120V. PROVIDE WITH WALL PLATE. COORDINATE FINISH WITH ARCHITECT. MOUNT 44" A.F.F. U.O.N. 3 HUBBELL HBL1223 AC SWITCH SPECIFICATION GRADE, TOGGLE TYPE, THREE-WAY, 20A, 120V. PROVIDE WITH WALL PLATE. COORDINATE FINISH WITH ARCHITECT. MOUNT 44" A.F.F. U.O.N. 44W LED ARRAY 2'x4' SHIELDED RECESSED LED FIXTURE. RECTANGULAR PERF INLAY SHEILD WITH 4000K LED LAMP. 120V. 3D HUBBELL AS63 ARCHITECTURAL GRADE SLIDER TYPE THREE-WAY DIMMER SWITCH, PRESET, 600w, 120V AC. PROVIDE WITH WALL PLATE. COORDINATE FINISH WITH ARCHITECT. MOUNT 44" A.F.F. U.O.N. HUBBELL HBL5262 DUPLEX SPECIFICATION GRADE RECEPTACLE, 20 AMPS, 3 WIRE GROUNDING. PROVIDE WITH WALL PLATE. COORDINATE FINISH WITH ARCHITECT. MOUNT 18" A.F.F. U.O.N. HUBBELL ---- SAME AS ABOVE EXCEPT MOUNT 44" A.F.F. HUBBELL ---- QUAD SPECIFICATION GRADE RECEPTACLE, 20 AMPS, 3 WIRE GROUNDING. PROVIDE WITH WALL PLATE. COORDINATE FINISH WITH ARCHITECT. MOUNT 18" A.F.F. U.O.N. 50W LED ARRAY 6"x48" RECESSED CEILING LED FIXTURE. LED DRIVER 4000K, 120V. "CALCULITE" CFL OPEN DOWNLIGHT WITH 8" APERATURE. 26W TRIPLE TUBE CFL, 120V. (1) 26W C.F. "TRILOGY CRADLE" TRIPLE ARM LIGHTING FIXTURE. HIGH FREQUENCY ELECTRONIC BALLASTS, 120V. FINISH SELECTION BY ARCHITECT. (3) 32W C.F. "TRILOGY" PENDANT MOUNT LIGHTING FIXTURE. HIGH FREQUENCY ELECTRONIC BALLASTS, 120V. FINISH SELECTION BY ARCHITECT. (2) 32W C.F. GFI HUBBELL GF5362 14W LED ARRAY GFI HUBBELL ---- SAME AS ABOVE EXCEPT MOUNT 44" A.F.F. (1) 32W C.F. GFI WP HUBBELL ---- SAME AS ABOVE EXCEPT PROVIDE WITH WEATHER PROOF COVER PLATE PER EXTERIOR RECEPTACLES. MOUNT 18" A.F.F. U.O.N. HUBBELL HBL45123C ---- ---- TV JACK IN SINGLE GANG BOX WITH WITH PULL STRING MOUNT 40" A.F.F ---- ---- TELEPHONE OUTLET SINGLE GANG BOX WITH 3/4" CONDUIT TO ABOVE CEILING WITH PULL STRINGS. COORDINATE WORK WITH FIELD CONDITIONS AND OTHER TRADES. ---- ---- DATA/TELEPHONE OUTLET. DOUBLE GANG BOX WITH 3/4" CONDUIT TO ABOVE CEILING WITH PULL STRINGS. COORDINATE WORK WITH FIELD CONDITIONS AND OTHER TRADES. CR SCHLAGE AD300CY50PR SPA626PDC123 4. SEE SPECIFICATION SECTION 263600 - TRANSFER SWITCHES FOR ADDITIONAL REQUIREMENTS CR2 HID PROXPRO 5355 GENERATOR SPECIFICATIONS SP ---- ---- TYPE: 208Y/120V, 3PH, 4W, 200 KW, DIESEL FUELED. MANUFACTURER: GENERAC MODEL: SD-200 GENERATOR SET SPECIFICATIONS: VOLTAGE REGULATION, NO LOAD TO FULL LOAD: RANDOM VOLTAGE VARIATION: FREQUENCY REGULATION: RANDOM FREQUENCY REGULATION: ±1.0% ±1.0% ISOCHRONOUS (ELECTRONIC GOVERNOR STANDARD) ±.0.25% ENGINE SPECIFICATIONS: DESIGN: BORE: STROKE: DISPLACEMENT: STARTING