www.reinhausen.com On-Load Tap-Changer Type R Operating Instructions BA 119/06 2 119/06 EN Contents Contents 1 General ......................................................................................................................................... 1.1 Safety instructions ............................................................................................................... 1.2 Specified application ........................................................................................................... 5 5 5 2 Design ....................................................................................................................................... 6 3 Shipment ................................................................................................................................... 6 4 Installation of the on-load tap-changer for cover attachment .............................................. 4.1 Mounting flange ................................................................................................................... 4.2 Attaching the on-load tap-changer head to the transformer cover .................................... 4.3 Mounting the tap selector and the diverter switch oil compartment .................................. 8 8 8 9 5 Installation of the on-load tap-changer into the bell-type tank ............................................. 5.1 Assembly of diverter switch oil compartment and tap selector, connection of tap selector connecting leads ..................................................................... 5.2 Installation of the on-load tap-changer into the supporting structure ................................. 5.3 Preparations ..................................................................................................................... 5.4 Mounting the bell-type transformer cover ......................................................................... 11 11 11 12 13 6 Connection of tap winding and tap-changer take-off leads .................................................. 6.1 Tap selector ...................................................................................................................... 6.2 Parallel bridges for R I 2002 an R I 3000 .......................................................................... 6.3 Connecting the tap-changer take-off lead ......................................................................... 16 16 17 17 7 Transformer ratio test .............................................................................................................. 18 8 Drying procedure and filling with oil ...................................................................................... 8.1 Drying procedure .............................................................................................................. 8.1.1 Vacuum-drying process .......................................................................................... 8.1.1.1 Drying in the autoclave .............................................................................. 8.1.1.2 Drying in the transformer tank ................................................................... 8.1.2 Vapor-phase drying process ................................................................................... 8.1.2.1 Drying in the autoclave .............................................................................. 8.1.2.2 Drying in the transformer tank ................................................................... 8.1.3 Operating the OLTC ............................................................................................... 8.2 Filling with oil .................................................................................................................. 18 18 18 18 18 19 19 19 19 20 9 Pipe connections ...................................................................................................................... 9.1 Pipe connection R for protective relay RS 2001 ............................................................... 9.2 Pipe connection S for suction pipe ................................................................................... 9.3 Pipe connection Q ............................................................................................................ 9.4 Connection flange E2 ....................................................................................................... 20 20 20 20 20 NOTE Data contained herein may differ in details from the tap-changing equipment delivered. We reserve the right to make alterations without notice. 119/06 EN 3 Contents 10 Mounting the motor drive unit, the bevel gear and the drive shaft ...................................... 10.1 Mounting the motor drive unit ........................................................................................... 10.2 Mounting the bevel gear ................................................................................................... 10.3 Mounting the drive shaft (square tube) ............................................................................. 21 21 21 21 11 Putting the on-load tap-changer into operation at the transformer factory ........................ 11.1 Operational tests .............................................................................................................. 11.2 Final oil filling .................................................................................................................. 11.3 Ground connections ......................................................................................................... 11.4 Electrical transformer tests ............................................................................................... 22 22 22 23 23 12 Transport to the operating site ................................................................................................ 24 13 Putting into service at the operating site ............................................................................... 24 14 Supervision during service, failures ....................................................................................... 25 15 Inspections ............................................................................................................................... 26 16 Appendix ................................................................................................................................... 