2727-IN010A-EN-P, MobileView Junction Box Installation Instructions

advertisement
Installation Instructions
MobileView Junction Box
(Catalog Number 2727-MRJB2)
English
The MobileView Junction Box (2727-MRJB2) integrates the following terminals into
the control system:
• MobileView Guard G750
• MobileView Machine Terminal MT750
The Junction Box can be used either inside or outside a control cabinet based on its
IP65 rating.
The cables that connect the MobileView terminal to the Junction Box are available
as separate catalog numbers.
• MobileView Connection Cable (Catalog Numbers 2727-MRTxx) connects the
MobileView terminal to the Junction Box. The Connection Cable is available
in 5, 10, 15, 20 meter (16.4, 32.8, 49.2, 65.6 foot) lengths.
• MobileView Junction Box Cable (2727-MREY1) connects the Junction Box to
the MobileView Connection Cable when the Junction Box is mounted inside
a cabinet. The cable is 2 meters (6.56 feet) long.
Inside. . .
Junction Box Dimensions and Connections ...................................................................... 2
Mounting the Junction Box on a DIN Rail ......................................................................... 3
Connecting the MobileView Terminal to the Junction Box ............................................... 5
Junction Box Pinout and Wiring ........................................................................................ 6
Specifications .................................................................................................................... 7
Publication 2727-IN010A-EN-P - May 2004
2
MobileView Junction Box
70 mm
(2.76 in)
Junction Box Dimensions and Connections
X3
X1
1
1
10
6
140 mm
(5.52 in)
165 mm (6.50 in)
K1
SHIELD
K1
17-pin female connector for connection cable
X1
Terminal block for power and control lines
X3
Terminal block for data lines
SHIELD
ATTENTION
Cable shield clamp with connection surface for shield of data lines (not used
for strain-relief of the cable)
The Junction Box and the MobileView terminal meet the safety
class III in accordance with EN 61131-2 and EN 50178. When
connecting the MobileView terminal, make sure all voltages
connected to the terminal are safety low voltages and isolated
from the low voltage supply system by a safety transformer or
a similar safety component.
Publication 2727-IN010A-EN-P - May 2004
MobileView Junction Box
3
Mounting the Junction Box on a DIN Rail
Mount the Junction Box on a DIN rail inside the enclosure.
Attach DIN Rail Adapter to MobileView Terminal
Attach the DIN Rail Adapter to the back of the Junction Box using the screws
provided.
To install the Junction Box on a DIN rail:
1. Mount the DIN rail.
2. Hook the top slot of the adapter over the DIN rail.
3. While pressing the Junction Box against the DIN rail, snap the Junction Box
into position.
Publication 2727-IN010A-EN-P - May 2004
4
MobileView Junction Box
To remove the Junction Box from the DIN rail:
1. Place a screwdriver in the adapter latch at the bottom of the Junction Box.
2. Holding the Junction Box, pry downward on the latch until the Junction Box
is released from the DIN rail.
Mounting Junction Box to a Wall
10.2 mm
(0.40i n)
64.8 mm
(2.55 in)
Use the dimensions below for drilling the holes to mount the MobileView Junction
Box to a wall. Use the manufacturer’s recommendation for hole size based on the
screw type and mounting surface.
40 mm (1.58 in)
155 mm (6.10 in)
Publication 2727-IN010A-EN-P - May 2004
MobileView Junction Box
5
Connecting the MobileView Terminal to the Junction Box
Control Cabinet
Junction Box
Run
Erro
r
MobileView Terminal
ESC
7
8
9
4
5
6
1
2
3
.