VOLTAGE: FUEL SYSTEMS: AIR CLEANER TYPE: LUBE OIL FILTER TYPE(S): BMEP: ASPIRATION: 6 CYCL., WATER-COOLED 4.61" 5.31" 8.7L 24 VOLT, NEGATIVE GROUND DIESEL DRY ELEMENT SPIN-ON, FULL FLOW 265 PSI TURBO CHARGED/AFTERCOOLED ALTERNATOR SPECIFICATIONS: DESIGN: STATOR: ROTOR INSULATION SYSTEM: TEMPERATURE RISE: EXCITER TYPE: PHASE ROTATION: ALTERNATOR COOLING: AC WAVEFORM TOTAL HARMONIC DISTORTION: TELEPHONE INFLUENCE FACTOR (TIF) BRUSH LESS, 4 POLE, DRIP PROOF REVOLVING FIELD 2/3 PITCH DIRECT COUPLED BY FLEXIBLE DISC CLASS H PER NEMA MG1-1.65 125°C STANDBY PERMANENT MAGNET A (U), B (V), C (W) DIRECT DRIVE CENTRIFUGAL BLOWER <5% TOTAL NO LOAD TO FULL LINEAR LOAD <50 PER NEMA MG1-22.43. (2) 28W T5 "ENERGOS" LINEAR PENDANT FIXTURE. (DIRECT/INDIRECT) 3 BULB T5. PARABOLIC LOUVER WITH DUAL SWITCHING. 120V. 2'x2' RECESSED DIRECT/INDIRECT FLUORESCENT 1 LAMP FIXTURE. SOLID GLASS SHIELD. ALTER SOFT LIGHTS, 120V. S6014840 SAME AS FIXTURE ABOVE EXCEPT 48" IN LENGTH. 14W LED ARRAY "MEDLEY C" LINEAR LED ACCENT FIXTURE. 24" LENGTH, SURFACE MOUNT, ADJUSTABLE DOWNWARD LIGHT THROW. 5000K, 120V. 26W LED ARRAY 68070184 WZNC P EUROFASE 19240-015 CM (1) 50W TT5 7W LED ARRAY RESTORATION HARDWARE R "CALCULITE" CFL OPEN DOWNLIGHT WITH 6" APERATURE. 32W TRIPLE TUBE CFL, 120V. SLIM COVE LED LIGHTING FIXTURE. MOUNTED UNDER BAR FOR SOFT DISPLAY ACCENT LIGHTING. 4000K. 24" IN LENGTH. O Q "HALO" SERIES STASIS LED SMALL. 4000K 8° SPOT BEAM. ADJUSTABLE ON MOUNTED ARCHITECTURAL TRACK. FINISH BY SELECTION ARCHITECT. TV W (1) 26W C.F. w/ EDISON BASE VINTAGE BARN PENDANT WEATHERED ZINK FIXTURE. 18" ZINK SHADE, 75W. SURFACE MOUNTED, FULLY ADJUSTABLE, LED SPOTLIGHT. METAL CONSTRUCTION, FINISH BY ARCHITECT. (1) 1W LED "TRILOGY" CRADLE SEMI-RECESSED FIXTURE. 120V. TRIM FINISH BY ARCHITECT. (2) 32W C.F. BETA-CALCO 63 2130 PL-T LIGHTOLIER ST74WA43 A40UUADB SEALATRON LED ENCLOSED INDUSTRIAL WET LOCATION SURFACE MOUNTED LUMINAIRE PRODUCING 4300 LUMENS AND 4000 DEGREE KELVIN COLOR TEMPERATURE, 120V. LIGHTOLIER ST74WA43 A40UUADB SEALATRON LED ENCLOSED INDUSTRIAL WET LOCATION SURFACE MOUNTED LUMINAIRE PRODUCING 4300 LUMENS AND 4000 DEGREE KELVIN COLOR TEMPERATURE, 120V. WAC LIGHTING LED-RL-30 LOW PROFILE LED ROPE LIGHT. 