28 4 119/06 EN 1 General 1 1.1 General Safety instructions All personnel involved in installation, commissioning, operation, maintenance or repair of the equipment must: be suitably qualified and strictly observe these Operating Instructions. Improper operation or misuse can lead to a reduction in the efficiency of the equipment damage to the equipment and property of the user serious or fatal injury. Safety instructions in this manual are presented in three different forms to emphasize important information. WARNING 1.2 Specified application CAUTION Only use the on-load tap-changer with the transformer specified in the order. Installation, electrical connection and commissioning of the on-load tapchanger may only be carried out by qualified, skilled personnel and only in accordance with these operating instructions. It is the responsibility of the user to make sure that the on-load tap-changer is used for the specified application only. For safety reasons, any unauthorized work, i.e. installation, modification, alteration of the tap-changing equipment, electrical connection or commissioning of the equipment is forbidden without first consulting MR! The trouble-free operation of the drive, the on-load tap-changer and the transformer may be put at risk. This information indicates particular danger to life and health. Disregarding such a warning can lead to serious or fatal injury. CAUTION CAUTION All relevant fire protection regulations must be strictly observed. This information indicates particular danger to the equipment or other property of the user. Serious or fatal injury cannot be excluded. NOTE These notes give important information on a certain subject. 119/06 EN 5 2 3 2 Design Shipment Design The on-load tap-changer (OLTC) consists of the diverter switch with the tap selector mounted below (fig. 1). The diverter switch is installed in its own oil compartment. 3 SHIPMENT On-load tap-changer and motor drive are shipped in the adjustment position. The on-load tap-changer is packed in two parts, diverter switch and tap selector, and is well protected against moisture. Both the diverter switch and the tap selector are blocked in the adjustment position. The on-load tap-changer is attached to the transformer cover by means of the tap-changer head. The tap-changing equipment is shipped as follows: If required, the tap selector may be equipped with a change-over selector. Diverter switch oil compartment with tap-changer head and diverter switch unit (max. weight approx. 210 kg), fig. 2. The change-over selector of all type R OLTCs is laterally attached to the fine tap selector. Tap selector (max. weight approx. 270 kg), fig. 3. OLTC models without change-over selector are available for max. 18, and with change-over selector for max. 35 operating positions. Motor drive unit ED-S (approx. 80 kg) fig. 4. Drive shaft with coupling parts and bevel gear (max. weight approx. 20 kg), fig. 5. The design of the on-load tap-changer and the designation of its main parts are shown in the installation drawing 896 705 in the appendix. Protective relay RS 2001(weight 3.5 kg), fig. 6. These Operating Instructions contain all information regarding installation and operation of the following OLTC standard models, which are available with and without change-over selector. The tap-changer parts must be left wrapped in their airtight cover, unwrap just before installation. Check shipment against documents. Store all parts in a dry place until installation. Three-phase OLTC: R III 1200 (see fig. 1) Single-phase OLTC: R I 2000/2002/2402, R I 3000/3600. All single-phase OLTCs are also available as a group 3 x R I 2002/2402 or 3 x R I 3000/3600 with a common motor drive. A V2 U1 W1 3 1 4 2 3 1 4 2 3 1 4 2 U21 V1 V2 W1 W2 1 6 KHW 1086-4 119/06 EN 3 Shipment NOTE In general, drive shaft, bevel gear and protective relay are packed with the on-load tap-changer. 4 KHW 915-4 A MR V2 W1 2 KHW 1087-4 5 KHW 766-4 MR 3 119/06 EN 3 1 4 2 3 1 4 2 3 1 4 2 KHW 1097-4 6 KHW 848-4 7 4 Installation of the on-load tap-changer for cover attachment 4.1 Mounting flange To mount the tap-changer head to the transformer cover a mounting flange is necessary. This mounting flange should meet the requirements of the tap-changer head gasket surface (see fig. 7, and section 16, drawing 896 705). 25 M12 15 15° To position the thread studs (M12, max. length = 45 mm) we recommend the use of a drilling template (see fig. 8 and section 16, dwg. 890 183). If requested, the drilling template will be supplied without charge with the first on-load tap-changer type R. 15° 0 74 710 Attachment of the tap-changer head to the transformer cover 0 The diverter switch oil compartment is lowered through the cover aperture (= mounting flange) of the transformer. The tap-changer head is attached to the mounting flange by means of bolts. Then, the tap selector is fastened to the diverter switch oil compartment (see section 4.3). 65 4.2 45 Installation of the on-load tapchanger for cover attachment (fig. 7) 7,5° 4 7 KHW 770-4 7,5° 15° 24 x1 5° =3 5 Proceed as follows: 60 ° 74 0 1. Place the diverter switch oil compartment on a level surface. 2. Clean sealing surfaces of mounting flange and tapchanger head. 0 71 20 60 650 3. Put an oil-proof gasket on the mounting flange of the transformer cover. 200 200 4. Lift the diverter switch oil compartment by hooking up the tap-changer head. Lower the oil compartment cautiously into the mounting flange. Take care of screening rings (with Um ≥ 170 kV only). 5. Check position of tap changer head. 8 8 KHW 769-4 6. Attach the tap-changer head to the mounting flange with bolts. NOTE Remove the blocking plate from the coupling (fig. 9) of the oil compartment bottom. 8 119/06 EN 4 Installation of the on-load tap-changer for cover attachment 4.3 Mounting the tap selector and the diverter switch oil compartment Raise the tap selector to the oil compartment and attach. At the same time the mechanical coupling for the tap selector drive has to be performed. Finally, connect the tap selector connecting leads to the diverter switch oil compartment. Proceed as follows: 1. Put the tap selector down on a level surface. Get ready 4 lock nuts M12 with washers. NOTE Remove the blocking strip from the tap selector coupling (fig. 10). The coupling must not be displaced afterwards. 2. Put the tap selector on an appropriate lifting device. Remove the ring nuts. 9 KHW 1111-4 rh-1111-4-0/1 3. Raise the tap selector to the diverter switch oil compartment. Be sure that tap selector connecting leads clear the diverter switch oil compartment and remain undamaged. 4. Position coupling parts and attachment points of tap selector and oil compartment to match properly. 5. Raise the tap selector to its final height (fig. 11). 6. Bolt tap selector attachment points to the oil compartment bottom: 4 lock nuts M 12/w.s.19, washers, max. torque 65 Nm (fig. 12). 7. Remove the wooden support from the laterally attached change-over selector. 