RTLED Luminaire_Sample-Spec_2513.docx Section 26 5100 INTERIOR LIGHTING Interior Solid State Luminaires PART 1. 1.1 1.2 PRODUCT REQUIREMENTS MANUFACTURERS 1.1.1 Approved Manufacturers: Provide products of firms regularly engaged in the manufacture of recessed lighting fixtures of types and ratings required, whose products have been in satisfactory use in similar service for not less than 5 years. The manufacturer of the lighting fixtures shall comply with the provisions of the appropriate code and standards. All fixtures shall be pretested before shipping. 1.1.2 Conformance: Fixtures shall be manufactured in strict accordance with the Contract Drawings and Specifications. 1.1.3 Codes: Materials and installation shall be in accordance with the latest revision of the National Electrical Code and any applicable Federal, State, and local codes and regulations. 1.1.4 UL or CSA US Listing: All fixtures shall be manufactured in strict accordance with the appropriate and current requirements of the “Standards for Safety" to UL 8750 or others as they may be applicable. A listing shall be provided for each fixture type, and the appropriate label or labels shall be affixed to each fixture in a position concealing it from normal view. 1.1.5 Luminaire shall be DLC Certified (Design Lights Consortium). Low lumen versions of luminaires may not meet DLC, if so delete line. 1.1.6 Specifications and scale drawings are intended to convey the salient features, function and character of the fixtures only, and do not undertake to illustrate or set forth every item or detail necessary for the work. 1.1.7 Base Bid Manufacturers: Are listed on fixture schedule and specification. Manufacturers listed without accompanying catalog numbers are responsible for meeting the quality standards and photometric distribution set by the specified product. 1.1.8 Alternate Manufacturers: Identification by means of manufacturers names and catalog numbers is to establish basic features, quality and performance standards. Any substitutions must meet or exceed these standards LUMINAIRES TYPE XX, YY, ZZ – Recessed Ambient 1.2.1 Each luminaire shall consist of an assembly that utilizes LEDs as the light source. In addition, a complete luminaire shall consist of a housing, LED array, and electronic driver (power supply) and integral controls as per this specification. 1.2.2 Each luminaire shall be designed to operate at an average operating temperature of 25°C. 1.2.3 The operating temperature range shall be 0°C to +25°C. 1 2/5/2013 RTLED Luminaire_Sample-Spec_2513.docx 1.2.4 Each luminaire shall meet all parameters of this specification throughout the minimum operational life when operated at the average operating temperature. 1.2.5 Nominal luminaire dimensions: a) Type XX - 1x4 – Length – 48”(121.9cm), Width – 12”(30.5cm), Depth – 41/2”(11.4cm) max. b) Type YY - 2x2 – Length – 24”(61.0cm), Width – 24”(61.0cm), Depth – 4”(10.16cm) max. c) Type ZZ - 2x4 – Length – 48”(121.9cm), Width – 24”(61.0cm), Depth – 4”(10.16cm) max. 1.2.6 Luminaire Construction: a) Luminaire housing to have no visible welding, screws, springs, hooks, rivets, bare LED’s or plastic supports. b) The luminaire shall be a single, self-contained device, not requiring on-site assembly for installation. The power supply and circuit board for the luminaire shall be integral to the unit. c) Luminaires shall be fabricated from post painted cold rolled steel and shall be a rigid structure with integral T-bar clips. d) Finish: Polyester powder coat painted with 92% high-reflective paint after fabrication. e) Reflector: rugged one-piece cold rolled steel with embossed multi-facets, echoing the frequency of the refractor prisms to distribute soft light at multiple angles, without flashing thus reducing high luminance contrast. f) End caps shall be sloped at 70 degrees to create depth. g) Luminaire to have smooth transition between t-bar and reflector arch. No doorframe or exposed hardware. h) Polymeric materials (if used) of enclosures containing either the power supply or electronic components of the luminaire shall be made of UL94VO flame retardant materials. Luminaire lenses are excluded from this requirement. i) Integral Grid Clips required on recessed mounted luminaires along with integral tie wire mounting points. j) Luminaire to have air removal capability as specified. k) The assembly and manufacturing process for the SSL luminaire shall be designed to assure all internal components are adequately supported to withstand mechanical shock and vibration. 1.2.7 LED Sources a) LED’s shall be manufactured by, Nichia, Samsung or Osram. 