General Transformers

advertisement
Dry Type 600 Volts and Below
Single Phase
Class 7400
Single Phase – General Purpose Transformers
Single Phase – Export Model Transformers
General purpose standard transformers are intended for power, heating,
lighting, and light-duty control applications. See page 12-4 or contact
your nearest Square D/Schneider Electric sales office for voltages not
listed below.
These general-purpose transformers are designed to accommodate
voltage systems worldwide.
kVA
Catalog
Number q
Price
Full Capacity
Taps
Degree C
Weightk Enclosure
Temp. Rise (Pounds)
ck
Single Phase – 240 X 480 V Primary 120/240 V Secondary 60 Hz
UL Listed through 167 kVA
cUL Listed through 10 kVA
.050
.100
.150
.250
.500
50SV1A
100SV1A
150SV1A
250SV1B
500SV1B
.750
1
1.5
2
3
750SV1F
1S1F
1.5S1F
2S1F
3S1F
$
87.
102.
121.
129.
184.
None
None
None
None
None
55
55
55
80
80
4.2
4.5
6.2
10.5
13.8
1A
2A
3A
4A
5A
219.
287.
345.
427.
545.
None
None
None
None
None
115
115
115
115
115
15.5
21.2
30.1
39.1
60
6A
7A
8A
9A
10A
Export model transformers 10 kVA and smaller, certified by TUV (file no.
E9571881.01) to meet EN60-742, are CE marked in addition to being
UL and cUL Listed.
For CE marked transformers in other ratings, see pages 12-12
through 12-16 in this Digest. Or contact your nearest
Square D/Schneider Electric sales office for CE marked
transformers up to 300 kVA, single and three phase.
See page 12-9 for optional Fingersafe terminal block cover kit.
Single Phase – 190/200/208/220 X 380/400/416/440
5
7.5
10
15
15
25
5S1F
7S1F
10S1F
15S1F
15S1H
25S3H
741.
1042.
1291.
2586.
1731.
2253.
None
None
None
None
None
6–2.5%2+4–a
115
115
115
115
150
150
115
135
165
225
200
245
13B
13B
13B
15B
17D
17D
kVA
37.5
50
75
100
167
37S3H
50S3H
75S3H
100S3H
167S3H
3003.
3652.
4953.
6403.
9406.
6–2.5%2+4–a
6–2.5%2+4–a
6–2.5%2+4–a
6–2.5%2+4–a
6–2.5%2+4–a
150
150
150
150
150
325
350
450
640
975
18D
18D
21D
22D
24D
7.5
10
15
25
200
250
200S3H
250S3H
14814.
19448.
6–2.5%2+4–a
6–2.5%2+4–a
150
150
1220
1535
25D
25D
Single Phase – 480 V Primary 120/240 V Secondary 60 Hz
UL/cUL Listed through 25 kVA
3
5
7.5
10
15
15
25
3S40F
5S40F
7S40F
2–5%FCBN
2–5%FCBN
2–5%FCBN
115
115
115
60
115
135
10A
13B
13B
1291.
2069.
1731.
2646.
2–5%FCBN
2–5%FCBN
2–5%FCBN
2–5%FCBN
115
115
150
115
165
225
200
300
13B
15B
17D
15B
Single Phase – 600 V Primary 120/240 V Secondary 60 Hz
UL Listed through 167 kVA
cUL Listed through 10 kVA
.050
.100
.150
.250
.500
50SV51A
100SV51A
150SV51A
250SV51B
500SV51B
.750
1
1.5
2
750SV51F
1S51F
1.5S51F
2S51F
3
5
7.5
$
Catalog
Numberq
1t
2
3
5
1S67F
2S67F
3S67F
5S67F
7S67F
10S67F
15S67H
25S67H
Price
Full Capacity
Taps
Deg. C.
Weight k Enclosure
Temp. Rise (Pounds)
ck
$ 562.
817.
1090.
1216.
None
None
None
None
115
115
115
115
21.2
39.1
55.2
135
7A
9A
10A
13B
1578.
1907.
2995.
4138.
None
None
None
None
115
115
150
150
165
165
225
260
13B
13B
17D
17D
LUGS: Furnished by customer
t 0.750 kVA EN rating per EN 60-742
1-10 kVA CE marked per EN 60-742
Single Phase – Buck and Boost Transformers
$ 545.
741.
1042.
10S40F
15S40F
15S40Hj
25S40F
V Primary,
110/220 V Secondary 50/60 Hz
UL Listed through 25 kVA
CE marked/cUL Listed through 10 kVA
87.
102.
125.
138.
194.
None
None
None
None
None
55
55
55
80
80
4.2
4.5
6.2
10.5
13.8
1A
2A
3A
4A
5A
231.
302.
361.
448.
None
None
None
None
115
115
115
115
15.5
21.2
30.1
39.1
6A
7A
8A
9A
3S4F
5S4F
7S4F
590.
798.
1118.
2–5%FCBN
2–5%FCBN
2–5%FCBN
115
115
115
60
115
135
10A
13B
13B
10
15
25
10S4F
15S5H
25S5H
1391.
1870.
2450.
2–5%FCBN
4–2.5%FCBN
4–2.5%FCBN
115
150
150
165
200
245
13B
17D
17D
37.5
50
75
100
37S5H
50S5H
75S5H
100S5H
3252.
3953.
5353.
6955.
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
150
150
150
150
325
350
450
640
18D
18D
21D
22D
167
167S5H
10806.
4–2.5%FCBN
150
975
24D
FCBN: full capacity taps below normal
LUGS: furnished by customer
Buck and Boost transformers are isolating transformers that have
120 X 240 volt primaries and either 12/24 or 16/32 volt secondaries.
When used as isolating transformers they carry the full load stated on
the nameplate. By special interconnection of the windings, an
autotransformer is obtained. When used this way for bucking or boosting
small voltage changes, the kVA load they carry is large compared to
their physical size.
See bulletin 7414PD9301 (D-FAX 2543) for application tables and
wiring diagrams for buck and boost transformers.
NOTE: When used to supply a 3-phase, 4-wire load, the source must be
3-phase, 4-wire.
Single Phase – 120 x 240 V Primary 60 Hz
UL/cUL Listed. Copper Windings.
Catalog Numbersq
kVA
12/24 V
Secondary
16/32 V
Secondary
Price
Degree C
Temp.
Rise
.05
.10
.15
.25
.50
.75
1.0
1.5
2.0
3.0
50SV43A
100SV43A
150SV43A
250SV43B
500SV43B
750SV43F
1S43F
1.5S43F
2S43F
3S43F
50SV46A
100SV46A
150SV46A
250SV46B
500SV46B
750SV46F
1S46F
1.5S46F
2S46F
3S46F
$ 98.
117.
131.
156.
200.
263.
322.
395.
510.
705.
55
55
55
80
80
115
115
115
115
115
Weight k
(Pounds)
Enclosure
ck
4.2
4.5
6.2
10.5
13.8
15.5
21.2
30.1
39.1
60
1A
2A
3A
4A
5A
6A
7A
8A
9A
f
12
TRANSFORMERS
f Dimensions: 14.5" high x 8.6" wide x 6.5" deep.
k Not for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
q Catalog Numbers shown in bold type are available from Distribution Center.
a When 240 volt connection is used, there will be 3–5% taps, 1 above and 2 below 240 volts.
c For enclosure styles, see dimensions table, page 12-8.
FCBN: full capacity taps below normal
LUGS: furnished by customer
j 15S40H is UL Listed only.
k Not for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
For an index of all product information available via D-FAX™ for low voltage transformers, request D-FAX TM number 09.
For additional information, reference Selection Guide No. 7400CT9601 or D-FAX TM number 1673 (pages 1-20) and 2284 (pages 21-41).
12-2
© 2000 Square D
All Rights Reserved
PE2
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type 600 Volts and Below
Three Phase
Class 7400
kVA
kVA
Catalog
Numberq
Price
Full Capacity
Taps
Degree C
Weight
Enclosure
Temp. Rise (Pounds)k
ck
Three Phase – 480 V Delta Primary 208Y/120 V Secondary 60 Hz
UL/cUL Listed, Copper Wound.
3
6
9
15
15
30
3T2F
6T2F
9T2F
15T2F
15T68F
30T2F
$ 960. 2–5%FCBN
1100. 2–5%FCBN
1470. 2–5%FCBN
2211. 2–5%FCBN
2211. 4–2.5%2+2–
4065. 2–5%FCBN
115
115
115
120
145
235
12C
12C
14C
115
115
115
300
300
660
14C
14C
16C
UL Listed
Price
Full Capacity
Taps
Degree C
Weight Enclosure
Temp. Rise (Pounds)k
ck
Three Phase – 480 V Delta Primary 380Y/220 V Secondary 60 Hz
UL Listed
15
30
45
15T96H
30T96H
45T96H
2602. 4–2.5%2+2–
3202. 4–2.5%2+2–
4002. 4–2.5%2+2–
150
150
150
200
250
340
17D
17D
18D
75
112.5
150
75T96H
112T96H
150T96H
5953. 4–2.5%2+2–
7953. 4–2.5%2+2–
9775. 4–2.5%2+2–
150
150
150
500
750
800
19D
21D
22D
225
300
500
225T96H
300T96H
500T96H
13438. 4–2.5%2+2–
17961. 4–2.5%2+2–
27316. 4–2.5%2+2–
150
150
150
1025
1450
2100
24D
25D
30D
Three Phase – 600 V Delta Primary 208Y/120 V Secondary 60 Hz
UL/cUL Listed, Copper Wound.