10 KHW 1098-4 rh-1098-4-0/1 1500 11 119/06 EN KHW 1102-4 9 4 Installation of the on-load tap-changer for cover attachment Connection of the tap selector connnecting leads to the diverter switch oil compartment: CAUTION All connections must be carried out carefully. The tightening torques indicated must be applied. Be sure that bolts are tightened carefully and screened by the screening caps supplied with the equipment (fig. 13). OLTCs R III 1200 and R I 3000/3600 6 connecting leads to oil compartment terminals according to fig. 14. Each one attached by 1 bolt M12 (w.s.19) lock nut and screening cap, torque 80 Nm. 13 KHW653-3 OLTC R I 2002/2402 4 connecting leads to oil compartment terminals according to fig. 15. Each one attached by 1 bolt M12, lock nut and screening cap, torque 80 Nm. A 1V1 1V2 14 KHW 1088-4 A 3 12 10 KHW 1091-4 15 4 KHW 1093-4 119/06 EN 5 Installation of the on-load tap-changer into the bell-type tank 5 Installation of the on-load tapchanger into the bell-type tank To install the on-load tap-changer into a transformer with bell-type tank the on-load tap-changer must be mounted onto a supporting structure. For this purpose, the OLTC is equipped with a supporting flange at the diverter switch oil compartment (= special design, section 16, dwg. 896 762). Firstly, lift the on-load tap-changer into the supporting structure and connect it to the tap winding. The OLTC must be attached to the supporting structure in such a way that it cannot be displaced. The supporting flange is provided with through-holes which allow it to be fixed to the supporting structure. It is advisable to put spacer blocks temporarily between supporting structure and supporting flange and to remove them before the belltype cover is set up. Once the bell-type cover is attached, lift the on-load tapchanger (with the diverter switch unit removed) by means of the lifting traverse (see section 16, drawing 890 180) and fix it to the bell-type cover together with the top part of the head. To attach the tap-changer head to the bell-type cover, we recommend using a mounting flange as described in section 4.1. 5.1 Assembly of diverter switch oil compartment and tap selector, attachment of tap selector connecting leads The assembly of diverter switch oil compartment and tap selector as well as the connection of tap selector connecting leads has to be carried out according to section 4.3. 119/06 EN 5.2 Installation of the on-load tap changer into the supporting structure Lift the assembled on-load tap-changer, according to section 4.1, into the supporting structure. Make sure that the on-load tap-changer is in proper mounting position and fasten it there safely. NOTE In the supporting structure the on-load tap-changer must be in an exactly vertical position. The on-load tap-changer must be mounted to the supporting structure ensuring that it need not be lifted by more than 5 to 20 mm to reach its final position after the bell-type cover is set up. It is of advantage to install spacer blocks between supporting structure and supporting flange in such a way that the on-load tap-changer is in its final position after the bell-type cover is set up. This measure helps to cut the tap leads to their correct lengths. Remove the spacer blocks after the leads have been connected. To connect the tap winding and the tap-changer take-off terminal follow the instructions according to section 6. CAUTION The connected leads must not exercise any force on the on-load tap-changer. Moreover there must be sufficient clearance so that it is possible to lift the onload tap-changer in its final installation position after the bell-type tank has been mounted. The drying procedure and the transformer ratio test are to be performed in accordance with sections 7 and 8. 11 5 Installation of the on-load tap-changer into the bell-type tank 5.3 Preparations Prior to setting up the bell-type tank the tap-changer head must be removed from the on-load tap-changer. 1. For this purpose, open the tap-changer head cover (24 hexagonal head screws M10, w.s.17, with lock washers). 2. Take care of the cover gasket (round rubber gasket, fig. 16). 3. Remove the position indicator dial (remove the clip from the shaft end, fig. 17). 4. Take note of the red-marked area not covered by the supporting plate of the diverter switch unit (fig. 18). 5. Remove the fixing nuts of the supporting plate (4 nuts M8, w.s.13, lock washers, fig. 19). 6. Withdraw the diverter switch unit carefully from the oil compartment (fig. 20). Keep the diverter switch unit in a vertical position. 17 KHW 1101-4 rh-1101-4-0/1 7. Remove the suction pipe. The pipe connection has to be withdrawn from within the tap-changer head (fig. 21). Take care of O-rings. 8. Unscrew the remaining nuts in the tap-changer head (fig. 22), 17 nuts M8, w.s.13, lock washers. Lift off the tap-changer head from the supporting flange. Take care of the gasket. 18 16 12 KHW 762-4 19 KHW 1103-4 rh-1103-4-0/1 KHW 1105-4 rh-1105-4-0/1 119/06 EN 5 Installation of the on-load tap-changer into the bell-type tank 5.4 Mounting the bell-type transformer cover 1. Before mounting the bell-type transformer cover clean the sealing surface of the oil compartment supporting flange. Place the gasket onto the flange (fig. 23). Withdraw the spacer blocks (see section 5.2). 2. Lift the bell-type cover over the transformer active part and lower it to its final position. 3. Before mounting the tap-changer head clean the sealing surfaces (bottom of tap-changer head, mounting flange). Put an oil-resistant gasket on the mounting flange. 21 20 119/06 EN KHWrh-1109-4-0/1 1109-4 KHW 1106-4 22 rh-1110-4-0/1 KHW 1110-4 23 KHW 1107-4 rh-1107-4-0/1 13 5 Installation of the on-load tap-changer into the bell-type tank 4. Place the tap-changer head on the mounting flange. Check the mounting position of the tap-changer head by means of 2 adjusting bolts (fig. 23) and the marks of the supporting flange and tap-changer head (fig. 24) which allow assembly in the correct position only. Depending on the final height adjustment leave a clearance of 5 to 20 mm between tap-changer head and supporting flange 5. Lift the on-load tap-changer slightly by means of the lifting traverse (see fig. 25 and section 16, drawing 890 180). Make sure that all supporting flange studs easily slide through the fixing holes of the tapchanger head. CAUTION 24 KHW 1100-4 25 KHW 1108-4 Take care not to drop any parts into the diverter switch oil compartment. Otherwise the diverter switch can block and cause severe damage to the on-load tap-changer and transformer. Therefore, make sure that the number of small parts is complete when disassembling and reinstalling. Count them to be sure. 14 119/06 EN 5 Installation of the on-load tap-changer into the bell-type tank 6. Attach the tap-changer head in the red marked area not covered by the supporting plate of the diverter switch (fig. 26, see also section 5.3). Use 17 nuts M8 (wrench size 13, max. torque 14 Nm, lock washers). Attach the tap-changer head to the mounting flange. 7. Remount the suction pipe. Make sure that the Orings are placed properly. The O-rings should slightly be greased before being mounted. 