Vacuum Circuit-Breaker Modules Medium-Voltage Equipment Description Catalog HG 11.51 · 1998 © Siemens AG 1998 NXACT Vacuum Circuit-Breaker Module Description Construction and mode of operation Features • Stored-energy mechanism via closing and opening spring • Charging of springs manually or electrically • Storage of switching sequence 1 The operating mechanism is generally of the stored-energy type. The mechanism operates the pole assemblies through rods. The closing spring can be charged either electrically or manually. It latches in when charging is complete. The closing spring acts as the stored-energy mechanism. For closing, the closing spring can be unlatched either mechanically by means of the local “CLOSE” pushbutton or electrically by remote control. The closing spring charges the contact-pressure/opening springs as the breaker closes. The now discharged closing spring will be charged again automatically by the mechanism motor – if this exists. The breaker is now capable of performing the OPEN – CLOSE – OPEN switching sequence that is required for an unsuccessful auto-reclosing operation. All stored-energy mechanisms perform the switching duties of synchronizing and rapid load transfer (U) as well as autoreclosing (K). 1 7 2 8 3 9 4 10 5 6 R-HG11-116eps Stored-energy mechanism Operating mechanism unit with stored-energy mechanism and secondary equipment 1 Operating mechanism for 7 Low-voltage plug connector 8 Auxiliary switches for disconnector function 2 3 4 5 Motor and gearbox switching function 9 Opening block 10 1st shunt release Closing spring Closing solenoid Auxiliary switch for disconnector function 6 Operating mechanism for feeder earthing switch Trip-free mechanism Features • To VDE 0670 • To IEC 60 056 Operating mechanism motors Features • DC or AC motors • Short-time duty • Varistor circuitry In the event of an opening command being given after a closing operation has been initiated, the moving contacts return to the open position and remain there even if the closing command is sustained. This means that the contacts of the circuit-breaker module reach the closed position under these circumstances, as is permitted by IEC 60 056 and VDE 0670. The motors operate in shorttime duty. Therefore, the voltage and power consumption need not agree with the data on the rating plate. Protection of operating mechanism motors (see adjacent table) The inrush current in the operating mechanism motor can be neglected due to its very short duration. 1/8Siemens HG 11.51 · 1998 Power consumption and rated normal currents for motor short-circuit protection Rated voltage of operating mechanism Voltage range Power consumption of the motor Smallest possible rated normal current of the m.c.b. with G-characteristic max. V min. V W VA A 24 48 60 26 53 66 20 41 51 350 350 350 – – – 8 6 4 110 220 121 242 93 187 350 350 – – 2 1.6 AC 100 110 230 121 121 244 93 93 187 – – – 400 400 400 2 2 1.6 V DC Bereich Energieübertragung und -verteilung Geschäftsgebiet Mittelspannung Postfach 32 20 D-91050 Erlangen http://www.ev.siemens.de Siemens Aktiengesellschaft Order No.: E50001-K1511-A511-A1-7600