Review of Series Compensation for Transmission Lines FINAL Prepared by John Miller Marc Brunet-Watson Jed Leighfield PSC North America For Southwest Power Pool PSC reference JU4715 Date May 09, 2014 Proprietary & Confidential Review of Series Compensation for Transmission Lines Revision Table Revision 1 2 2.1 Issue Date Description 3/21/2014 4/16/2014 5/09/2014 Final Draft for submission to client Final submission. Final with corrections: - general typos, - fig 2.2 – show impact of increasing K - fig 2.3 - removed FSC - fig 6.3 – reversed light load and SIL curves Reviewers Name Andrew Robbie Brad Railing Interest Principal Engineer Principal Engineer Date 3/17/2014 4/14/2014 Approval Name Marc Brunet-Watson Position Power Networks Manager PSC North America – Power Networks Date 5/09/2014 Page 2 of 65 Review of Series Compensation for Transmission Lines TABLE OF CONTENTS 1.......... Introduction ..........................................................................................7 2.......... Applicability of Series Compensation Technology ...........................9 2.1 General Review ...................................................................................... 9 2.1.1 Reducing Rotor Angle Separation................................................... 9 2.1.2 Voltage Regulation........................................................................ 11 2.2 Fixed Series Compensation (FSC) ...................................................... 13 2.3 Thyristor Controlled Series Compensation (TCSC)........................... 14 3.......... Sub-synchronous Interaction with Series Compensation ..............16 3.1 Key Section References ...................................................................... 16 3.2 Sub-synchronous Interaction.............................................................. 16 3.2.1 Fundamentals of Series Compensation and SSI ........................... 17 3.2.2 Classic SSR-TI and SSR-TA......................................................... 18 3.2.3 Induction Generator Effect (IGE)................................................... 19 3.2.4 SSCI Considerations for Wind Generation .................................... 20 3.3 Assessment of SSI in Series Compensated Networks ...................... 21 3.3.1 SSI Analysis.................................................................................. 21 3.3.2 Frequency Scan Screening ........................................................... 22 3.3.3 Eigenvalue Analysis ...................................................................... 23 3.3.4 Damping Torque Analysis ............................................................. 24 3.3.5 Detailed Time-Domain Analysis .................................................... 24 3.4 ERCOT – SSI Impact Study Framework for Wind Generators........... 25 4.......... SSI Mitigation and Protection Measures and Practical Applications26 4.1 Key Section References ...................................................................... 26 4.2 General Considerations and Definitions ............................................ 26 4.3 Network-Based Mitigation Measures .................................................. 27 4.3.1 Operational Procedures ................................................................ 27 4.3.2 Passive Filter Damping ................................................................. 27 4.3.3 Active Shunt Filter Damping (SVC or STATCOM)......................... 28 4.3.4 Active Series Damping (TCSC) and Shunt-Series Damping (UPFC)28 4.4 Generator-Based Mitigation Measures ............................................... 30 4.4.1 Passive Filter Damping ................................................................. 30 4.4.2 Active Filter Damping .................................................................... 31 PSC North America – Power Networks Page 3 of 65 Review of Series Compensation for Transmission Lines 4.4.3 Supplementary Excitation Control Damping .................................. 31 4.4.4 Wind Turbine Control Damping ..................................................... 32 4.5 Network-Based Protection Measure ................................................... 33 4.5.1 Series Capacitor By-pass.............................................................. 33 4.6 Generator-Based Protection Measures .............................................. 33 4.6.1 SSI Relays .................................................................................... 33 5.......... Protection Schemes and Protection Relay Considerations ...........35 5.1 Key Section References ...................................................................... 35 5.2 General ................................................................................................. 35 5.3 Influence of Capacitor Protection ....................................................... 36 5.3.1 Voltage Inversion and Current Inversion ....................................... 36 5.3.2 Distance Protection – Measured Impedance................................. 38 5.3.3 Sub-synchronous Transient Signal Impacts .................................. 39 5.3.4 Adjacent Line Protection Impacts.................................................. 40 5.3.5 Other Impacts ............................................................................... 41 5.3.6 Automatic Reclosing for Series Compensated Transmission Lines41 5.4 Relay Protection Solutions.................................................................. 43 5.4.1 Advanced Relays for Series Compensation Application ................ 43 5.4.2 Protection Schemes...................................................................... 44 5.4.3 Protection Design and Performance Verification ........................... 45 5.5 Protection Case Studies ...................................................................... 46 5.5.1 BC Hydro ...................................................................................... 46 5.5.2 Hydro-Québec TransÉnergie (HQT).............................................. 49 5.5.3 Pacific Gas & Electric.................................................................... 50 6.......... Project Planning and Implementation Considerations ...................52 6.1 Key Section References ...................................................................... 52 6.2 Location of Series Compensation....................................................... 52 6.2.1 Mid-Line ........................................................................................ 53 6.2.2 Line Ends...................................................................................... 55 6.3 Modularity of Series Compensation ................................................... 57 6.4 Future Development of the Series Compensated Lines.................... 58 6.5 Operations and Maintenance Considerations.................................... 58 6.5.1 Operations and Reliability ............................................................. 59 7.......... Roadmap for Further Analysis ..........................................................60 7.1 Preliminary Design Stage Studies ...................................................... 60 PSC North America – Power Networks Page 4 of 65 Review of Series Compensation for Transmission Lines 7.2 Steady state data for analyzing the active and reactive power flows and voltage profiles in the system ............................................................. 60 7.3 Transient Stability Analysis................................................................. 61 7.4 Harmonics and Frequency Scans ....................................................... 61 7.5 Short-term Transient Voltage and Switching Studies ....................... 61 7.6 Small-signal Analysis .......................................................................... 62 8.......... References ..........................................................................................63 PSC North America – Power Networks Page 5 of 65 Review of Series Compensation for Transmission Lines TABLE OF FIGURES Figure 2-1 - Power transfer equation Figure 2-2 - Pmax with all lines in service Figure 2-3 - Equal Area Criterion for a simple system Figure 2-4 - Self-regulation of series compensation – 500 kV line, 300 miles long Figure 2-5 – Effect of increasing compensation levels – 500 kV line, 300 miles long Figure 2-6 - FSC main circuit components Figure 2-7 - TCSC primary circuit components Figure 3-1 - Generator turbine lumped mass model Figure 3-2 - System electrical damping vs. torsional frequency (w/torsional modes) Source [4] Figure 4-1 - Passive filter in parallel with series capacitor Figure 4-2 - Primary components of a TCSC Figure 4-3 - TCSC impedance characteristic with SVR. Source: [2] Figure 4-4 - DFIG Basic One-Line (Type-3) Figure 5-1 - MOV protected series capacitor Figure 5-2 - Voltage profile for a line side fault near a series capacitor (Forward Fault) Figure 5-3 - Voltage profile for an adjacent line side fault near a series capacitor (Reverse Fault) Figure 5-4 - Example of current reversal condition in a SC line Figure 5-5 - Impedance protection on a mid-point SC line Figure 5-6 - Transmission line with remote line end SC Figure 5-7 - Distance relay overreach due to sub-synchronous transient signals Figure 5-8 - Zone 1 distance relay on SC line (solid) and adjacent line (dotted) Figure 5-9 Main and back-up proctection schemes for line end and mid-line SC Source: [33] Figure 6-1 - Midline compensation at 33% and 66% of line length Figure 6-2 - Mid-line compensation at 50% of line length Figure 6-3 – Line voltage profile for mid-line series compensation Figure 6-4 - Line end compensation, bus side shunt reactors Figure 6-5 - Line end compensation, line side shunt reactors Figure 6-6 – Line voltage profile for line-end series compensation PSC North America – Power Networks Page 6 of 65 Review of Series Compensation for Transmission Lines 1 Introduction The High Priority Incremental Load Study (HPILS) was initiated in 2013 to develop a long range plan that identified system reinforcements required in the Southwest Power Pool (SPP) footprint in order to accommodate the unprecedented load growth that had not been identified by previous planning studies. This rapid expansion of load was brought about by an increase in the development of oil and gas fields, the firming of previously interruptible loads and an increase in the forecast expansion of major industrial loads. As part of the HPILS process, initial screening of options by SPP staff suggested that 50% series compensation (SC) should be considered on the existing Tolk - Eddy Country 345kV line as part of a potential EHV solution set to address the reliability needs associated with large load additions in southeast New Mexico and west Texas. Due to the fact that the proposed solution would introduce the first series compensated line in the SPP footprint, significant concerns and uncertainties were expressed about the merits and implications of adding SC to existing or planned EHV lines in SPP. Series compensation has been in use in electrical networks worldwide since the 1950s. It is a tried and true technology that continues to grow in popularity as an effective means of resolving a number of network issues such as: Improving transient system performance of the system following system disturbances by reducing rotor angle difference between generators; Compensating for reactive power losses in transmission lines to better regulate system voltages; Modifying and improving the balance of power flows between adjacent transmission corridors by changing impedances, similar in effect to phaseshifting transformers and HVDC; Damping of system oscillations when used with actively controlled Thyristor Controlled Series Capacitors (see Section 2.3); and Mitigating geomagnetic induced currents by blocking low frequency current flow. The first two points are further discussed in Sections 2.1.1 and 2.1.2 whereas the remainder are beyond the scope of this paper. By addressing the above issues with less capital intensive solutions such as series compensation, the capacity of existing transmission lines can be increased thereby allowing for the deferral of major transmission line investments and the optimization of total build out. This permits better management of risk through the preservation of right of ways and corridors for future needs using an option that requires minimal permitting and siting requirements. Overall asset utilization increases and losses are lowered. Series compensation improves system reliability while minimizing the impact on rate payers. The various sub synchronous interactions between the network and the series capacitor are well known phenomena and there are a variety of ways available to counter-act them. The literature on the topic is extensive and the techniques are well documented and their relative merits are discussed at length. PSC North America – Power Networks Page 7 of 65 Review of Series Compensation for Transmission Lines This document seeks to provide a better understanding of the implications of adding series compensation technology to the SPP network. The current status of the technology is reviewed and recent advances in the techniques that deal with known issues that affect the network are explored. PSC North America – Power Networks Page 8 of 65 Review of Series Compensation for Transmission Lines 2 Applicability of Series Compensation Technology 2.1 General Review A general review of the applicability of series compensation shows that it serves to increase power transfer under steady state and transient conditions, as well as regulating voltage variations. A series compensation installation can be ‘Fixed’, ‘Thyristor Controlled’, or a combination of both. 2.1.1 Reducing Rotor Angle Separation The classic power transfer equation, adapted to take account of the series capacitance, XC, shows that as the level of compensation, K, increases, the power transfer increases for a given angle δ. This is because capacitive impedance is negative with respect to an inductance thereby reducing the overall impedance of the line. The equation and a simplified network representation are shown in Figure 2-1 for illustrative purposes. P VS ܲோ = XL VR XC ܸோ ܸௌ ܸோ ܸௌ sin ߜ = sin ߜ ܺ − ܺ ܺ(1 − )ܭ Figure 2-1 - Power transfer equation From this, we see that when there are no changes to system impedance, the maximum power that can be transferred occurs when the phase angle between the two ends reaches 90o as demonstrated in Figure 2-2. P P= PMAX INCREASING COMPENSATION (K = 50%) VR VS sin(δ) XL (1-K) PMAX (K = 0%) δMAX = 90˚ ܲ ௫ = ܸோ ܸௌ ܸோ ܸௌ = ܺ − ܺ ܺ(1 − )ܭ Figure 2-2 - Pmax with all lines in service PSC North America – Power Networks Page 9 of 65 Review of Series Compensation for Transmission Lines The effect of adding series compensation is shown in Figure 2-2 where for a same angle δMAX, the theoretical maximum power transfer, PMAX, doubles when compensation level, K, reaches 50%. Analogously, for a given power flow (say PMAX when K=0%), rotor angle separation goes from 90o with no compensation to a much smaller value when compensation is increased. As faults occur and branch elements are switched out of service, the resulting changes in network impedance cause imbalances between the electrical and mechanical torques at play in the generator and an oscillatory behavior, best characterized by the swing equation: 2݀ ܪଶߜ = ܲ − ܲ ߱ ௦ ݀ݐଶ where H is generator inertia, ωs = 2 π fs is synchronous angular speed, Pmec is the mechanical power generated by the turbine, Pelec is the electrical power generated by the alternator that responds to the system demand. During steady state, when the system frequency is at its nominal 60 Hz, both the mechanical and electrical power are equal and the machine continues to spin at synchronous speeds. VS Pmec Pelec VR FAULT Pelec Pelec both lines in service Pelec after fault cleared (one line out) A2 Pmec Pelec during fault A1 δO δCL δMAX δ Figure 2-3 - Equal Area Criterion for a simple system Prior to fault inception, the generator in Figure 2-3 has angle δo and is generating Pmec on the Pelec curve with both lines in service. At the instant of the fault, the impedance seen by the generator reduces and very little active power is generated due to the fault being situated between the load and the generator. The generator’s operating point is now where δo crosses the curve of P during the fault. Mechanical power from the PSC North America – Power Networks Page 10 of 65 Review of Series Compensation for Transmission Lines turbine remains constant1 and the sudden drop in electrical power results in an imbalance causing the rotor to speed up. The angle between rotor field and network field increases and the generator’s operating point moves along P for the duration of the fault until the angle reaches δCL at which time the line’s protective relays clear the fault by disconnecting the line. Once the fault has been cleared, the generator changes its operating point by moving up to the graph of P after the fault is cleared. Since the impedance of the single line is double the impedance of the two lines in parallel, this curve has a smaller amplitude than the initial but greater than during the fault. Electrical power is now greater than mechanical power produced by the turbine and the rotor begins to decelerate until eventually coming to rest where the electrical power is equal to the mechanical power of the turbine. The area identified as A1 in Figure 2-3 corresponds to the acceleration energy absorbed by the rotor during the fault. The area A2 corresponds to the decelerating energy that the rotor can return to the network to return to a stable operating point. The Equal Area Criterion states that the generator will return to a stable operating point if A2 ≥ A1. This is equivalent to saying that the decelerating energy available to the rotor is at least equal to the accelerating energy absorbed during the fault. The relative sizes of A1 and A2 are determined by: The initial phase angle, δo ; The protection clearing time that determines δCL ; and The before and after impedances that determine the amplitude of the power relationship. 