Description of functions SF2 circuit breakers fixed version GMH stored energy operating mechanism Wiring diagram 028368 Operation of the electrical GMH stored energy mechanism This gives the device an opening and closing speed that is independent of the operator whether the order is electrical or manual. The electrical control mechanism carries out reclosing cycles and is automatically recharged by a geared motor each time after closing. It consists of: b the stored energy operating mechanism which stores in springs the energy required to open and close the device b a manual lever arming device for the springs b an electrical arming device with a motor to automatically rearm the control mechanism as soon as the circuit breaker is closed (optional) b manual push-button controls on the front face of the circuit breaker (red and black) b an electrical remote-closing device comprising a release and an anti-pumping relay. b an electrical opening device comprising one or several releases of the following type: v shunt opening v undervoltage v Mitop, low energy release only used Sepam 100 LA protection relays b an operation counter b an open/closed position indicator with a mechanical indicator (black and white) b an “armed” control mechanism status indicator with a mechanical indicator and an electrical contact (optional) b a block of 14 auxiliary contacts, available according to the wiring layout used b a pressure switch contact activated by a drop in gas pressure (optional: single or double threshold pressure switch) DE57420EN Wiring diagram (principle) Close CB Open CB M M3 YF + anti-pumping Motor Shunt closing release + anti-pumping system Remote control 28 YO1 “Control mechanism armed” indicator contact YO2 Shunt opening release YM Undervoltage release Mitop Low energy release (Mitop) Changeover contact Pressostat NO NC contacts contacts