8. Remount the diverter switch unit. Make sure that the diverter switch supporting plate is in its proper position within the tap-changer head (the red marked areas must be left free). Attach the supporting plate by means of 5 nuts M8 (wrench size 13, max. torque 14 Nm, lock washers). 9. Attach the position indication dial: Put the clip onto the shaft end. The dial can be mounted in correct position only by means of its coupling pin (fig. 27). 26 KHW 1110-4 rh-1110-4-0/1 27 KHW 1101-4 rh-1101-4-0/1 28 KHW 1104-4 rh-1104-4-0/1 10.Mount the cover on the tap-changer head. Make sure that the rubber gasket (O-ring) in the cover is in proper position.Fasten the 24 screws M10 (wrench size 17) equally, max. torque 34 Nm (fig. 28). 119/06 EN 15 6 Connection of tap winding and tap-changer take-off leads 6 Connection of tap winding and tapchanger take-off leads The tap winding has to be connected to the on-load tapchanger according to the connection diagram supplied with the particular tap-changer equipment. CAUTION All connections to the on-load tap-changer must be made carefully and locked safely. The tap leads must be assembled in such a way to allow for connecting all leads to the on-load tap-changer without tension. If necessary, lead ends must be shaped in form of expansion loops. Single-phase OLTCs R I 2002 and R I 3000 require the parallel connection of the tap selector terminals with identical terminal numbers in order to avoid overvoltages between parallel contacts. 3 1 4 2 3 1 4 2 3 1 4 2 29 If requested, bridges for the parallel connection of tap selector terminals according to dwg. 896 706 (see appendix) can be supplied. KHW 1096-4 A10 In case of OLTCs R I 2402 and R I 3600 the parallel connection of tap selector terminals by means of parallel bridges is not applicable as the enforced current splitting of tap leads is provided by two or three isolated winding branches on each tap selector terminal. B9 B10 6.1 Tap selector (fig. 29) Fine tap selector terminals with through-hole for M12 screws(fig. 30). If requested, screening caps (MR part number 078 957) will be supplied with the delivery. C9 30 KHW 1090-4 rh-1090-4-0/1 31 KHW 1089-4 rh-1089-4-0/1 Change-over selector terminals Reversing switch: terminals (+) and (–) like the fine tap selector terminals, terminals (0) as terminal lug of the connecting lead (0/K) with through-hole for M12 screws (see fig. 31). Coarse tap selector: terminals (0) and (–) like the fine tap selector terminals, terminals (+) as terminal lug of the cranked connecting lead (+/K) with through-holes for M12 screws (see fig. 31). 16 119/06 EN 6 Connection of tap winding and tap-changer take-off leads 6.2 Parallel bridges for R I 2002 and R I 3000 (fig. 32) Parallel bridges for the fine tap selector and changeover selector according to dwg. 896 706 (see appendix) can be supplied on request. Parallel bridges consist of two identical parts which are joined by a single M12 bolt with lock nut (wrench size 19, max. torque 60 Nm). They are provided with two through-holes to accommodate connection of tap leads. 6.3 Connecting the tap-changer take-off lead The tap-changer take-off lead is to be connected to the bus bar ring of the diverter switch oil compartment (fig. 33). The screw connection must be locked safely (Md = 60 Nm). 33 894 490 0M OLTC type R III 1200 (starpoint connection) One throughhole each for M12 bolts is provided on different points of the bus bar ring displaced by 120° (fig. 34). A OLTC type R I 2002/2402 and R I 3000/3600 Three or four throughholes each for M12 bolts are provided on different points of the bus bar ring displaced by 120° (fig. 35). 1V1 1V2 34 KHW 1094-4 rh-1094-4-0/1 A 3 32 119/06 EN KHW 1099-4 rh-1099-4-0/1 35 4 KHW 1095-4 17 7 8 7 Transformer ratio test Drying procedure and filling with oil Transformer ratio test 8 8.1 We recommend to ratio-meter the transformer with a low AC voltage before drying. To operate the drive shaft in the tap-changer head a short tube of nominal width 25 mm with an insert coupling bolt of 12 mm dia. together with a hand wheel or a hand crank may be used. In case of OLTC set 3 x R I 2002 ... 3600 all three tapchanger heads have to be coupled by the horizontal drive shafts (see section 10). The dielectric properties of the on-load tap-changer can only be guaranteed, if the on-load tap-changer is subjected to a drying treatment according to the following instructions (8.1.1 or 8.1.2). 8.1.1 Vacuum-drying process 8.1.1.1 Drying in the autoclave NOTE When using an ED, 16.5 drive shaft revolutions of the tap-changer drive shaft are required for one tap-change operation. The diverter switch action can be heard distinctly. To operate the change-over selector a higher torque is necessary. The end positions shown on the connection diagram supplied with the delivery must never be overrun. It is therefore necessary to check the operating position through the inspection glass in the tap-changer head cover (fig. 36). Keep the number of tap-change operations to a minimum as long as the on-load tap-changer has not been immersed in oil. After the transformer ratio test the on-load tap-changer has to be set back to the adjustment position in which it was delivered by MR. The position is indicated in the connection diagram delivered with the equipment. Drying procedure and filling with oil Drying procedure When drying the transformer in the autoclave remove the tap-changer cover and store it outside the vacuum autoclave. • Heating up the on-load tap-changer in air of atmospheric pressure with a temperature rise of approx. 10 °C/ hour to a final temperature of at most 110 °C. • Preparatory drying in circulating air at 110 °C max. applied to the onload tap-changer for a duration of 20 hours. • Vacuum drying at a temperature of 110 °C max. applied to the onload tap-changer and a residual pressure of at most 10-3 bar for a duration of at least 50 hours. 8.1.1.2 Drying in the transformer tank NOTE If the transformer is to be vapor-phase dried in its own tank, open the kerosene drain plug (see section 8.1.2). NOTE If the transformer is to be dried in its tank the interior of the diverter switch oil compartment must be connected to vacuum, as the tap-changer head cover remains closed during the entire drying process. The tap-changer head cover is vacuum-proof. To ensure sufficient drying of the interior of the oil compartment and the diverter switch insert, connect a by-pass tube of 25 mm nominal width between the transformer tank and the connecting flange which leads into the oil compartment. b For ease of handling connect the bypass tube either between flanges E2 and Q or flanges E2 and R of the tap-changer head (for position of connecting flanges see section 9 and dwg. 893 899 of appendix). 9 36 18 KHW 764-4 Procedure, temperature, pressure and duration of the drying process are as described in section 8.1.1.1. 