2.1.2 Voltage Regulation Voltage stability is improved due to the self-regulation characteristic of series capacitors. Contrary to shunt devices where reactive output is a function of the inverse square of the voltage change, the reactive power output of series elements increases with the square of the current. As transfer increases across a transmission line, reactive losses caused by the inductive nature or transmission lines are partially offset by the increase in reactive power generated by the capacitor. Consider Figure 2-4, the reactive power balance for a 500 kV line of 300 miles in length. The maximum power transfer is increased for the series compensated line due to the increased availability of reactive power to support local voltage as flow increases. Selfregulation also means that lines subject to sudden load variations due to nearby loads or generators switching on or off will have better regulation2. 1 In the time frames where protective devices operate (~ 50 – 200 ms), governor action is negligible and the turbine output can be said to remain constant. 2 Voltage regulation of a line generally refers to the tendency of the voltage at the receiving end to vary for given changes in flow. PSC North America – Power Networks Page 11 of 65 Review of Series Compensation for Transmission Lines Figure 2-4 - Self-regulation of series compensation – 500 kV line, 300 miles long As compensation levels, K, increase the reactive output of the series capacitor increases and the voltage regulation across the line is improved as shown in Figure 2-5. VR / VS 1.1 1.0 NOMINAL VOLTAGE RANGE 0.9 P Figure 2-5 – Effect of increasing compensation levels – 500 kV line, 300 miles long The range of power transfer for which the voltage stays within the normal range increases as the level of compensation increases. It must be noted that the Critical Voltage, the point at which voltage will collapse for any increase in transfer, also increases considerably as compensation levels increases. Post contingent voltages in compensated systems must be verified to ensure that a voltage collapse scenario has not been introduced along with the series compensation. This is particularly true for PSC North America – Power Networks Page 12 of 65 Review of Series Compensation for Transmission Lines situations where unplanned outages result in unusually high flows across compensated lines. 2.2 Fixed Series Compensation (FSC) A fixed series compensation installation consists of a parallel combination of capacitors, over-voltage protection, and a bypass breaker, which are all installed on an elevated platform insulated to the line voltage. The FSC main circuit components are shown in Figure 2-6. The capacitor bank is usually rated to line currents associated with normal peak power flow and power swing conditions. Rating the capacitor banks to current and voltage levels associated with fault conditions is generally not considered economical and over voltage protection is provided to limit the voltage across the capacitor during fault conditions. The over voltage protection typically consists of two parts: A zinc oxide varistor (MOV) with highly non-linear characteristics that conducts negligible current during normal operation and conducts freely once the voltage across it reaches the protection level thereby bypassing the capacitor bank. The MOV is built up of individual MOV blocks placed in series to obtain the desired voltage protection level and in parallel to be to absorb the desired energy during faults. If the fault is cleared without the ratings of the MOV being exceeded, the MOV will stop conducting once the voltage across it drops below the protection level and the capacitor will return to normal operating conditions. A fast protective device (FPD) that can be triggered for certain fault conditions such as faults on compensated line segments or for extreme faults when the energy absorbed by the MOV exceeds rated values. Fast protective devices have typically consisted of triggered air gaps although new technologies are being introduced that use arc-plasma injectors in parallel with a fast contact to avoid the difficulty of correctly distancing and maintaining the electrodes in the air gap. The bypass breaker is normally in the open position and can be used to switch the series capacitor in or out during planned operations. It also serves to bypass the series capacitor, MOV and FPD if the fault is not cleared within a pre-determined time. It must be able to carry the rated MOV voltage as well as the maximum capacitor discharge current. Bypass breakers are specially designed and rated to withstand the higher transient frequency and interrupting currents when bypassing a series capacitor. Bypass breakers are normally SF6 puffer type with controls at ground level. A damping circuit - usually an air core reactor - is placed in series with the FPD and the by-pass breaker to limit and dampen capacitor discharge currents when the FPD triggers or the bypass breaker is closed. PSC North America – Power Networks Page 13 of 65 Review of Series Compensation for Transmission Lines Series Capacitor MOV Damping Reactor FPD Bypass Swit ch Fixed Series Compensation Figure 2-6 - FSC main circuit components 2.3 Thyristor Controlled Series Compensation (TCSC) A thyristor controlled series compensation installation typically consists of two modules connected in series: A fixed series compensation module (as described above), and A module consisting of a series capacitor in parallel with a thyristor controlled, aircore reactor. As with the FSC, the TCSC is platform mounted and insulated at line voltage. A TCSC installation can be green field or thyristors can be added to control part or all of an existing FSC installation [2]. When the thyristor gate is blocked, full current flows through the capacitance and the line is fully compensated. When the thyristor gate is fully conducting, the capacitor is effectively bypassed. If the valves are gated for partial conductance, it is possible to smoothly vary the impedance of the TCSC. Over-voltage protection is assured by the connection of an MOV across the capacitor. A bypass breaker or disconnect is generally included to allow for maintenance and better over-voltage protection. Depending on the network requirements TCSC installations may be 100% variable although most typically have a fixed level of compensation combined with a variable level of compensation as shown in Figure 2-7. This allows the cost to be optimized by only controlling the series capacitance that provides reliability or other benefits. The controlled part can be scaled as required. PSC North America – Power Networks Page 14 of 65 Review of Series Compensation for Transmission Lines Series Capacitor Series Capacitor MOV Reactor Damping Reactor Thyristors MOV FPD Damping Reactor Bypass Swit ch Fixed Series Compensation FPD Bypass Swit ch Thyristor Controlled Series Compensation Figure 2-7 - TCSC primary circuit components PSC North America – Power Networks Page 15 of 65 Review of Series Compensation for Transmission Lines 3 Sub-synchronous Interaction with Series Compensation 3.1 Key Section References For gaining more in-depth knowledge on the subject matter in this Section 3, the following primary references are suggested: [11] Anderson and Farmer. (1996). “Series Compensation of Power Systems”. Encinitas, CA: PBLSH, Inc. [19] Farmer, Agrawal and Ramey. (2006). “Power System Dynamic Interaction with Turbine Generators”, Taylor and Francis Group, LLC. http://www.beknowledge.com/wp-content/uploads/2010/09/327.pdf [22b] IEEE. (1992). “Reader’s Guide to Subsynchronous Resonance”. Transactions on Power Systems, Vol. 7, No. 1, 0885-8950/92: IEEE Additional subject references are indicated in square brackets throughout the section with the complete paper reference list presented in Section 8. 3.2 Sub-synchronous Interaction When series compensation of transmission is introduced into the power network there is potential for various forms of sub-synchronous interaction (SSI) with other network components. SSI can lead to sub-synchronous oscillations (SSO), which if not inherently damped, in turn, could lead to unpredicted outages and possibly damage to network equipment. The subject of SSI is not new to the electric power transmission industry as SSI events have occurred and the associated phenomena as a result have been well-studied. As a result, SSI study techniques, risk assessment, and preventative measures have been developed as will be described in Section 3. Some actual SSI events will also be presented. SSI is a general term used to in place of more specific forms of sub-synchronous conditions that have been defined for electric power industry. These definitions are provided below in a structure that correlates the various types of SSI. [4][22b] Sub-synchronous Interaction (SSI) – Is a condition where two of more parts of the electrical system exchange energy at one or more natural frequencies below the fundamental frequency of the power system. The most prominent forms of SSI include: 1. Sub-synchronous Resonance (SSR) – Is a condition where an electric power system, most often with series compensated transmission lines, exchanges energy with a turbo-generator at one or more of the natural frequencies below the fundamental frequency of the power system. The three types of SSR are: a. Torsional Interaction (SSR TI) – A condition when the fundamental complement of electric system natural frequency (i.e., fundamental – natural frequency) of a series compensated electric power system is at or close to one of the mechanical torsional frequencies of the turbogenerator shaft system. If the rotor torsional frequency torque developed by this condition is greater than the inherent mechanical damping, the overall electro-mechanical system becomes excited. This is a classic PSC North America – Power Networks Page 16 of 65 Review of Series Compensation for Transmission Lines SSR condition which was defined following a damaging oscillatory events involving a turbine-generator (Mohave Generating Station) and a series compensated transmission line back in 1970 and 1971 in Nevada, USA. b. Self-excitation due to Induction Generator Effect (IGE) – A condition, independent of the generator shaft torsional modes, where the combined generator and electric power system results in a negative effective rotor resistance at a natural frequency below fundamental frequency. If the negative rotor resistance is greater than the apparent stator plus network resistance, self-excited, sub-synchronous current and electromagnetic torque in the machine can result. This phenomenon is a purely electric resonance condition. c. Torque Amplification (SSR TA) – A condition where transient torques amplify turbo-generator shaft system stress resulting from subsynchronous currents due to a major disturbances in the power network. These torques are proportional to the magnitude of sub-synchronous current, so transient current due to a short circuit and fault clearing can produce large torques, particularly if the transient current’s frequency complements a shaft torsional mode. 2. Sub-synchronous Control Interaction (SSCI) – An electric power system condition where a power electronic device (such as HVDC, SVC, STATCOM, wind turbine control etc.) interacts, at a natural frequency, with the electric power network containing near-by series compensated transmission. 3. Sub-synchronous Torsional Interaction (SSTI) – A condition involving control interactions between a power electronic device (such as an HVDC link, SVC, wind turbine etc.) and the mechanical mass system of a turbo-generator. While SSTI is not associated with series compensation, the definition is provided above for completeness and differentiation from the other SSI forms that are correlated with series compensation. SSTI is not further addressed in this paper. The term SSI will be used within this document unless the subject matter is only relevant to a more specific type. 3.2.1 Fundamentals of Series Compensation and SSI Series compensation is designed to partially compensate for the inductive reactance of a transmission line to increase power transfer capability and system stability. Compensation levels typically range from 20% to 80%. Consequently, the reactance due to the series capacitor (XC) will always be less than the inductive reactance of the transmission line (XL). Whenever capacitance (C) is introduced into an electric system that is primarily inductive (L) and resistive (R) in nature, new natural electrical frequencies and resonant conditions result. In general terms, the natural frequency (f n) is a function for the R-L-C components of the system, and when R is small the natural frequency can be approximated by: f୬ = 1 √ܥܮ which can also be expressed in terms of reactance as: PSC North America – Power Networks Page 17 of 65 Review of Series Compensation for Transmission Lines fn = fo ∗ ට ಽ where fo is the fundamental frequency of the system (60 Hz in the United States). Consequently, since XC will always be less than XL for a series compensated network, the natural frequencies will be less than the 60 Hz fundamental frequency. As the amount of series compensation is increased, the natural system frequency approaches the fundamental frequency. 3.2.2 Classic SSR-TI and SSR-TA As discussed above, series compensation introduces new natural frequencies in the transmission network that are below the system’s fundamental frequency. When currents at these natural frequencies flow through the stator of a generator, they create a rotating MMF that induces currents in the rotor. The induced rotor current will have a sub-synchronous frequency that is fundamental complement of the stator current frequency. For example, if a generator and series compensated network formed a resonant electrical circuit with a natural frequency of 40 Hz, the sub-synchronous frequency induced into the generator shaft system would be the fundamental complement: 60-40 Hz, or 20 Hz. [22b] 3.2.2.1 Generation Mechanical Modes of Oscillation A generator mechanical system can have a complex mechanical structure and often consists of multiple masses coupled on a shaft system such as high pressure turbine, low pressure turbine, generator, and exciter as shown in Figure 3-1. Figure 3-1 - Generator turbine lumped mass model The system can be represented as a lumped parameter model of rotating masses connected by torsional spring segments, and mechanical dashpots on and between the masses to represent any known inherent mechanical damping. From this model, the torsional modes can be determined through eigenvalue analysis. The torsional modes express the natural frequency of oscillation of one mass against one or more of the other masses (fm). If a generator has four masses as shown above, there will be four modes of oscillation: Mode 0 is typically 1-2 Hz, all masses move together, typically used in generator models for transient simulation programs such as PSS/E using a single, lumped inertia (H). PSC North America – Power Networks Page 18 of 65 Review of Series Compensation for Transmission Lines Modes 1-3 involve oscillations between the masses; the more masses that participate in a mode, the lower the frequency. Typically, these modes will all be below the fundamental 60 Hz frequency.[23] Only the torsional modes of oscillation that involve a participation with the generator are of concern with regard to SSI. 3.2.2.2 Generator Electro-Mechanical Energy Exchange In a sub-synchronous resonance condition, exchange of energy takes place in an oscillatory form. In the case of SSR-TI, this exchange of energy and torsional interaction occurs between the turbine-generator electro-mechanical system and the electric power network. As discussed in Section 4.4.1, the natural frequency (f n) of stator side currents is transformed into the rotor windings at a fundamental complement frequency (60 – f n). Energy can readily transfer between the electrical system and the mechanical system at this sub-synchronous frequency (60 - fn). If (60 - fn) is at or near one of the generator mechanical torsional modes (fm), this condition can potentially destabilize the mechanical torsional mode if there is insufficient mechanical dampening to overcome the developed electro-magnetic torque. As the rotor oscillates at the sub-synchronous torsional mode, voltage is induced into the stator, which sustains the sub-synchronous torque. This combined electro-magnetic-mechanical system is then said to be self-excited. This is the classic SSR-TI phenomenon that has historically been a concern for highpower steam generators. A generator that is connected electrically-close to a highly series-compensated transmission network can be at considerable risk for un-damped sub-synchronous oscillations. The risk is highest when a generator is radially connected compensated transmission line, however, risk also exists for generators in a more interconnected and meshed network that contains series compensation, although to a lesser degree. The fundamentals behind SSR-TA are the same as described above for SSR-TI; they both involve the oscillatory exchange in energy between the electrical network and the electro-mechanical characteristics of a generator. SSR-TA occurs when subsynchronous transients following major network disturbances have a frequency near the fundamental complement of a generator mechanical mode. SSR-TA conditions can lead to generator shaft oscillations with high amplitude and prolonged duration. Even though these oscillations may be positively damped, generator shaft segments can be subject to increased stress, and accelerated loss of life due to SSR-TA. As with SSR-TI, generators that are connected radially, or near radially to a series compensation transmission line are more at risk for adverse impacts from SSR-TA. 3.2.3 Induction Generator Effect (IGE) As explained in Section 3.2, IGE is a self-excitation condition involving the electrical characteristics of the generator and the series compensated network. Self-excitation due to IGE could result in excessive voltages and currents on the network, and possible equipment damage or accelerated fatigue. [22b] For thermal generators, pole-face amortisseur windings can be applied as an effective countermeasure to IGE. [22b] IGE is a moderate concern with wind generation located in the vicinity of series compensated transmission lines. Electrical self-excitation and resonance with series PSC North America – Power Networks Page 19 of 65 Review of Series Compensation for Transmission Lines compensation is of most concern during the generator start-up sequence or during crowbar action in a Type-3 (rotor double-fed through converter). This is because an IGE condition becomes less damped (more likely) when the rotor resistance is increased. [4] Crowbar action involves switching in a resistor on rotor side of a Type-3 wind generator to limit overvoltage within the converter. Refer to Figure 4-4 for a basic one-line arrangement of a DFIG (Type-3) wind generator. 