0
-
KE TOP
Power Supply, E-Stop,
enabling switch
MobileView
Connection Cable
Dust Cover
K1
maximum wall
thickness 5 mm (0.2 in)
K1
Junction Box Cable
25 ± 0.1 mm
(1.0 ± 0.0039 in)
Connector Cutout
25 ± 0.1 mm
(1.0 ± 0.0039 in)
Server
10 Base-T Connection
to Ethernet Network
Cable Clearance
Required minimum distance outside and inside the control cabinet
Minimum 100 mm (3.937 in)
Minimum 130 mm (5.118 in)
Publication 2727-IN010A-EN-P - May 2004
6
MobileView Junction Box
Junction Box Pinout and Wiring
MobileView
MobileView
Connection Cable
S19 K3
pink
6
black
7
green-brown
8
9
white-green
10
grey-pink
11
red-blue
1
brown
yellow
2
green
3
grey
4
violet
5
S4
K2
1
2
3
blue
white
orange
6
red
MobileView
Junction Box Cable
K1
K2
pink
1
black
2
3 green-brown
4 white-green
5 grey-pink
6 red-blue
brown
7
yellow
8
green
12
grey
17
violet
11
9
10
13
14
15
16
blue
white
orange
red
Junction Box
K1
1 24V DC
2 GND_IN
3 E-Stop, circuit 1, pos.*
4 E-Stop, circuit 1, neg.*
5 E-Stop, circuit 2, pos.*
6 E-Stop, circuit 2, neg.*
7 Enbl. sw. circ. 1, pos*
8 Enbl. sw. circ. 1, neg*
12 Enbl. sw. circ. 2, pos*
17 Enbl. sw. circ. 2, neg*
11 Not used
9 Not used
K2 K1
13
14
15
16
X1
1
2
3
4
5
6
7
8
9
10
+24V
GND
ES1+
ES1ES2+
ES2ED1+
ED1ED2+
ED2-
X3
1
2
3
4
5
6
RD+
RDTD+
TDSHLD
* Junction Box connections are for
connection to MobileView Guard
G750 Terminals only.
ATTENTION
Refer to the MobileView Guard User Manual (Publication
2727-UM002) for important information on wiring and
implementing into machine safety systems.
Publication 2727-IN010A-EN-P - May 2004
MobileView Junction Box
7
Specifications
Electrical Specifications
24V dc Power Supply
Use a 24V dc Safety Extra Low Voltage power supply.
Supply Voltage Range: 18V dc to 32V dc
Current Consumption: 450mA at 24V dc, 600mA at 18V dc (with
MobileView Terminal attached)
Peak Inrush Current: 5.6a maximum
Environment Specifications
Operating Temperature
+0°C to +50°C (+32°F to +122°F)
Storage Temperature
-20°C to +70°C (-4°F to +158°F)
Relative Humidity (non-condensing)
5% to 95%
Vibration resistance (operation)
5≤ f < 9 Hz 7mm
9 ≤ f ≤ 150 Hz 2g
Shock Resistance (operation)
15g / 11 ms
Housing
Construction
Double-walled ABS housing withstands grease, oil, lubricants,
alcohol, etc.
Flammability Class
UL 94-V0
Dimensions (W x H x D)
160 mm x 140 mm x 70 mm (6.3 in x 5.5 in x 2.76 in)
NEMA Rating
IP65
ATTENTION
The device meets the safety class III in accordance with
EN 61131-2 and EN 50178. The 24V power supply for the
equipment must provide appropriate isolation between the
safety-extra-low-voltage circuits and dangerous-contact voltage
circuits (for example, by safety transformers).
The power supply circuit must be protected by a 3.5A fuse.
The nominal supply voltage of the MobileView terminal
without the connection cable is 24V dc (supply voltage range:
18 -32V dc.
When planning the power supply, consider the voltage drop
in the connection cable. Specifications of the power supply
lines in the cable are:
• Cross section: AWG24 (0.24mm2)
• Material: zinc-coated copper strand
• Line resistance: <90 Ohm/km (<145 Ohm/mile)
Publication 2727-IN010A-EN-P - May 2004
Publication 2727-IN010A-EN-P - May 2004
Supersedes Publication XXXX-X.X.X - Month Year
PN 41061-351-01(1)
Copyright © 2004 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.