6
9
15
Three Phase – 480 V Delta Primary 208Y/120 V Secondary 60 Hz
Catalog
Numberq
6T7F
9T7F
15T7F
$ 1169. 2–5%FCBN
1551. 2–5%FCBN
2321. 2–5%FCBN
115
115
115
145
235
300
15
15T3H
2001. 6–2.5%2+4–
150
200
17D
Three Phase – 600 V Delta Primary 208Y/120 V Secondary 60 Hz
30
45
75
30T3H
45T3H
75T3H
2952. 6–2.5%2+4–
3553. 6–2.5%2+4–
5353. 6–2.5%2+4–
150
150
150
250
340
500
17D
18D
19D
UL Listed
112.5
150
225
300
112T3H
150T3H
225T3H
300T3H
7124.
9306.
12406.
15910.
6–2.5%2+4–
6–2.5%2+4–
6–2.5%2+4–
6–2.5%2+4–
150
150
150
150
750
800
1025
1450
21D
22D
24D
25D
500T68H
750T90H
1000T77H
25215. 4–2.5%2+2–
40973. 4–3.5%2+2–
49428. 2–5%1+1–
150
150
150
2100
3950
6300
30D
31D
33F
500
750
1000
Three Phase – 208 V Delta Primary 480Y/277 V Secondary 60 Hz
UL Listed
15
30
45
15T64H
30T64H
45T64H
2602. 2–5%FCBN
3202. 2–5%FCBN
4002. 2–5%FCBN
150
150
150
200
250
340
17D
17D
18D
75
112.5
150
75T64H
112T64H
150T64H
5953. 2–5%FCBN
7953. 2–5%FCBN
9775. 2–5%FCBN
150
150
150
500
750
800
19D
21D
22D
225
300
500
225T64H
300T64H
500T64H
13438. 2–5%FCBN
17961. 2–5%FCBN
27316. 2–5%FCBN
150
150
150
1025
1450
2100
24D
25D
30D
Three Phase – 480 V Delta Primary 240 V Delta Secondary 60 Hz
UL/cUL Listed, Copper Wound.
6
9
15
6T5F
9T75F
15T75F
$ 1100. 2–5%FCBN
1470. 4–2.5%FCBN
2211. 4–2.5%FCBN
115
115
115
145
235
300
12C
14C
14C
Three Phase – 480 V Delta Primary 240 V Delta Secondary 60 Hz
UL Listed
15
30
45
75
15T6H
30T6H
45T6H
75T6H
2001.
2952.
3553.
5353.
6–2.5%2+4–
6–2.5%2+4–
6–2.5%2+4–
6–2.5%2+4–
150
150
150
150
200
250
340
500
17D
17D
18D
19D
112.5
150
225
300
112T6H
150T6H
225T6H
300T6H
7124.
9306.
12406.
15910.
6–2.5%2+4–
6–2.5%2+4–
6–2.5%2+4–
6–2.5%2+4–
150
150
150
150
750
800
1025
1450
21D
22D
24D
25D
500T63H
750T91H
1000T78H
25014. 4–2.5%2+2–
40774. 4–3.5%2+2–
49027. 2–5%1+1–
150
150
150
2100
3950
6000
30D
31D
33F
500
750
1000
Three Phase – 480 V Delta Primary 240 V Delta Secondary
with 120 V Center Tapa – See Note #1, 60 Hz
UL Listed
30
45
75
30T6HCT
45T6HCT
75T6HCT
112.5
150
225
300
112T6HCT
150T6HCT
225T6HCT
300T6HCT
7754.
9727.
12868.
17909.
500T63HCT
750T91HCT
1000T78HCT
500
750
1000
$ 3103. 6–2.5%2+4–
3703. 6–2.5%2+4–
5504. 6–2.5%2+4–
75
112.5
150
225
300
500
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
150
150
150
150
200
250
340
500
17D
17D
18D
19D
112T8H
150T8H
225T8H
300T8H
7953.
9775.
13438.
17961.
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
150
150
150
150
750
800
1025
1450
21D
22D
24D
25D
500T8H
750T8H
1000T88H
27316. 4–2.5%FCBN
41584. 4–2.5%FCBN
50030. 4–3.5%FCBN
150
150
150
2100
3950
6600
30D
31D
33F
Three Phase – 240 V Delta Primary 208Y/120 V Secondary 60 Hz
UL Listed
15
30
45
15T12H
30T12H
45T12H
2602. 4–2.5%2+2–
3202. 4–2.5%2+2–
4002. 4–2.5%2+2–
150
150
150
200
250
340
17D
17D
18D
75
112.5
150
75T12H
112T12H
150T12H
5953. 4–2.5%2+2–
7953. 4–2.5%2+2–
9775. 4–2.5%2+2–
150
150
150
500
750
800
19D
21D
22D
225
300
500
225T11H
300T11H
500T11H
150
150
150
1025
1450
2100
24D
25D
30D
13438. 2–5%FCBN
17961. 2–5%FCBN
27316. 2–5%FCBN
Three Phase – Copper Wound Transformers
All Square D transformers are available with optional copper windings.
Contact your nearest Square D/Schneider Electric sales office for
voltage or kVA not listed below.
kVA
Catalog
Numberq
Price
Full Capacity
Taps
Deg. C.
Weight Enclosure
Temp. Rise (Pounds)k
ck
Three Phase – 480 V Delta Primary 208Y/120 V Secondary 60 Hz
UL/cUL Listed. Copper Windings.
3
6
9
3T2F
6T2F
9T2F
$ 960. 2–5%FCBN
1100. 2–5%FCBN
1470. 2–5%FCBN
115
115
115
120
145
235
12C
12C
14C
Three Phase – 480 V Delta Primary 208Y/120 V Secondary 60 Hz
UL Listed. Copper Windings.
15
30
45
75
15T3HCU
30T3HCU
45T3HCU
75T3HCU
$ 3252.
4002.
5001.
7443.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
150
150
150
150
240
300
385
600
17D
17D
18D
19D
112.5
150
225
300
112T3HCU
150T3HCU
225T3HCU
300T3HCU
9942.
12220.
16798.
22452.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
150
150
150
150
780
1100
1300
1800
21D
22D
24D
25D
500
750
500T68HCU
750T90HCU
34144. 4–2.5%2 + 2–
55324. 4–3.5%2 +2–
150
150
2550
4800
30D
31D
17D
18D
19D
6–2.5%2+4–
6–2.5%2+4–
6–2.5%2+4–
6–2.5%2+4–
150
150
150
150
750
800
1025
1450
21D
22D
24D
25D
25582. 4–2.5%2+2–
40733. 4–3.5%2+2–
49527. 2–3.5%1+1–
150
150
150
2100
3950
6300
30D
31D
33F
Three Phase – 480 V Delta Primary 240 V Delta Secondary 60 Hz
Three Phase – 480 V Delta Primary 240 V Delta Secondary 60 Hz
$ 2602. 4–2.5%2+2–
3103. 4–2.5%2+2–
3721. 4–2.5%2+2–
150
150
150
200
250
340
17D
17D
18D
75T76H
112T76H
150T76H
5603. 4–2.5%2+2–
7504. 4–2.5%2+2–
9705. 4–2.5%2+2–
150
150
150
500
750
800
19D
21D
22D
225T76H
300T76H
500T76H
13107. 4–2.5%2+2–
15972. 4–2.5%2+2–
27014. 4–2.5%2+2–
150
150
150
1025
1450
2100
24D
25D
30D
a CAUTION: Single Phase load limited to maximum 5% of rated kVA. Contact your
nearest Square D/Schneider Electric sales office for other loading.
Note #1: Connect “B” Ø to X3 to meet NEC 384-3.
c For enclosure styles, see Dimensions Table, page 12-8.
FCBN = Full capacity below normal
Lugs: Furnished by customer.
Taps on transformers 225 kVA and larger may vary in 3% to 5% steps to obtain best
design.
3/00
112.5
150
225
300
500
750
1000
2602.
3103.
3703.
5504.
250
340
500
UL Listed
15T76H
30T76H
45T76H
15T8H
30T8H
45T8H
75T8H
150
150
150
Three Phase – 480 V Delta Primary 480Y/277 V Secondary 60 Hz
15
30
45
15
30
45
75
PE2
12C
14C
14C
UL/cUL Listed. Copper Windings.
6
9
15
6T5F
9T75F
15T75F
$ 1100. 2–5%FCBN
1470. 4–2.5%FCBN
2211. 4–2.5%FCBN
115
115
115
145
235
300
12C
14C
14C
UL Listed. Copper Windings.
15
30
45
75
15T6HCU
30T6HCU
45T6HCU
75T6HCU
$ 3252.
4002.
5001.
7443.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
150
150
150
150
240
300
385
600
17D
17D
18D
19D
112.5
150
225
300
112T6HCU
150T6HCU
225T6HCU
300T6HCU
9942.
12220.
16798.
22452.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
150
150
150
150
780
1100
1700
1800
21D
22D
24D
25D
500
500T63HCU
34144. 4–2.5%2 + 2–
150
2550
30D
TRANSFORMERS
General purpose standard transformers are intended for power, heating,
and lighting applications. See page 12-4 or contact your nearest
Square D/Schneider Electric sales office for voltages not listed below.