1/2" ROPE WITH LEDS SPACED EVERY 1". DIMMABLE WATERPROOF AND UV RESISTANT. DIRECTLY CONNECTED TO 120V POWER SUPPLY TO PROVIDE SOFT GLOW BEHIND SIGNAGE, TO BE CONNECTED TO SITE LIGHTING CONTACT TO OPERATE FROM DUSK TO DAWN. T 1. AIPHONE IS-IPMV IP SECURITY DESK CONTROLLER. DESK MOUNTED STATION WITH 3.5" LCD MONITOR. EQUIPPED WITH AUDIO OUTPUT AND DOOR RELEASE BUTTON. PROVIDE AND INSTALL CAT 5E CABLING WITH PULLSTRING IN CONDUIT TO ABOVE CEILING. AIPHONE AX-DV-P IP INTERCOM VIDEO DOOR STATION. EQUIPPED WITH COLOR VIDEO CAMERA, AUDIO INTERCOM, AND EMBEDDED CARD READER. PROVIDE AND INSTALL CAT 5E CABLING. --- --- G GENERAC SD-200 EMERGENCY INDUSTRIAL DIESEL GENERATOR. 250 KVA, 200 KW, 60 HZ. PROVIDE WITH LEVEL 2 SOUND ENCLOSURE. 5000 MITEL SERIES 5000 5000 IP 52002686 COMMUNICATION PLATFORM - SYSTEM HARDWARE BASE KIT HX NO CF MT 5000 HX. PROVIDE WITH THE FOLLOWING: VI REFER TO MEP-2 FOR OUTDOOR LIGHTING SCHEDULE & DETAILS. ML-1 PP-3 (MECH. RM.) SPECIFICATIONS: SEE SPECIFICATION SECTION 26 32 13 FOR ADDITIONAL REQUIREMENTS MITEL DESKTOP DEVICE 50006476 COMMUNICATION PLATFORM - SOFTWARE LICENSES MT5000 LIC FILE BASED MUSIC SOURCE 5330e IP PHONE. MULTI-FUNCTION PROGRAMMABLE SELF-LABELING KEYS, LARGE PRAGHIC DISPLAY, WIDEBAND AUDIO SUPPORT, HANDS FREE SPEAKER PHONE OPERATION. 25CX30L3G 726008 BK1000 BK1001 CA 1013 MS 1050 MP-1 (PENTHOUSE) LP-2 (MECH. RM.) 150A MCB NETWORK SWITCHES 250A MCB J9087A#ABA MPC4PL5ST-05 CONNECT IP PHONE VIA CAT. 5E OR CAT. 6 CABLE BACK TO COMMUNICATION PLATFORM LOCATED IN IT ROOM. CONTRACTOR TO PROVIDE ALL NECESSARY HARDWARE AND APPURTENANCES FOR A COMPLETE AND OPERABLE SYSTEM. COORDINATE WITH OWNER FOR FINAL PHONE LOCATIONS. NEW 300 KVA 13.2KV:208Y/120V PAD-MOUNT TRANSFORMER 10'-0" 800 AMP METER WITH CT CABINET M #1/0 GND KP-1 (STORAGE) IG-1 (IT RM.) PP-4 (ELEC. RM.) EN 0 PR 7 3 0 8 4 OF E S S I ON AL 1 200A MCB 150A MCB 200A MCB 200A MCB 150A MCB No 150A MCB Date Revision Drawn By: Checked By: Proj. #: CSArch Proj. #: Date: 150A-3P 150A-3P DS-1 EL L 2 200A-3P #4/0 GND N 3 PP-1 PP-2 LP-1 (ELEC. RM.) (ELEC. RM.) (ELEC. RM.) 800A-3P 800AF/800AT DEA 4 150A-3P 200A-3P C OF NEW Y OR F NY PROFESSIONAL ENGINEER NO. 073084-1 250A-3P NEW 800A FUSED DISCONNECT WITH CLASS L TIME DELAY FUSE TE R EX C E L S IO D 1. 150A-3P 200A-3P TA SE NOTES: 150A-3P END OF RGS HP 2610-24-PWR 10/100 POE 2 GIG 2SFP L 5' RJ-45 CAT-5E + PATCH CORD SECOND FLOOR MDP (ELEC. RM.) 800A-3P ERIC D. FELLENZER R 150A MCB 25 PAIR 30 FOOT FEMALE TAIL GROUND CLAMP 89B BRACKET 66M 1-50 BLOCK GROUND CABLE POWER ARRESTER ZE (4)#1/0, (1)#6 GND IN 2" CONDUIT G By Author Checker 811-11-01 10/30/12 Sheet Title FIRST FLOOR 2'-6" MIN. START OF RGS SERIES 5000 840.0819 L I C EN PVC & RGS BY ELECTRICAL CONTRACTOR MITEL K (4)#250 MCM, (1)#2 GND IN 3" CONDUIT NEW 200 KW 120/208 VOLT 3 PHASE 4W DIESEL GENERATOR (INSTALLED BY E.C.) LEAVE