3.2.4 SSCI Considerations for Wind Generation An event that initiated SSI between wind generators and a series compensated transmission line on the ERCOT grid in October 2009 led to a nearly 2 per-unit overvoltage which damaged wind generator rotor side protection circuits. The SSI was initiated when wind generator became radially connected to the transmission grid through a series compensated line. The SSI condition lasted only 1.5 seconds before being mitigated by a protective action which by-passed the series capacitor. [20][30][36] Prior to this event, it was generally accepted that there was minimal risk of SSI involving wind generation. As a consequence, this event sparked considerable research by various industry specialists, wind turbine vendors, and academics, especially when considering the increasing application of large scale wind farms and series compensation. Detailed analysis of event records and post-event simulations determined that the SSI was due to neither classical SSR nor SSTI. Rather, it was determined that the exchange in energy between the wind turbines and the series capacitor was due to an electricalside resonance involving the wind turbine converter and controls. This form of SSI and been specifically labeled Sub-synchronous Control Interaction (SSCI). As SSCI involves only the electrical characteristics of the wind turbine and the network, oscillations can develop extremely fast. In the 2009 ERCOT event, it is estimated that oscillations commenced within 200 ms from initiation of the event, and damage likely occurred within the next few hundred milliseconds. [20] This is unlike an SSI event involving machine mechanical interaction where oscillations typically develop over seconds rather than msec. Fortunately, there were no mechanical shaft torsional modes near the frequency of SSCI or catastrophic damage to the wind machines could have resulted. SSCI with wind turbines involves the associated converter and control system and as such, only Type-3 (rotor double-fed through converter) and Type-4 (full converter directly connected to stator) wind turbines are at risk for SSCI. Type-1(squirrel cage) and Type-2 (wound rotor) wind turbines do not have converters, so they are immune to SSCI, however, there is a moderate risk for SSR-TI and IGE when radially connected to series compensated line. [4][27] Type-3 wind generators are more at risk than Type-4 wind generators based on our research. In some cases the turbine vendor claims their Type-3 converter control system can be tuned to mitigate SSCI. [27] Conclusions in a study by Siemens indicate that their Type-4 wind turbine can be designed to be immune to SSCI over a wide range of sub-synchronous frequencies and are suitable to be applied in series compensated networks with proper control tuning. [31] PSC North America – Power Networks Page 20 of 65 Review of Series Compensation for Transmission Lines Because of the non-linear nature of the converter and controls of Type-3 and Type-4 wind generators, special care must be taken in their modeling for SSI assessment. This is further emphasized in Sections 3.3 and 7. 3.3 Assessment of SSI in Series Compensated Networks The previous section presented the theory and consequences of SSI with particular focus on interactions with series compensation. This section highlights the methodologies and tools that are available to assess the potential for SSI within series compensated networks. 3.3.1 SSI Analysis Depending on the form of SSI that is being evaluated, different study techniques are required. For certain forms of SSI, screening techniques can be used to make the overall process more manageable. Results of the screening analysis can be used to determine if more detailed analysis is required. Classic SSR, IGE and SSCI can be initiated from a minor perturbation, and thus small signal, linear analysis models and techniques can be applied. Eigenvalue analysis is a technique often applied to understand the natural frequencies of oscillation and the associated damping of each oscillatory mode. A frequency scan method can also be used to assess the potential for SSI. When non-linear system components and control systems such as control strategies for power-electronic based devices are involved, damping torque analysis methods in a time-domain-based system model may be most suitable. SSR TA can result as in response to a major network disturbance where system nonlinear characteristics can influence the condition. Consequently, more sophisticated modelling and time-domain, EMT-type, simulation programs are used to evaluate potential SSI TA. Information from the generator manufacturer on the generator impedance as a function of sub-synchronous frequency, as well as information on the torsional characteristic of the machine can be very beneficial for SSI analysis. [4] It should also be noted that if turbine-generators are connected to the electric network at the same point of interconnection and possess the same characteristics, the units can be lumped together for the analysis. The total generation plant MVA should be used as the basis for the per unit representation. This aggregation technique holds true for both large turbine generators as well as wind farms with common wind generation units. Depending on the network configuration, the level of series compensation, and the number of transmission lines containing series compensation, the quantity and subsynchronous level of natural frequencies will change. Comprehensive analysis must be performed to evaluate the potential for SSI in all credible network conditions. Combinations of the following system conditions should be considered in the overall SSI analysis: All credible network line outage conditions. Different levels of series compensation, including the outage of one or more series capacitor segments. PSC North America – Power Networks Page 21 of 65 Review of Series Compensation for Transmission Lines Outage of any near-by HVDC, SVC or other power electronic based devices that may influence system damping. Low and high generation output levels. This can be influential in the SSI evaluation associated with large scale turbo-generators and wind generation. Future planned changes to the network as practical. Depending on the nature of the system under study, the above variable system conditions can escalate to hundreds if not thousands of combinations to be evaluated. However, SSI issues typically manifest only when generation plant (e.g. wind generators or conventional generators), are part of a network that becomes radial or nearly radial with a series capacitor installation. These situations are generally the most critical ones. The sections below provide screening techniques that can be employed to make the evaluation process more manageable and practical. 3.3.2 Frequency Scan Screening The frequency scan screening process involves the following steps for each potential network configuration and level of series compensation: 1. From behind the generator in question looking out into the interconnected network, scan the network and calculate the apparent impedance for frequencies from 0 to 60 Hz. 2. Determine the equivalent reactance and resistance over the range of frequency to evaluate the potential for IGE. A near zero reactance coincident with a negative resistance indicates the high probability of IGE. 3. For classic SSR evaluation, the calculated impedance and electrical damping coefficient should be reflected to the rotor reference frame and compared to the torsional modes of the turbine-generator as shown in Figure 3-2. 4. For SSCI with wind turbines, the calculated impedance and the electrical damping characteristics are compared to the modes of the wind turbine including its electric power electronic-based control system. The screening should start with system conditions where the generation in question is radially or near-radially connected to a series compensated transmission line (i.e., perhaps several contingency levels from the normal all-lines-in base condition, up to N5) as these would conditions would generally pose the most of SSI. This approach could rule out the need to evaluate network conditions with more elements in-service, depending on the results associated with the more onerous network conditions. PSC North America – Power Networks Page 22 of 65 Review of Series Compensation for Transmission Lines Figure 3-2 - System electrical damping vs. torsional frequency (w/torsional modes) Source [4] For SSI screening associated with wind generation (i.e., Type 3 and Type 4), [12] suggests the frequency scans should be performed separately for the electrical network and the generator. The scans should be performed from the point of interconnection (POI) looking out into the network, and looking back into the generator independently. Since the wind generators with active power electronic devices are highly non-linear, the frequency scan method used on the generator must take this factor into account. The use of a white noise excitation technique is suggested in [12] for the turbine side frequency scan. System resonance points and negative damping indicators can be deduced from the pair of frequency scans to assess the possibility of SSR and SSCI. 3.3.3 Eigenvalue Analysis Eigenvalue analysis involves modeling the electrical network, generators, and controls of interest in a common linear system of differential equations. The linear system is used to closely predict the change in system states due to a small perturbation. This method can provide additional information on system performance beyond the screening frequency screening analysis. The results provide both frequency and associated damping for each identified mode of oscillation for the combined system. PSC North America – Power Networks Page 23 of 65 Review of Series Compensation for Transmission Lines For classic SSR TI, the generator mechanical system must be modeled along with the generator electrical representation. [34] For the study of SSCI, the wind turbine converter and control system must also be represented in detail. This method is more complex and computationally intensive as it requires more detailed system models and a separate linear model must be established for each network configuration to be analyzed. 3.3.4 Damping Torque Analysis Damping torque analysis can also be used to predict the frequency of sub-synchronous oscillations and the associated electrical damping through the application of time-domain simulation. The approach does not require the modelling of the mechanical characteristics of system generation; only the electrical representation is necessary within an EMT-type digital simulation or real-time simulation program. In this method, a small sinusoidal change in generator speed is used to determine the resulting change in electrical torque at the generator. The resulting change in electrical torque is simulated and if the electrical torque counters the machine speed it provides positive damping and vice-versa. The complex electrical torque response to the small speed perturbation can be used to calculate the electrical damping at the frequency of the injected perturbation signal. In general terms, the real part of the transfer function (or system apparent impedance) between speed change and the electrical torque represents the electrical damping factor. This damping torque analysis is performed over the full range of sub-synchronous frequencies to produce a damping factor curve versus frequency as shown in Figure 3-2. Even though this is a small-signal analysis method, the system model can be non-linear and represent system control strategies such as controls associated with SVC, HVDC and TSCS, and thus is practical for evaluating SSTI. This offers an advantage over eigenvalue analysis methods presented previously. 3.3.5 Detailed Time-Domain Analysis Time-domain analysis requires even more computational power as it involves determination of the system state with time though numerical integration of a system set of differential equations represented in a EMT-type digital software program or real-time simulator. As noted previously, the technique is useful for the evaluation of SSR-TA as system non-linearities are realized in response to a major network disturbance. Both electrical and mechanical dynamic characteristics are typically modelled, and the generator torque response can be simulated for large network disturbances and protective actions. [42] In the condition of SSR-TA, the response over time would show torque amplification and any undesirable oscillatory behavior. Detailed time-domain analysis has the advantage over linear analysis techniques as the overall system response can be simulated with account for control actions and limits, protection system actions, and unbalanced system conditions. The drawback with the method is that system set-up and simulations can be very time consuming and often times impractical. This is especially true when multiple combinations of network topologies and system conditions are to be analyzed. Accordingly, screening techniques should first be performed to determine those system conditions that should be evaluated using detailed time-domain analysis. [42] PSC North America – Power Networks Page 24 of 65 Review of Series Compensation for Transmission Lines The effectiveness of any mitigation measures (see Section 4) designed with regard to SSI can also be evaluated through detailed time-domain analysis. 3.4 ERCOT – SSI Impact Study Framework for Wind Generators ERCOT has established special requirements for the interconnection of wind generation in the generator interconnection process considering the existing and planned series compensated transmission lines in their region. ERCOT employs a multi-phase approach to their interconnection studies including a Screening Study, Full Interconnection Study, followed by and Interconnection Agreement. [17] For a generator project to be approved in ERCOT, it must be demonstrated that the project meets ERCOT’s technical grid compliance requirements, which include SSI per Section 5 of the ERCOT Planning Guide. The risk of SSI is first evaluated in the Screening Study phase through the use of frequency scan methodology. Based on the outcome of the SSI screening study, more detailed SSI analysis will performed during the Full Interconnection Study phase of the project interconnection process. The model used for the SSI screening will be prepared using the appropriate ERCOT power flow base case. An equivalent model will be created in PSCAD for the screening analysis that extends, as a minimum, to include local series compensated transmission lines. In general, detail would be maintained for five to six buses away from the POI. Reference [6] indicates that the level of buses in the equivalent can influence the frequency scan results and suggests that the GSU should be included in the model as it can have a significant influence on electrical damping. Looking out into the network from the behind the GSU at the POI, impedance versus frequency plots are produced under various system conditions to evaluate the risk of SSI. ERCOT requires the evaluation of both Critical and Credible Contingencies and various levels of series compensation as may be relevant to the analysis: Credible Contingencies – as defined in the ERCOT Planning Guides. Critical Contingencies – outage of transmission elements to achieve a radial or near radial topology between the POI and a series compensated line. Generally up to the N-5 level of contingency is the practical limit for selection. The combination of network topology that provides the most risk of SSI is determined from the frequency scans. Interpretation of the frequency scans will show worst case conditions through the identification of significant apparent dips in the apparent reactance, negative values of resistance, and negative values of resistance coincident with zero crossings of reactance. From the screening analysis, the system conditions and range of sub-synchronous frequencies of concern can be identified for detailed SSI studies. [12][35] For the detailed SSI studies, ERCOT will provide the appropriate base PSCAD model and list of contingencies that should be studied. ERCOT has set the proximity criteria limit to N-5 from the POI for the detailed SSI studies [35]. The developer is required to introduce a detailed representation of the generator in the PSCAD model. For a wind farm, this can be an appropriately aggregated representation. The developer is responsible for performing the detailed SSI analysis using PSCAD or equivalent, and for providing results to ERCOT for review and approval. PSC North America – Power Networks Page 25 of 65 Review of Series Compensation for Transmission Lines 4 SSI Mitigation and Protection Measures and Practical Applications 4.1 Key Section References For gaining more in-depth knowledge on the subject matter in this Section 4, the following primary references are suggested: [11] Anderson and Farmer. (1996). “Series Compensation of Power Systems”. Encinitas, CA: PBLSH, Inc. [19] Farmer, Agrawal and Ramey. (2006). “Power System Dynamic Interaction with Turbine Generators”, Taylor and Francis Group, LLC. http://www.beknowledge.com/wpcontent/uploads/2010/09/327.pdf [22b] IEEE. (1992). “Reader’s Guide to Subsynchronous Resonance”. Transactions on Power Systems, Vol. 7, No. 1, 0885-8950/92: IEEE Additional subject references are indicated in square brackets throughout the section with the complete paper reference list presented in Section 8 4.2 General Considerations and Definitions Consideration must be given to the potential for SSI whenever series compensation is being considered to improve that transfer capacity of a network. The ability to analyze and mitigate SSI has been clearly demonstrated over the last 30 years. Various countermeasures for SSI control have been researched, developed and successfully applied and advances in mitigation and protection measures are continuing. SSI risk assessment and management is not a simple task as the risk level is generally low, however, the consequence of an SSI event can be significant. The risk of SSI and the consequence of an event from both a generator and network reliability perspective should factor into the appropriate level of mitigation and/or protective measures to be applied. Other factors that will dictate the preferred measures include: Effectiveness of various measures Initial capital cost and O&M costs Responsibility for implementation and allocation of costs, and O&M Future plans for additional generation and/or series compensation Consequence of operating restrictions if measures are not implemented beyond operation procedures There are several measures that can be applied to mitigate the potential for SSI and protect equipment from exposure or damage from SSI. The measures can be classified as follows: Mitigation Measures (or Countermeasure) – Preventative measures implemented if the risk of SSI is probable for credible system configurations. Protection Measures – Measures implemented to protect equipment due to the detection of an SSO conditions. These can be applied as a back-up to mitigation PSC North America – Power Networks Page 26 of 65 Review of Series Compensation for Transmission Lines measures. Protection may be the only measure implemented if SSI is only likely as a result of contingencies beyond the credible set. Furthermore, the mitigation and/or protective measures may be sub-classified as: Network-based – measures applied in the network. For example, an SSI damping scheme installed at the series capacitor would be a Network-based Mitigation Measure. This can also be designated as an “outside-the-fence” measure as it would be applied on the network beyond the generator developer/owner’s asset boundary. Generator-based – measures applied at the generator or at the generator POI. For example, a torsional relay installed on a generator would be a Generatorbased Protection Measure. This can also be considered an “inside the fence” measure. The subsequent sections present various forms of SSI mitigation and protection measures, and based on our findings, summarize some of the basic pros and cons of each. Focus is on those measures that have been applied in the industry, however, some others that appear more commonly in literature are described, even though we were not always able to confirm an actual application. 