12
Three Phase – General Purpose Transformers
k Not for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
q Catalog Numbers shown in bold type are available from Distribution Center.
Discount
Schedule
© 2000 Square D
All Rights Reserved
12-3
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type 600 Volts and Below
Special Voltage Transformers, Shielded Isolation Transformers
Class 7400
Special Voltage Transformers — Shielded and Non-shielded
Square D offers special voltage transformers built to customer
specifications. Many options such as lower sound level, copper
windings, special frequency, etc. are available but not listed below.
Contact your nearest Square D/Schneider Electric sales office for
details.
Three Phase – Shielded and Non-shielded
UL Listed
15
All two-winding transformers are “isolating” or “insulating” because there
is no electrical connection between the primary and secondary
windings. Additionally, critical equipment might require an electrostatic
shield be furnished between primary and secondary to attenuate some
of the source line interference and common-mode noise.
Protection from transverse-mode transients is obtained by adding surge
suppressors and filters to the shielded isolation transformer. These
products are listed on page 12-6. Product Data Bulletin 7400PD9202
(D-FAX 2539) describes technical details of shielded and filtered
transformers.
30
45
75
112
150
225
300
Price
Degree C
Temp. Rise
Weight
(Pounds)k
Enclosure
ck
$ 2602.
2862.
3203.
3523.
4003
4403.
5954.
6549.
7956.
8752.
9777.
10754.
13442.
14786.
17964.
19760.
150
200
17D
150
250
17D
150
340
18D
150
500
19D
150
750
21D
150
800
22D
150
1025
24D
150
1450
25D
Electrostatic Shield is indicated by the letters IS at the end of the
catalog number.
To Complete Catalog Number:
Single Phase–Shielded and Non-shielded
1. Select the voltage required from chart 2.
UL Listed through 167 kVA
cUL Listed through 10 kVA
kVA
Catalog
Number
Price
1
1
1.5
1.5
2
2
1S( )F
1S( )FIS
1.5S( )F
1.5S( )FIS
2S( )F
2S( )FIS
$ 518.
569.
741.
831.
831.
901.
7
6, 7
None
6, 7
None
6, 7
115
115
115
115
115
115
3
3
5
5
7.5
7.5
3S(
3S(
5S(
5S(
7S(
7S(
901.
951.
1151.
1251.
1531.
1640.
None
6, 7
None
6, 7
None
6, 7
115
115
115
115
115
115
60
60
110
110
135
135
10A
10A
13B
13B
13B
13B
)F
)FIS
)F
)FIS
)F
)FIS
Stocked
Degree C
Weight Enclosure
Voltage Codes Temp. Rise (Pounds)k
ck
21.2
21.2
30.1
30.1
39.1
39.1
7A
7A
8A
8A
9A
9A
10
10
15
15
25
25
10S(
10S(
15S(
15S(
25S(
25S(
)F
)FIS
)H
)HIS
)H
)HIS
1903.
2043.
2591.
2851.
3402.
3742.
None
3, 6, 7
None
3, 6, 7
None
3, 6, 7
115
115
150
150
150
150
150
150
205
205
240
240
13B
13B
17D
17D
17D
17D
37.5
37.5
50
50
37S(
37S(
50S(
50S(
)H
)HIS
)H
)HIS
3755.
4130.
4568.
5021.
None
3
None
3
150
150
150
150
325
325
350
350
18D
18D
18D
18D
To Complete Catalog Number:
2. Insert the voltage code number in place of the ( ) in the catalog
number.
Chart 2
Voltage
Code
Primary
Secondary
Full Capacity Taps
127
153
74
10
99
600 Delta
600 Delta
600 Delta
600 Delta
480 Delta
600Y/347
480 Delta
480Y/277
240 Delta
480 Delta
4-2.5% 2+24-2.5% 2+24-2.5% FCBN
4-2.5% FCBN
4-2.5% 2+2-
1834
1841
1768
2463
3tj
480 Delta
480 Delta
480 Delta
480 Delta
480 Delta
600 Delta
600Y/347
416Y/240
400Y/231
208Y/120
4-2.5% 2+24-2.5% 2+24-2.5% 2+24-2.5% 2+26-2.5% 2+4-
911
918
884
890
441
240 Delta
240 Delta
240 Delta
240 Delta
208 Delta
600 Delta
600Y/347
480 Delta
480Y/277
600 Delta
2-5% 1+12-5% 1+12-5% 1+12-5% 1+12-5% 1+1-
447
414
66
85j
208 Delta
208 Delta
208 Delta
208 Delta
600Y/347
480 Delta
240 Delta
208Y/120
2-5% 1+12-5% 1+12-5% FCBN
2-5% FCBN
t Use pricing from page 12-3 for non-shielded units.
j Use pricing below for shielded units.
1. Select the voltage required from chart 1.
Three Phase 480 V Delta Primary
2. Insert the voltage code number in place of the ( ) in the catalog
number.
Chart 1
TRANSFORMERS
Catalog
Number
15T( )H
15T( )HIS
30T( )H
30T( )HIS
45T( )H
45T( )HIS
75T( )H
75T( )HIS
112T( )H
112T( )HIS
150T( )H
150T( )HIS
225T( )H
225T( )HIS
300T( )H
300T( )HIS
kVA
Voltage
Code
Primary
Secondary
Full Capacity Taps
6
7
60 f
9
1292
120x240
208
208
208
208
120/240
120/240
120/240
208
277
None
None
2-5% FCBN
None
None
8
61 f
3f
72
78
277
277
240x480
480
480
120/240
120/240
120/240
208
277
None
2-5% FCBN
6-2.5% 2+4None
None
k Not for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
c For enclosure styles, see Dimensions Table, page 12-8.
FCBN = Full capacity below normal
Lugs: Furnished by customer.
Taps on transformers 225 kVA and larger may vary in 3% to 5% steps to obtain best
design.
f Taps are available on transformers 10 kVA and larger.
208Y/120 V Secondary 60 Hz with Electrostatic Shield, UL Listed
kVA
9
15
30
45
75
112.5
150
225
300
500
Catalog
Number q
9T2FIS
15T3HIS
30T3HIS
45T3HIS
75T3HIS
112T3HIS
150T3HIS
225T3HIS
300T3HIS
500T68HIS
Price
Stocked
Degree C
Weight
Enclosure
Voltage Codes Temp. Rise (Pounds)k
ck
$ 2201.
2741.
3452.
4152.
6254.
2–5%FCBN
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
115
150
150
150
150
235
200
250
340
500
14C
17D
17D
18D
19D
8143.
10389.
13913.
18261.
27930.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
4–2.5%2 + 2–
150
150
150
150
150
815
800
1025
1450
2100
21D
22D
24D
25D
30D
208 V Delta Primary
208Y/120 V Secondary 60 Hz with Electrostatic Shield, UL Listed
9
15
30
45
75
9T85FIS
15T85HIS
30T85HIS
45T85HIS
75T85HIS
$ 2201.
2741.
3452.
4152.
6254.
2–5%FCBN
2–5%FCBN
2–5%FCBN
2–5%FCBN
2–5%FCBN
115
150
150
150
150
235
200
250
340
500
14C
17D
17D
18D
19D
112.5
150
225
300
500
112T85HIS
150T85HIS
225T85HIS
300T85HIS
500T85HIS
8143.
10389.
13913.
18261.
27930.
2–5%FCBN
2–5%FCBN
2–5%FCBN
2–5%FCBN
2–5%FCBN
150
150
150
150
150
815
800
1025
1450
2100
21D
22D
24D
25D
30D
12
q Catalog Numbers shown in bold type are available from Distribution Center.
k Not for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
c For enclosure styles, see Dimensions Table, page 12-8.
FCBN = Full capacity below normal
Lugs: Furnished by customer.
Taps on transformers 225 kVA and larger may vary in 3% to 5% steps to obtain best
design.
12-4
© 2000 Square D
All Rights Reserved
PE2
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type 600 Volts and Below
EE Energy Efficient Transformers
Class 7400
WATCHDOG®, Type
The Environmental Protection Agency (EPA) has determined 61 billion kWH of electricity is wasted each year in transformer losses. Square D offers a
complete line of transformers that can significantly reduce energy losses.
Surveys have shown the 24-hour average loading of low voltage dry type transformers in the United States is appoximately 35% of nameplate rating.
The new Type EE Energy Efficient Transformers are optimized for maximum efficiency at these most common loading levels.
Square D WATCHDOG 115°C or 80°C rise transformers offer significant energy savings in less common applications where the average daily loading
exceeds 50% of nameplate rating.
Type EE Energy Efficient Transformers
WATCHDOG Low Temperature Rise Transformers
k Comply with NEMA standard TP-1 for optimum energy efficiency
at 35% load.
k Designed for low energy losses at loads greater than 50% of
nameplate rating.
k Labeled for EPA Energy Star program.
k More efficient than standard 150°C rise transformers at all load
levels.
k Extra long life expectancy using 220°C insulation system designed
for full load operation at a maximum temperature rise of 115°C or
80°C instead of 150°C.
k Identical dimensions to standard, 150°C rise General Purpose
transformers.
k Continuous emergency overload capability of 15% on 115°C rise
and 30% on 80°C rise.
k Cost optimized to allow energy savings payback to owner in
average 3–5 year period based on energy rate of $0.065 per kWH.
kVA
Catalog
Numberq
Price
Full Capacity
Taps
Weight Enclosure
Degree C
Temp. Rise (Pounds)
ck
k
Single Phase – 240x480 V Primary 120/240 V Secondary 60 Hz
UL Listed
15
25
15S1HEE
25S3HEE
37.5
50
75
100
167
37S3HEE
50S3HEE
75S3HEE
100S3HEE
167S3HEE
$ 2250. None
2929. 6–2.5%2 + 4–a
3904.
