SESSION 3 Short Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University 1 Short Circuit Calculations Leonard Bohmann Michigan State University 2 Line to Ground Short 2003 IEEE T & D CONFERENCE 3 Short Circuit Fault Currents 7 dc offset decaying sinusoid 6 5 Amps (kA) 4 3 2 1 0 -1 0 t 0.05 0.1 0.15 0.2 -2 -3 high frequency transient 2003 IEEE T & D CONFERENCE 4 Short Circuit Fault Currents (continued) X(t) v(t) R if v( t ) = Vm cos(ωt + α) Z( t )∠θ = R + jX( t ) then V i( t ) = m [cos(ωt + α − θ) Z( t ) 5 4 3 2 − cos(ωt 0 + α − θ)e 1 0 -1 0 0.05 0.1 0.15 − Rωt X( t ) 0.2 -2 -3 2003 IEEE T & D CONFERENCE 5 ] dc offset 5 4 3 2 1 0 -1 0 0.05 0.1 0.15 0.2 -2 -3 Vm i( t ) = Z cos(ωt + α − θ) − cos(ωt + α − θ)e − Rωt X 0 2003 IEEE T & D CONFERENCE 6 Variable magnitude 6 4 2 0 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 -2 -4 -6 t Vm i( t ) = cos(ωt + α − θ) Z( t ) 2003 IEEE T & D CONFERENCE 7 reactance (pu) Reactance of Synchronous Machine Xd 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 X'd X"d 0 0.2 0.4 0.6 0.8 1 1.2 1.4 t 2003 IEEE T & D CONFERENCE 8 • Use sub-transient reactance to calculate fault currents – worst case for when CB is opening • Do not calculate dc offset directly – use X/R to approximate offset (asymmetry ratio) at opening time – X/R is the time constant of the decay in cycles 2003 IEEE T & D CONFERENCE 9 ZG1 ZL2 1 ZT15 2 ZT12 ZT23 3 5 If ZT35 ZL5 ZT34 4 How do you calculate the fault current (If) at bus 3? ZG4 2003 IEEE T & D CONFERENCE 10 Use Thevenin equivalent 3 ZTh If VTh • VTh: open circuit voltage – also called the prefault voltage, Vf – often use 1∠0° 2003 IEEE T & D CONFERENCE 11 Use for: • symmetrical faults – single phase networks – three phase faults in three phase networks (per phase equivalent) • concept for solving all faults 2003 IEEE T & D CONFERENCE 12 • This method calculates the current going into the fault • Often want the current elsewhere in the network (through a circuit breaker, in bus bars, in other lines, etc.) 2003 IEEE T & D CONFERENCE 13 A current source, with the magnitude of the fault current, placed at the fault, has the same effect on the rest of the circuit as the short circuit. 3 ZTh Vf 3 ZTh If If Vf 2003 IEEE T & D CONFERENCE 14 Adding a current source to the original circuit has the same electrical Z effect as adding it to 1 the equivalent circuit ZL2 G1 ZT15 2 ZT12 3 5 3 ZT35 If ZT34 ZTh If Vf ZT23 ZL5 4 ZG4 2003 IEEE T & D CONFERENCE 15 ZG1 ZL2 1 ZT15 All the voltages and all the currents can be found using the new circuit. 2 ZT12 ZT23 3 5 If ZT35 ZT34 ZL5 4 ZG4 Use superposition: – Use the original sources (or assume currents are 0 and voltages are 1∠0°) – Use just the current source, gives changes due to the fault 2003 IEEE T & D CONFERENCE 16 Calculation details Bus Admittance Matrix: Ybus ZG1 ZL2 1 I = Ybus V ZT15 vector of current injections vector of bus voltages 5 2 ZT12 ZT23 3 ZT35 If ZT34 ZL5 4 ZG4 2003 IEEE T & D CONFERENCE 17 Diagonals: Σ of Y connected at node Y22 = 1/ZT12 + 1/ZL2 + 1/ZT23 ZG1 ZL2 1 ZT15 5 2 ZT12 3 ZT35 ZT34 ZL5 4 ZG4 ZT23 Ybus If Y11 Y 21 =0 0 Y51 0 Y15 Y22 Y23 0 0 