119/06 EN 8 Drying procedure and filling with oil 8.1.2 Vapor-phase drying process 8.1.2.1Drying in the autoclave NOTE NOTE Before starting the drying procedure, open the kerosene drain plug (fig. 37) to drain the condensate from the oil compartment. The kerosene drain plug has an hexagonal recess screw (w.s. 8) and is easily accessible between oil compartment bottom and tap selector gear. It can be unscrewed from the outside. The thread of the kerosene drain plug has a plastic coat so that it can only be turned with some force. NOTE Do not continue turning the kerosene drain plug beyond the point where it starts moving tightly. When drying the transformer in its own tank (see section 8.1.2.2) the drain plug, in general, is not accessible from outside and can only be opened from inside the oil compartment. In this case the diverter switch unit must be removed and the kerosene drain plug must be unscrewed with a socket wrench (see section 16, dwg. 890 182). Then reinstall the diverter switch unit. CAUTION The kerosene drain plug must be closed again after the drying process to ensure that no oil from the diverter switch oil compartment can flow into the transformer tank! 8 mm When drying in the autoclave remove the tap-changer head cover first and store it outside the vacuum autoclave. • Heating up by admitting the kerosene vapor at a temperature of about 90°C. Keep this temperature constant for 3 to 4 hours. • Drying by increasing the kerosene vapor temperature by about 10°C per hour to the desired final temperature with not more than 125 °C applied to the on-load tapchanger. The duration of the drying procedure is normally the same as that of the transformer. 8.1.2.2 Drying in the transformer tank If the transformer is to be dried in its own tank, the tapchanger head cover remains closed during the entire drying process. The tap-changer head cover is vacuumproof. To ensure sufficient drying of the interior of the diverter switch oil compartment and of the diverter switch unit connect a common tube of at least 50 mm width between the vapor lead and two connecting flanges of the tap-changer head leading into the oil compartment. Use flanges Q and R for OLTCs type R. (For position of connecting flanges see section 9 and 16, dwg. 893 899). Procedure, temperature and duration of the drying process are described in item 8.1.2.1. 8.1.3 Operating the OLTC CAUTION Do not operate the on-load tap-changer without oil after drying otherwise bearings and gaskets will be damaged. 8 mm Coating 37 119/06 EN KHW 831-4 The on-load tap-changer must not be operated before the diverter switch oil compartment has been filled with oil and the tap selector has been completely immersed in the transformer oil. 19 8 9 Drying procedure and filling with oil Pipe connections 9 8.2 Pipe connections Filling with oil CAUTION The tap-changer oil compartment and the associated oil conservator must only be filled with new mineral insulating oil for transformers according to IEC 296. The use of other oil affects the trouble-free operation of on-load tap-changer and transformer. Place the cover on the tap-changer head. Tighten all 24 cover bolts M10 (wrench size 17, max. torque 34 Nm). The tap-changer head is provided with 3 pipe connections for different purposes. After loosening the thrust collar (4 bolts M10, w.s. 17) these pipe connections can be swivelled (see fig. 38 and appendix, dwg. 893 899). 9.1 Pipe connection R for protective relay RS 2001 The mounting of the protective relay RS 2001 (see section 16, dimension drawing 892 608) is pursuant to our Operating Instructions No. 59. On-load tap-changer and transformer are filled simultaneously with new oil under vacuum. For this purpose use pipe connection S or R. To evacuate, a by-pass tube between connections E2 and Q is to be installed in order to apply vacuum to both diverter switch oil compartment and transformer tank simultaneously. NOTE The relay serial number must be the same as that of the on-load tap-changer. The relay must be mounted in horizontal position and as near to the tap-changer head as possible. The arrow on the relay should point towards the oil conservator when mounted. The pipe to the oil conservator must be installed with an inclination of at least 2%. 9.2 Pipe connections S for suction pipe This is the connection for the feeding pipe of a stationary oil filter. If there is no filter, the pipe connection should be provided with a pipe with a drain cock easily accessible on one side of the transformer tank. R S 9.3 Q E2 Pipe connection Q (special design, required for stationary oil filter only) This is the pipe connection for the return pipe of a stationary oil filter. If no oil filter is provided, a dummy plug is mounted instead of the pipe connection. 9.4 Connection flange E2 In general, this flange is covered by a dummy plug. The flange hole is open to the transformer tank directly beneath the tap-changer head. 38 20 KHW 805-4 If necessary, it may be connected to the gas accumulating tube for the Buchholz relay. 119/06 EN 10 Mounting the motor drive unit, the bevel gear and the drive shaft 10 10.1 Mounting the motor drive unit, the bevel gear and the drive shaft Mounting the motor drive unit (see 10.3 Mounting the drive shaft appendix, dwg. 898 801, 898 802) You may find comprehensive mounting instructions in our Operating Instructions No. 138 for motor drive ED. NOTE Serial number of motor drive unit and on-load tapchanger must be identical (nameplate). Motor drive unit and on-load tap-changer must be in the same operating position. The adjustment position is indicated in the connection diagram supplied with the equipment. The motor drive unit must be mounted at the provided place on the transformer tank in a vertical position and protected against excessive transformer vibrations. The drive shaft must be assembled according to our Operating Instructions No. 42. The drive shaft is the mechanical connection between the motor drive and the tap changer head. The bevel gear diverts the driving force from the vertical to the horizontal direction. Accordingly, the vertical part of the drive shaft is to be mounted between motor drive unit and bevel gear, whereas the horizontal part of the drive shaft is to be mounted between bevel gear and tap-changer head. The drive shaft itself consists of a square tube and is to be connected on both ends to the respective equipment by two coupling brackets and one coupling bolt. NOTE When mounting the drive shaft make sure that the shaft ends to be connected are aligned properly. 