4748.
6439.
8324.
12288.
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
150
150
190
270
17D
17D
150
150
150
150
150
340
395
575
818
1246
18D
18D
21D
22D
24D
Three Phase–480 V Delta Primary 208Y/120 V Secondary 60 Hz
UL Listed
kVA
Catalog
Numberq
Price
Full Capacity
Taps
Weight
(Pounds)k
Enclosurec k
115°C Rise Single Phase – 240x480 V Primary 120/240 V Secondary 60 Hz
UL Listed
15
25
37.5
50
75
100
15S3HF
25S3HF
37S3HF
50S3HF
75S3HF
100S3HF
$ 2209.
2870.
3601.
4804.
6503.
7304.
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
230
325
350
450
650
1050
17D
18D
18D
21D
22D
24D
80°C Rise Single Phase – 240x480 V Primary 120/240 V Secondary 60 Hz
UL Listed
15
25
37.5
50
75
100
15S3HB
25S3HB
37S3HB
50S3HB
75S3HB
100S3HB
$ 2425.
3150.
3992.
5282.
7155.
8036.
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
6–2.5%2 + 4–a
230
325
350
450
675
1100
17D
18D
18D
21D
22D
24D
15
15T3HEE
$ 2600. 6–2.5%2 + 4–
150
218
17D
115°C Rise Three Phase–480 V Delta Primary 208Y/120 V Secondary 60 Hz
30
45
75
30T3HEE
45T3HEE
75T3HEE
3185. 6–2.5%2 + 4–
4795. 6–2.5%2 + 4–
7225. 6–2.5%2 + 4–
150
150
150
266
382
546
17D
18D
19D
UL Listed
112.5
150
225
300
112T3HEE
150T3HEE
225T3HEE
300T3HEE
9625.
12565.
16750.
21480.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
150
150
150
150
657
816
1162
1646
21D
22D
24D
25D
500
750
500T68HEE
750T90HEE
30040. 4–3.5%2 + 2–
55315. 4–3.5%2 + 2–
150
150
2170
3000
30D
31D
k Not for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
15
30
45
75
112.5
150
225
300
500
15T3HFj
30T3HFj
45T3HFj
75T3HFj
112T3HFj
150T3HFj
225T3HF
300T3HFj
500T90HF
$ 2401.
3553.
5353.
7103.
8905.
11877.
16410.
19952.
29218.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
4–3.5%2 + 2–
250
340
500
620
800
1025
1450
2495
3450
17D
18D
19D
21D
22D
24D
25D
30D
31D
80°C Rise Three Phase – 480 V Delta Primary 208Y/120 V Secondary 60 Hz
UL Listed
For additional information reference Bulletin No. 7400CT9801 or
D-Fax™ number 2893.
15
30
45
75
112.5
150
225
300
500
15T3HBj
30T3HBj
45T3HBj
75T3HBj
112T3HB
150T3HB
225T3HB
300T3HBj
500T90HB
$ 2578.
3801.
5703.
7603.
9606.
12907.
18052.
21953.
32519.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
4–3.5%2 + 2–
250
340
500
750
850
1075
1450
2100
3900
17D
18D
19D
21D
22D
24D
25D
30D
31D
12
TRANSFORMERS
c For enclosure styles, see Dimensions Table on page 12-8.
a When 240 volt connection is used, there will be 3-5% taps, 1 above and 2 below 240 volts.
FCBN = Full Capacity Below Normal
Lugs: furnished by customer.
q Catalog numbers shown in bold type are available from Distribution Center.
j Available from Distribution Center with copper windings. Add suffix CU to complete catalog
number. Example: 15T3HFCU.
3/00
PE2
Discount
Schedule
© 2000 Square D
All Rights Reserved
12-5
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type 600 Volts and Below
K-Rated, Shielded Filtered and Drive Isolation Transformers
Class 7400
Transformers Designed for High Harmonic Loads –
NL and NLP Series
Drive Isolation Transformers – Three Phase
• Class 220 insulation
Special design considerations must be made for the requirements of
both adjustable frequency and dc motor drive power isolation.
Allowance for high surge, harmonic and offset currents are taken into
account in the design of Square D Company drive isolation
transformers. Drive isolation transformers are not shielded isolation
transformers, but act to lessen transient generation into the supply
power and act as a buffer for SCR current surges. UL Listed.
• NLP Series has maximum sound level 3dB below NEMA Standard
Three Phase
• Three phase dry type transformers, 480 Delta – 208Y/120
• Aluminum or Copper windings
• Electrostatic shield
• 115 degree C temperature rise standard j
• Double size neutral terminal for additional customer neutral cables
kVA
Catalog
Numberq
• Additional coil capacity to compensate for higher non-linear load loss
7.5
11
15
20
27
7T( )HDIT
11T( )HDIT
15T( )HDIT
20T( )HDIT
27T( )HDIT
34
40
51
63
75
34T(
40T(
51T(
63T(
75T(
• Heavy gauge ventilated indoor enclosures (weathershields available)
• UL Listed
NL Series for Typical Non-Linear Load Service –
UL K-4 Rated – Aluminum Windings
kVA
Catalog
Numberq
Price
Taps
Weight
(Pounds)k
Enclosure
ck
15
30
45
15T3HFISNL
30T3HFISNL
45T3HFISNL
$ 2545.
3904.
4513.
6-2.5% 2+46-2.5% 2+46-2.5% 2+4-
240
300
500
17D
18D
19D
75
112.5
150
75T3HFISNL
112T3HFISNL
150T3HFISNL
6164.
10259.
13734.
6-2.5% 2+46-2.5% 2+46-2.5% 2+4-
725
800
985
21D
22D
24D
225
300
500
225T3HFISNL
300T68HFISNL
500T90HFISNL
20892.
28941.
39984.
6-2.5% 2+44-2.5% 2+24-3.5% 2+2-
1450
1725
3600
25D
30D
29D
15
30
45
15T3HFISNLP
30T3HFISNLP
45T3HFISNLP
$ 3340.
4590.
5394.
6-2.5% 2+46-2.5% 2+46-2.5% 2+4-
245
350
600
17D
18D
19D
75
112.5
150
75T3HFISNLP
112T3HFISNLP
150T3HFISNLP
7637.
15755.
19137.
6-2.5% 2+46-2.5% 2+46-2.5% 2+4-
725
850
1380
22D
22D
25D
225
300
500
225T3HFISNLP
300T68HFISNLP
500T90HFISNLP
27897.
39217.
59820.
6-2.5% 2+44-2.5% 2+24-3.5% 2+2-
2010
2100
4000
25D
30D
32F
15
30
45
15T3HFISCUNL
30T3HFISCUNL
45T3HFISCUNL
$ 4292.
6588.
7615.
6-2.5% 2+46-2.5% 2+46-2.5% 2+4-
330
380
475
18D
18D
18D
75
112.5
150
75T3HFISCUNL
112T3HFISCUNL
150T3HFISCUNL
10404.
17315.
23181.
6-2.5% 2+46-2.5% 2+46-2.5% 2+4-
865
925
1275
21D
22D
24D
225
300
225T3HFISCUNL
300T68HFISCUNL
35257.
39071.
6-2.5% 2+44-2.5% 2+2-
1700
2750
25D
25D
NLP Series for More Severe Non-Linear Load Service –
UL K-13 Rated – Copper Windings
15
30
45
15T3HFISCUNLP
30T3HFISCUNLP
45T3HFISCUNLP
$ 5635.
7745.
9103.
6-2.5% 2+46-2.5% 2+46-2.5% 2+4-
310
370
600
18D
18D
19D
75
112.5
150
75T3HFISCUNLP
112T3HFISCUNLP
150T3HFISCUNLP
12919.
22649.
32294.
6-2.5% 2+46-2.5% 2+46-2.5% 2+4-
875
1100
1500
22D
22D
25D
225
300
225T3HFISCUNLP
300T68HFISCUNLP
37661.
52953.
6-2.5% 2+44-2.5% 2+2-
1700
2600
25D
30D
TRANSFORMERS
q Catalog Numbers shown in bold type are available from Distribution Center.
c For enclosure styles, see dimensions table, page 12-8.
FCBN = Full capacity below normal
LUGS: Furnished by customer
k Not for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
j Available with optional 80° C temperature rise. To complete catalog number, replace “F” with
“B”. Example: 15T3HBISNL.
For additional information on Type NL/NLP Transformers reference
7455BR9301.
For additional information on Drive Isolation Transformers reference
7460PD9501.
For additional information on Thermal Switch Kit for DITs reference
7400PD9701.
© 2000 Square D
All Rights Reserved
C. Weight
StockVoltage Degree
Temp.
(Pounds)
Codes
Rise
k
Price
Enclosure
ck
$ 2125.
2523.
2602.
3119.
3200.
144, 145
144, 145
144, 145
144, 145
144, 145
150
150
150
150
150
180
180
190
210
250
17D
17D
17D
17D
17D
3520.
4002.
4679.
5091.
5951.
