UL 1449 3rd Edition ♦ Creates SPD types ♦ New Nominal Dis charge Surge Current test, In “stress” test ♦ Declare MCOV per mode ♦ SVR 6kV, 500A replaced with VPR (Voltage Protective Rating) 6kV, 3kA ♦ Surge Arrestor incorporated into UL1449 as Type 1 device 1 Competitors Surge Arrestor Our Surge Arrestor SPD Types - UL 1449, 3 rd Edition Type 1 SPD Permanently Connected SPD – Installation between the secondary of the service transf ormer and the LINE side of the service disconnect over current device, as well as the LOAD side, including watt-hour meter socket enclosures. (Not exceeding 1000V): 2 SPD Types (Continued) Type 2 SPD Permanently Connected SPD intended for installation on the LOAD side of the service disconnect over current device; including SPDs located at the branch panel. 3 SPD Types (Continued) Type 3 SPD Point of utilization SPDs, installed a minimum of 10 meters (30 feet) from the electrical service panel, for example cord connected, direct plug-in (DPI), receptacle type and SPDs installed at the utilization equipment being protected. 4 SPD Types (Continued) Type 4 SPD Component SPDs, including discrete components as well as component assemblies. (Note: as proposed the 3rd Edition will allow Type 4 SPDs to be tested and applied where T ypes 1 and 2 are allowed) 5 Measured Limit ing Voltage Test (MLV) ♦ All SPD Types are to be tes ted to 6kV/3kA - 3 pulses per mode with applied voltage. VPR (Voltage Protection Rating) is determined by averaging results. (Per 34.9 and Table 34.1) ♦ SVR was 6kV/500A 6 Nominal Discharge Current Test (In) ♦ Nominal Discharge Current Test has been established to ensure product integrity by exposing the SPD to repetitive surges and over voltage conditions to determine if significant degradation or failure will occur. The before and after VPR test results cannot vary by more than 10%. ♦ Stress test to optimally test coordination between integrally designed disconnecting means and surge components. 7 Nominal Discharge Current Test (In) ♦ Type 1: 10kA or 20kA/Mode ♦ Type 2: 3kA, 5kA, 10kA, or 20kA ♦ 15 pulses per MODE with MCOV applied no more than one second after pulse. ♦ Pulses to be done in groups of 5 with a 30 minute rest in between each group. OCP shall not open. Sample must be functional. 8 Nominal Discharge Test 3 Pre VPR shots Average and 3 Post VPR shots average can not deviate by more than 10% The MCOV value of an SPD is now a tested value 9 In Test for Type 3 and 4 devices Duty Cycle Test ♦ Type 3 and Type 4: Operating Duty Cycle at 6kV/3kA. 15 Surges per mode with applied voltage. OCP (Over Current Protection Device) shall not open. ♦ Easier to pass than the In tes t. 10 Internal or External ♦ Do Internally mounted SPDs have shorter lead lengths? ♦ Lead length is determined by the overall length of a mode, to include length of phase connection PLUS the length of Neutral and Ground connections . ♦ Internally mounted SPDs have very short phase connections , but have long Neutral and Ground connections . 11 A properly installed side mounted SPD can have a shorter system lead length than an internally mounted SPD 12 Upstream Over Current Protection ♦ Does a breaker upstream of an SPD limit the effectiveness of the SPD? ♦ Breakers have trip values and failure values Trip kA CB Pulse Performance Fail kA 160 These values are based on testing performed by Current Technology’s Surge generator on commercially available off the shelf breakers. 140 Pulse kA 120 100 80 60 A 30A breaker will trip when subjected to a 64kA surge 40 20 0 15 30 40 60 100 CB Rating 13 Examples of Installations Type 1 SPD ♦ ♦ ♦ ♦ Type 2 SPD ♦ 200kA per mode SPD 200kA per mode SPD ♦ Surge Rated Integral Disconnect Surge Rated Integral Disconnect ♦ Installed on load side behind a Installed on line or load side of main 30 Amp breaker Surge Rating of Installed system = ♦ Surge Rating of Installed system = 200kA per mode 64kA per mode ♦ Installed on load side behind a 60 Amp breaker ♦ Surge Rating of Installed system = 82kA per mode ♦ Installed on load side behind a 100 Amp breaker ♦ Surge Rating of Installed system = 140kA per mode 14 Specification Updates ♦ Must require 3rd Edition listed products ♦ Must require the service entrance protector be a Type1 SPD to maximize installation capabilities ♦ Must require all other SPDs to be Type2 SPDs ♦ Must require the In rating be 20kA for Service Entrance and 20kA or 10kA for downstream panels. ♦ Must require that the MCOV value be derived from the In test and not be a calculated or claimed figure. ♦ Must reflect VPR clamping levels and not SVR clamping levels ♦ Replace the word “TVSS” with “SPD” 15 Specification Updates Continued ♦ Must not require a surge limiting upstream over current protection device ♦ Must not require the SPD be integrally mounted 16