123 CHAPTER 7 ATC ENHANCEMENT BY SERIES AND SHUNT COMPENSATION 7.1 INTRODUCTION Deregulation of power system around the world is aimed at providing non discriminatory and fair participation of all the market players. The transmission system being the natural monopoly should have the adequate capacity to meet all the transaction requirements. The economic efficiency of the restructured power system can be realized by accommodating all the transactions without violating system operating limits. The power transaction between an interface is limited by factors such as thermal limits of the branches and bus voltage limits. In spite of having adequate power generation to meet the power demands the system bottlenecks restricts the transactions. These bottlenecks can be resolved by providing series compensation at few branches which in turn reroute the power to the sink buses. Hence the ATC of an interface can be enhanced without overloading the branches. The limitation due to the bus voltage limits can be solved by reactive power injections at the weak buses. This chapter proposes a SVM based model to estimate the degree of series and shunt compensation needed to obtain the desired ATC value at a given operating condition. 124 7.2 BASIC PRINCIPLE OF COMPENSATION IN TRANSMISSION SYSTEM Figure 7.1 shows the simplified model of a power transmission system. Two power grids are connected by a transmission line which is assumed lossless Figure 7.1 Power transmission system simplified model The expression for the current in the transmission line is given by V1 I 1 V2 2 (7.1) jX L The active power and reactive power at bus 1 are given by: V1V2 sin , XL P1 where = 1 - Q1 V1 (V1 V2 cos ) XL (7.2) 2 The active power and reactive power at bus 2 are given by: P2 V1V2 sin , XL Q2 V2 (V2 V1 cos ) XL (7.3) Equations (7.1) through (7.3) indicate that the active and reactive power flow can be regulated by controlling the voltages, phase angles and line impedance of the transmission system. 125 7.2.1 Shunt Compensation Shunt compensation, especially shunt reactive compensation has been widely used in transmission system to regulate the voltage magnitude and enhance the system stability. A simplified model of a transmission system with shunt compensation is shown in Figure 7.2. The voltage magnitudes of the two buses are assumed equal as V and the phase angle between them is . The transmission line is assumed lossless and represented by the reactance XL. At the midpoint of the transmission line a controlled capacitor C is shunt connected. The voltage magnitude at the connection point is maintained as V. Figure 7.2 Transmission system with shunt compensation As discussed previously, the active powers at bus 1 and bus 2 are equal. P1 P2 V2 2 sin XL 2 (7.4) The injected reactive power by the capacitor to regulate the voltage at the mid-point of the transmission line is calculated as Qc V2 4 (1 cos ) XL 2 (7.5) 126 7.2.2 Series Compensation Series compensation aims to directly control the overall series line impedance of the transmission line. A simplified model of a transmission system with series compensation is shown in Figure 7.3. The voltage magnitudes of the two buses are assumed equal as V and the phase angle between them is . The transmission line is assumed lossless and represented by the reactance XL. A controlled capacitor is series-connected in the transmission line with voltage addition Vinj. Figure 7.3 Transmission system with series compensation Defining the capacitance of C as a portion of the line reactance, Xc = kXL (7.6) The overall series inductance of the transmission line is, X XL Xc (1 k)X L (7.7) The active power transmitted is , P V2 sin (1 k)X L (7.8) 127 The reactive power supplied by the capacitor is calculated as: Qc 7.3 V2 k (1 cos ) X L (1 k) (7.9) ATC ENHANCEMENT BY SHUNT COMPENSATION The bus voltage is one of the important limiting factors for ATC. The transmission system may not be utilized to its maximum capacity due to the poor voltage profiles at few buses. Hence the ATC can be enhanced by maintaining good voltage profile at all buses irrespective of the loading conditions. Reactive power injections at the weak buses will help in maintaining the voltage profile. The theory of shunt compensation is explained in the section 7.2.1. Identification of weak bus and the estimation of amount of reactive power to be injected to obtain the desired ATC value are the major problem in shunt compensation. This chapter proposes a method to estimate the shunt compensation required to get the desired ATC for an interface. 