144, 145
144, 145
144, 145
144, 145
144, 145
150
150
150
150
150
295
350
445
465
550
18D
18D
20D
20D
20D
93T( )HDIT
118T( )HDIT
145T( )HDIT
175T( )HDIT
220T( )HDIT
7629.
8497.
9528.
10996.
13440.
144, 145
145
145
145
145
150
150
150
150
150
845
920
1025
1120
1200
22D
22D
22D
25D
25D
275
330
440
550
275T(
330T(
440T(
550T(
17960.
18899.
23167.
28783.
145
145
None
None
150
150
150
150
1500
1390
2700
3800
25D
25D
30D
30D
)HDIT
)HDIT
)HDIT
)HDIT
Voltage Codes
Code
Primary
Secondary
142
143
144
230 Delta
230 Delta
460 Delta
230Y/132
460Y/265
230Y/132
145
146
147
460 Delta
575 Delta
575 Delta
460Y/265
230Y/132
460Y/265
Full Capacity Taps
2-5%1 + 1–
To Complete Catalog Number:
1. Select the voltage required from chart.
2. Insert the voltage code number in place of the ( ) in the catalog
number.
NL Series for Typical Non-Linear Load Service –
UL K-4 Rated – Copper Windings
12-6
)HDIT
)HDIT
)HDIT
)HDIT
)HDIT
Class B (IEEE Standard 597-1983)
93
118
145
175
220
NLP Series for More Severe Non-Linear Load Service –
UL K-13 Rated – Aluminum Windings
12
60 Hz
PE2
Shielded Transformers with Filters –
Three Phase
Additional attenuation of transverse (across-the-line) surges and
transients is available with the addition of primary surge suppression
and secondary filters. For details, see Product Data Bulletin
7400PD9202. Surge suppression and filtering are indicated by the
letters FIL at the end of the catalog number.
480 V Delta Primary 208Y/120 V Secondary 60 Hz with Electrostatic Shield, Surge
Suppressors and Filter – UL Listed
kVA
Catalog
Numberq
Price
15
30
45
75
112.5
15T3HISFIL
30T3HISFIL
45T3HISFIL
75T3HISFIL
112T3HISFIL
$ 5907.
6617.
8024.
10127.
12581.
150
225
150T3HISFIL
225T3HISFIL
C. Weight
Full Capacity Degree
Temp.
(Pounds)
Taps
Rise
k
Enclosure
ck
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
150
150
150
150
150
265
295
390
610
840
19D
19D
19D
21D
22D
14827. 6–2.5%2 + 4–
18703. 6–2.5%2 + 4–
150
150
1100
1400
25D
26D
208 V Delta Primary 208Y/120 V Secondary 60 Hz with Electrostatic Shield, Surge
Suppressors and Filter – UL Listed
15
30
45
75
112.5
15T85HISFIL
30T85HISFIL
45T85HISFIL
75T85HISFIL
112T85HISFIL
$ 5907.
6617.
8024.
10127.
12581.
2–5% FCBN
2–5% FCBN
2–5% FCBN
2–5% FCBN
2–5% FCBN
150
150
150
150
150
265
295
390
610
840
19D
19D
19D
21D
22D
150
225
150T85HISFIL
225T85HISFIL
14827.
18703.
2–5% FCBN
2–5% FCBN
150
150
1100
1400
25D
26D
c For enclosure styles, see Dimensions Table on page 12-8.
FCBN = Full Capacity Below Normal
Lugs: furnished by customer.
q Catalog numbers shown in bold type are available from Distribution Center.
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type 600 Volts and Below
Stainless Steel, Non-Ventilated Transformers
Class 7400
Stainless Steel Enclosed Transformers–
Single and Three Phase
Non-Ventilated Transformers –
Single and Three Phase
Stainless steel enclosures provide better corrosion resistance than
standard painted enclosures. Square D has a complete line of stainless
steel transformers to meet demands for extra protection in corrosive
environments.
Non-ventilated enclosures are used in environments where large
quantities of dust, airborne contaminants, metal particles, or moisture
make ventilated transformers impractical. These transformers are also
used when water spray from any direction is possible.
The transformers listed below are built with an epoxy-resin encapsulated
core and coil assembly inside of a non-ventilated #316 stainless steel
enclosure. Terminals are flexible copper lead wire. When connections are
made using an appropriate method, the final transformer installation is
virtually impervious to contamination from materials such as acids, food
products, organic solvents, salt water, or similar. Transformers are UL
listed for NEMA Type 3R indoor or outdoor use.
The 150 rise transformers listed below are built using 220 class
insulated core and coil assemblies similar to ventilated units. However,
the core and conductors are oversized to maintain proper temperature
rise with the limited cooling capacity of a non-ventilated enclosure.
Therefore non-ventilated transformers are larger and heavier than the
same kVA and voltage ventilated equivalent.
Additional voltages not listed below and UL Listed NEMA Type 4X
enclosures are available. Contact your nearest Square D/Schneider
Electric sales office for details.
Ventilated and non-ventilated transformers built using #304 stainless
steel enclosures are also available. These are well suited for moderately
corrosive locations where enclosure protection and appearance are
important. Contact your nearest Square D/Schneider Electric sales
office for details.
Single Phase – 240x480 V Primary
120/240 V Secondary 60 Hz
UL Listed
Degree C
Weight
Temperature (Pounds) Enclosure
ck
Rise
k
Catalog
Number
Price
Full Capacity
Taps
1
1.5
2
1S1FSS
1.5S1FSS
2S1FSS
$ 607.
847.
911.
None
None
None
115
115
115
21
30
39
7A
8A
9A
3
5
7.5
3S1FSS
5S1FSS
7S1FSS
1278.
1848.
1983.
None
None
None
115
115
115
60
110
135
10A
13B
13B
10S1FSS
15S1FSS
25S1FSS
2269.
3350.
4574.
None
None
None
115
115
115
150
225
300
13B
15B
15B
KVA
10
15
25
Single Phase – 480 V Primary
3
5
7.5
10
15
25
Non-ventilated enclosures meet protection code IP55 (dust and jetting
water protection) per standard IEC-529. While not listed to a specific
NEMA standard, they are suitable for indoor or outdoor use.
kVA
Catalog
Numberq
Price
Full Capacity
Taps
Weight Enclosure
Degree C
Temp. Rise (Pounds)
ck
k
Single Phase – 240X480 V Primary 120/240 V Secondary 60 Hz
15
25
37.5
50
75
100
15S3HNV
25S3HNV
37S3HNV
50S3HNV
75S3HNV
100S3HNV
$ 2401.
3601.
5356.
6850.
8381.
10612.
6–2.5%2 + 4–★
6–2.5%2 + 4–★
6–2.5%2 + 4–★
6–2.5%2 + 4–★
6–2.5%2 + 4–★
6–2.5%2 + 4–★
150
150
150
150
150
150
230
310
350
450
880
975
17E
18E
18E
21E
24E
25E
230
310
350
450
880
975
17E
18E
18E
21E
24E
25E
Single Phase – 600 V Primary 120/240 V Secondary 60 Hz
15
25
37.5
50
75
100
15S5HNV
25S5HNV
37S5HNV
50S5HNV
75S5HNV
100S5HNV
$ 2582.
3893.
5884.
6830.
9297.
11452.
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
150
150
150
150
150
150
Three Phase – 480 V Delta Primary 208Y/120 V Secondary 60 Hz
120/240 V Secondary 60 Hz UL Listed
3S40FSS
5S40FSS
7S40FSS
$1278.
1848.
1983.
2-5% FCBN
2-5% FCBN
2-5% FCBN
115
115
115
60
110
135
10A
13B
13B
10S40FSS
15S40FSS
25S40FSS
2269.
3350.
4574.
2-5% FCBN
2-5% FCBN
2-5% FCBN
115
115
115
150
225
300
13B
15B
15B
Three Phase – 480 V Delta Primary
The 115 rise epoxy-resin encapsulated transformers listed below are
furnished non-ventilated at standard price.
208Y/120 V Secondary 60 Hz UL Listed
3
6
9
3T2FSS
6T2FSS
9T2FSS
$1960.
2345.
2891.
2-5% FCBN
2-5% FCBN
2-5% FCBN
115
115
115
120
145
234
12C
12C
14C
15
30
15T2FSS
30T2FSS
3679.
6201.
2-5% FCBN
2-5% FCBN
115
115
300
660
14C
16C
k Not for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
15
30
30
45
15T68F
30T2F
30T3HNV
45T3HNV
$ 2211.
4065.
3852.
5903.
4–2.5%2 + 2–
2–5%FCBN
6–2.5%2 + 4–
6–2.5%2 + 4–
115
115
150
150
300
660
340
510
14C
16C
19E
19E
75
112.5
150
225
300
75T3HNV
112T3HNV
150T3HNV
225T3HNV
300T3HNV
9104.
12309.
15880.
23923.
26263.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
150
150
150
150
150
1025
1250
2000
2100
3300
22E
24E
25E
23E
28E
Three Phase – 480 V Delta Primary 240 V Delta Secondary 60 Hz
15
30
45
15T75F
30T6HNV
45T6HNV
75
112.5
150
225
300
75T6HNV
112T6HNV
150T6HNV
225T6HNV
300T6HNV
$ 2211. 4–2.5%FCBN
3852. 6–2.5%2 + 4–
5903. 6–2.5%2 + 4–
9104.
12309.
15880.
23923.
26263.