2 2/5/2013 RTLED Luminaire_Sample-Spec_2513.docx b) Lumen Output – minimum initial lumen output of the luminaire shall be as follows for the lumens exiting the luminaire in the 0-90 degree zone - as measured by IESNA Standard LM-79-08 in an accredited lab. Exact tested lumen output shall be clearly noted on the shop drawings. a. Type XX - 1x4 – 3883 initial lumens @ 3500k b. Type YY - 2x2 – 3313 initial lumens @ 3500k c. Type ZZ - 2x4 – 4845 initial lumens @ 3500k c) Lumen output shall not decrease by more than 20% over the minimum operational life of 50,000 hours. d) Individual LEDs shall be connected such that a catastrophic loss or the failure of one LED will not result in the loss of the entire luminaire. e) LED Boards shall be suitable for field maintenance or service from below the ceiling with plug-in connectors. LED boards shall be upgradable. f) Light Color/Qualitya. Correlated Color temperature (CCT) range as per specification, between 3500K, 4100K and 5000K shall be correlated to chromaticity as defined by the absolute (X,Y) coordinates on the 2D CIE chromaticity chart. b. The color rendition index (CRI) shall be 80 or greater. c. Color shift over 6,000 hours shall be <0.007 change in u’ v’ as demonstrated in IES LM80 report. 1.2.8 Power Supply and Drive a) Driver: AccuDrive, 120 – 277 volt, UL Listed, CSA Certified, Sound Rated A+. Driver shall be > 80% efficient at full load across all input voltages. Input wires shall be 18AWG solid copper minimum. b) Driver shall be suitable for full-range dimming. The luminaire shall be capable of continuous dimming without perceivable flicker over a range of 100% to 5% of rated lumen output with a smooth shut off function. Dimming shall be controlled by a 0-10V signal. c) Driver shall be UL listed. d) Maximum stand-by power shall be 1 Watt. e) Driver disconnect shall be provided where required to comply with codes. 3 2/5/2013 RTLED Luminaire_Sample-Spec_2513.docx f) The electronics/power supply enclosure shall be internal to the SSL luminaire and be accessible per UL requirements g) The surge protection which resides within the driver shall protect the luminaire from damage and failure for transient voltages and currents as defined in ANSI/IEEE C64.41 2002 for Location Category A, where failure does not mean a momentary loss of light during the transient event. 1.2.9 Electrical a) Power Consumption: Maximum power consumption, +/- 5% when operating between 120 – 277V (or 346V) shall be as follows: b) Type XX - 1x4 – 41W (94 Lumens per Watt) c) Type YY - 2x2 – 38W (87 Lumens per Watt) d) Type ZZ - 2x4 – 48W (100 Lumens per Watt) e) Operation Voltage - The luminaire shall operate from a 50 or 60 HZ ±3 HZ AC line over a voltage ranging from 120 VAC to 277 VAC. The fluctuations of line voltage shall have no visible effect on the luminous output. The standard operating voltages are 120 VAC, 277 VAC, 347 VAC. f) Power Factor: The luminaire shall have a power factor of 90% or greater at all standard operating voltages and full luminaire output. g) THD: Total harmonic distortion (current and voltage) induced into an AC power line by a luminaire shall not exceed 20 percent at any standard input voltage. h) Surge Suppression: The luminaire shall include surge protection to withstand high repetition noise and other interference. i) RF Interference: The luminaire and associated on-board circuitry must meet Class A emission limits referred in Federal Communications Commission (FCC) Title 47, Subpart B, Section 15 Non-Consumer requirements for EMI/RFI emissions. j) Electrical connections between normal power and driver must be modular utilizing a snap fit connector. All electrical components must be easily accessible after installation and be replaceable without removing the fixture from the ceiling. k) All electrical components shall be RoHS compliant. 1.2.10 Emergency Battery Pack 4 2/5/2013 RTLED Luminaire_Sample-Spec_2513.docx a) Shall be factory installed and provide 1400 lm of light output for 90minutes. 1.2.11 Photometric Requirements a) Luminaire performance shall be tested as described herein. a. Luminaire performance shall be judged against the specified minimum illuminance in the specified pattern for a particular application. b. Luminaire lighting performance shall be adjusted (depreciated) for the minimum life expectancy (Section 2.2.5). c. The performance shall be adjusted (depreciated) by using the LED manufacturer’s data or the data from the IESNA Standard TM-21 test report, which ever one results in a higher level of lumen depreciation. b) The luminaire may be determined to be compliant photometrically, if: d. The initial minimum illuminance level is achieved in 100% of the area of the specified lighting pattern c) The measurements shall be calibrated to standard photopic calibrations. d) Add specific project requirements. 1.2.12 Thermal Management a) The thermal management (of the heat generated by the LEDs) shall be of sufficient capacity to assure proper operation of the luminaire over the expected useful life (Section 1.2.9 c)). b) The LED manufacturer’s maximum junction temperature for the expected life (Section 1.2.9 c)) shall not be exceeded at the average operating ambient (Section 1.2.4). c) The LED manufacturer’s maximum junction temperature for the catastrophic failure shall not be exceeded at the maximum operating ambient (Section 1.2.5). d) The luminaire shall have an UL IC rating. e) The Driver manufacturer’s maximum case temperature shall not be exceeded at the maximum operating ambient. Thermal management shall be passive by design. The use of fans or other mechanical devices shall not be allowed. 