7.4 ATC ENHANCEMENT BY SERIES COMPENSATION The feasibility of a proposed transaction through an interface will be decided based on the availability of adequate transmission capacity. In an interconnected power system the power sharing between the branches is based on their respective impedance values. Assume an interface between the source and sink bus is connected by two paths. Let the path 1 is having lesser impedance compared to path 2. The maximum share of power that is injected at the source bus will tend to reach the sink bus through path 1. This in turn may over load one or more branches in that path. Hence the ATC between the given interface is restricted by the thermal limits of few branches of path 1. But the ATC between the given interface can be enhanced by achieving proper sharing of power between the paths. The sharing of power can be 128 controlled by changing the value of reactance of the paths. The basic principle of series compensation is explained in section 7.2.3. This chapter proposes a method to estimate the degree of compensation required to obtain the desired ATC for an interface. 7.5 SELECTION CRITERIA FOR COMPENSATION Selection of type of compensation, identification of location for reactive power compensation and degree of compensation required are the major tasks in ATC enhancement. The ATC of the given operating condition will be estimated using the RPF algorithm. The limiting factor is identified from the RPF results. Shunt compensation is selected if the voltage magnitudes are the limiting factor and the series compensation is chosen if the line loading is the limiting factor. RPF is conducted with a particular degree of compensation and the respective ATC is obtained. This value will be treated as desired ATC. The loading condition and the desired ATC are selected as inputs and the degree of compensation will be the output. Data patterns are obtained in two ways. First method for a given operating condition degree of compensation is varied and the respective ATCs are obtained. In second method both operating conditions and degree of compensation are changed. SVM model is developed using the data patterns generated. The proposed AI model will estimate the degree of compensation required to obtain the desired ATC value for a given operating condition. 7.6 ALGORITHM FOR DATA GENERATION Step 1. Select an operating condition Step 2. Run Repeated Power Flow (RPF) and obtain the ATC value for a given interface. 129 Step 3. Identify the limiting factor which limits ATC Step 4. If the bus voltage is the limiting factor inject reactive power at the weak buses by some value. Step 5. Run RPF and obtain ATC with reactive power injection. This ATC is considered as desired ATC Step 6. A data set is formed with the loads at buses, the desired ATC as inputs and the degree of compensation as output. Step 7. Steps 1-6 are repeated to obtain more number of data sets with different loading conditions and with different degree of compensation. Step 8. If the line loading is the limiting factor, provide series compensation at the alternate path and obtain ATC value by conducting RPF. This value is considered as desired ATC Step 9. For some loading conditions both series and shunt compensation is provided simultaneously and the respective ATC values are obtained. More number of data sets is generated by repeating the steps 1-9. The loading condition, the source bus injections and the desired ATC are inputs. The required degree of series and shunt compensation will be the output. SVM model is developed using the data sets generated. 7.7 SYSTEM STUDIES AND RESULTS IEEE 24 bus Reliability Test System is used to test the feasibility of proposed method. The interface considered is connected between the source bus 23 and sink bus 3. The weak buses are identified as 3 and 24. The reactive power is injected at these weak buses and the ATC obtained with reactive 130 injections are obtained by conducting RPF. V3 and V24 are the voltage magnitudes at buses 3 and 24 respectively. From the off-line power flow studies it is observed that 24-3 is the limiting line which hits the MW limit. To enhance the ATC without overloading the line 24-3 the series compensation is provided at the alternate path connected by the lines 16-14, 14-11, 11-9 and 9-3. This in turn increases the power sharing of the alternate path and reduces the power flow through the limiting line and hence enhances the ATC. Table 7.1 shows the degree of shunt compensation required to obtain the desired ATC for a given operating condition. The results of SVM model is compared with RPF results. Table 7.1 Comparison of shunt compensation required to obtain desired ATC estimated by RPF and SVM Compensation Compensation Limiting Actual Desired obtained using RPF obtained using SVM factor Data ATC ATC obtained set No Shunt (MVAr) Shunt (MVAr) (MW) (MW) using RPF Bus 3 Bus 24 Bus 3 Bus 24 1 70 210 V24 45 50 49 53 2 120 355 V3 . 