10.2 Mounting the bevel gear The bevel gear is to be attached to a support on the transformer cover by means of 2 bolts (through-holes 18 mm dia., see section 16, drawing 892 916). NOTE Make sure that bevel gear serial number and on-load tap-changer serial number are identical. The horizontal drive shaft must be in proper alignment with the trunnion in the tap-changer head. After loosening the thrust collar (6 bolts M8, w.s. 13) the upper gear unit can be swivelled (fig. 39). After adjusting the upper gear unit, the thrust collar must be re-tightened (max. torque 15 Nm). Tab-lock the screws. Square shafts, coupling brackets, coupling bolts, screws, nuts and lock tabs are made of corrosion-proof steel. We recommend, however, to apply the same outside coating here as to the transformer tank. The square shafts and the guard plate for the footstep protection for the horizontal drive shaft at the transformer cover are supplied in oversize (various standard lengths). These parts must be cut to the required size before mounting. Finally equalize the rotation lag between on-load tapchanger and motor drive unit (according to Operating Instructions No. 138 for ED). In case of bevel gears in special design and intermediate bearings of the vertical or horizontal drive shaft above instructions apply analogously. 39 119/06 EN KHW 767-4 21 10 11 Mounting the motor drive unit, the bevel gear and the drive shaft Putting the OLTC into operation in the transformer factory 11 11.1 OLTCs 3 x R I 2002 ... 3600 The following procedure is also recommended for OLTC R III 1200. Due to the special arrangement of the tap-changer phases in three columns, the horizontal drive shaft must be mounted between the three tap-changer heads above the tank cover. Since a swivelling of the upper gear unit will initiate a switching action, make sure that the adjustment position of the diverter switch is regained after the alignment of the gear units. Before applying voltage to the transformer check the mechanical operation of on-load tap-changer and motor drive. For these test operations the on-load tap-changer has to be run through the complete operating cycle. Make sure that in each operating position the indicators of motor drive and on-load tap-changer (tapchanger head) read the same position. CAUTION For this purpose proceed as follows: 1. Check that the operating positions of all columns are identical (tap-changer head, inspection win dow). Each one of the one-phase OLTCs must be in the adjustment position. 2. Turn the upper gear unit of the tap-changer heads into the desired installation position and fix them there (tighten thrust collars and tab-lock the screws). Take note of the arrow on the drive shaft flange below the punched serial number. The direction of the arrow indicates the rotation sense when cranking the motor drive clockwise and must be identical on all gear units. 3. Operate the tap-changer poles separately by one step by rotating the trunnions counter-clockwise until the diverter switch operates once. Check coincidence of operating positions of all tap-changer heads. 4. Mount the horizontal drive shaft between the tapchanger heads. 5. Return the OLTC set, that is all tap-changer poles together, into the adjustment position.The adjustment position is reached by turning the drive shaft in clockwise direction. Check simultaneous operation of all diverter switches. Check coincidence of position of all tapchanger heads and the motor drive unit. 6. Misalignment between on-load tap-changer and motor drive unit exists, if on-load tap-changer and motor drive unit show different operating positions. Misalignment of coupling between on-load tapchanger and motor drive unit leads to severe damage of on-load tap-changer and transformer, if operation is continued. The transformer must not be taken in operation. Make sure that in both end positions the electrical and mechanical limit stops function automatically (see Operating Instructions No. 138 for ED). 11.2 Final oil filling Fill up the on-load tap-changer completely with transformer oil via the oil conservator and evacuate. • Bleed the tap-changer head via the bleeder valve in the head cover (E1): Remove screw cap M30/w.s. 36 (fig. 40), lift valve tappet by means of a screw driver. • Bleed the suction pipe (S) via the bleeder screw of the elbow: cap nut M16 (w.s. 22, max. torque 9 Nm), slotted bleeder screw M6 (max. torque 2 Nm, fig. 41). Mount the vertical drive shaft. CAUTION The supervisory control must be installed according to the connection diagram of the relevant motor drive unit. Incorrect installation will cause damage of both on-load tap-changer and transformer in case of malfunction. 22 Putting the OLTC into operation in the transformer factory Operational tests CAUTION Make sure that the suction pipe has been bled completely. The insulation capability of the on-load tap-changer to ground is otherwise significally impaired. 119/06 EN 11 Putting the OLTC into operation in the transformer factory 11.3 Ground connections Connect the ground screws (2 screws M12 with nuts, w.s. 19, max. torque 60 Nm, fig. 42) of the tap-changer head to the transformer cover. Connect the ground screw (M12, w.s. 19, max. torque 60 Nm) of the motor drive housing to the transformer tank. 11.4 Electrical transformer tests After the afore mentioned steps the necessary electrical acceptance tests of the transformer can be performed. 40 KHW 773-4 41 KHW 811-4 42 119/06 EN KHW 811-4 23 12 13 12 Transport to the operating site Putting into service at the operating site Transport to the operating site If the transformer is to be transported without the motor drive unit, set the motor drive to the adjustment position and uncouple. CAUTION 13 Putting into service at the operating site Before putting the transformer into service, operational tests of on-load tap-changer and motor drive have to be performed according to section 11.1. At the same time check the function of the protective relay. Loop in signaling contact for undershooting the minimum oil level in the on-load tap-changer oil conservator in the on-load tap-changer tripping circuit. Do not operate the motor drive unit while the on-load tap-changer is uncoupled. NOTE To remount the motor drive unit follow the instructions according to section 10.1 and 10.3. NOTE If the transformer is filled with oil but stored or transported without oil conservator, a bypass tube must be installed between the interior of the tap changer and the transformer tank to compensate the static pressure caused by expansion of oil. Install this by-pass tube between pipe connections E2 and Q of the tap-changer head. For short time conditions of 2 to 4 weeks without oil conservator, lower the oil level by approx. 5 litres. If the transformer is to be transported or stored without oil filling, drain the oil of the on-load tap-changer completely. The interior of the on-load tap-changer should be conserved and protected in the same way as the transformer itself (nitrogen-sealing). If a prolonged stand-by period is expected, the heater of the motor drive unit must be connected to the suitable power supply. 