SUFFICIENT SLACK FOR CONNECTION BY UTILITY COMPANY 1 : 580.1003 MT5000 HX CONTROLLER CHASSIS ONLY 1 : 580.3000 MT5000 HX PROCESSOR Mdl (HPM) 16 : 840.0416 MT5000 LIC IP PHONE CATEGORY D 1 : 840.0844 MT5000 LIC DYN EXT EXPR SYSTEM 1 : 50006271 PWR CRD C13 10A 125V - NA PLUG 1 : 580.9126 MT5000 HX CTRL PWR SUP 120W 24VDC 5A 4 : 840.0411 LICENSE INTL5000 BVM SINGLE PT 1 : 999.9000 99.9000 1 : 54005357 MT5000 LIC UVM E-MAIL SYNCHRONIZATION 1 : 54005359 MT5000 LIC MEET-ME CONF 1 : 54005399 MT5000 LIC HOT DESKING SYSTEM - WIDE 1GB COMPACT FLASH MITEL 5000 NA INSTALLATION HARDWARE REMOTE ANNUNIATOR: NFPA 110 COMPLIANT UTILITY POLE SLIDING GATE MAGNETIC LOCK 120V/1 DIAMETER 841.1152 GENERATOR SET: BATTERIES BATTERY CHARGER BATTERY RACK COOLANT DRAIN EXTENSION MAIN LINE CIRCUIT BREAKER (800A, 3P) OIL DRAIN EXTENSION SOUND ANTINUATION ENCLOSURE W/ CRITICAL GRADE SILENCER LEVEL 2 SOUND ENCLOSURE TO ALLOW 73 Db AT 23 FT. 2 YEAR STANDBY WARRANTY * ALL VALUES 208 VOLT, RMS SYMMETRICAL, LESS THAN 20% POWER FACTOR SPEAKER FOR PHONE INTERCOM. PROVIDE BACK BOX AND CONDUIT WITH PULL STRING TO ABOVE CEILING HEIGHT. HIGH BAY OCCUPANCY SENSOR WITH PASSIVE INFRARED TECHNOLOGY, LOW VOLTAGE, 68' DIAMETER COVERAGE. PROVIDE WITH MODEL #:B120E POWER PACK (ONE FOR BOTH) AND JUNCTION BOX ADAPTOR PLATE. ENGINE: 208 VOLT, 2000 WATT COOLANT HEATERS CONTROL PANEL: DETECTOR 12 CONTROL (NFPA 110 COMPLIANCE) EMERGENCY STOP LOW BATTERY VOLTAGE WARNING LOW COOLANT LEVEL WARNING/SHUTDOWN OIL PRESSURE GAUGE REMOTE FAULT SIGNAL PACKAGE WATER TEMPERATURE GUAGE 125 KHZ WALL SWITCH SECURITY PROXIMITY READER. PROVIDE BACK BOX AND CONDUIT WITH PULL STRING TO ABOVE CEILING HEIGHT. HB-150-4CP-1 ADDITIONAL REQUIREMENTS: ALTERNATOR: 105°C RISE ALTERNATOR ANTI-CONDENSATION HEATER EXTENDED STACK (FULL SINGLE PHASE OUTPUT) PERMANENT MAGNET EXCITATION HARDWIRED ELECTRONIC LOCK WITH PROXIMITY READER. WATTSTOPPER H VIC NOTE: CONDUIT TO ABOVE CEILING DUAL TECHNOLOGY, PASSIVE INFRARED AND ULTRASONIC, OCCUPANCY SENSOR, CEILING MOUNTED, LOW VOLTAGE. POWER WITH MATCHING POWER PACK TYPICAL OF WATTSTOPPER MODEL# BZ-150. (2) 28W T5 120W LED 3/ " 4 DT-300 OS S SPRING DRIVEN ELECTRIC CABLE REEL. MOUNT TO CEILING. PROVIDE WITH 45' OF 12Awg CABLE AND SINGLE 20A, 3 WIRE RECEPTACLE. WATTSTOPPER OS 49W LED ARRAY DUPLEX SPECIFICATION GRADE GROUND FAULT INTERRUPTER TYPE 3-WIRE GROUNDING RECEPTACLE, PROVIDE WITH FACE PLATE, 20A,125V. COORDINATE FINISH WITH ARCHITECT. MOUNT 18"AFF. 19 Front St., Newburgh, New York 12550 845.561.3179 FAX 845.561.3215 