4.3 Network-Based Mitigation Measures 4.3.1 Operational Procedures One countermeasure for dealing with SSI is to alter the network configuration or generation dispatch to limit the risk of SSI. This may involve restricting the operation of the generator under certain configurations that pose a risk to the unit(s). Another operating procedure may involve the by-pass or reduction of the level of series compensation under certain conditions to mitigate the chance of an SSI condition. For example under light load conditions when system damping is low it may be advantageous to simply bypass the series compensation to mitigate a possible SSI condition, as the series compensation is not needed at low power transfers. Overall, implementing appropriate operational procedures may be an acceptable and cost effective process if the system is not complex and where network conditions that pose a high risk are unlikely (i.e., several levels of contingency), or where the SSI condition only manifests during light load or low power transfers. 4.3.2 Passive Filter Damping As explained in Section 3.2.1 the risk of SSI in a series compensated network stems from the natural resonant condition of the network. From the fundamental standpoint, a series compensated line can form a series resonant R-L-C circuit which at a certain frequency has very low apparent impedance. This condition cab be countered by adding additional passive elements to the network with the appropriate impedance as a function of frequency. This approach can be used to effectively dampen the SSI and can be accomplished with either a shunt filter, series filter or a combination of the two. A properly designed series filter will provide the most influence considering the SSI risk is due to a series resonant condition of the network. PSC North America – Power Networks Page 27 of 65 Review of Series Compensation for Transmission Lines The addition of a 60-Hz blocking filter in parallel with series capacitor is one means of series passive filtering. The primary components of such a passive blocking filter is shown in Figure 4-1 below. The filter would block 60-Hz currents while effectively bypassing the capacitor for lower frequency currents. This would be a fairly expensive option as the ratings of the elements would have to be high due to short circuit exposure, and protections (MOV) would likely be required to control the voltage across the capacitive elements of the blocking filter. Series Capacitor I line XC Ic I filter XCF XLF Passive Filter Figure 4-1 - Passive filter in parallel with series capacitor 4.3.3 Active Shunt Filter Damping (SVC or STATCOM) A network connected SVC or STATCOM can be designed and tuned to actively mitigate SSI through the use of a supplemental damping control. The advantage of an active device is that it can be effective independent of the network configuration or level of series compensation. The input to the supplemental control can be generator speed, local voltage, or line current to provide damping by modulating the reactive current reference of the STATCOM. While this approach may be somewhat effective out on the network in providing positive damping over a range of sub-synchronous frequencies, it is generally more effective if applied close to specific generator(s). Various control strategies have been designed to mitigate SSI through the use of a STATCOM. Refer to Section 4.4.2 for further discussion. If an SVC or STATCOM is already present on the network to provide AC voltage control, Var compensation, and/or power system stability enhancement, the addition of a supplemental damping controller may prove beneficial depending on its location relative to generators. These active devices will produce harmonics that must be controlled in accordance with applicable harmonic standards. The capital cost and O&M cost of a new SVC or STATCOM installation is appreciable. 4.3.4 Active Series Damping (TCSC) and Shunt-Series Damping (UPFC) 4.3.4.1 Thyristor-Controlled Series Compensation (TCSC) Through the application of a TCSC, power flow over a transmission line can be dynamically controlled, providing improved power system stability and transfer capacity. Furthermore, through the introduction of a specific thyristor angle control method, the effective reactance of a TCSC can by modulated to effectively mitigate SSI. PSC North America – Power Networks Page 28 of 65 Review of Series Compensation for Transmission Lines XC Iline Iloop XL THYRISTOR CONTROL Figure 4-2 - Primary components of a TCSC As shown in Figure 4.2, the main circuit components of a TCSC includes a capacitor in parallel with a reactor that is controlled with opposite-poled thyristors. There are three basic operating modes: 1. Blocked Mode – the thyristor is not fired and the reactor is therefore blocked. The TCSC then appears as a pure capacitive reactance based on the series capacitor. 2. By-passed Mode – the thyristor is controlled to conduct current continuously, and the apparent impedance becomes inductive. 3. Controlled Mode – the thyristor path is partially conducting resulting in a current flow around the capacitor-reactor loop. Depending on the control angle of the thyristors, the apparent impedance can be either capacitive or reactive. Through certain control schemes such as Synchronous Voltage Reversal (SVR) the apparent capacitive reactance can even be boosted above the reactance of the capacitor alone. [2] Figure 4-3 - TCSC impedance characteristic with SVR. Source: [2] PSC North America – Power Networks Page 29 of 65 Review of Series Compensation for Transmission Lines As illustrated in Figure 4-3, a TCSC can include control methods which make the apparent impedance of the TCSC reactive in the sub-synchronous frequency range. Consequently, the TCSC can be very effective in mitigating the potential for SSI. At the same time, the scheme presents a capacitive reactance that can be controlled around the fundamental frequency. A TCSC includes several additional components as compared to a fixed series capacitor, including a control system, water cooled thyristors, and an appropriately rated series reactor. Consequently, the initial capital cost and ongoing maintenance costs must be factored into the decision to use a TCSC solution. A fixed series capacitor can be designed and constructed such that conversion to a TCSC can more efficiently accomplished in the future. TCSC have been installed in many locations around the world, and studies and performance show the risk of SSI can be mitigated through a specially designed control scheme. [2] Harmonic currents will be generated by a TCSC, however, the harmonics substantially remain within the loop formed by the capacitor and reactor and only low levels flow out to the transmission network. While the application of a TCSC provides effective and proven SSI mitigation, this approach would present a relatively high capital investment and O&M requirement that must be considered. 4.3.4.2 Unified Power Flow Controller (UPFC) A UPFC is another type of FACTS device that can be applied to actively mitigate the risk of SSI. As an UPFC provides a combination of shunt and series dynamically controlled compensation to a transmission system, studies have shown that a UPFC with supplemental control logic can introduce positive electrical damping at sub-synchronous frequencies. [32] Reference [21b] provides a comparison of SSR damping performance between a TCSC and a UPFC on an IEEE SSR Benchmark Case. The presented results show the UPFC can be supplemented with control to provide positive electrical damping for SSR mitigation with wind turbines, and performance is somewhat better than the TCSC that was simulated. More research is required to determine if a UPFC has been specifically designed and applied in the field to mitigate SSI. In general, the application of a UPFC would present a relatively high capital investment and O&M requirement as compared to other mitigation solutions. 4.4 Generator-Based Mitigation Measures 4.4.1 Passive Filter Damping A static blocking filter connected in series with a generator can protect a generator unit from SSI at specific sub-synchronous frequencies of concern. The blocking filter can be applied at the neutral or network-side of the associated GSU transformer and consists of a parallel inductor and capacitor which creates a parallel resonance (really high impedance) at the electrical frequency corresponding to the critical torsional mode of the generator. The blocking filter prevents the resonant sub-synchronous current from PSC North America – Power Networks Page 30 of 65 Review of Series Compensation for Transmission Lines entering the generator stator to effectively mitigate the potential for SSR-TI and SSR-TA. The design is independent of the current and future network conditions. Reference [13] states that this form of passive filter protection was installed at the Navajo Generation Station in Arizona in 1976. Component ratings, de-tuning impacts, and maintenance considerations would need to be considered to optimize the appropriate design. 4.4.2 Active Filter Damping Active filters at the generator side of the generator step-up transformer or at the point of interconnection can be effective at controlling SSI. Shunt devices can be more practical as they don’t have to be rated to carry the rated current of the generator as would be required in a series filter application. An active shunt device used solely for SSI damping purposes only has to be rated to counteract the highest initial expected levels of subsynchronous current through the generator. Active shunt filters can include thyristor-controlled reactors (TCR) much like an SVC, thyristor-controlled resistors, or a STATCOM. With generator speed as the control input, an active shunt filter can be effective in damping torsional oscillations within the bandwidth of control no matter what the form of SSI. In addition, an electrical side control input signal can provide the feedback needed to dampen purely electrical side oscillations such as IGE or SSCI. Other advantages of active filtering are: detuning is not a concern; and it is substantially immune to network changes including the level series compensation. STATCOMs and VSCs have been studied extensively in regard to SSI mitigation, including the mitigation of SSCI in wind turbines. In some cases, it has been shown that the device may be used in combination with other mitigation measures to provide increased positive electrical damping at the local generator(s). [39] 4.4.3 Supplementary Excitation Control Damping Supplementary Excitation Control Damping (SECD) modulates the synchronous generator excitation voltage to dampen torsional oscillations. It can be implemented through the fast active voltage regulator (AVR) and/or a Power System Stabilizer using an input signal derived from the shaft speed. Industry literature presents extensive research and efforts to demonstrate the use for excitation control to dampen SSI since the 1970s. More recently, advanced non-linear control techniques have been studied considering different types of excitation systems and PSS with regard to SSR-TI damping characteristics. [37] SECD can be a cost effective solution to mitigating SSR-TI as no new significant high voltage equipment is required. [15] This method of control is not practical for all types of exciters, as the time constants of exciters are critical to performance. Rotating exciters generally have effective time constants that are too large for the control of signals in the sub-synchronous frequency range. The power rating and location of the exciter on the shaft must also be considered in the possible implementation of SECD. In should be noted that the presence of a PSS may inherently contribute negative electrical damping at sub-synchronous frequencies, which can exacerbate an SSI PSC North America – Power Networks Page 31 of 65 Review of Series Compensation for Transmission Lines condition. [47] Consequently, care must be taken to properly include the representation of existing PSS in any SSI evaluation. Our research findings indicate that SEDC has been successfully applied together with TSR protection on the Shangdu steam turbine-generation plant in China [15], however, more research is recommended to determine if this SSI countermeasure has been successfully applied in the US. In general, it appears that SEDC may be practical to increase positive electrical damping of SSI when applied in conjunction with other mitigation measures such a specifically designed FACT device or when the risk of SSI is marginal. 4.4.4 Wind Turbine Control Damping The use of doubly-fed (DFIG) and direct connected induction wind turbines is becoming more prevalent in the industry. The benefits of these variable speed wind turbines include improved power efficiency and control of reactive power exchange with the AC system. Both of these types of wind turbines use voltage source converters (VSC) as the basis for the variable speed drive and reactive power control. Figure 4-4 presents a basic one-line diagram of a Type-3, DFIG that shows the back-toback VSC arrangement. The rotor side converter connects to the turbines rotor winding and the grid side converter connects to the generator terminal. ST A TO R IS AC NETWORK ROTOR XTG IG IR RSC GSC Figure 4-4 - DFIG Basic One-Line (Type-3) Since the first occurrence of the SCCI phenomenon involving wind turbines in Texas in 2009, there has been extensive study of the mitigation measures through the proper design and tuning of the turbine’s control system. Several papers on the subject have been published by wind turbine suppliers, academics and consultants. The papers consider various control input signals as well as rotor versus grid side converter supplemental control strategies in Type-3 wind turbines. [36][44] In a presentation by General Electric, it is shown that control strategy used in their wind turbines can mitigate SSCI. [27] Vestas also claims that most SSCI issues can be addressed through the proper tuning of their control system [36]. Regardless of the wind turbine supplier and control scheme, care should be exercised to demonstrate the performance through detailed simulation if the potential for SSCI exists. Modification of the control scheme on wind turbines that are in service prior to the application of a near-by series compensated line will be much more involved and costly than designing and testing a proper scheme for a new installation. PSC North America – Power Networks Page 32 of 65 Review of Series Compensation for Transmission Lines 4.5 Network-Based Protection Measure 4.5.1 Series Capacitor By-pass A protection to by-pass the capacitor can be implemented upon the detection of sustained or growing sub-synchronous currents through the element. This would quickly change the resonant state of the network to cease the SSO. The drawback of this method is that permanently bypassing the series capacitor will reduce the dynamic stability of the network and thus generation may have to be tripped concurrently. 