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
6–2.5%2 + 4–
115
150
150
300
340
510
14C
19E
19E
150
150
150
150
150
1025
1250
2000
2100
3300
22E
24E
25E
23E
28E
15
30
45
15T7F
30T8HNV
45T8HNV
75
112.5
150
225
300
75T8HNV
112T8HNV
150T8HNV
225T8HNV
300T8HNV
$ 2321. 2–5%FCBN
4203. 4–2.5%FCBN
6403. 4–2.5%FCBN
9805.
13307.
15910.
24621.
27014.
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
4–2.5%FCBN
115
150
150
300
340
510
14C
19E
19E
150
150
150
150
150
1025
1250
2000
2100
3300
22E
24E
25E
23E
28E
12
q Catalog Numbers shown in bold type are available from Distribution Center.
c For enclosure styles, see dimensions table, page 12-8.
a When 240 volt tap is used, there will be 3–5% taps, 1 above and 2 below.
FCBN = full capacity below normal
Lugs: furnished by customer
TRANSFORMERS
Three Phase – 600 V Delta Primary 208Y/120 V Secondary 60 Hz
3/00
PE2
Discount
Schedule
© 2000 Square D
All Rights Reserved
12-7
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type 600 Volts and Below
Enclosures
Class 7400
Enclosure Styles
Table 1: Enclosure Dimensions and Accessories (Note 1)
Enclosure
Number/
Style
Style A–NEMA Type 3R Rated
Style B–
NEMA Type 3R Rated
Style C –NEMA Type 3R Rated
IN
mm
Depth
IN
mm
Mtg. Weathershield
Wall
Mounting
Bracket
Ceiling
Mounting
Bracket
Insulation
Class °C
A
5
127
4.47
114
3.44
87 Wall
Note 2
Note 3
—
105
2
A
5.5
140
4.47
114
3.44
87 Wall
Note 2
Note 3
—
105
3
A
5
127
4.85
123
3.75
95 Wall
Note 2
Note 3
—
105
4
A
5.5
140
5.23
133
4.06
103 Wall
Note 2
Note 3
—
130
5
A
6.19
157
6.19
157
4.69
119 Wall
Note 2
Note 3
—
130
6
A
6.69
170
6.19
157
4.69
119 Wall
Note 2
Note 3
—
180
7
A
8.13
270
6.94
176
5.31
135 Wall
Note 2
Note 3
—
180
8
A
8.25
210
8.68
220
6.56
167 Wall
Note 2
Note 3
—
180
9
A
9.56
243
8.68
220
6.56
167 Wall
Note 2
Note 3
—
180
10
A
10.5
267
8.62
219
6.5
165 Wall
Note 2
Note 3
—
180
11
A
12.56
319
8.62
219
6.5
165 Wall
Note 2
Note 3
—
180
12
C
13.5
343 14.75
375
9
229 Wall
Note 2
Note 3
—
180
13
B
14.75
375
248 11.75
298 Wall
Note 2
Note 3
—
180
14
C
14.75
375 19.1
485 12.25
311 Wall
Note 2
Note 3
—
180
15
B
20
508 15
381 13.5
343 Wall
Note 2
Note 3
—
180
Note 3
—
16
18
19
20
21
22
23
24
25
26
9.75
C
22
559 25
635 13.5
343 Wall
Note 2
D
27
686 20
508 16
406 Floor
WS363
180
WMB361–362 CMB363
220
E
27
686 20
508 16
406 Floor
Note 5
WMB361–362 CMB363
220
D
30
762 20
508 20
508 Floor
WS363
WMB363–364 CMB363
220
E
30
762 20
508 20
508 Floor
Note 5
WMB363–364 CMB363
220
D
30
762 30
762 20
508 Floor
WS364
WMB363–364 CMB364
220
E
30
762 30
762 20
508 Floor
Note 5
WMB363–364 CMB364
220
D
37
940 30
762 20
508 Floor
WS364
WMB363–364 CMB364
220
WMB363–364 CMB364
E
37
940 30
762 20
508 Floor
Note 5
D
37
940 30
762 24
610 Floor
WS364
N/A
CMB364
220
220
E
37
940 30
762 24
610 Floor
Note 5
N/A
CMB364
220
D
43.75 1111 32
813 27
686 Floor
WS380
N/A
CMB380
220
E
43.75 1111 32
813 27
686 Floor
Note 5
N/A
CMB380
220
E
48
1219 29.5
749 Floor
Note 5
N/A
N/A
220
220
1219 48
D
49.5
1257 35
889 28.5
724 Floor
WS381
N/A
CMB381
E
49.5
1257 35
889 28.5
724 Floor
Note 5
N/A
CMB381
220
D
49.5
1257 41
1041 32
813 Floor
WS382
N/A
N/A
220
E
49.5
1257 41
1041 32
813 Floor
Note 5
N/A
N/A
220
D
57.5
1461 41
1041 32
813 Floor
WS382
N/A
N/A
220
D
60
1524 56
1422 36
914 Floor
WS370A
N/A
N/A
220
E
60
1524 56
1422 36
914 Floor
Note 5
N/A
N/A
220
29
D
68
1727 56
1422 36
914 Floor
WS370A
N/A
N/A
220
30
D
71
1803 48
1219 36
914 Floor
WS383
N/A
N/A
220
31
D
74
1880 56
1422 40.5
1029 Floor
WS384
N/A
N/A
220
32
F
94
2388 56
1422 54
1372 Floor
Note 4
N/A
N/A
220
33
F
94
2388 72
1829 54
1372 Floor
Note 4
N/A
N/A
220
34
F
94
2388 84
2134 54
1372 Floor
Note 4
N/A
N/A
220
35
F
94
2388 96
2438 54
1372 Floor
Note 4
N/A
N/A
220
28
Style E–IP55 Rated
Width
mm
1
17
Style D –NEMA Type 2 Rated
Converts to NEMA Type 3R with Weathershield
Height
IN
12
TRANSFORMERS
Note 1: These dimensions are not for construction. Contact your nearest Square D/Shneider Electric sales office for
certified prints.
Note 2: Transformer is NEMA Type 3R Standard. Weathershield not required for outdoor use.
Note 3: Wall mounting brackets are a standard part of transformer enclosure. Accessory not required.
Note 4: Special outdoor construction required for NEMA Type 3R applications. Contact your nearest
Square D/Schneider Electric sales office for details.
Note 5: Indoor/outdoor enclosure standard. Weathershield not required.
N/A:
Wall mounting/ceiling mounting bracket not available due to weight of these parts.
Style F–NEMA Type 1 Rated
12-8
© 2000 Square D
All Rights Reserved
PE2
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Enclosure Replacement Parts, Accessories,
Lug Kits and Sound Levels
Class 7400
Replacement Enclosure Parts List for Low Voltage Stock Transformers
Enclosure
Number–Style
17–D
18–D
19–D
21–D
22–D
24–D
25–D
Base
43101-914-01
43055-018-01
43055-009-01
43055-124-50
43101-895-50
43101-912-50
43101-904-50
Top Cover
43101-915-01
43055-021-01
43055-012-01
43055-125-01
43101-890-01
43101-907-01
43101-899-01
30-D
43101-934-50
43101-926-01
Part Number
Frontj
43101-916-01
43055-020-01
43055-011-01
43005-074-02
43101-891-01
43101-908-01
43101-900-01
Upper: 43101-929-01
Lower: 43101-930-01
Rear
43101-916-01
43055-020-01
43055-011-01
43005-074-02
43101-891-01
43101-908-01
43101-900-01
Upper: 43101-929-01
Lower: 43101-930-01
Sides (Ends)
43101-917-01
43055-010-01
43055-010-01
43055-126-01
43101-892-01
43101-909-01
43101-901-01
43101-928-01
j When replacing a front panel, specify tranformer catalog number and “with nameplate and labels” on order.
Transformer Lug Kits
VERSAtile™ Compression Lugs and Mechanical Set-Screw Types – UL Listed Lugs AL9CU (90°C Rated)
Transformer
kVA Sizes
Kit
Catalog Number
Terminal Lugs
Price
Per Kit
VERSAtileTM Compression Equipment Lugs
15-371⁄2 1Ø
VCEL-SK1
$ 180.
15-45 3Ø
50-75 1Ø
VCEL-SK2
292.
75-1121⁄2 3Ø
100-167 1Ø
150-300 3Ø
VCEL-SK3
500 3Ø
VCEL-SK4
Mechanical Set – Screw Type Lugs
15-371⁄2 1Ø
DA-SK1
15-45 3Ø
50-75 1Ø
DA-SK2
75-1121⁄2 3Ø
100-167 1Ø
DA-SK3
150-300 3Ø
500 3Ø
DA-SK4
Qty.
Catalog Number
8
5
VCEL-021-14S1
VCEL-030-516H1
13
3
26
1666.
Aluminum or Copper
Conductor Range
(AWG or kcmil)
Hardware Included
Qty.
#8–1/0
#4–300 kcmil
VCEL-030-516H1
#4–300 kcmil
VCEL-030-516H1
VCEL-075-12H1
#4–300 kcmil
500–750 kcmil Al
500 kcmil Cu
500–750 kcmil Al
500 kcmil Cu
VCEL-075-12H1
Type
8
1
8
8
3
1⁄4"
1⁄4"
16
3⁄8"
x 2" Cap Screws
21
3⁄8"
x 2" Cap Screws
x 1" Cap Screws
x 1" Cap Screws
x 2" Cap Screws
1⁄4" x 1" Cap Screws
1⁄4" x 2" Cap Screws
1⁄4" x 3⁄4" Cap Screws
1812.
