- REMOTE ALARM MODULE TAMlV OPERATION GUIDE OVERVIEW: The Remote Alarm Module provides visual, audio, and secondaty electrical contacts as a response to an alarm condition. The alarm condition is the application of 24 VAC or +24VDC to the J2 Connector. The alarm response delay is user adjustable from approximately 30 seconds to approximately 3 minutes. Overall Size: 4.75 in. x 3.0 in. x 1.1 in. Audible alarm sound pressure level: 70dB CONNECTIONS: Alarm Power Input (J2): +24 VDC or 24 VAC @ 100 mA Remote Alarm Indicator (Jl): Contacts rated at: 0.5A @125VAC, 1A @ 24 VDC. N.O. to C: Normally Open during No Fault and deisy period. N.C. to C: Normally Closed during No Fault and delay period. N.O. to C: Contact Closed during Alarm state (i.e. after delay) N.C to C: Contact Opened during Alarm state (i.e. after delay) OPERATION: Alarm process begins with the application of power via J2 (+24 VDC or 24 VAC). A user selectable delay (via S2) occurr prior to any alarm indications. DIP Switch S2 adjusts the delay by adding fixed increments. The minimum delay is approximately 30 seconds, and is achieved by setting all four switches to the opposite side from the additional delay screening (to the d right). The arrow below shows the switch settings for minimum delay. +72SEC +72SEC Additional Delay is added by moving the DIP switches to the I& he +36SEC I +36SEC +8SEC adds approximately 8 +16SEC I +l6SEC I seconds to the 30-second minimum. +8SEC yielding approximately 38 second delay. The times are additive, thus 16 delays are possible. The MINIMUMDELAY SETTING DELAY SETIWG OF 74 SEC maximum delay is selected by 30+8+36 = 74 OF 30 SEC setting all four DIP switches to the left. After the delay period has completed, the Alarm light will illuminate, the audible alarm will sound, and the relay contacts will switch. Pressing the fmnt panel SILENCE button (SI) will silence the audible alarm, but the ALARM light will remain illuminated, and the relay contacts will remain in the alarm state. The alarm circuit automatically resets M e n the input alarm voltage to J2 is turned-off or removed. , - - D 1 1 - T.E.A.S.S. TOTAL ENERGY APPLICATIONSYSTEMSSALES,Inc. 17 NORTH BELLE MEADE ROAD, EAST SETAUKET, NY 11733 Ph: 800-732-6297 1 1