4.6 Generator-Based Protection Measures 4.6.1 SSI Relays Relay protection can be applied to a specific generator or group of generators to protect the unit(s) from damage due to an SSI condition. Typically, the relays are set to trip the generator unit(s) based on a level and duration of the SSI. This type of protection is sometimes applied as back-up to SSI mitigation measures. These types of relays were initially developed in the 1970 timeframe in response to the first occurrence of SSR-TI events. More recently, relay manufacturers have researched and developed solid-state, micro-processor relays for the purpose of SSI protection. The following table presents a summary of generator-based SSI relay types currently available in the industry: [45] Relay Signal Input Comments Torsional Motion (Stress) Relay Shaft Speed Developed and applied in the late 1970s. Speed is processed by band-pass filters to calculate conditions at particular sub-synchronous frequencies of interest. Torsional Stress Relays (TSR) have been applied at several generator units and are still available. Newer torsional motion relays are micro-processor based. S. California Edison patent Terminal voltage Micro-processor relay that uses exclusive timedomain analysis on wave parameters of successive half cycles. More research is recommended as to the application of this 1986 patent, performance information, and current status. ABB Research Ltd. patent Generator terminal voltage Micro-processor based relay developed in the 2011 timeframe. ERLPhase Power Technologies Generator terminal voltage and currents Micro-processor based relay is used to perform frequency spectrum analysis on the inputs to compare sub-synchronous frequency components with fundamental component. PSC North America – Power Networks Page 33 of 65 Review of Series Compensation for Transmission Lines Relay Application Innovation Armature current Micro-processor based relay. Developed in late 2009 and applied in 2010 by AEPSC at two locations as backup generator protection. The torsional stress relay (TSR) appears to be the most widely applied measure to protect generators from the potential of SSI due to the proximity of HVDC converters or series compensated lines. The input to a TSR is shaft speed measured by magnetic pickups at toothed wheels installed on the turbine and generator end of the shaft. The shaft speed measurements are evaluated for indications of torsional oscillations at the critical mechanical frequencies of interest. A TSR relay can have programmable settings for the critical frequencies and magnitude/duration of oscillations to issue actions such as a warning, alarm or trip. Some TSR relays have a built in event and signal recorder to aid in fault tracing. In addition to shaft speed, a TSR would need electrical inputs to be effective for protection of IGE or SSCI since these forms of SSI do not involve the mechanical aspects of the generator and can’t be detected from shaft speed. A generator outage would be required to install and commission a TSR and there is always risk of mis-operation of a TSR that could result in an undesired generator outage. Information of generator stress versus cycles to failure is required to properly set the relays. Our research indicates that TSR relays have been applied on several generating units, primarily to protect against the possible occurrence of SSTI since the late 1970s. However, detailed performance information and operations and maintenance experience with TSR relays was not found to be readily available. In response to the recent SSCI phenomenon, relay manufactures have proposed and developed new SSI protection based on high speed signal measuring, advanced filtering, and fast processing with micro-processor based relays using electrical quantity inputs. Oscillations in an SSCI event can develop very rapidly which imposes the requirement for a very fast detection scheme. [20] The filtering and signal processing for the older generation of SSI relays introduce a long time delay which makes these relays less reliable or even ineffective for SSCI protection. PSC North America – Power Networks Page 34 of 65 Review of Series Compensation for Transmission Lines 5 Protection Schemes and Protection Relay Considerations 5.1 Key Section References For gaining more in-depth knowledge on the subject matter in this Section 5, the following primary references are suggested: [3] ABB. (2012). “Series Compensated Line Protection”. ABB Webinar. http://www.youtube.com/watch?v=rKWnMyTYUDM Altuve, Mooney and Alexander. (2008). “Advances in Series-Compensated Transmission Lines”. TP6340-01, Schweitzer Engineering Laboratories, Inc. Anderson and Farmer. (1996). “Series Compensation of Power Systems”. Encinitas, CA: PBLSH, Inc. IEEE. (2007). “IEEE Guide for Protective Relay Application to Transmission-Line Series Capacitor Banks”, IEEE Power Engineer Society – Power Systems Relaying Committee, Std C37:116-2007 Kasztenny. (2001). “Distance Protection of Series-compensated Lines: Problems and Solutions”. GER-3998: GE Power Management Wilkinson. “Series Compensated Line Protection Issues”. GER-3972: GE Power Management [10] [11] [22] [26] [43] Additional subject references are indicated in square brackets throughout the section with the complete paper reference list presented in Section 8 5.2 General Series compensation may be installed in the middle of a transmission line or at one or both ends. In general, there are more protective relay complexities when the series capacitor is installed at the line end(s). Of course, if series compensation is initially installed in the middle of a transmission line the addition of a new substation within the line may increase the protection complexities - therefore it is important to understand the line end issues as will be highlighted in this section. The addition of series compensation within a transmission line presents complexities with regards to the relay protection of the line itself, and in many cases the relay protection of adjacent and parallel lines. These complexities will be a function of: system configuration, level of series compensation, series capacitor protection and control schemes, and other factors. The application of series compensation first occurred in the 1950s in the US, and the use of series compensation is becoming more prevalent, so fortunately there is sufficient industry experience and knowledge available with regard to associated protection issues and solutions. If the complexities are well understood, relay protection systems can be reliably designed, tested and applied, especially through the use of modern relay technologies. [43] PSC North America – Power Networks Page 35 of 65 Review of Series Compensation for Transmission Lines This section begins by describing the unique system protection issues associated with the introduction of transmission line series compensation. It then describes the advanced relays and schemes that can be applied to address the issues described. Lastly, case examples which present philosophies and experience with the protection of series compensated transmission lines from three utilities are summarized. 5.3 Influence of Capacitor Protection Modern series capacitors are protected by a parallel metal oxide varistor (MOV) as illustrated in Figure 5-1. The MOV limits the voltage across the capacitor based on its rated protective level. For transient conditions, the MOV will conduct to absorb energy as necessary to limit the periodic overvoltages across the capacitor. When the MOV conducts, the apparent series impedance of the parallel elements changes in a nonlinear manner as the MOV has non-linear resistive characteristics. The protective voltage level of the MOV is selected based on normal conditions, system power swing conditions and anticipated overload conditions. [29] VS C Series Capacitor MOV Bypass Switch Figure 5-1 - MOV protected series capacitor The MOV is also protected by a bypass switch which is triggered based on its rated energy dissipation level. When this switch operates, both the MOV and the series capacitor are bypassed until the energy level decreases below the desired setting. For most faults that result in high currents through the series capacitor, the MOV-based protection will bypass the series capacitor and impedance relays will see the line transmission line impedance only. For high impedance line-ground faults however, the current may not be sufficient to trigger the bypass switch and the capacitive reactance will influence the apparent impedance seen by impedance distance relays. For singlephase faults, only the MOV protection on the faulted phase may function, while the capacitors on the un-faulted phases will not be circumvented. Consequently, the MOV protection can greatly influence the apparent impedance seen by impedance relays and this must be carefully considered in the relay protection system design. High impedance faults as well as faults under minimum generation conditions should be evaluated as part the relay system design and evaluation. [10][29] 5.3.1 Voltage Inversion and Current Inversion Faults electrically close to series capacitors can lead to voltage and or current inversions where the phase angle changes by 180 degrees. [3][10][26] When the impedance between a relay and a fault is capacitive, the local voltage at the relay may invert depending on the relative magnitude of other system impedances. The diagram in Figure 5-2 presents a fault condition on a series compensated line between PSC North America – Power Networks Page 36 of 65 Review of Series Compensation for Transmission Lines Bus B and Bus REMOTE, where voltage inversion will occur across the series capacitor; VB is 180 degrees out of phase from VC. For this particular voltage inversion condition to occur the Xc impedance conditions listed must hold true. If the line has impedance (or distance) protection, then if the relay uses Bus B for the voltage input, the relay would sense the fault as a reverse fault rather than an actual forward fault, and may fail to operate. However if point C was used as the voltage input then the forward fault would be correctly detected. As shown, the voltage at Bus B is reversed and remains reversed as you move toward the source until you reach Point A. If a new bus were to be added in this segment in the future, voltage reversal would be a concern at this bus as well as at Bus B. kXL2 SO URCE XS XL1 B A VS XC REMOTE XR XL2 C VC XC > kXL2 VR VA XC < XS + XL1 + kXL2 VF VB Figure 5-2 - Voltage profile for a line side fault near a series capacitor (Forward Fault) Figure 5-3 shows a voltage profile for a fault on a line behind a series compensated transmission line. For the impedance conditions listed, the voltages on either side of the capacitor will again be 180 degrees out of phase. If an impedance relay protecting the series compensated line at Bus B uses the line side voltage (Point C), under this condition the voltage will reverse and the apparent impedance will indicate a forward fault rather than an actual reverse fault, and mis-operation may result. Conversely, if the Bus B voltage was used then the relay would correctly register the fault in the reverse direction. gXL2 SO URCE XS REMOTE B XL1 XC C XR XL2 VB VS VR VF XC > gXL1 XC < XR + XL2 + gXL1 VC Figure 5-3 - Voltage profile for an adjacent line side fault near a series capacitor (Reverse Fault) PSC North America – Power Networks Page 37 of 65 Review of Series Compensation for Transmission Lines The simple voltage inversion examples presented above are based on three phase faults and positive sequence impedance. Similar voltage reversal conditions can affect the directional discrimination of both negative and zero sequence relays. Refer to Reference [10] for supporting explanation and examples. When the impedance on one side of the line fault is inductive and the other side of a line fault is capacitive a current inversion can occur. This condition is illustrated in Figure 5-4. As shown the current from one end of the line is 180 degrees out of phase from the current of the other side of the series compensated line. This current inversion condition is opposite of the condition that defines an internal fault on an uncompensated line as one appears as an in-feed and the other as an out-feed. There are also system conditions that may result in the current being indeterminate at one end during an internal fault. The same current reversal issues can occur with the negative and zero sequence currents if Xc is larger than the negative sequence source impedance or zero sequence source impedance, respectively. [10] SOURCE XS REMOTE XC XR XL IS IR VR XC > XS IS IR VS Figure 5-4 - Example of current reversal condition in a SC line Current inversion and indeterminate current conditions can affect the desired operation of distance, phase comparison, and directional elements of protection relays. [10] 5.3.2 Distance Protection – Measured Impedance Special considerations have to be made when applying distance protection on a series compensated line as explained in this section and in Section 5.3.3. Distance relay impedance characteristics (blue circles) shown in Figure 5-5 are associated with the protection of a mid-point series compensated transmission line. The apparent impedance seen by the relay is much less if the series capacitor remains inservice, as opposed to if the capacitor is by-passed. If the Zone 1 mho relay is set for the condition of the series capacitor by-passed (dashed circle), it can overreach beyond the end of the line and potentially trip the line inadvertently for an external fault condition. Depending on the level of series compensation, the Zone 1 reach would have to be reduced well below the typical 80-90% reach used to protect an un-compensated line. [10] PSC North America – Power Networks Page 38 of 65 Review of Series Compensation for Transmission Lines X B ZL B A R -jXC Figure 5-5 - Impedance protection on a mid-point SC line The example above explains the measured impedance difference for the two system states with and without the series capacitor by-passed. This issue gets further compounded with the dynamic and non-linear characteristics of the MOV when the element is triggered and is not in the by-passed state. The location of the series capacitor and the degree of compensation will impact the measured apparent impedance. For a close-in fault to the series capacitor, the net reactance seen by a distance relay could be capacitive. In such a case, a standard impedance relay would sense that the fault was in the reverse direction, leading to potential mis-operation. Thus, series capacitors located at the line end can also effect directional discrimination in addition to the measured impedance. [10][26] 5.3.3 Sub-synchronous Transient Signal Impacts As explained previously in Section 3.2.1, the application of series compensation within a power system introduces new electrical resonance conditions at sub-synchronous frequencies. When faults and switching operations occur in the vicinity of series compensation, transient electrical system oscillations at sub-synchronous frequency will be imposed on the fundamental frequency response. The magnitude and number of sub-synchronous transients will depend on the degree and number of series compensated transmission lines in service and the operation of the protection function associated with each series capacitor. The transient response of the power system due to large disturbances can adversely impact the operation of protective relay systems on the series compensation line and potentially on adjacent lines. The input signal filter response of protective relays should be appropriately considered. [26] Figure 5-6 illustrates a transmission line that is compensated on the remote end. For a fault at the remote end past the series capacitor, the capacitor’s reactance in series combination with the line’s inductance will produce a sub-synchronous transient. Considering that this transient response will be at a frequency less than the fundamental frequency as explained in the previous paragraph, the lines inductance will appear less and the capacitance of the will be higher. This will result in a higher transient voltage drop across the capacitor and the line will appear to have a higher compensation level during the transient period from the perspective of a distance relay at the sending end of the line. [26] This can result in mis-operation of the distance relay for faults beyond the line end series capacitor as further explained below. PSC North America – Power Networks Page 39 of 65 Review of Series Compensation for Transmission Lines XL XC FAULT Figure 5-6 - Transmission line with remote line end SC The apparent impedance seen by a Zone 1 distance relay at the sending end of the line is shown in Figure 5-7 by the red arrowed trace along with the zone 1 characteristic as the blue circle. The apparent impedance (red trace) changes over several cycles due to the transient response superimposed on the line from the fault. In this case, it is assumed that there is some resistance in the system to dampen the transient response. The apparent impedance initially appears less due to the transient response, so the relay sees the impedance entering the Zone 1 trip region (blue circle). The outcome is that the relay could erroneously trip the local end for faults which are actually beyond the Zone 1 intended reach, or potentially beyond the remote end itself, and may lead to coordination issues with other protection schemes. It may be possible to alleviate this problem by further reducing the reach (reduce diameter of the blue circle to below the red apparent impedance trace) and/or by introducing a Zone 1 time delay to allow time for the transient to move out of the blue circle before the relay initiates a trip. In either case, the consequence for coordination with other protections would have to be carefully studied. X A R Figure 5-7 - Distance relay overreach due to sub-synchronous transient signals Sub-synchronous transients will also occur after a fault is cleared if the series capacitor MOV stops conducting and the series capacitor is effectively re-inserted into the network. These transients may adversely impact relay operation and thus they must also be considered. 5.3.4 Adjacent Line Protection Impacts When series compensation is added to a transmission line, attention must be paid to the protection of adjacent transmission lines in addition to the protection on the series PSC North America – Power Networks Page 40 of 65 Review of Series Compensation for Transmission Lines compensated line itself. This is particularly true for line end applications of series compensation. Distance relays on adjacent lines can be influenced by the negative reactance characteristic of the series capacitor. [10] The dotted circle in Figure 5-8 below depicts a Zone 1 relay on an adjacent line to a local end series compensated transmission line. As shown as standard distance relay would incorrectly operate for line faults on the series compensated line that are close-in to the capacitor. X B B A -jXC R A’ Figure 5-8 - Zone 1 distance relay on SC line (solid) and adjacent line (dotted) If the adjacent lines are short and the line reactance is less than the capacitor reactance, the concern gets extended to the remote bus as well as the local bus of the adjacent line; two or more line sections away. [3] 5.3.5 Other Impacts Series capacitors can exacerbate relaying issues associated with un-transposed lines and zero sequence mutual impedance between parallel lines. Since the addition of a series capacitor effectively lowers the line balanced self-impedance, any unbalanced line impedance and mutual impedance will become more pronounced with increased series compensation. [26] Series compensation provides for higher steady-state power flows in the power system and the increase in load current can impact the sensitivity setting of protective relays. 