Y32 Y33 Y34 Y35 0 Y43 Y44 0 0 Y53 0 Y55 Y12 0 Off diagonals: - of Y connected between nodes Y53 = -1/ZT35 2003 IEEE T & D CONFERENCE 18 Ybus is sparse (lots of zero) – small size – easy to build – quick algorithms to manipulate 2003 IEEE T & D CONFERENCE 19 Bus Impedance Matrix: Zbus V = Zbus I ZG1 ZL2 vector of bus vector of current injections voltages 1 ZT15 5 Zbus = Ybus-1 2 ZT12 ZT23 3 ZT35 If ZT34 ZL5 4 ZG4 2003 IEEE T & D CONFERENCE 20 Z bus Z11 Z 21 = Z 31 Z 41 Z 51 Z12 Z13 Z14 Z15 Z 22 Z 23 Z 24 Z 25 Z 32 Z 33 Z 34 Z 35 Z 42 Z 43 Z 44 Z 45 Z 52 Z 53 Z 54 Z 55 Zbus is a full matrix – slow to invert – slow to manipulate – avoid using if possible Diagonal element is the Thevenin Impedance at that bus – Z33 is the Thevenin Impedance at bus 3 2003 IEEE T & D CONFERENCE 21 To find the change in voltages due to the fault current at bus 3: ∆V1 Z11 ∆V Z 2 21 ∆V3 = Z 31 ∆V4 Z 41 ∆V5 Z 51 Z12 Z13 Z14 Z15 0 Z 22 Z 23 Z 24 Z 25 0 Z 32 Z 33 Z 34 Z 35 ⋅ - I f Z 42 Z 43 Z 44 Z 45 0 Z 52 Z 53 Z 54 Z 55 0 2003 IEEE T & D CONFERENCE 22 To calculate current in line 2-3: 1 ∆I 23f ∆V2 − ∆V3 = ZT 23 2 ∆I23f ZT23 3 5 If 4 2003 IEEE T & D CONFERENCE 23 Asymmetry ratio: S • Method calculates the RMS worst case of the 60 Hz component – this is needed to set protective relays • For circuit breaker selection, need to know the total RMS current (60 Hz and dc offset) – Circuit breakers are rated on symmetrical fault current, assuming an X/R ratio of 15 2003 IEEE T & D CONFERENCE 24 Asymmetry ratio I RMS = I + I 2 ac I RMS 2 dc = I + 2I ac e 2 ac I RMS = I ac 1 + 2 ⋅ e − ωt XR − 2 ωt X R 2 − 2 ωt I RMS = S(t ) where S(t) is 1 + 2 ⋅ e X R I ac 2003 IEEE T & D CONFERENCE 25 Calculating X/R ZG1 • Equations presented are for a single order system • For higher order systems, ZL2 1 ZT15 2 ZT12 ZT23 3 5 ZT35 ZL5 If ZT34 4 ZG4 – ignore R and find equivalent X, – ignore X, and find equivalent R • Actual decay is typically quicker than this approximation 2003 IEEE T & D CONFERENCE 26 Algorithm • Calculate Thevenin Impedance • Calculate current into fault • Find the needed elements of Zbus (not all of them) • Find the needed changes in bus voltages • Find the line currents of of interest • Find the dc offset 2003 IEEE T & D CONFERENCE 27 Example • The oneline drawing of a system, along with Zbus are shown below. i) Calculate the fault current for a three phase solid fault at bus 3. j0.1pu j10 pu ii) Calculate the voltages at bus 1, 2, and 3 during this fault. 2 1 iii) Calculate the current flowing j 0.08 pu j0.05 pu j0.025 pu from bus 2 to bus 3. 3 5 If j0.03 pu j15 pu j0.05 pu 4 Z bus j0.1 pu 0. 0656 0.0538 = j 0. 0502 0. 0334 0. 0559 0.0538 0. 0502 0. 0334 0. 0559 0. 0831 0.0675 0. 0450 0. 0623 0.0675 0. 0731 0.0487 0. 0644 pu 0. 0450 0.0487 0. 0658 0. 0429 0.0623 0. 0644 0. 0429 0. 0799 2003 IEEE T & D CONFERENCE 28 Part (i): Calculate the fault current for a three phase solid fault at bus 3. 3 • Assume all initial bus voltages are 1∠0° j0.731 1∠0° – therefore all initial currents are 0 • Use the 3,3 element of Zbus for the Thevenin impedance. If 1 If = j 0.0731 I f = − j13. 