TECHNICAL TOPIC Howtoavoidmistakeson Bill Allan suggests ways of tackling this section on certificates and reports with confidence In the Electrical Installation Certificate, the Periodic Inspection Report and NAPIT’s popular Single Circuit/ Minor Works Certificate there is a box entitled Supply Characteristics and Earthing Arrangements. Within that box, there is a section called Nature of Supply Parameters. This seems to cause more problems than any other part of the above mentioned certificates. So I’ll give some guidance on completing this section. Nominal voltage U/U0 The symbol U is the nominal voltage between phases. The nominal voltage between phases in a threephase system is 400 volts. The symbol, U0 represents the nominal phase voltage to Earth (for TN systems). The nominal value of U0 in three-phase and singlephase systems is 230 volts. When completing the nominal voltage line, nominal voltages should be used rather than measured values of voltage. For three-phase systems, the nominal voltage line should be completed thus: 400/230. For single-phase systems, it should be recorded as: 230. The Electricity Safety, Quality and Continuity Regulations 2002 permit tolerances of +10% to – 6% of the nominal supply voltage. the energy let-through of the upstream device doesn't exceed a value which can be withstood by the device (or devices) on the load side.(see Regulation 434-03-01). The term prospective fault current includes the prospective short-circuit current and the prospective earth fault current. It is the greater of the two values which must be compared with the breaking capacity Fig 1 Measurement of prospective short-circuit current Note: The neutral and earth probes are connected to the neutral terminal Supply Earth connection block N P E P N Consumer unit Nominal frequency The nominal frequency of public supplies in the UK is 50 Hertz and a tolerance of +/- 1% is permitted. Therefore, in the case of a three-phase or singlephase system being referred to, insert 50 next to nominal frequency. E P N Prospective fault current, Ipf The design requirements of Regulation 434-02-01 are included in the testing section in Regulation 713-12-01. The requirements are that the prospective short-circuit current and the prospective earth fault current are to be measured, calculated or determined by another method (e.g. enquiry of the supplier) at the origin of the installation and also at other relevant points in the installation. A relevant point is a point where a protective device, required to operate under fault conditions, has been installed. It is necessary to ascertain that the breaking capacity rating of each fuse and miniature circuit breaker is not less than the prospective short-circuit current or the prospective earth fault current at the point at which it is installed. However, a lower breaking capacity is allowed if another protective device which has the necessary breaking capacity is installed on the supply side. In this case, it is necessary that the characteristics of the devices are co-ordinated so that 10 NAPIT 0870 444 1392 www.napit.org.uk Main earthing terminal (MET) Main bonding conductors Test instrument of the protective device and recorded on the certificate. Measurement is the preferred method for determining the value of the prospective fault current using an instrument capable of giving a direct reading. Fig. 1 shows how the prospective short-circuit current is measured using a three-lead test instrument. As many test instruments cannot measure the voltage between phases, when working on threephase systems, the maximum balanced prospective short-circuit is taken to be twice the single-phase value. In three-phase systems, the prospective short-circuit current will always be larger than the prospective earth fault current. Fig. 2 shows how the prospective earth fault current is measured using a three lead test instrument. supplyparameters Prospective fault current rating of overcurrent devices and the means of earthing. It is most important that the means of earthing is disconnected for the duration of the test to avoid false readings being obtained through the main bonding conductors. These are called parallel paths. As the means of earthing is disconnected, care must be taken to avoid any shock risk to For a single-phase 100 A supply, the prospective fault current may be as high as 16,000A (16 kA), depending upon the external supply network conditions. In practice however, it is more likely to be less than 5 kA. BS EN 1361. Type 1 cartridge fuses of the type frequently found in Fig 2 Measurement of electricity suppliers’ prospective earth cut-out boxes have a rated breaking fault current capacity of 16.5 kA. BS EN 1361, type 11 cartridge fuses are Supply Earth also increasingly connection common and they N block P have a rated breaking capacity of 33K. Domestic mcbs are commonly rated at 6 kA. Further information on breaking capacities of protective devices can be found in IEE Guidance Note 1, Selection and Erection. The external loop impedance Ze E P Measurement of external loop impedance, Ze Note: The main earth is disconnected from main bonding conductors and circuit protective conductors for this test Supply Earth connection block N P E Main switch in ‘off’ position Consumer unit N Fig 3 P N Consumer unit N N P P E Regulation 313-01-01 requires the value of Test instrument Ze to be determined and this can be achieved by measurement, enquiry of the electricity supplier or calculation. The main reason for requiring Ze to be established is to confirm that the main earthing terminal provided by the electricity supplier is actually connected with Earth. Therefore, however a value for Ze is arrived at, a test must be made to ensure that a connection with Earth has indeed been provided. This test can be carried out using an earth fault loop impedance tester or a test lamp. NAPIT recommends that the value of Ze is determined by direct measurement. Fig. 3 shows how Ze is measured using a threelead phase-earth fault loop impedance tester at the origin of the installation. The measurement is made between the incoming phase conductor E (MET) (MET) Main bonding conductors Main bonding conductors Test instrument the tester and to others on the site. The main switch must be switched to the OFF position. The tester must ensure that the means of earthing has been replaced following the test. Values for Ze are normally about 0.35 ohms for TN-C-S systems and around 0.8 ohms for TN-S systems. See overleaf for Student Activities Conclusion I hope this article has been helpful but please remember when using test instruments such as those discussed in this issue it is most important to read the manufacturer’s instructions before use. NAPIT 0870 444 1392 www.napit.org.uk 11