5.3.6 Automatic Reclosing for Series Compensated Transmission Lines Automatic reclosing strategies may be used in conjunction with series compensated transmission lines. The relay protection complexities presented within this paper must be factored into an automatic reclosing design strategy. Furthermore, the scheme must be properly coordinated with the series capacitor control and protection. Based on the system requirements, either three-phase reclosing or single-phase reclosing may be appropriate. The primary advantage of for single-phase reclosing is to maintain the healthy two phases to maintain some level of power transfer to enhance system stability. The series compensated case studies summarized in Section 5.5 address the general automatic reclosing philosophies applied by the corresponding transmission owner. For example, BC Hydro does not switch their series capacitors as part of the transmission PSC North America – Power Networks Page 41 of 65 Review of Series Compensation for Transmission Lines line; rather the series capacitor is switched separately but in coordination with the transmission line switching sequence. [33] Definitions used in this Section 5.3.6 include: SPT/SPR – Single-pole tripping and single-pole reclosing 3PT/3PR – Three-pole tripping and three-pole reclosing 5.3.6.1 Series Capacitor Switching When designing the automatic reclosing philosophy and practice for a series compensated transmission line, consideration should be made for whether the capacitor is to be switched as part of the transmission line, or if the capacitor will be separately switched. In the latter case, the capacitor switching must be carefully coordinated with the transmission line protections and switching. Benefits associated with separately switching the series capacitor include: 1. Minimizing transmission line circuit breaker transient recovery voltage (TRV) duty requirements, 2. Reducing the series capacitor MOV capacity requirements, 3. Mitigating dc current component in transmission line shunt reactors, 4. Mitigating low-frequency transients and the possibility of SSR-TA with nearby generators during reclosing, 5. Reducing the secondary short circuit arc by increasing the network impedance during reclose dead time (for SPT/SPR schemes only). [22] If by-passing the series capacitor is required to keep the TRV duty within the rating of the transmission line circuit breakers, the by-pass operation would need to occur prior to the line breakers opening. The series capacitor switching logic and coordination can be accomplished by using local current and voltage signals. Zero sequence mutual coupling from unbalanced faults on parallel lines should be analyzed to prevent undesired operation of the series capacitor switching logic. Alternatively, signals can be communicated from the transmission line terminals to properly operate and time the series capacitor by-pass and re-insertion. The speed and reliability of the communication channels needs to be factored into the design. [22] The benefits listed in this Section apply to the switching of series capacitors during line energization as well as to automatic reclosing. 5.3.6.2 Three-phase Automatic Reclosing (3PT/3PR) Coordination of 3PT/3PR is more straightforward than using single-pole reclosing on a series compensated transmission line. If it is decided to implement only 3PT/3PR on a series compensated line, both the line protection switching, and capacitor protection and switching should be done on the three-phase basis. The reclosing scheme should be carefully tested using an EMT-type simulation program to assess breaker duties, transient effects, dependability and security of local and adjacent line relaying, and coordination with any series capacitor protections and enabled switching schemes. PSC North America – Power Networks Page 42 of 65 Review of Series Compensation for Transmission Lines 5.3.6.3 Single-phase Automatic Reclosing (SPT/SPR) System stability may be improved by employing a SPT/SPR scheme on a critical series compensation transmission line. Furthermore, it may be beneficial to leave the series capacitors of the healthy two phases in service to maximize the transfer capacitor during the SPT/SPR interval. It is important that the series capacitor protection is properly coordinated with the SPT/SPR scheme such that no three-phase capacitor switching is triggered during the automatic reclosing sequence. Rapid and precise phase selection is required for SPT. With series compensated transmission lines, phase selection can be more complex due to possible current and voltage signal inversions for high impedance faults, so proper relays and phase selection methods must be applied and tested. Furthermore, low frequency transients associated with series compensated lines can introduce errors in the signals measured by the relays. With advanced relays and high-speed, multi-channel communications for PILOTaided schemes, these complexities can be overcome. [43] 5.3.6.4 Spurious By-pass Operation There is the possibility of spurious operation of series capacitor protection due to certain external faults. If the series capacitor protection results in a single phase by-pass/reinsertion, it can be problematic for the transmission line protection on the series compensated line. This circumstance is more prevalent when directional-based comparison schemes are utilized with sensitive ground fault protective elements, as undesired tripping may occur. [33] 5.4 Relay Protection Solutions 5.4.1 Advanced Relays for Series Compensation Application Protective relays have advanced for the special purpose of protecting series compensated transmission networks. Modern relays and systems have been devised and proven to enhance the reliability of distance, directional, and differential based protection of series compensated networks. The relays described below are substantially based on documentation produced by two vendors; Schweitzer and General Electric. Other vendors may offer variations or other advanced relays for the protection of series compensated lines that are not covered in this summary. 5.4.1.1 Memory Polarization Standard distance relays are self-polarized through the typical use of positive sequence voltage or un-faulted phase voltages. Use of these quantities for polarization may lead to relay mis-operation in the case of voltage inversion or close-in three-phase faults where the relay input voltage is very low. Modern distance relays provide the capability to use memory polarization with multi-input comparators to enhance relay pickup and fault directional recognition. Memory polarization uses a time-dependent combination of pre-fault and post-fault voltage conditions when this feature is enabled in a relay. The time-dependent memory function is used to phase out the pre-fault information with time to position the relay for proper operation in response to situations such as system swings or line switching into a fault. [10][26] PSC North America – Power Networks Page 43 of 65 Review of Series Compensation for Transmission Lines In series compensated networks, the duration of the polarization memory should be set for proper relay pickup with consideration of the series capacitor MOV protection response, and the slowest fault clearing time. [10] 5.4.1.2 Special Series Compensation Logic Over the many years of developing and testing protection systems for series compensated lines, special logic has been incorporated to improve overreach in Zone 1 of distance relays. Through the proper setting of the special logic, the relay can detect when a fault is beyond the series capacitor and block the operation to prevent overreach. If the fault is between the relay and the series capacitor, the relay will correctly operate. This is accomplished through the comparison of a measured voltage with a calculated voltage by the relay. The special logic requires the capacitive reactance to be specified as part of the setting, with the appropriate sign based on the value measured by the relay. With the relay logic and careful setting, correct directional sensing will be accomplished regardless of the location of the voltage transformer in relation to the series capacitor. The zone 1 reach is set based on the uncompensated transmission line impedance. [10] 5.4.1.3 Sequence Component Impedance for Directional Discrimination Relays that use negative or zero sequence component inputs provide superior directional discrimination for single-phase faults. When analyzing the apparent impedance with negative sequence quantities for example, there is generally sufficient margin in the calculated apparent impedance between forward and reverse fault conditions and the sign of the apparent impedance is opposite depending on the faults direction. Proper settings in these relays provide correct directional discrimination even with the possibility of voltage reversal. [10][26] 5.4.2 Protection Schemes 5.4.2.1 Line Current Differential Protection Line current differential schemes can be a very good choice for protection of series compensated transmission lines. Some of the advantages of this scheme include: Immunity to voltage inversion No impact due to series capacitor protection (i.e., MOV operation) The location of the associated potential transformers is not a concern The sub-synchronous transients may influence the operational time of differential element so the relay’s filter response should be understood. As series compensated lines may be very highly loaded, load flow impacts should be reflected in the design, setting selections, and testing. Reference [10] suggests the use of Alpha Plane differential elements to accommodate the potential for current inversion and sub-synchronous transients. The use of a negative sequence differential scheme in parallel with the positive sequence scheme may also be used to contend with current inversion and ensure correct operation. A reliable communications path between line end relays is required as the scheme requires a precise measurement and comparison of current signals from each end. PSC North America – Power Networks Page 44 of 65 Review of Series Compensation for Transmission Lines Improvements in communications and signal conditioning techniques has enhanced the security of differential scheme performance. 5.4.2.2 Directional Comparison Protection Directional comparison can provide a secure and reliable protection system for series compensated lines with the application of the advanced relays such as those summarized previously in this Section 5.4, and through careful consideration of the relay complexities discussed herein. Directional comparison schemes should be equipped with blocking units and transient blocking circuits to eliminate the possibility of false tripping due to CT saturation and transient blocking logic may be necessary for situations where directional integrity cannot be maintained for slow clearing faults. [10][26][43] In contrast to a line current differential scheme, variations in signal communication time can be easily accommodated though use of a time delay greater than the maximum communication time. Furthermore, a directional comparison scheme is comparing discrete relay signals rather than instantaneous current phasor signals, so it can again be easier to make adjustments to optimize dependability and security. [43] Permissive Overreach Scheme A permissive overreach scheme can provide secure protection of a series compensated line. The reach of the schemes distance devices should cover the condition where the series capacitor is by-passed by its overvoltage protection (i.e., the uncompensated line impedance). The drawback to this is that the relays will have a high degree of overreach when the series capacitor is not by-passed and this presents more potential for misoperation during external faults. [10][26] Underreaching Direct Trip and Direct Transfer Trip Scheme As series compensated lines are often very long, direct trip schemes are frequently added to supplement a differential or directional comparison scheme to provide an enhanced level of security. As presented in Section 5.3.1, current reversal is possible in series compensated lines, and this can be an issue for directional comparison protection schemes. For faults at one end of the line, the current at the other end can be indeterminate or reversed depending on network impedances. This condition causes permissive overreach schemes to be less reliable for line end fault as compared to faults near the middle of the line. In series compensated lines, a direct transfer trip scheme using underreaching relay settings can be used to provide dependable protection for near end line faults. Thus, a direct transfer trip scheme together with a permissive overreach scheme can greatly enhance the dependability of the overall protection system. 5.4.3 Protection Design and Performance Verification Design and testing protective relaying schemes for and in the vicinity of a series compensated transmission line with detailed models of the transmission network and key components is essential. Digital simulation of relay performance using an electromagnetic transient program (EMT-Type) or real time digital simulator (RTDS) is PSC North America – Power Networks Page 45 of 65 Review of Series Compensation for Transmission Lines recommended to ensure a secure and dependable relay protection design. A steadystate short circuit program will not reflect transients due to series compensation. Detailed electromagnetic transient simulation is required to produce the subsynchronous transients that will be associated with series compensation in the network and determine impacts to the relay system performance. Other important modeling requirements include detailed representation of: The non-linear MOV characteristics for the series capacitor protection and reinsertion control Relay performance Potential transformer or CCVT transient response Frequency dependency of the local transmission lines and transformers Automatic reclosing controls Various system conditions should be analyzed with a combination of fault location and fault types. It is important to apply ground faults with low and high resistance as this may influence the operation the series capacitor protection, which in turn, can impact the relay system response. Variation of the fault inception angle is also recommended to produce different dc transients and different levels of sub-synchronous frequency transients. [10][18] The use of an RTDS program will go one step further in the performance verification as actual relays can be connected directly to the simulator. 5.5 Protection Case Studies 5.5.1 BC Hydro Source Protection of EHV Transmission Lines with Series Compensation: BC Hydro’s Lessons Learned [33] Summary Protection challenges with regard to series compensation of BC Hydro’s 500 kV transmission network included: Undesired operation of fault direction and detection elements: o Zone 1 overreach o Voltage inversion o Current inversion Influences of unbalanced currents caused by single pole switching (SPS) or line tripping (SPT) and reclosing (SPR). Series capacitor switching. Sub-synchronous transient impacts on relay operation. PSC North America – Power Networks Page 46 of 65 Review of Series Compensation for Transmission Lines The paper focuses on capacitor switching issues during line faults and routine line energization. Issues magnified by the addition of series compensation in the BC Hydro system include: Unequal line transpositions. Unequal transmission line lengths per phase (adjacent cable circuit). Transmission line single pole open (SPO) conditions. Protection Scheme BC Hydro uses identical primary and standby systems with minor setting differences (dual primary systems). They claim this arrangement provides the benefit of increased security and lower costs. Permissive overreaching transfer trip (POTT) with echo logic is used on all 500 kV transmission lines. Residual and negative-sequence directional overcurrent elements are used as part of the POTT. Phase-segregated direct transfer trip (DTT) is also applied to improve selectivity and lower operating time for certain single-phase faults. Time-overcurrent ground relays are used for backup ground fault protection. The paper presents their approach for setting the negative-sequence directional overcurrent element to minimize the chance for mis-operation based on lessons learned from actual studies and application. The suggested approach is to: Set considering the minimum Z2 source for forward and reverse faults, as well as the line Z2 and setting the elements to half of this total impedance. This method is recommended when the system impedances are dissimilar at each line terminal. An appendix in the reference paper discusses the pros and cons to this approach over the method recommended by the rely manufacturer for BC Hydro’s applications. BC Hydro addresses the impact of security of negative-sequence directional element operation due to non-transposed circuits by appropriately adjusting the unbalanced-tobalanced current ratio factors, and forward and reverse negative sequence impedance settings accordingly. Auto-reclosing challenges BC Hydro has multiple modes of protection, and the normally operated mode is: SPT/SPR for single line to ground faults Three pole tripping/reclosing (3PT/3PR) for multi-phase faults The interval between SPT/SPR operations appears as an internal fault to a POTT scheme. When incorporating sensitive operation for high impedance ground faults, certain elements must be temporarily disabled to avoid undesired operation. For uncompensated lines, a time delay of 6 cycles is used to mitigate undesired operation of the ground elements. For a series compensated line, an extended time delay was required (12 cycles) to accommodate single pole capacitor switching (see next section). Alternatively, BC Hydro suggests that digital communications