68 pu 2003 IEEE T & D CONFERENCE 29 Part (ii): Calculate the voltages at bus 2, 3, and 4 during this fault. Multiply the negative of the fault current by elements in the 3rd column to get the change in voltages − 0.687 − 0.923 −1 = ∆V4 ∆V5 0.0656 0.0538 0.0502 0.0334 0.0559 0 0.0538 0.0831 0.0675 0.0450 0.0623 0 j 0.0502 0.0675 0.0731 0.0487 0.0644 ⋅ - - j13.68 0.0334 0.0450 0.0487 0.0658 0.0429 0 0.0559 0.0623 0.0644 0.0429 0.0799 0 2003 IEEE T & D CONFERENCE 30 Part (ii): Calculate the voltages at bus 2, 3, and 4 during this fault. (continued) The voltages during the fault are the initial voltages minus the changes in the voltages V1f = V1i − ∆V1 = 1∠0° − 0.687 = 0.313pu V2f = V2i − ∆V2 = 1∠0° − 0.923 = 0.0766pu V3f = V3i − ∆V3 = 1∠0° −1 = 0 pu 2003 IEEE T & D CONFERENCE 31 Part (iii): Calculate the current flowing from bus 2 to bus 3. The current is the difference between the voltages divided by the impedance I 23f I 23f 1 2 -j3.86 pu V2f − V3f = ZT23 5 0.0766− 0 = = − j3.86 pu j0.025 2003 IEEE T & D CONFERENCE 3 -j13.68 pu 4 32 Problem A small power system is sketched below along with Zbus. j0.1 pu j0.1 pu 1 j0.05 pu 2 j0.025 pu j 0.08 Z bus 3 j0.05 pu 4 4. 783 3. 044 = j 3. 261 2. 174 3. 044 4. 534 3. 634 2. 422 3. 261 3. 634 4. 658 3. 106 2. 174 2. 422 ×10 − 2 pu 3. 106 5. 404 j0.1 pu a) What is the fault current for a three-phase fault to ground at bus 3? b) What are the voltages at busses 2, 3, and 4? c) What is the current due to the fault from bus 4 to 3 and from 2 to 3? 33 2003 IEEE T & D CONFERENCE Unsymmetrical Faults Elham Makram Clemson University 2003 IEEE T & D CONFERENCE 1 SINGLE LINE TO GROUND FAULT Boundary Conditions at fault location a I bf = I cf = 0 b Vf = Zf * Iaf c Iaf Ibf From the current equations, Icf I0 + a 2 I1 + aI2 = I 0 + aI1 + a 2 I 2 = 0 (a 2 – a)I1 = (a 2 – a)I2 Zf I1 = I 2 Thus I 0 + ( a 2 + a) I1 = 0 n I0 = I1 = I 2 Fig.1. Single line to ground fault on phase A Now Va = Zf * I af Or, V0 + V1 + V2 = Zf * 3I0 2003 IEEE T & D CONFERENCE 1 SINGLE LINE TO GROUND FAULT (CONTD.) To satisfy the voltage and current boundary conditions, the sequence networks should be connected in series as shown in Fig. 2. I0 Zero Sequence Network + V0 I1 Zero Sequence Network + V1 - 3Zf I2 Zero Sequence Network + V2 - Fig.2. Sequence connection for A-G fault 2003 IEEE T & D CONFERENCE 2 LINE TO LINE FAULT Current boundary Conditions I af = 0 I bf = - I cf a b Thus, c I0 = 0 Iaf Ibf Icf + a 2 I1 + aI2 + aI1 + a 2 I 2 = 0 (a 2 + a)I1 = - (a 2 + a)I2 Vaf Vbf Zf Vcf I1 = - I 2 Voltage boundary conditions Vbf = Vcf + Zf I bf n Fig.3. Line to line fault V0 + a 2 V1 + aV2 = Zf (I 0 + a 2 I1 + aI 2 ) + V0 + aV1 + a 2 V2 This leads to (a 2 - a)V1 = (a 2 - a)I1 Zf + (a 2 - a)V2 V1 = V2 + Zf I1 2003 IEEE T & D CONFERENCE 3 LINE TO LINE FAULT (CONTD.) To satisfy the voltage and current boundary conditions, the sequence networks should be connected as shown in Fig. 4. I1 Positive Sequence Network + V1 I2 Negative Sequence Network Zf + V2 - Fig.4. Connection of sequence network for BC fault 2003 IEEE T & D CONFERENCE 4 DOUBLE LINE TO GROUND FAULT CurrentboundaryConditions a at the faultlocation, Iaf = 