34
59.
8
5
DA-2
DA-250
#14–#2
#6–250 kcmil
9
1⁄4"
104.
13
DA-250
#6–250 kcmil
1⁄4"
1⁄4"
481.
3
26
34
DA-250
DA-600
DA-600
#6–250 kcmil
#2–600 kcmil
#2–600 kcmil
8
8
3
16
21
656.
x 1" Cap Screws
x 13⁄4" Cap Screws
x 1" Cap Screws
x 2" Cap Screws
3⁄8" x 2" Cap Screws
1⁄4"
3⁄8"
FINGERSAFE® Terminal Block Cover Kit for Encapsulated Transformers
Can be used to meet touch-safe requirements of EN60-204.
Fits Enclosure
Kit Catalog
Number
Price
7A (1 kVA)
9A (2 kVA)
10A (3 kVA)
13B (5–10 kVA)
7400ENT9
7400ENT11
7400ENT11
7400 ENT13
$ 95.
95.
95.
145.
Add Height to
Dimensions on
page 12-8
1.5 IN/39 mm
1.5 IN/39 mm
1.5 IN/39 mm
2.0 IN/51 mm
Weathershields, Wall Mounting Brackets and Ceiling Mounting Brackets
Weathershields
q
c
k
t
Wall Mounting Bracketsc
Ceiling Mounting Bracketsk
Catalog Numberq
Price
Catalog Numberq
Price
Catalog Numberq
WS363
WS364
WS370A
WS380
No charge t
$ 219.
1706.
500.
WMB-361-362
WMB-363-364
...
...
No charge t
No charge t
...
...
CMB363
CMB364
CMB380
CMB381
WS381
WS382
WS383
WS384
500.
850.
851.
1808.
...
...
...
...
...
...
...
...
...
...
...
...
Price
$220.
220.
549.
549.
...
...
...
...
Catalog Numbers shown in bold type are available from Distribution Center.
Wall mounting breackets may be prohibited in some California areas requiring 12" spacing from wall.
Base Channels are supplied for ceiling mounting–trapeze hangers must be furnished by user.
Subject to minimum billing and freight charges when not ordered with transformer.
Sound Levels
NEMA Standard Sound Level
40 dB
45 dB
50 dB
55 dB
60 dB
62 dB
64 dB
TRANSFORMERS
kVA
0–9
10–50
51–150
151–300
301–500
501–700
701–1000
12
Square D transformers meet NEMA standards for sound level.
Lower sound levels are available at an additional charge.
FINGERSAFE is a Registered Trademark of Square D Company or related companies.
VERSAtile is a Trademark of Square D Company or related companies.
3/00
PE2
Discount
Schedule
© 2000 Square D
All Rights Reserved
12-9
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
MINI POWER-ZONE® Transformers
Indoor/Outdoor Packaged Power Supply
Class 7400
MINI POWER-ZONE, UL Listed, Suitable for Use as Service Equipment
The MINI POWER-ZONE® power supply from Square D Company provides the answer to requirements for a portable,
compact power supply for small loads. Because the MINI POWER ZONE is furnished as a complete package,
considerable savings in installation time and costs can be realized. Its NEMA 3R enclosure is suitable for both indoor
and outdoor use. The transformer is copper wound, 115°C rise, and epoxy-resin encapsulated. The panel section has
copper bus and uses QO® style circuit breakers.
MINI POWER-ZONE centers are furnished with factory-installed primary main and secondary main circuit breakers only.
Circuit breaker ratings are selected to meet National Electrical Code requirements and to coordinate with transformer
magnetizing inrush current. Feeder circuit breakers are standard Square D QO plug-on type which should be ordered,
as required, from your local Square D distributor’s stock. If ground fault protection is required, QWIK-GARD ® circuit
breakers may be used in all sizes. Tandem breakers are not permitted.
The MINI POWER-ZONE uses a separate transformer and panel board section. This allows the panel section to be
removed and wired first if desired. Also the transformer can be replaced without disturbing the panel section and
associated wiring. The new transformer simply slides into the top of the panel section and primary and secondary leads
are reconnected to the main circuit breakers.
Options Available on Special Order (UL Listed)
Contact Factory for Pricing
1. For primary breaker shunt trip, add suffix “SH” with coil voltage. EX: MPZ25S40FSH120.
2. For electrostatic shielding, add suffix “IS”. EX: MPZ10S40FIS.
3. To accommodate QOB bolt-on feeder circuit breakers, add “B” after “MPZ”. EX: MPZB5S40F.
4. To have unit manufactured with painted 316 stainless steel enclosure add “SS” Example: MPZ15T2FSS.
Standard Voltages
kVA
Catalog
Numberq
Price
High
Voltage
Low
Voltage
Full
Capacity
Taps
Weight
(Pounds)
Dimensions (Inches)f
H
W
D
Primary
Main
Circuit Breaker
Feeder Breakers
Secondary
Main
Circuit Breaker
Maximum Number Maximum
1-Pole or 2-Pole
Amps
Single Phase
5
7.5
10
MPZ5S40F
MPZ7S40F
MPZ10S40F
$1852.
2163.
2351.
480
480
480
240/120
240/120
240/120
2-5% FCBN
2-5% FCBN
2-5% FCBN
175
200
215
32.7
32.7
32.7
12.0
12.0
12.0
11.9
11.9
11.9
FAL24020 20 A
FAL24030 30 A
FAL24040 40 A
QO-230
QO-240
QO-260
30 A
40 A
60 A
6 or 3
8 or 4
10 or 5
20
30
40
15
25
MPZ15S40F
MPZ25S40F
3052.
4552.
480
480
240/120
240/120
2-5% FCBN
2-5% FCBN
390
390
42.9
42.9
17.4
17.4
13.5
13.5
FAL24060 60 A
FAL24100 100 A
QO-280
QO-2125
80 A
125 A
16 or 8
24 or 12
60
100
Maximum Number
1-Pole or 3-Pole
Three Phase
15
22.5
30
MPZ15T2F
MPZ22T2F
MPZ30T2F
$4804.
5953.
7304.
480s
480s
480s
208Y/120
208Y/120
208Y/120
2-5% FCBN
2-5% FCBN
2-5% FCBN
710
725
755
44.6
44.6
44.6
27.4
27.4
27.4
13.6
13.6
13.6
FAL 34040 40 A
FAL 34070 70 A
FAL 34090 90 A
QO-360
QO-380
QO-3100
60 A
80 A
100 A
12 or 4
18 or 6
24 or 8
40
60
80
Basic assemblies include main primary and secondary breakers. Order required QO plug-on feeder breakers. QWIK-GARD breakers, or QOFP filler plates for blank spaces from the Square D Catalog
Digest through your local Square D distributor.
Special Voltages
kVA
Catalog
Numberq
Price
Full
Capacity
Taps
Weight
(Pounds)
Dimensions (Inches)f
H
W
D
Primary Main Circuit Breaker
240 V Primary
600 V Primary
Secondary
Main
Circuit Breaker
Feeder Breakers
Maximum Number
1-Pole or 2-Pole
Maximum
Amps
Single Phase
5
7.5
10
MPZ5S( )F
MPZ7S( )F
MPZ10S( )F
$2314.
2704.
2938.
2-5% FCBN
2-5% FCBN
2-5% FCBN
175
200
215
32.7
32.7
32.7
12.0
12.0
12.0
11.9
11.9
11.9
FAL24040
FAL24060
FAL24080
40A
60A
80A
FAL26015
FAL26015
FAL26020
15 A
15 A
20 A
QO-230
QO-240
QO-260
30 A
40 A
60 A
6 or 3
8 or 4
10 or 5
20
30
40
15
25
MPZ15S( )F
MPZ25S( )F
3814.
5691.
2-5% FCBN
2-5% FCBN
390
390
42.9
42.9
17.4
17.4
13.5
13.5
Q2L2125
Q2L2200
125A
200A
FAL26030
FAL26050
30 A
50 A
QO-280
QO-2125
80 A
125 A
16 or 8
24 or 12
60
100
Maximum Number
1-Pole or 3-Pole
Three Phase
TRANSFORMERS
15
22.5
30
MPZ15T( )F
MPZ22T( )F
MPZ30T( )F
$6005.
7440.
9131.
2-5% FCBN
2-5% FCBN
2-5% FCBN
710
725
755
44.6
44.6
44.6
27.4
27.4
27.4
13.6
13.6
13.6
q Catalog Numbers shown in bold type are available from Distribution Center.
f Dimensions – DO NOT use for construction. Contact your nearest Square D/Schneider
Electric sales office for certified prints.
To Complete Catalog Number:
FAL34080
Q2L3125
Q2L3150
80A
125A
150A
FAL36020
FAL36035
FAL36045
QO-360
QO-380
QO-3100
60 A
80 A
100 A
12 or 4
18 or 6
24 or 8
40
60
80
Special Voltage Codes
Code
Primary Voltage
Secondary Voltage
240
600
208
120/240
120/240
120/240
240s
600s
208Y/120
208Y/120
Single Phase
62
4
60
1. Select the voltage required from chart.
12
20 A
35 A
45 A
2. Insert the voltage code number in place of the ( ) in the catalog
number.
Three Phase
11
7
QO, POWER-ZONE and QWIK-GARD are Registered Trademarks of Square D Company or related companies.