can be used to provide PSC North America – Power Networks Page 47 of 65 Review of Series Compensation for Transmission Lines signals from the series capacitor back to the terminal relays to block sensitive elements during switching. Series Capacitor Switching BC Hydro uses what they claim is a unique switching practice for their series compensated transmission lines. Rather than switching the transmission line and associated series capacitor as a single element, BC Hydro uses the practice of separately switching the capacitor when the line is tripped, and then reinserting the series capacitor after the line is successfully reclosed. For SPT/SPR operations, only the effected phase of the series capacitor is switched out/in to maximize the power transfer through the healthy series compensated phases. The capacitor switching takes place 6 cycles after the line (or phase) is tripped and is reinserted 10 cycles after the line (or phase) is successfully re-closed. Protection Scheme Testing and Verification The BC Hydro paper emphasizes the importance of detailed transient testing for protective relaying applications through the use of real-time digital simulation that incorporates the actual micro-processor based relay algorithms. BC Hydro recommends that the following be included in the simulation model: Reclosing controls on adjacent and parallel lines. Automatic shunt reactor switching controls. Circuit breaker closing controls and logic. Series capacitor bypass and automatic reinsertion controls. Series capacitor protection elements. PSC North America – Power Networks Page 48 of 65 Review of Series Compensation for Transmission Lines 5.5.2 Hydro-Québec TransÉnergie (HQT) Source Transmission Line Protection by Simon Chano - Cover Story PAC World Magazine, Winter, 2008 [14] Summary HQT has implemented series compensation into their EHV system since the early 1990’s to increase power transfer capacity. Series compensation levels ranged from 20 to 44%. Extensive system studies were performed to determine the best location to introduce series compensation and as a result, some lines have the series capacitor installed at one end and others lines have the series capacitor installed at mid line as shown in Figure 5-9. Figure 5-9 Main and back-up proctection schemes for line end and mid-line SC Source: [33] Relay Protection Challenges Voltage reversal issues were addressed primarily through the use of polarized or memorized voltage based directional elements. Current reversal was not observed due to the level and location of series compensation together with series capacitor MOV protections. Protection Schemes Relay selection and main protection philosophies were developed and implemented based on extensive real-time simulation testing on HQT’s Transients Network Analyzer (TNA). Figure 5-9 above shows the Main 1, Main 2 and backup protection arrangements used to protect HQT’s series compensated lines. As shown, different schemes are used based on the location of the series capacitor on the line (i.e., middle or end). PSC North America – Power Networks Page 49 of 65 Review of Series Compensation for Transmission Lines The Main 1 and Main 2 schemes are communications dependent whereas the backup scheme does not rely on communications between the line terminals. The integrity of the communications channel(s) is very important for the Main’s schemes and as such digital fiber-optic based communications are rapidly replacing analog communications in the HQT system for high-capacity performance and speed. The backup protection uses an impedance based measurement relay. The modified impedance relay incorporates a lens characteristic to avoid sensitivity to load and power swings. Based on careful selection and testing, the backup impedance relays proved reliable and secure for transient and dynamic effects associated with series compensation. Automatic Reclosing HQT utilizes three-phase automatic reclosing for single phase fault detection/clearing on their EHV series compensated transmission lines. The paper did not note any specific issues related to automatic reclosing of series compensated line. Testing and Verification HQT indicates that transient simulator testing using a real-time TNA was the most effective method to test and verify various relay protection devices and schemes. This method provides for the following complex issues to be effectively analyzed: Weak in-feed. Harmonic and sub-harmonic transient effects. Low frequency current oscillations. Zero sequence mutual coupling between parallel lines. Voltage and current reversal conditions. Shunt reactor and line reclosing switching operations/logic. Series capacitor control and protection systems. Varying fault incidence angles. CT and CVT characteristics. High resistive faults, evolving faults, and reclosing on a permanent fault. 5.5.3 Pacific Gas & Electric Source PG&E 500 kV Series-Compensated Transmission Line Relay Replacement: Design Requirements and RTDS Testing [18] Summary High speed protection was designed and implemented to: Improve system transient stability Maintain 500 kV system availability Reduce possible damage to insulators and conductors Permit high-speed reclosing Compensate for reduced Zone 1 reach in series compensated lines Relay Protections Schemes PSC North America – Power Networks Page 50 of 65 Review of Series Compensation for Transmission Lines PG&E uses the following main and backup schemes. Sets A, B and C rely on communication channels. The backup Set D does not use communications between the terminals. Relaying Challenges The series capacitors introduce the possibility of overreach and undesired operation of Zone 1 distance relays. The options that PG&E considered to mitigate this issue included: Introduce a Zone 1 time delay – this was not recommended Further reduce Zone 1 reach and verify though RTDS testing Enable SC logic in to block Zone 1 for fault beyond a series capacitor located in front of the relay The presentation demonstrates that Zone 1 overreach can occur for faults on adjacent series compensated lines as well as on a directly protected series compensated line. The use of advanced relays with series compensation logic and memory polarization mitigates the possibility of mis-operation due to voltage inversion and overreach. Automatic Reclosing The PG&E presentation indicates that both single phase and three phase automatic reclosing is utilized on the series compensated transmission lines. Testing and Verification The presentation strongly advises the use of a RTDS platform with direct connection of the relays to test and verify relay protection performance. See Section 5.4.3 of this paper. PSC North America – Power Networks Page 51 of 65 Review of Series Compensation for Transmission Lines 6 Project Planning and Implementation Considerations 6.1 Key Section References For gaining more in-depth knowledge on the subject matter in this Section 6, the following primary references are suggested: [11] Anderson and Farmer. (1996). “Series Compensation of Power Systems”. Encinitas, CA: PBLSH, Inc. [48] IEC 60143 ‘Series Capacitors for Power Systems’, Parts 1, 2, and 4 Figure 6-3 and Figure 6-6 are adapted directly from Chapter 4 of [11]. 6.2 Location of Series Compensation The location of series compensation along a transmission line is a critical design factor in selecting to integrate this technology into AC transmission networks. The principal considerations in selecting location of series compensation are [11]: The “effectiveness” of series compensation varies as a function of location along a transmission line; The location of series compensation affects the voltage profile along the transmission line; Transmission line protection settings and capacitor bank bypass energy dissipation specifications depend on the location of the series compensation along the transmission line; Future configurations of the transmission lines being compensated; and Operations and maintenance issues such as site accessibility, land availability and telecommunications depend on local conditions where the series compensation is installed. The “effectiveness” of a series capacitance is determined using the distributed parameter theory of transmission lines. It provides a measure of how well the receiving end voltage of a transmission line is maintained depending on the placement of the series capacitor from the sending end. From the perspective of the effectiveness of series compensation, the optimal location for a single series capacitive reactance is at the mid-point of a transmission line. [11] The voltage profile of a series compensated line varies according to the location of any series capacitor banks and the loading levels of the transmission line. Series capacitor installations can be installed mid-line, either a single unit at the mid-point or two units each a third of the way along the line, or they can be installed at the line ends with busside or line-side shunt reactors. The topologies are shown in Figure 6-4, Figure 6-5, Figure 6-2, and Figure 6-1. As the The following general observations can be made in regards to the voltage profile of a series compensated line: PSC North America – Power Networks Page 52 of 65 Review of Series Compensation for Transmission Lines Voltage varies smoothly along the transmission line and undergoes a step change at the capacitor; The amplitude of the voltage variation across series capacitors increases with the level of compensation of the line (the size of the capacitor) and the current flowing through the capacitor; For highly loaded lines (above impedance loading), the voltage profile is concave upwards3; Lightly loaded lines (below surge impedance loading) are concave downwards4; Lines loaded to surge impedance loading will generally show a linear voltage profile along the length of the transmission line; Increased levels of compensation result in a decrease of the “sag” in the voltage with a tendency to increase the overall voltage profile; The voltage variation across a series capacitor is always in the direction that improves the voltage profile whatever the loading level; 6.2.1 Mid-Line This can either consist of a single capacitor bank located halfway along the transmission line or two installations each located one-third of the length between the two line ends. Multiple installations may be required when the insulation coordination plan for existing lines do not allow for the relatively high voltages just prior to the series capacitor. Midline stations are unattended. XL 3 XC XL 2 3 XC XL 2 3 Figure 6-1 - Midline compensation at 33% and 66% of line length XL 2 XL XC 2 Figure 6-2 - Mid-line compensation at 50% of line length 3 4 Concave upwards refers to situations where the tangent to the curve lies below it. Concave downwards refers to situations where the tangent to the curve lies above it. PSC North America – Power Networks Page 53 of 65 Review of Series Compensation for Transmission Lines Mid-Line, 33%, 66% K=30% K=50% K=70% 1.10 1.00 0.90 150 Distance from Receiving End (miles) Voltage Magnitude (p.u.) Voltage Magn itude (p.u.) 1.00 300 150 Distance from Receiving End (miles) 1.10 1.00 0.90 300 150 Distance from Receiving End (miles) 0 0 K=30% K=50% K=70% 1.00 300 150 Distance from Receiving End (miles) 0 K=30% K=50% K=70% 1.20 Voltage Magn itude (p.u.) Voltage Magnitude (p.u.) Heavy Loading (2 x SIL) 150 Distance from Receiving End (miles) 1.10 0.90 0 K=30% K=50% K=70% 1.20 300 1.20 1.10 0.90 1.00 0 K=30% K=50% K=70% 1.20 Surge Impedance Loading (SIL) 1.10 0.90 300 K=30% K=50% K=70% 1.20 Voltage Magnitude (p.u.) Voltage Magnitude (p.u.) 1.20 Light Loading (½ x SIL) Mid-Line, 50% 1.10 1.00 0.90 300 150 Distance from Receiving End (miles) 0 Figure 6-3 – Line voltage profile for mid-line series compensation. Source [11] PSC North America – Power Networks Page 54 of 65 Review of Series Compensation for Transmission Lines Advantages: Results in lower short circuit through the series capacitor equipment; Improved effectiveness of series capacitors. Disadvantages: Access issues: the addition of series compensation installations along existing right of ways is not always possible; Future expansion: Tee-off on transmission line between sub stations and series capacitor Modular series capacitor consisting of two elements in series separated by a bus and breaker arrangement 6.2.2 Line Ends In this arrangement, the capacitors are located very close to the line terminal if not within the substation. Generally a shunt reactor will be installed along with the series compensation facility to keep voltages down during periods of low flow. The reactor can either be on the bus side of the series compensation or on the line side. XC XL 2 XC 2 Figure 6-4 - Line end compensation, bus side shunt reactors XC XL 2 XC 2 Figure 6-5 - Line end compensation, line side shunt reactors PSC North America – Power Networks Page 55 of 65 Review of Series Compensation for Transmission Lines Line-ends, bus side – reactors K=30% K=50% K=70% 1.10 1.00 0.90 300 150 Distance from Receiving End (miles) 1.10 1.00 0.90 300 150 Distance from Receiving End (miles) 1.10 1.00 0.90 300 150 Distance from Receiving End (miles) 150 Distance from Receiving End (miles) 0 K=30% K=50% K=70% 1.00 300 150 Distance from Receiving End (miles) 0 0 K=30% K=50% K=70% 1.20 Voltage Magnitude (p.u.) Voltage M agn itude (p.u.) Heavy Loading (2 x SIL) 300 1.10 0.90 0 K=30% K=50% K=70% 1.20 1.00 1.20 Voltage Magnitude (p.u.) Voltage Magn itude (p.u.) Surge Impedance Loading (SIL) 1.10 0.90 0 K=30% K=50% K=70% 1.20 K=30% K=50% K=70% 1.20 Voltage Magn itude (p.u.) Voltage Magn itude (p.u.) 1.20 Light Loading (½ x SIL) Line-ends, line-side – reactors 1.10 1.00 0.90 300 150 Distance from Receiving End (miles) 0 Figure 6-6 – Line voltage profile for line-end series compensation. Source [11] PSC North America – Power Networks Page 56 of 65 Review of Series Compensation for Transmission Lines Advantages: Use of available space, no access issues when in substation Easier access to banks and equipment for maintenance and operations No additional site to acquire Disadvantages: Lower effectiveness meaning more compensation for the same impact Increased short circuit-circuit currents require higher bypass equipment ratings Further expansion: Totally depends on space availability; Further compensation can be added at cut in points if flows are greatly increased. 6.3 Modularity of Series Compensation A series capacitor installation can consist of more than one module and the installation of the modules can be staged according to planning and project requirements. Each module consists of a capacitor bank, MOV and bypass circuit for the three phases so that each module can be operated independently. [48] Series capacitor installations are generally installed in single modules to reduce capital costs. In some cases, particularly where future uncertainty is high, modularity presents certain advantages [11]: Staged development lowers risk of stranded assets if ultimate transmission capacity is not required; The addition of a bus between modules increases flexibility for future connections allowing for the future connection of a circuit to a generator, load or substation in a tee-off arrangement; Individual modules can be switched independently in steps to allow for greater flexibility to the system operator under varying system loads; Additional modules could consist of TCSC units allowing for control of dynamic stability issues that could arise in the future; and Allows for conditions where high levels of compensation and high currents result in voltage variations across the banks that exceed standard equipment specifications. At a minimum, one platform is required per phase and generally each module will be built on its own platforms. However, in instances where it is virtually certain that the ultimate compensation levels will be achieved it may be economically viable to build a larger platform from the outset and add additional modules to the same platform. Provision would need to be made for allowing switching and control equipment to be accessible at ground level. The modules can be connected directly or to a common bus. Connecting directly will reduce capital costs but limit flexibility for future expansion and reconfiguration. PSC North America – Power Networks Page 57 of 65 Review of Series Compensation for Transmission Lines The principal disadvantage to modularity is the increased capital cost per ohm of compensation. 6.4 Future Development of the Series Compensated Lines The configuration of the initially installed series compensation will impact on the future extendibility of the network. The impact of future segmentation is dependent on the location of the series capacitor/s on the transmission line, the magnitude of compensation and the specific nature of the new addition. In general, if future network modifications are committed or likely, then this should be included in the initial studies for the series capacitors. The type of the new addition, i.e. load or generation, and its location in relation to the series capacitor/s are significant factors when analyzing the impact of said addition. Load may be subjected to over-voltages that significantly exceed the typical overvoltages impressed on other loads on the system. If generators are added then short-circuit, stability and SSR studies will need to be repeated. The magnitude and configuration of the initial capacitor bank installation may preclude future segmentation of the transmission line with significant cost to reconfiguration the series compensation if not considered up front. 