0 b Thus, I0 + I1 + I2 = 0 c Iaf Ibf Icf Voltageboundaryconditions Vbf = (Ibf + Icf )Zf Vcf and, Vbf = Vcf + Vaf Vbf Zf Thus, n V0 + a 2V1 + aV2 = V0 + aV1 + a2V2 Fig.5. Double line to ground fault ThusV1 = V2 Also, V0 + a 2V1 + aV2 = ( 2I0 + a2I1 + aI2 + aI1 + a 2I2 ) Zf ThusV0 - V1 = 3Zf I0 2003 IEEE T & D CONFERENCE 5 DOUBLE LINE TO GROUND FAULT (CONTD.) Considering the voltage and current boundary conditions, the sequence networks are connected as shown in Fig. 6. I0 Zero Sequence Network + V0 - 3Zf I1 Positive Sequence Network + V1 I2 Negative Sequence Network + V2 - Fig.6. Sequence network connection for double line to ground fault 2003 IEEE T & D CONFERENCE 6 Example 1 Consider the power system shown in Fig. 7. T1 1 P G1 2 T. L. T2 G2 Fig. 7. Example 1 Ratings G1 and G2: 100 MVA, 20 kV Find the voltages at Bus 1 and the currents from T1 to P due to X1 = X2 = 0.3 pu (i) X0 = 0.04 pu (ii) Line to line fault at P T1 and T2: 100 MVA, 345/20 kV Single line to ground fault at P (iii) Double line to ground fault at P XT1 = XT2 =0.08 pu T. L. X1 = X2 = 0.15 pu X0 = 0.5 pu 2003 IEEE T & D CONFERENCE 7 Positive sequence network j0.3 1 j0.08 j0.3 2 P j0.15 j0.38 j0.2213 j0.53 j0.08 P P If E1 = E 2 = V = 1∠0° Z th = (0.3 + j0.8) || (j0.3 + j0.08 + j0.15) = j0.2213 Negative sequence network Zero sequence network j0.2213 P Z1th = j0.2213 j0.08 j0.5 P 2003 IEEE T & D CONFERENCE Z0th = j0.08 8 (i) Single line to ground fault I1 = I 2 = I 0 = E (Z0th + Z1th 1∠0° = - j1.9134 + Z 2th ) (j0.2213 + j0.2213 + j0.08) The following are the sequence current components from T1 - - > P 0.53 = − j1.114 (0.53 + 0.38) I 2 = - j1.114 I1 = I1 * I 0 = - j1.9134 The sequence voltage components at the fault location are : V1 = E1 - I1Z1 = 1.0 – (-j1.114)(j0.38) = 0.57668 V2 = - I 2 Z 2 = - (j1.114) (j0.38) = - 0.42332 V0 = - I 0 Z0 = - j1.913 (j0.8) = - 0.15304 The current phase components from T1 - - > P I a 1 1 I = 1 a 2 b I c 1 a 1 I a0 a * I a1 a 2 I a2 2003 IEEE T & D CONFERENCE 9 I a = -j1.114 - j1.114 - j1.913 = - j3.027 I b = a 2 (-j1.114) + a(-j1.114) – j1.913 = - j0.799 I c = a(-j1.114) + a 2 (-j1.114) – j1.913 = - j0.799 c b -j0.799 -j0.799 -j3.027 -j2.712 c -j5.739= 3 I0 The phase voltages at the fault location are : Va = V0 + V1 + V2 = - 0.15304 + 0.57668 – 0.42332 = 0 Vb = V0 + a 2 V1 + aV2 = - 0.15304 + (1∠240°)(0.57668) + (1∠120°)(-0.42332) = -0.2297 - j0.866 Vc = V0 + aV1 + a 2 V2 = - 0.15304 + (1∠120°)(0.57668) + (1∠240°)(-0.42332) = -0.2297 + j0.866 2003 IEEE T & D CONFERENCE 10 (ii) Line to line fault Currents : I1 = −I 2 = (Z1th E 1∠0° = = − j 2.26 + Z 2th ) (j0.2213 + j0.2213) I1 (T1 - - > P) = − j2.26 0.53 = − j1.316 (0.38 + 0.53 ) I 2 (T1 - - > P) = j1.316 Ia = 0 I b = a 2 (-j1.316) + a(j1.316) = 2.279 I c = a (-j1.316) + a 2 (j1.316) = 2.279 Voltages : Va1 = E − I a1Z1 = 1.0 - (-j1.316)(j0.38) = 0.5 Va2 = - I a2 Z 2 = 0.5 Va = 1∠0° Vb = -0.5∠0° Vc = 0.5∠0° 2003 IEEE T & D CONFERENCE 11 SEQUENCE PHASE SHIFT THROUGH WYE/DELTA TRANSFORMER BANK •Positive and negative sequence impedance is independent of connection •These networks ignore phase shift •When current and voltages are