D7038 Remote Notification Appliance Circuit (NAC) Power Supply

advertisement
Fire Alarm Systems | D7038 Remote Notification Appliance Circuit (NAC) Power Supply
D7038 Remote Notification Appliance
Circuit (NAC) Power Supply
▶ 6 A of power
▶ Fully supervised outputs
▶ Can be configured for NAC output or constant auxiliary
power
▶ Regulated 24 V ouput (nominal) with over-current
protection
▶ Built-in NAC pattern
▶ Four Class B, Style Y circuits
▶ Form C trouble relay
▶ Supervised AC, battery, and circuit expander
▶ Ground fault indication
▶ Charger control monitor
Use the D7038 to add four additional notification appliance
circuits (NFPA 72, Class B, Style Y) to a fire alarm control
panel (FACP) or as a power supply for fire-protective
signaling systems. This regulated power supply provides up
to 6 A of power that is used to recharge batteries and
operate both continuous and intermittent alarm loads. This
6 A of power can be distributed through the four Class B,
Style Y circuits that are part of the D7038. The D7038 is UL
Listed for use in commercial fire alarm applications.
Functions
Compatible Control Panel Connections
The D7038 is compatible with any UL Listed control panel
that uses reverse polarity supervised notification outputs
with 12 VDC or 24 VDC regulated outputs. It is also
compatible with the following Bosch Control Panels:
•
•
•
D7022 Two-zone Conventional FACP
D7024 Four-zone Addressable FACP
D8024 and D10024 Analog FACPs
You can connect up to two D7038s to a D7024 Control
Panel. The D7024 can individually control each of the four
NFPA72 Class B, Style Y NAC outputs for each D7038. The
D7024 can also supervise each D7038's power supply.
Status Displays
There are seven local status display LEDs on the D7038's
printed circuit board that monitor the following conditions:
High Voltage, AC OK, Low Battery, Loop Trouble, Groun
Fault, Output Active and NAC Short.
DIP Switch Settings
If connected to the D7024's option bus, the D7038 needs
its own option bus address. Set this address through the
DIP switches.
Determine which inputs control which outputs through the
NAC Input Variable option. Set Input 1 to control all four
NAC outputs or only NAC Outputs 1 and 2. If you choose the
latter, Input 2 controls NAC Outputs 3 and 4.
If the AC voltage falls below 102 V for over 5 sec, a trouble
condition is registered, but not sent to the control panel.
The DIP switch setting for AC Failure Time Delay determines
the time delay of 1, 6, 12, or 24 hrs before sending an AC
failure. The default value is 6 hrs.
For the D7022 conventional panel and the D8024 and
D10024 analog panels, the D7038 connects through a NAC
circuit. No serial bus connection is necessary.
www.boschsecurity.com
2 | D7038 Remote Notification Appliance Circuit (NAC) Power Supply
Technical Specifications
Certifications and Approvals
Region
Certification
USA
UL
Environmental Considerations
UOXX: Control Unit Accessories, System
(UL864, 9th edition), UTOU: Control Units
and Accessories - Household System Type
(UL985), UTRZ: Power Supply Units
(UL1481)
FM
Temperature (operating):
+32°F to +120°F (0°C to +49°C)
Inputs (NAC)
Response Time (input to out- 50 ms maximum
put):
Voltage (input):
9 VDC to 30 VDC
CSFM
7165-1615: 147
Mechanical Properties
NYC-MEA
12-92-E, Vol. 14 12-92-E, Vol. 14
Color:
Red
26-02-E, Vol. III 26-02-E, Vol. III
Dimensions (H x W x D)
without door:
20.4 in. x 14.8 in. x 4.1 in.
(52 cm x 38 cm x 10.4 cm)
Material:
cold-rolled steel
Base: 18 gauge (1.2 mm)
Cover: 19 gauge (1.1 mm)
Installation/Configuration Notes
Compatible Products
The following products are compatible with the D7038
Remote NAC Power Supply:
Category
Product ID
Product Description
Batteries
D126
12 V, 7 Ah battery
D1218
12 V, 18 Ah battery
D1224
12 V, 24 Ah battery
D1238
Outputs
Auxiliary
Current (output):
850 mA maximum
Voltage (output):
24.1 VDC or 27.4 VDC
NAC
Output per circuit:
2.5 A maximum
12 V, 38 Ah battery
Output (total):
6A
Class B to Class A NAC converter
Voltage (output) at
+77°F (+25°C):
AC operation: 27.4 ± 0.1 VDC DC operation: 24.1 ± 0.6 VDC
Voltage (standby):
-5.0 VDC
Modules
D7015
Four-wire Smoke
Detectors
Refer to Technogram (P/N: 38779)
NAC Devices
Refer to Technogram (P/N: 38779)
Trouble Relay
Magnetic Door
Holders
Refer to Technogram (P/N: 38779)
Contact Type:
Form C
Rating (contact):
1.5 A at 32 VDC
Wiring
All wiring is connected to the power supply board by screw
terminals that can accept up to 12 AWG (2.3 mm) wire.
Parts Included
Quant.
Component
1
D7038 board
1
AE4 Large Enclosure (red)
4
2.21 kΩ end- of-line (EOL) resistors (P/N: 25899D)
1
Hardware pack
Power Requirements
Current (total output):
6 A maximum
Power (primary input):
120 VAC, 2.5 A maximum, 60 Hz
Voltage (battery):
24 VDC nominal
Voltage (ripple)
250 mVpp maximum
Ordering Information
D7038 Remote Notification Appliance
Circuit (NAC) Power Supply
Adds four additional notification appliance circuits (NFPA 72, Class B, Style Y) to a fire alarm
control panel
D7038
Accessories
KEY‑625 Replacement Key
Replacement key
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1245646475 | Cur: en-US, V5, 4 Jul 2010
Asia-Pacific:
Represented by
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
apr.securitysystems@bosch.com
www.boschsecurity.com
KEY-625