24 The protective relay has to be inserted into the tripping circuit of the circuit breakers so that energization of the protective relay switches off the transformer immediately (see Operating Instructions No. 59 for protective relay RS 2001). Make sure that the circuit breakers switching off the transformer operate when the test push button »OFF« is pressed. Be sure that they energize the transformer only after push button »IN SERVICE« of the protective relay has been pressed. CAUTION Check whether all stop valves between oil conservator and tap-changer head are open. After the transformer has been energized, tap-change operations under load can be performed. Gas accumulating under the cover of the tap-changer head will cause minor oil displacement and/or escape via the oil conservator. 119/06 EN Supervision during service, failures 14 14 Supervision during service, failures NOTE Damage to the on-load tap-changer due to not enough oil in the oil conservator of the on-load tapchanger! Actuation of the on-load tap-changer with too little oil in the on-load tap-changer’s oil conservator may cause damage to the on-load tap-changer! Make sure that the contact for signaling the falling below the minimum oil level in the on-load tapchanger’s oil conservator was looped through to the tripping circuit of the circuit-breaker and that the circuit-breaker will immediately de-energize the transformer when the oil has fallen below this minimum oil level in the oil conservator. Maschinenfabrik Reinhausen GmbH Technical Service Postfach 12 03 60 D-93025 Regensburg Phone: (+49) 9 41 / 40 90-0 Telefax: (+49) 9 41 / 40 90-5 01 Telex: 65881 It is only necessary to inspect the tap-changer head, the protective relay and the motor drive unit occasionally. Pay special attention to: • oil tightness of sealings of the tap-changer head, the protective relay and the pipe connections, • sealings at the motor drive housing, • proper function of the electrical space heater inside the motor drive unit, • the condition of the control devices in the motor drive unit. WARNING If the protective relay operates, do not reset until the on-load tap-changer and the transformer have been checked. For this purpose also withdraw the diverter switch unit and check it according to our Inspection Instructions. Proceed in detail according to our Operating Instructions No. 59 for the protective relay RS 2001. Before returning to energized operation, make sure that the cause of the trouble has been corrected and that the on-load tap-changer and the transformer are free of damage. Never reconnect the transformer without prior checking. Continued operation of the on-load tap changer can result in severe damage of on-load tapchanger and transformer. In case of serious trouble with on-load tap-changer or motor drive – provided that the repair cannot easily be done at site and in case of a tripping of the protective relay please contact the authorized MR representative, the transformer manufacturer or directly 119/06 EN 25 15 Inspections 15 Inspections NOTE The tap-changing equipment must be inspected at regular intervals to maintain a high level of operating reliability. In general, the inspection can be carried out by qualified and MR-trained personnel within one day, provided it is well prepared and organized. We strongly recommend to have inspections performed by our Technical Service. This guarantees a professional performance including all the latest updating measures. Inquire for spare parts when preparing an inspection which will not be carried out by MR personnel (please indicate OLTC number and number of operations). The number of tap-change operations determining the inspection intervals indicated in table II and table III are figures based on experience with oil qualities normally used. The tap selector of the on-load tap-changer is generally maintenance-free. In special cases, however, if OLTCs are used in industrial transformers where high operating numbers are to be expected, our technical service department must be contacted after about 1,000,000 operations. The diverter switch insert of the OLTC is to be replaced after 800,000 operations. If the number of operations per year is 15,000 or higher, the use of our oil filter plant type OF100 with paper filter insert (see Operating Instructions No. 18) is recommended. The use of our oil filter plant type OF100 with combination filter insert is obligatory for OLTC type R with insulation to ground Um < 245 kV. Filtering of switching oil allows to extend the inspection intervals. The user should regularly test the transformer insulating oil according to the relevant standards. If inspection has not been performed by MR-personnel, please give us your report for data collecting purposes. 26 119/06 EN 15 Inspections CAUTION Inspections of the tap-changer equipment are obligatory. Disregarding the inspection intervals endangers the trouble-free operation of on-load tap- changer and transformer. Standard values for oil testing according to CIGRE report 12-13 (1982) applying to transformer oil at service temperature: On-load tap-changer Water content*) Dielectric strengh**) Neutral-end tap-changers < 40 ppm > 30 kV/2,5 mm Single-pole tap-changers < 30 ppm > 40 kV/2,5 mm *) measured according to Karl-Fischer method based on IEC Publication 814 (1985) **) measured according to DIN 57370 Teil1/VDE 0370 Teil 1/12.78 Teil 1 Table I Guide values for monitoring the tap-changer oil On-load tap-changer Transformer rated current Number of tap-change operations without MR oil filter with oil filter R III 1200 up to 600 A up to 1200 A 80 000 60 000 100 000 100 000 R I 1201 up to 600 A up to 1200 A 80 000 60 000 100 000 100 000 R I 2002 up to 2000 A 40 000 80 000 R I 2402 up to 2400 A 40 000 80 000 R I 3000 up to 3000 A 40 000 80 000 R I 3600 up to 3600A 40 000 80 000 Table II Inspection intervals for – OLTC type R in star-point connection (Y) – One-phase OLTC with Um < 245 kV used in autotransformers or for regulation at the line end of winding of the transformer. First inspection and further inspections: after 7 years or the number of operations indicated in Table II, depending on what is reached first. 119/06 EN 27 15 Inspections 16 Appendix On-load tap-changer Transformer rarted current Number of tap-change operations without MR oil filter with MR oil filter R I 1201 up to 600 A up to 1200 A 40 000 30 000 50 000 50 000 R I 2002 up to 2000 A 20 000 40 000 R I 2402 up to 2400 A 20 000 40 000 R I 3000 up to 3000 A 20 000 40 000 R I 3600 up to 3600 A 20 000 40 000 Table III Inspection intervals for one-phase OLTCs type R with Um ³ 245 kV and used in autotransformers or for the regulation at line end of winding of the transformer. First inspection: after 2 years or 20,000 operations, depending on what is reached first. Next inspections: without MR filter plant after every 4 years, with MR filter plant (combination filter) after every 6 years or the number of operations indicated in table III – whatever is reached first. 