transformed from one side to the other phase shift must be considered. •Standard ANSI connection has been shown in figs. 8 (a) and 8 (b). High side Low side High side Low side Ia n:1 n:1 IA a A Ia I Ia/n IA nIA AA Ib IB b B Ib IB Ib/n IB nIB B Ic IC c C Ic IC Ic/n IC nIC C A a A a C C B c b Fig. 8 (a) Wye/Delta a b c Bc b Fig. 8 (b) Delta/Wye 2003 IEEE T & D CONFERENCE 12 Refer to fig. 8(a) Positive sequence current : I a 1 = n(I A1 - I C1 ) = n(I A1 - aI A1 ) = nI A1 (1 - a) = n 3 I A1 ∠ - 30 ° In per unit, I A1 = I a1 ∠ 30 ° Positive sequence volatge : VA1 = n(V a1 - a 2 Va1 ) = nV a (1 - a 2 ) = n 3 Va1 ∠ 30 ° or in per unit, VA1 = Va1 ∠ 30 ° Negative sequence current : I a 2 = n(I A2 - I C2 ) = n(I A2 - a 2 I A2 ) = nI A2 (1 - a 2 ) = n 3 I A2 ∠ 30 ° or In per unit I A2 = I a2 ∠ − 30 ° Negative sequence voltage : VA2 = n(V a2 - Vb2 ) = n(V a2 - aV a2 ) = nV a2 (1 - a) = n 3 Va2 ∠ − 30 ° or In per unit VA2 = Va2 ∠ − 30 ° 2003 IEEE T & D CONFERENCE 13 Refer to fig. 8 (b) Postitive sequence current : 3 1 1 I a1∠ 30 ° (I a1 - I b1 ) = (I a1 - a 2 I a1 ) = n n n or, in per unit, I A1 = I a1∠ 30 ° I A1 = Postitive sequence voltage : 1 3 (VA1 - aVA1 ) = VA1 ∠ − 30 ° n n or, in per unit, VA1 = Va1∠ 30 ° Va1 = Negative sequence current : 3 1 I a2 ∠ − 30 ° (I a2 - aI a2 ) = n n or In per unit I A2 = I a2 ∠ − 30 ° I A2 = Negative sequence voltage VA2 = Va2 ∠ − 30 ° 2003 IEEE T & D CONFERENCE 14 In general, in Y - ∆ or ∆ - Y connections : (i) Positive sequence High voltage = Positive sequence Low voltage∠ + 30° (ii) Negative sequence High voltage = Negative sequence Low voltage∠ - 30° 2003 IEEE T & D CONFERENCE 15 Example 2 Find the currents and voltages at G1 of Example 1, due to single line to ground fault at P. (i) Currents : I ag1 = - j1.114 ∠ - 30° = - j1.114 ∠ - 120° I ag2 = - j1.114 ∠ + 30° = j1.114 ∠ - 60° I ag0 = 0 I ag = I ag1 + I ag2 = - j1.114 ∠ - 120° + j1.114 ∠ - 60° = - j1.9295 I bg = a 2 I ag1 + aIag2 = 1∠240° (1.114 ∠ - 120°) + 1∠120° (1.114 ∠ - 60°) = (1.114 ∠120°) + (1.114 ∠60°) = j1.9295 I cg = 0 2003 IEEE T & D CONFERENCE 16 Example 2 ( contd.) (ii) Voltages : Vag1 = E – I a1 Zg1 = 1.0 - (-j1.114)(j0.3) = 0.666 (from sequence Network neglecting phase shift) Vag2 = – I a2 Zg2 = - 0.3342 (from sequence Network neglecting phase shift) Vag1 = 0.666 ∠ - 30° Vag2 = - 0.334 ∠30° Vag = Vag1 + Vag2 = 0.666 ∠ - 30° - 0.334 ∠30° = 0.577∠ − 60° Vbg = a 2 Vag1 + aVag2 = 0.666 ∠210° - 0.334 ∠150° = 0.577 ∠240.12° Vcg = aVag1 + a 2 Vag2 = 1.0∠90° Vag 1 1 2 V = 1 a bg Vcg 1 a 1 Vag0 0.577∠ − 60° a * Vag1 = 0.577∠240.12° 2 1∠90° a Vag2 2003 IEEE T & D CONFERENCE 17 PROBLEMS PROBLEM #1 For the system shown below, find the currents in the transformer and generator windings in per unit and amperes for a single-line-to-ground fault at (i) P (ii) R 15/115 kV R P G1 G: 100 MVA, 15 kV Transformer: X1=X2= 0.1, 100 MVA, 15/115 kV X0 = 0.05 X = 0.1 2003 IEEE T & D CONFERENCE 18 PROBLEMS PROBLEM #2 Solve examples 1 and 2 for a double-line-to-ground fault at P. 2003 IEEE T & D CONFERENCE 19 PROBLEMS PROBLEM #3 Solve examples 1 and 2 for a line-line fault at P. 2003 IEEE T & D CONFERENCE 20