1.2.13 Optics 5 2/5/2013 RTLED Luminaire_Sample-Spec_2513.docx a) The optical assembly shall provide volumetric distribution to eliminate cave effect and provide uniform illumination in the space and increased luminance on vertical surfaces. b) Optics shall consist of a ribbed metal reflector system and extruded refracting optical lens with high-transmission internal optical film applied to the inside of the refracting lens. No individual LED images shall be visible to the occupant of the space. c) Refractor or lens shall be 2 piece assembly composed of impact-resistant (20%) DR acrylic with a polymer optical film. d) 2x2 and 2x4 luminaires shall have double barrel, faceted reflector and center V. e) 1x4 luminaire shall have center optic and faceted reflector. 1.2.14 DIGITAL CONTROLS (Edit as required for specific project requirements) a) Each luminaire shall be equipped with two (2) digital RJ45 ports and interface with other digital control equipment. b) Digital manual wall control shall integrate with the SSL luminaire via CAT5E cable and be self-commissioning. c) Digital occupancy sensor shall integrate with the SSL luminaire via CAT5E cable and be self-commissioning. d) Digital photocell shall integrate with the SSL luminaire via CAT5E cable and be self-commissioning. e) Lumen Management: The luminaire shall be capable of continuously monitoring system performance to allow for constant lumen management / compensation function. Lumen output to be maintained at 80% for life of the luminaire, initial input to be 80% of rated input watts and climb to rated watts by end of rated life. Energy savings shall be 20% initial and 10% over rated life of luminaire f) Each luminaire shall be supplied with a unique network address. This address shall be printed on two identification labels. One label shall be permanently affixed to the luminaire and one label shall be easily removed for network control commissioning purposes. Both labels shall be in a location which is easily accessible by the installing contractor. 1.2.15 LUMINAIRE IDENTIFICATION a) Each luminaire shall have the manufacturer's name, trademark, model number, serial number, date of manufacture (month-year), and lot number as identification permanently marked inside the each unit and the outside of each packaging box. b) The following operating characteristics shall be permanently marked inside each unit: rated voltage and rated power in Watts and Volt-Ampere. 1.2.16 QUALITY ASSURANCE 6 2/5/2013 RTLED Luminaire_Sample-Spec_2513.docx a) The luminaires shall be manufactured in accordance with a manufacturer quality assurance (QA) program. The QA program shall include two types of quality assurance: (1) design quality assurance and (2) production quality assurance. The production quality assurance shall include statistically controlled routine tests to ensure minimum performance levels of the modules built to meet this specification. These tests shall include: CCT, CRI, Lumen output and wattage. Tests shall be recorded, analyzed and maintained for future reference. b) QA process and test results documentation shall be kept on file for a minimum period of seven years. c) LED luminaire designs not satisfying design qualification testing and the production quality assurance testing performance requirements described below shall not be labeled, advertised, or sold as conforming to this specification. 1.2.17 DESIGN QUALIFICATION TESTING a) Design Qualification Testing shall be performed by a National Voluntary Laboratory Accreditation Program (NVLAP) testing facility. Such testing may be performed by the manufacturer or an independent testing lab hired by the manufacturer on new luminaire designs, and when a major design change has been implemented on an existing design. A major design change is defined as a design change (electrical or physical) which changes any of the performance characteristics of the luminaire, results in a different circuit configuration for the power supply, or changes the layout of the individual LED's in the module. b) A quantity of two units for each design shall be submitted for Design Qualification Testing. c) Product submittals shall be accompanied by product specification sheets or other documentation that includes the designed parameters as detailed in this specification. These parameters include (but not limited to): a. Maximum power in Watts b. L80 in hours, when extrapolated for the worse case operating temperature (section 2.2.6). TM21 report shall be submitted to demonstrate this. c. Product submittals shall be accompanied by performance data that is derived in accordance with appropriate IESNA testing standards and tested in a laboratory that is NVLAP accredited for Energy Efficient Lighting Products. d) Luminaire shall be tested per IESNA LM 79-08. 7 2/5/2013 RTLED Luminaire_Sample-Spec_2513.docx 1.3 WARRANTY 1.3.1 The manufacturer shall provide a warranty against loss of performance and defects in materials and workmanship for the Luminaires for a period of 5 years after acceptance of the Luminaires. Warranty shall cover all components comprising the luminaire. All warranty documentation shall be provided to customer prior to the first shipment. END OF SECTION 8 2/5/2013