6.5 Operations and Maintenance Considerations Operation of series compensation equipment requires a robust Control and Protection (C&P) system to operate efficiently with the connected transmission line. The C&P system provides constant monitoring of the equipment to provide appropriate protective actions during external line and internal equipment fault conditions, and deliver real time monitoring of components. The C&P system’s real time monitoring can give indication of abnormal operating conditions within the equipment to allow for repairs to be scheduled to appropriately mitigate the risk of a subsequent forced outage of the series compensation or possibly the entire line. Operations and Maintenance (O&M) requirements for series compensation would add minimal impacts to the current utility operations. A majority of the equipment used in series compensation is most likely already found in the typical high voltage transmission systems. Equipment includes capacitor banks, reactors, circuit breakers, switches, and MOV arresters which can easily be introduced into the current utility O&M policies. Usual maintenance items would include: Infrared (IR) scans of equipment for hotspots or overloads; Visual inspections to identify damaged equipment such as leaking capacitors or broken insulators; Verification of density monitors in SF6 filled equipment; Periodic capacitor measurements; and Ordinary inspections maintenance as required by the manufacturer. Thyristor Controlled Series Compensation (TCSC) requires power electronics which will have additional maintenance requirements. These power electronics are the same that have operated reliably in HVDC converters, SVCs, and medium voltage motor drives for PSC North America – Power Networks Page 58 of 65 Review of Series Compensation for Transmission Lines decades. The additional maintenance would be limited to periodic inspection of the power electronic cooling system and replacement of faulty power electronic modules when they are identified by the C&P system. The TCSC will have redundant power electronic modules built in to system to allow for replacement during planned maintenance periods. 6.5.1 Operations and Reliability Real time information such as alarms or equipment status would typically be provided via RTU or Remote Control Interface to the SCADA/EMS at the local and/or area system control center(s). The switch from local to remote control would typically require handoff from the local control unit. Remote control capabilities can be customized to permit the system operator to perform certain functions from the SCADA/EMS. For example, the system operator could be permitted to manually by-pass the series capacitor based on network conditions (i.e., to avoid the potential for SSI following certain contingencies). Special C&P interlocking may be required for remote access security. Remote control functionality should be determined and specified as early as possible to avoid modification requirements after initial design, installation and testing. The expected utilization level and required availability of a series compensated transmission should be factored into the location and design for the compensation device(s). Some basic considerations include: Single, partly redundant, or completely redundant C&P systems. Compensation in the middle of the transmission line or alternatively, at one or both ends. The time for personnel to respond to series capacitor location(s) as well as the reliability of required communications will be a function of the location(s). Split of the series capacitor blocks onto separate energized platforms, per phase. 50% series compensation could be split into two 25% blocks to increase overall availability and power transfer capability with consideration of scheduled and forced outage rates for each block. Staffing and availability of qualified maintenance personal to respond to alarms and device issues on a 24/7 basis in accordance with utility best practices and procedures. Specification of digital fault recorders (DFR) and/or sequence of events recorders (SER) to provide tools for more efficient fault tracing and corrective measures. PSC North America – Power Networks Page 59 of 65 Review of Series Compensation for Transmission Lines 7 Roadmap for Further Analysis 7.1 Preliminary Design Stage Studies During the preliminary design stage of series compensation projects, various steady state and transient studies are required to determine technical specifications to provide to vendors. The model used for the series capacitor and the bypass system is dependent on the study conducted. The design parameters required from the preliminary analysis are Series capacitor bank rated impedance; Series capacitor bank rated current, overload current; Series capacitor bank insulation requirements; Varistor energy requirements; and Number of series compensation modules and or intermediate steps. To determine these variables, the following studies are required. 7.2 Steady state data for analyzing the active and reactive power flows and voltage profiles in the system The series capacitor can be modelled simply as a negative reactance connected in series with the transmission line. Note that when conducting the study either “Newton” or “Modified Gauss-Seidel” solution techniques must be used as the traditional “GaussSeidel” solution technique cannot handle series capacitors. Short circuit data for analyzing the fault currents flowing in the system as well as the series capacitor for various system configurations during internal and external faults. The through fault current is needed to identify the required ratings for the series capacitor. The model representation of the series capacitor during the short circuit will change depending on whether the bypass spark gap has triggered or the bypass varistors are conducting a significant amount of current. This depends on how the fault type and location affects the voltage across the bypass devices. For faults external to the series capacitor several iterations of short circuit calculations may be required to determine the bypass path representation for any given fault location and type, so a range of values for positive, negative, and zero sequence information may be appropriate for an accurate representation in a short circuit study. An EMT analysis can be used to determine an equivalent impedance for the bypass path, to be used in the PSS/E short circuit analysis but would only be valid for a particular fault location and system configuration. If only the worst case extremes of fault current magnitude (ignoring fault current phase, which is important for relay settings) are required then for external faults: The highest fault currents (at the point of fault) would be obtained with the bypass circuit open, so the positive and zero sequence impedance of the series capacitor itself is sufficient information for sequence components of the model, and; The lowest fault currents (at the point of fault) would be obtained with the series capacitor bypassed completely. In this case no information is required – the series capacitor can be modelled as a zero impedance branch. PSC North America – Power Networks Page 60 of 65 Review of Series Compensation for Transmission Lines 7.3 Transient Stability Analysis The short circuit representation of the bypass path is be used to represent the fault impedance. After the fault is cleared the bypass path must continue to be modelled until it ceases to conduct current. PSS/E v30 (and higher) dynamics application offers a series capacitor gap model (SCGAP2). This model will bypass the capacitor after a defined time, if the capacitor current (and associated capacitor voltage) exceed a defined value. The capacitor can be reinserted if the current falls below a defined value, or permanently shorted by a bypass switch. Note that the varistor action is not modelled as it is assumed to be sufficiently brief so as to not affect the stability response. 7.4 Harmonics and Frequency Scans Frequency scan studies will need to be carried out for both sub-synchronous and harmonic frequencies. For sub-synchronous frequencies, frequency scans should be conducted to determine the driving-point system impedance as seen from the neutral point of each nearby generator. The intent is to identify any sub-synchronous resonance issues. For harmonics, scans will assess the change in system impedance at either end of the interconnector and at selected major buses elsewhere in the system, between the present conditions and following installation of the series compensation in credible operating conditions. This information can then be used to identify whether harmonic resonances are likely to be worsened appreciably by the introduction of series compensation. 7.5 Short-term Transient Voltage and Switching Studies The following fast transient studies are typically carried out using an electromagnetic transient type program such as EMTP-RV or PSCAD/EMTDC: 1) Lightning Strikes in the vicinity of the series capacitor a) Direct strikes to phase conductors due to shielding failure b) Back-flash from tower to phase conductor due to high stroke current c) Shielding failure at the substation 2) Energization and de-energization of compensated line a) Energization from either end with capacitor inserted/bypassed b) De-energization from either end with capacitor inserted/bypassed, including breaker TRV 3) Bypass and insertion of capacitor under load 4) Fault response for a) Different fault types i) 1-phase-ground (with and without single phase auto-reclose) ii) 2-phase iii) 2-phase-ground PSC North America – Power Networks Page 61 of 65 Review of Series Compensation for Transmission Lines iv) 3-phase b) Different fault locations i) Within capacitor ii) On compensated line iii) On adjacent lines c) Transformer or shunt reactor energization on lightly loaded series compensated line for ferro-resonance effects. These studies will determine the maximum energy on varistors, maximum transient voltage and current on capacitors, and TRV on circuit breakers. They also serve to size MOV and damping circuit components. 7.6 Small-signal Analysis The use of series capacitors in a power system typically improves small signal stability by reducing the series inductive reactance between regions. In general the impact of series capacitors range from increasing the frequency of local/area/regional modes of oscillation, dampening the oscillations, or a combination of both. No special mitigation measures are envisaged however an eigenvalue analysis should still be carried out on the pre and post compensated system to determine the specific impact of the series capacitors. This will identify the impact of the series capacitors on current modes of oscillations, and should consider a range of credible network configurations, generation dispatch profiles (including wind), demand scenarios, and inter-state power transfers. In addition, small signal models are needed for generators (including wind) and HVDC. This may require the re-tuning of any Power System Stabilizers present on generating units. PSC North America – Power Networks Page 62 of 65 Review of Series Compensation for Transmission Lines 8 References [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18] [19] [20] ABB. (2010). “Series Compensation – Boosting transmission capacity”. A020135E, 2010-12 ABB. (2010). “TCSC – Thyristor Controlled Series Compensation – Keeping grids together”. A02-0158E, 2010-03 ABB. (2012). “Series Compensated Line Protection”. ABB Webinar. http://www.youtube.com/watch?v=rKWnMyTYUDM ABB Group. (2010). “ERCOT CREZ Reactive Study, RPG SSI Discussion 2010”. ABB Group Presentation Adams. (2011). “Sub-Synchronous Problems and Prevention in ERCOT”. ERCOT RPG Presentation Adams. (2012). “ERCOT Experience Screening for Sub-Synchronous Control Interaction in the Vicinity of Series Capacitor Banks”. IEEE PES General Meeting, San Diego, CA. Presentation Adams. (2012). “Planning Guide concepts for dealing with Subsynchronous Resonance in ERCOT and other issues”. ERCOT Agrawal and Farmer. (1979). “Use of Frequency Scanning Techniques for Subsynchronous Resonance Analysis”. Vol.PAS-98, No.2: IEEE Transactions on Power Apparatus and Systems Alomari and Rodanski. (2007). “STATCOM for Controlling Bifurcations of SSR as Applied to Multimachine Power System”. University of Technology, Sydney, Australia Altuve, Mooney and Alexander. (2008). “Advances in Series-Compensated Transmission Lines”. TP6340-01, Schweitzer Engineering Laboratories, Inc. Anderson and Farmer. (1996). “Series Compensation of Power Systems”. Encinitas, CA: PBLSH, Inc. Badrzadeh, Sahni, Muthumuni, Zhou and Gole. (2012). “Sub-synchronous Interaction in Wind Power Plants – Part I: Study Tools and Techniques”. 978-14673-2729-9: IEEE Buntales. “SSR Protection”. Chapter 29 Chano. (2008). “Transmission Line Protection – Doing it Right”. Cover StoryWinter 2008, pacworld Donghui, Xiaorong, Shiya and Shuqing. (2004). “Optimal design of SEDC for damping multi-mode SSR based on GASA”. Department of Electrical Engineering, Tsinghua University, Beijing, China Donohoo. “Planners Perspective on Series Compensated Transmission Lines” ONCOR Presentation ERCOT. “Resource Interconnection Handbook”. Version 1.2: ERCOT Erwin, Pineda, Anderson, Tziouvaras and Turner. (2013).”PG&E 500kV SeriesCompensated Transmission Line Relay Replacement: Design Requirements and RTDS Testing”. PG&E and SEL, Inc. Presentation. Farmer, Agrawal and Ramey. (2006). “Power System Dynamic Interaction with Turbine Generators”, Taylor and Francis Group, LLC. http://www.beknowledge.com/wp-content/uploads/2010/09/327.pdf Gross. (2010). “Sub-Synchronous Grid Conditions: New Event, New Problem, and New Solutions”. 37th Annual Western Protective Relay Conference, Spokane, WA PSC North America – Power Networks Page 63 of 65 Review of Series Compensation for Transmission Lines [21] Gusmán, Mooney, Benmouyal and Fischer. (2001). “Transmission Line Protection System for Increasing Power System Requirements”. 20020401: Schweitzer Engineering Laboratories, Inc. [21b] Hosseini and Tousi. (2012). “Mitigating of Sub-synchronous Resonance in a Series Compensated Hybrid System with Steam and Wind Turbine Using FACTS Controllers”. Majlesi Journal of Electrical Engineering. Vol. 6. No. 3 [22] IEEE. (2007). “IEEE Guide for Protective Relay Application to Transmission-Line Series Capacitor Banks”, IEEE Power Engineer Society – Power Systems Relaying Committee, Std C37:116-2007 [22b] IEEE. (1992). “Reader’s Guide to Subsynchronous Resonance”. Transactions on Power Systems, Vol. 7, No. 1, 0885-8950/92: IEEE [23] Irwin. (2010). “Sub-Synchronous Interactions with Wind Turbines”, CREZ Presentation 2010 [24] Jianbo, Gesong, Jiming, Baiquing and Weizhou. (2005). “Chengxian 220kV Thyristor Controlled Series Compensation: Parameters Design, Control & Overvoltage Protection”, IEEE/PES Transmission and Distribution Conference, Asia and Pacific, Dalian China, 0-7803-9114-4: IEEE [25] Karawita. (2012). “Analysis of Sub-synchronous Frequency Interactions in Power Systems Using TGSSR”. IEEE PES Winnipeg Section Luncheon Meeting. TGS Presentation. [26] Kasztenny. (2001). “Distance Protection of Series-compensated Lines: Problems and Solutions”. GER-3998: GE Power Management [27] Larsen. (2012). “Wind Power On Series-Compensated Lines”. IEEE PES General Meeting, San Diego, CA. Presentation by GE Energy Consulting [28] Leonidaki, Hatziargyiou, Papadias and Geoargantzis. (1998). “Investigation of Power System Harmonics and SSR Phenomena related to Thyristor Controlled Series Capacitors”. 8th International Conference on Harmonic and Quality of Power (ICHQP), Athens Greece, 0-7803-5105-3: IEEE [29] Nekoubin. (2011). “Simulation of Series Compensated Transmission Lines Protected with MOV”. World Academy of Science, Engineering and Technology, Vol: 58 [30] NERC. (2011). “Lessons Learned – SSI between Series Compensated Transmission Lines and Generation”. LL_45_SSSI: NERC [31] Ma, Brogan, Jensen and Nelson. (2012) “Sub-Synchronous Control Interaction Studies between Full-Converter Wind Turbines and Series-Compensated AC Transmission Lines”. IEEE PES General Meeting, San Diego, CA. Presentation by Siemens Wind Turbines [32] Padiyar and Prabhu. “Investigation of SSR characteristics of UPFC”. Department of Electrical Engineering, Indian Institute of Science, Bangalore 560012, India [33] Plumptree, Nagpal, Chen and Thompson. (2009). “Protection of EHV Transmisison Lines With Series Compensation: BC Hydro’s Lessons Learned”. 978-1-42444183: IEEE [34] Rajaraman and Dobson. (1996). “Damping estimates of subsynchronous and power swing oscillations in power systems with thyristor switching devices”. Vol. 11, No. 3: IEEE Transactions on Power Systems [35] Sahni, Badrzadeh, Muthumuni, Cheng, Yin, Huang and Zhou. (2012). “Subsynchronous Interaction in Wind Power Plants – Part II: An ERCOT Case Study”. 978-1-4673-2729-9: IEEE PSC North America – Power Networks Page 64 of 65 Review of Series Compensation for Transmission Lines [36] Saylors. (2013). “Understanding and Assessing Subsynchronous Resonance”. NAW1308: North American Windpower [37] Shahgholian. (2013). “Review of PSS: Application, Modeling, Analysis and Control Strategy”. Issue 16, Vol. 3, Num. 3, Pages 41-52: IJTPE Journal [38] Subhash, Tripathy, Padiyar, Nayyar, Kumar, Thakkar and Arya. (2005). “SSR study for the TCSC application on the Kanpur-Ballabgarh 400 kV line in India”. International Conference on Power System Transients. Paper No. IPST05-043 [39] Sun, Ban, Yang and Wang. (2013). “Application of STATCOM for Damping Subsynchronous Resonance in a Multi-machine System”. Engineering, 2013, 5, 180-184: Scientific Research [40] Suriyaarachchi, Annakkage, Karawite, Kell, Mendis and Chopra. (2012). “Application of an SVC to Damp Sub-synchronous Interaction Between Wind Farms and Series Compensated Transmission Lines”. IEEE PES Presentation, San Diego, CA [41] Varma, Auddy and Semsedini. (2008). “Mitigation of Subsynchronous Resonance in Series-Compensated Wind Farm Using FACTS Controllers”. Vol. 23, No.3: IEEE Transactions on Power Delivery [42] Vuorenpää, Rauhala, Järventausta and Acha. (2013). “On Assessing the Risk of SSR Related Torque Amplification in Series Compensated Networks”. International Conference on Power Systems Transients (IPST2013), Vancouver, Canada [43] Wilkinson. “Series Compensated Line Protection Issues”. GER-3972: GE Power Management [44] Wu, Zhu and Hu. (2012) “Supplementary Controller Design for SSR Damping in a Series-compensated DFIG-Based Wind Farm”. ISSN 1996-1073: Energies [45] Xia, Johnson, Fischer, and Xia. (2013). “A Comparison of Different Signal Selection Options and Signal Processing Techniques for Subsynchronous Resonance Detection”. International Conference on Power Systems Transients (IPST2013) in Vancouver, Canada [46] Zellagui and Chaghi. (2011). “Impact of Series Compensation (SC) on the MHO Distance Relay in Algerian 220 kV Transmission Line”. Canadian Journal on Electronic and Electronics Engineering, Vol. 2, No. 6 [47] Zhang and Zheng. (2007). “Effect of Exciter and PSS on SSR Damping”. 1-42441298-6: IEEE [48] IEC 60143 ‘Series Capacitors for Power Systems’, Parts 1, 2, and 4 PSC North America – Power Networks Page 65 of 65