www.csarchpc.com ---- (3) 42W C.F. S6012440 MC1250K8 SMS24INT-1W Arch UNLESS OTHERWISE NOTED. F 3.07 THE AUTOMATIC TRANSFER SWITCH SHALL BE PROTECTED BY 5 YEAR MANUFACTURERS WARRANTY. Architecture Engineering Construction Management ---- 181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 845-454320-8735 LIS64GPN4OULAG ---- U.O.N. 22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986 TRANSFER SWITCH NORMALLY CONNECTS AN ENERGIZED UTILITY POWER SOURCE (SOURCE 1) TO LOADS AND A GENERATOR SET (SOURCE 2) TO THE LOADS WHEN NORMAL SOURCE FAILS. THE NORMAL POSITION OF THE TRANSFER SWITCH IS SOURCE 1 (CONNECTED TO THE UTILITY), AND NO START SIGNAL IS SUPPLIED TO THE GENERATOR. E LIGHTOLIER NEW HOME RUN TO PANEL AS INDICATED. NEER 2.01 D 44W LED ARRAY ---- GI 2.0 SEQUENCE OF OPERATION R3-WG-2L40 -1C-120-24-T1 C 2'x2' SHIELDED RECESSED LED FIXTURE. RECTANGULAR PERF INLAY SHEILD WITH 4000K LED LAMP. 120V. ---- EN 1.05 THE WITHSTAND CURRENT OF THE MAIN CONTACTS SHALL NOT BE LESS THAN 20 TIMES THE CONTINUOUS DUTY RATING AS ESTABLISHED BY TEST DATA. * AUXILIARY CONTACT CLOSED IN EMERGENCY POSITION * AUXILIARY CONTACT CLOSED IN NORMAL POSITION * ENGINE START CONTACT, 1 N.O., 1 N.C. * PILOT LIGHT TO INDICATE SWITCH IN EMERGENCY POSITION * PILOT LIGHT TO INDICATE EMERGENCY SOURCE AVAILABILITY * ADJUSTABLE TIME DELAY ON RETRANSFER TO NORMAL, 0-30 MIN * ADJUSTABLE TIME DELAY ON TRANSFER TO EMERGENCY, 0-30 MIN * ADJUSTABLE TIME DELAY ON ENGINE START, .5-6 SECONDS * ADJUSTABLE TIME DELAY FOR ENGINE COOL DOWN, 0-30 MIN * LOAD TEST SWITCH * TRANSITION MODE SELECTOR SWITCH TO ALLOW OPEN OR CLOSED TRANSITION TRANSFER. * ALARM AND SHUNT TRIP CIRCUIT WITH DIAGNOSTIC INDICATORS * EXTENDED PARALLEL ELECTRICAL OPERATOR REVERSAL SAFETY CIRCUIT AND LOCKOUT R3-WG-2L40 -1C-120-22-T1 EMERGENCY EXIT SIGN, RED LETTERS, WHITE BACKGROUND, THERMOPLASTIC HOUSING. ENGINEERING LLP 1.04 AS A PRECONDITION FOR APPROVAL, ALL TRANSFER SWITCHES SHALL BE LISTED BY UNDERWRITERS LABORATORIES, UNDER STANDARD UL 1008 (AUTOMATIC TRANSFER SWITCHES) AND APPROVAL FOR USE ON EMERGENCY SYSTEMS. COOPER LIGHTING B ---- JOB# 09-167B 1.03 THE UNIT SHALL BE RATED BASED ON ALL CLASSES OF LOADS: I.E., RESISTIVE, TUNGSTEN, BALLAST, AND INDUCTIVE LOADS. SWITCHES RATED AT 800A OR LESS SHALL BE UL LISTED FOR 100% TUNGSTEN LAMP LOADS. 