16 APPENDIX Installation drawing _____________________________________________________________________ 896 705 OLTCs R I 2002 / R I 3000, bridges for parallel connection of tap selector terminals ___________________ 896 706 Tap-changer head ______________________________________________________________________ 893 899 Drilling template for tap-changer head ______________________________________________________ 890 183 Supporting flange for the installation into bell-type tank _________________________________________ 896 762 Lifting traverse _________________________________________________________________________ 890 180 Socket wrench for kerosene drain plug ______________________________________________________ 890 182 Protective relay RS 2001, dimension drawing _________________________________________________ 899 084 Motor drive unit ED-S, dimension drawing ___________________________________________________ 898 801 Motor drive unit ED-L, dimension drawing ____________________________________________________ 898 802 Bevel gear CD 6400, dimension drawing ____________________________________________________ 892 916 28 119/06 EN 16 Appendix max. withdrawal height 1750 mm Flat surface Protective relay Take-off terminal 11 12 13 14 15 16 17 Mounting flange on transformer cover Fixing bolt M12 Gasket for tap-changer head Position indicator Inspection window Drive shaft for position indicator Through-hole 15 mm dia. 21 22 23 24 25 26 27 28 29a 29b 29c Tap-changer head Bolt for tap-changer head cover Gasket for tap-changer head cover Tap changer head cover Centric gear unit with drive shaft 25a Pipe connection R for protective relay Pipe connection S for suction pipe Pipe connection Q for return pipe (with oil filter only) Bleeder valve of tap-changer head cover Bleeding facility for transformer oil Bleeder screw for suction pipe 31 32 33 34 35 36 Diverter switch oil compartment Bottom of oil compartment Grading ring (with Um = 170/245 kV) Terminal of diverter switch oil compartment Tap-changer take-off terminal (with R III 1200 neutral) Suction pipe 41 42 43 44 45 48 48a Suspension of tap selector Tap selector gear Fine tap selector Change-over selector Tap selector terminals. see corresponding dimension drawing Change-over selector terminals. see corresponding dimension drawing Connecting lead for tap selector Holding strip for 48 51 52 53 54 55 56 Diverter switch unit Supporting cylinder Gear plate Fixing bolt Lifting Lug Transition resistors 46 See also variants of tap selector bottom 896 702 provide sufficient clearance! Transformer tank bottom Tap selector drive side On-load tap-changer type R Installation drawing 119/06 EN 896 705:5E 29 16 Appendix On-load tap-changer type R Bridges for parallel connection of tap selector terminals for OLTCs R I 2002, R I 3000 (not applicable in case of enforced current splitting) 30 896 706:5E 119/06 EN 16 Appendix width of gasket Detail at A Connection flange for Q, S, R 16 Thickness Tap selector drive side E1 = Bleeding facility for tap- changer head E2 = Bleeding facility for space under the head outside the tap-changer oil compartment (same pipe connection as R, S, Q or bleeder screw can be used) Q = Connection for oil return pipe (only for oil filter) O-Ring 44.2 - 5.7 S = Connection for suction pipe Connections orientable R = Connection for protective relay (exchangeble with connection Q) through 360° = Earth connection M12 On-load tap-changers type MS, M, T, R Tap-changer head 119/06 EN 893 899:9E 31 16 Appendix 3 thick Marks to be pounded On-load tap-changers type MS, M, T, R Drilling template 32 890 183:6E 119/06 EN 16 Appendix Lifting device O-Ring 44.2 - 5.7 Suction pipe Drilling hole represented in the sectional plane Transformer cover Gasket Level traverse Grading ring with Um170/245/300 kV only Supporting flange Level traverse Tap selector drive side Z = Guiding pin On-load tap-changer type R Special design for installation into bell-type tank 119/06 EN 896 762:6E 33 16 Appendix Sheet steel St 37-2 DIN 17 100 On-load tap-changer type R Lifting traverse 34 890 180:3E 119/06 EN 16 Appendix Socket wrench Item-No. 014 820 L = 1350 mm Item-No. 017 660 L = 1860 mm To be used for OLTC Type M (except M Δ) Typ MS M III 350/600 Δ Type T, R, G On-load tap-changer type MS, M, T, R Socket wrench for kerosene draining screw 119/06 EN 890 182:7E 35 16 Appendix Cable gland PG 16 Inspection window Identification label Gasket Gasket Test push buttons IN SERVICE OFF (reset) (test tripping) Metal - dummy plug PG 16 The arrow must always point towards the oil pipe leading to the oil conservator of the transformer. Plan view of test push buttons (cover removed) Key of variants Contact positions 1) Reed contact 1 0.65 1.2 3.0 4.8 - NO - NO - NO - NO A 2 0.65 1.2 3.0 4.8 - NC - NC - NC - NC B 3 0.65 1.2 3.0 4.8 - CO - CO - CO - CO C 4 0.65 1.2 3.0 4.8 - 2NO - 2NO - 2NO - 2NO 2A 5 0.65 1.2 3.0 4.8 - 2NC - 2NC - 2NC - 2NC 2B 6 0.65 1.2 3.0 4.8 - NO + NC - NO + NC - NO + NC - NO + NC Arrangement of terminals In service Design Off Standard design Relay designation1) Special design against surcharge Variant 1A &1B NO - normally open, NC - normally closed, CO - change-over contact The protective relay is to be connected in such a way that if it is energized, the power transformer is switched off immediately by the corresponding circuit breakers. Protective Relay RS 2001 (STANDARD) 36 899 084:0E 119/06 EN 16 Appendix Vertical guard plate with spacing ring Handcrank * for design with intermediate bearing 3 dummy plates for packing glands special design with OLTC monitoring required Wall of transformer tank Shm i Attachment of protective housing ca. 690 if opened 130° ca. 864 if opened 180° Aperture of fixing holes on protective housing (rear view) Aperture in protective housing for cables (underside view) Motor Drive ED-S Protective Housing 119/06 EN The cover can be opened to the left or to the right depending on the arrangement of the hinge pins. 898 801:2E 37 16 Appendix Vertical guard plate with spacing ring Hand crank * for design with intermediate bearing 3 dummy plates for packing glands special design with OLTC monitoring required Wall of transformer tank Shm i Attachment of protective housing The cover can be opened to the left or to the right depending on the arrangeca. 690 if opened 130° ment of the hinge pins. ca. 864 if opened 180° Aperture of fixing holes on protective housing (rear view) Aperture in protective housing for cables (underside view) Motor Drive ED-L Protective Housing 38 898 802:2E 119/06 EN Bevel gear CD 6400 Dimension drawing 119/06 EN e2 = 215 for design with ball joint e1 = 205 for standard design 16 Appendix 892 916:6E 39 www.reinhausen.com © Maschinenfabrik Reinhausen GmbH Postfach 12 03 60 D-93025 Regensburg Telefon: (+49) 9 41 / 40 90-0 Telefax: (+49) 9 41 / 40 90-111 Telex: 65881 BA 119/06 EN • 02/11 • F0002203 • Printed in Germany