80 65 85 61 3 140 275 V3 65 45 61 49 The voltage magnitude at 3rd bus without compensation was 0.9 p.u for 120 MW increase in the demand at the sink bus. With the compensation at 3rd and 24th buses as given in Table 7.1 the voltage magnitude at 3rd bus is1.103 p.u for the same 70MW increase in the demand at the sink bus. As the voltage magnitude is above 0.9 p.u demand is increased further. ATC with compensation is found to be 355MW. 131 From the off-line power flow studies it is observed that 24-3 is the limiting line which hits the MW limit. To enhance the ATC without overloading the line 24-3 the series compensation is provided at the alternate path connected by the lines 16-14, 14-11, 11-9 and 9-3. This in turn increases the power sharing of the alternate path and reduces the power flow through the limiting line and hence enhances the ATC.The percentage of series compensation required to get the desired ATC is estimated by RPF method and SVM model. The results are presented in Table 7.2. Table 7.2 Comparison of series compensation required to obtain desired ATC estimated by RPF and SVM Data set No 4 5 6 Actual Desired Limiting factor obtained using ATC ATC RPF (MW) (MW) 90 130 120 210 225 195 line loading 24-3 line loading 24-3 line loading 24-3 Compensation obtained using SVM Series % % compensation compensation 55 49 45 51 30 27 Compensation obtained using RPF Series From the Table 7.2 it is observed that the ATC between an interface can be enhanced by providing series compensation at the branches of alternate path. For data set 4, the possible increase in demand (ATC value) at the sink bus load is limited to 90MW by the line loading limit of the branch 24-3. For data set 4, the power flow through the branch 24-3 is 392 MVA for the ATC of 90MW. The ATC can be enhanced by providing the series compensation at the alternate path. The alternate path for the interface 23-3 is connected by the lines 16-14, 14-11, 11-9 and 9-3. 55% of series compensation is provided at these lines to increase the ATC to 210MW. The power flow through the lines 16-14, 14-11, 11-9 and 9-3 without 132 compensation is 246MW, 147MW, 125MW and 37MW for the ATC of 90MW. As the series compensation reduces the reactance the power flow through these branches with compensation is found to be 365MW, 310MW, 115MW and 55MW and the ATC is increased to 210MW. Table 7.3 Comparison of series and shunt compensation required to obtain desired ATC estimated by RPF and SVM Compensation Compensation obtained using RPF obtained using SVM Limiting Actual Desired Shunt Shunt factor Data set ATC ATC Series Series No obtained (MVAr) (MVAr) (MW) (MW) using RPF % Bus Bus Bus Bus % compensation 3 24 compensation 3 24 7 90 300 V3, V24. 45 110 95 43 115 46 and line loading24-3 8 70 350 V3 , V24. 55 130 110 58 137 119 and line loading24-3 9 260 510 V3 , V24. 30 80 65 24 83 68 and line loading24-3 From the Table 7.3 it is inferred that some operating conditions require both series and shunt compensation to get the desired ATC. From the values of degree of compensation obtained by RPF method and SVM model it is inferred that the SVM model can estimate the degree of compensation accurately. Table 7.4 Comparison of Computation time (in secs) Test case RPF SVM 1 1.104 0.0045 2 0.986 0.0052 133 From the Table 7.4 it is observed that the computation time of SVM model is much lesser than the RPF method. The proposed SVM model estimates the degree of compensation accurately in lesser computation time. Therefore it is suitable for real time operation of large scale power systems. 7.8 CONCLUSIONS The economic efficiency of restructured power system is greatly depends on transaction management. The adequate transmission capacity to meet all the proposed transactions is essential to realize this. The transmission capacity or ATC of an interface will often be limited by the system bottle necks. The series and shunt compensation enable the system operators to utilize the transmission capacity to its maximum value. The effectiveness of the proposed SVM model was tested and validated on IEEE 24 bus RTS. The results obtained from SVM model were reasonably accurate and the computation time of SVM model was much lesser than the RPF method.