3.06 THE CLOSED TRANSITION TRANSFER SWITCH SHALL INCLUDE THE FOLLOWING STANDARD EQUIPMENT: (3) 42W C.F. DESCRIPTION I 1.02 THE CURRENT RATING SHALL BE A 800A CONTINUOUS RATING WHEN THE SWITCH IS INSTALLED IN AN UNVENTILATED ENCLOSURE, AND SHALL CONFORM TO NEMA TEMPERATURE RISE STANDARDS. A3 SAME AS FIXTURE ABOVE EXCEPT MOUNTED WITH A LONGER CONNECTION TO BE 18'-9" FROM FINISHED FLOOR AND PARALLEL TO OTHER FIXTURES. SAME AS FIXTURE ABOVE EXCEPT MOUNTED WITH A LONGER CONNECTION TO BE 18'-9" FROM FINISHED FLOOR AND PARALLEL TO OTHER FIXTURES. MCPHILBEN MODEL NO. S 1.01 THE AUTOMATIC OPEN TRANSITION TRANSFER SWITCH SHALL BE RATED FOR 208Y/120V, 3PH, 3P, SOLID NEUTRAL, 800A, AND SHALL HAVE 600 VOLT INSULATION ON ALL PARTS IN ACCORDANCE WITH NEMA STANDARDS. 3.05 SWITCHED COMPOSED OF MOLDED CASE BREAKERS, CONTACTORS OR COMPONENTS THEREOF NOT SPECIFICALLY DESIGNED AS AN AUTOMATIC TRANSFER SWITCH WILL NOT BE ACCEPTABLE. (3) 42W C.F. MANUFACTURER ER 1.0 GENERAL A2 "REFRACTOR" PENDANT MOUNT LIGHTING FIXTURE. ALUMINUM BODY WITH HIGH TEMPERATURE CLEAR PRISMATIC ACRYLIC REFRACTOR AND GLASS DECORATIVE DISK. 120V MOUNTED 18'-9" FROM FINISHED FLOOR. SYMBOL SOUTH SPRING VALLEY FIRE DISTRICT NEW FIRE HOUSE CHESTNUT RIDGE, NY 3.04 THE SWITCH SHALL BE MOUNTED IN NEMA 1 ENCLOSURE UNLESS OTHERWISE INDICATED IN PLANS. LAMPS DESCRIPTION Consultant BELARO 22 20 2202-1 BETA-CALCO A1 MODEL NO. Project Title 208Y/120V, 3 , 4W, 800A, 3 POLE. SOLID NEUTRAL MANUFACTURER S SYMBOL 3.03 A MANUAL HANDLE SHALL BE PROVIDED FOR MAINTENANCE PURPOSES WITH THE SWITCH DE-ENERGIZED. AN OPERATOR DISCONNECT SWITCH SHALL BE PROVIDED TO DEFEAT AUTOMATIC OPERATION DURING MAINTENANCE, INSPECTION OR MANUAL OPERATION. LEGEND AND SCHEDULE OF ELECTRICAL EQUIPMENT S TYPE: OPEN TRANSITION AUTOMATIC MAKE: TRANSFER SWITCH (ATS) ASCO LEGEND AND SCHEDULE OF LIGHTING EQUIPMENT 3.02 A DIELECTRIC TEST AT THE CONCLUSION OF THE WITHSTAND AND CLOSING TESTS SHALL BE PERFORMED. S AUTOMATIC TRANSFER SWITCH SPECIFICATIONS 13.2 KV (3)#2 PRIMARY WITH CONCENTRIC NEUTRALS IN 4" SCH. 80 PVC CONDUIT 2 SETS OF: (4)#600 MCM IN 4" SCH. 80 PVC CONDUIT 2 SETS OF: (4)#600 MCM (1)#1/0 GND IN 4" CONDUIT NEW 800A SERVICE ENTRANCE RATED OPEN TRANSITION ATS SPARE (4)#4/0, (1)#2 GND IN 2 1/2" CONDUIT (4)#4/0, (1)#6 GND, (1)#6 IG IN 2" CONDUIT ELECTRICAL SCHEDULES NEW 208 VOLT 800 AMP SQUARE 'D' TYPE 'HCM' I-LINE PANEL NOTES: 1. ELECTRICAL CONTRACTOR RESPONSIBLE FOR SECONDARY CONDUCTORS, CONDUITS, TRANSFORMER PAD AND INSTALLATION. UTILITY COMPANY RESPONSIBLE FOR CONNECTION AT POLE AND PAD MOUNT TRANSFORMER. 2. METER BY UTILITY COMPANY. METER ENCLOSURE & METERING BY ELECTRICAL CONTRACTOR. 1 Sheet No. E-801 ELECTRICAL ONE-LINE DIAGRAM N.T.S. COPYRIGHT zALL RIGHTS RESERVED ISSUE FOR BID