For additional information, reference Bulletin No. 7440BR9401.
12-10
© 2000 Square D
All Rights Reserved
PE2
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type
Open Core and Coil
Class 7400
B
C
Open Core and Coil Transformers Designed for
General Applications for 600 V and Below
Units are designed with 220°C Insulation, Aluminum windings, top terminations, compact
design to save space, UL component recognized, and available in single phase 5 to 75
kVA and three phase 3 to 112.5 kVA. We also have single phase units designed to meet
EN 60742 and units are CE compliant and carry the CE mark 6.7 to 25 kVA.
A
Single Phase Open Core and Coil Transformers –
D
240 X 480 V Primary 120/240 V Secondary 60 Hz
E
Figure 1
Catalog
Number
Price
Degree C
Temp.
Rise
Full Capacity
Taps
5
7.5
10
15
5S1HFOC
7S1HFOC
10S1HFOC
15S1HOC
$1366.
1458.
1617.
1755.
115
115
115
150
none
none
none
none
25
37.5
50
75
25S3HOC
37S3HOC
50S3HOC
75S3HOC
2061.
2745.
3341.
4529.
150
150
150
150
6-2.5% 2+4- a
6-2.5% 2+4- a
6-2.5% 2+4- a
6-2.5% 2+4- a
kVA
C
A
Dimensions (Inches)f
A
B
Weight Figure
(lbs)
C
D
E
8.0
9.0
8.0
9.0
8.0
9.0
14.5 14.0
11.0
14.25
14.25
12.5
8.0
8.0
8.0
13.0
8.0
8.5
8.5
8.5
66
80
100
110
1
1
1
2
14.5
19.0
19.0
19.0
12.5
16.0
17.0
17.0
13.0
13.0
13.0
13.0
8.5
11.0
13.5
13.5
120
230
260
565
2
2
2
2
14.0
16.5
18.0
28.0
a When 240 volt primary taps are 3-5% 1+ and 2-.
f Not for construction. Contact your nearest Square D/Schneider Electric sales office for certified prints.
Three Phase Open Core and Coil Transformers
D
E
B
Figure 2
C
kVA
Catalog
Number
Price
Degree C
Temp.
Rise
A
B
C
3T( )HFOC
6T( )HFOC
9T( )HFOC
15T( )HOC
$1057.
1212.
1630.
1921.
115
115
115
150
8.0
9.5
13.0
13.0
9.0
10.5
18.0
18.0
6.5
8.5
12.5
12.5
7.0
8.25
16.0
16.0
30
45
75
112.5
30T( )HOC
45T( )HOC
75T( )HOC
112T( )HOC
2700.
3250.
4895.
6519.
150
150
150
150
14.0
14.5
19.5
19.5
18.0
18.0
21.0
21.0
12.5
15.0
16.0
19.0
16.0
16.0
16.0
16.0
A
D
B
Figure 3
E
Weight
(lbs)
Figure
2.38
2.75
4.0
8.5
45
80
120
120
3
170
260
365
565
3
D
3
6
9
15
8.5
8.5
11.0
11.0
Voltages
Primary
Secondary
Full Capacity
Taps
12
240
208Y/120
4-2.5% 2+2-
3
480
208Y/120
6-2.5% 2+4-
8
600
208Y/120
4-2.5% FCBN
Voltage Code
E
Dimensions (Inches) f
To Complete Catalog Number:
1. Select the voltage required from chart.
2. Insert the voltage code number in place of the ( ) in the catalog number.
C
Single Phase Open Core and Coil Transformers,
Units comply with CE specification EN 60-742
These models are designed to accommodate voltage systems worldwide. 190/200/208/220x380/400/416/440 V
Primary 110/220 V Secondary 50/60 Hz – UL Listed.
A
kVAc
6.7
D
E
B
Price
Degree C
Temp.
Rise
A
Dimensions (Inches) f
B
C
D
E
Slot
Weight
(lbs)
Figure
EN6S67HFOC $1886.
115
10.0
9.0
11.25
8.0
9.12
.44 X .88
88
4
16
EN16S67HOC
2272.
150
16.5
15.0
12.50
13.0
4.50
.56 X 1.0
130
5
25
EN25S67HOC
2667.
150
17.5
15.0
12.50
13.0
4.50
.56 X 1.0
225
5
c kVA per EN 60-742 and UL 1561.
f Not for construction. Contact your nearest Square D/Schneider Electric sales office for certified prints.
TRANSFORMERS
Figure 4
Catalog
Number
E
E
12
A
D
C
B
Figure 5
3/00
PE2
Discount
Schedule
© 2000 Square D
All Rights Reserved
12-11
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type Transformers
Motor Starting Autotransformers
Class 7400
Motor Starting Autotransformers with Open Core and Coil
• 600 Volts and below
• Class 220°C insulation
• Available in 2-coil or 3-coil to match starter requirements
• UL component recognized
Two-Coil Motor Starting Autotransformers – 60 Hz, Medium Duty, Taps 50%/65%/80%/100%
Horse
Power
10
20
30
50
Catalog
Number
MSA10T(
MSA20T(
MSA30T(
MSA50T(
Price
Dimensions
A
B
8.25
8.25
8.25
8.25
10.75
10.75
10.75
10.75
D
E
Weight
(Pounds)
Figure
12.0
12.0
12.0
12.0
9.0
9.0
9.0
9.0
7.5
7.5
7.5
7.5
45
45
65
65
A
A
A
A
C
)H2
)H2
)H2
)H2
$1031.
1096.
1165.
1199.
75
100
125
150
MSA75T( )H2
MSA100T( )H2
MSA125T( )H2
MSA150T( )H2
1535.
1664.
2019.
2187.
9.5
9.5
11.0
11.0
12.25
12.25
14.5
14.5
11.0
11.0
11.5
11.5
9.0
9.0
9.0
9.0
7.5
7.5
7.5
7.5
95
95
125
125
A
A
A
A
200
250
300
400
MSA200T(
MSA250T(
MSA300T(
MSA400T(
2656.
3087.
3464.
4138.
11.0
14.25
14.25
18.5
14.5
17.0
17.0
19.5
11.5
12.25
12.25
13.37
9.0
9.0
9.0
17.5
7.5
9.0
9.0
11.5
145
160
180
225
A
A
A
A
)H2
)H2
)H2
)H2
Voltage Code
Primary Voltage
200
208
201
240
202
480
203
600
C
A
D
E
7/16" Dia. Mounting Holes (4)
(10 Hp–50 Hp)
9/16" Dia. Mounting Holes (4)
(75 Hp–400 Hp)
B
Figure A
Three-Coil Motor Starting Autotransformers – 60 Hz, Medium Duty, Taps 50%/65%/80%/100%
Horse
Power
TRANSFORMERS
10
20
30
50
Catalog
Number
MSA10T(
MSA20T(
MSA30T(
MSA50T(
Price
Dimensions
A
B
C
D
E
Weight
(Pounds)
Figure
7.0
7.0
7.25
7.25
9.0
9.0
9.0
9.0
4.0
4.0
6.0
6.0
37
37
55
85
B
B
B
B
)H3
)H3
)H3
)H3
$1031.
1096.
1165.
1199.
7.5
7.5
7.5
7.5
10.5
10.5
13.0
13.0
75
100
125
150
MSA75T( )H3
MSA100T( )H3
MSA125T( )H3
MSA150T( )H3
1535.
1664.
2019.
2187.
12.0
12.0
12.0
14.0
14.5
14.5
14.5
15.5
9.5
9.5
9.5
10.0
9.0
9.0
9.0
9.0
7.25
7.25
7.25
7.5
85
85
135
135
B
B
B
B
200
250
300
400
MSA200T(
MSA250T(
MSA300T(
MSA400T(
2656.
3087.
3464.
4138.
14.0
14.0
14.0
14.75
15.5
15.5
15.5
18.25
10.0
10.5
10.5
12.0
9.0
9.0
9.0
9.0
7.5
7.62
9.12
9.12
135
145
210
230
B
B
B
B
)H3
)H3
)H3
)H3
Voltage Code
Primary Voltage
200
208
201
240
202
480
203
600
B
C
A
To Complete Catalog Number:
1. Select the voltage required from chart.
2. Insert the voltage code number in place of the ( ) in the catalog
number.
12
E
1/2 x 7/8"
Mounting Slots (4)
D
Figure B
12-12
© 2000 Square D
All Rights Reserved
PE2
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Industrial Control Transformers
Class 9070
Triple Rated Voltage Codes
k The Type T unit is designed for the global market and
is the best choice when size and cost are of concern.
This is our most popular and complete offering of
industrial control transformers. Also available are the
Type TF units with factory installed primary and
secondary fuse blocks. The Type T and TF offering is
50/60 Hz rated and includes customer installable
accessories such as FINGERSAFE® covers, fuse
pullers, fuse blocks, and fuse clips.
As part of the Type T designs are MultiTap ™ units
having a variety of primary voltages on just one
transformer. Our new Universal Control Transformer
will provide 120 V, or near 120 V, power from all
common primary voltages, 208 through 600 V, and is
listed as voltage code D50.
k The Type E unit is our high regulation design with
exceptional voltage regulation. These control
transformers are constructed using traditional
materials and manufacturing techniques. When
exceptional regulation and very low temperature rise
are an absolute necessity, choose the Type E units.
Selection Guide
1. Determine inrush and sealed VA of each coil in the
control circuit and VA of all other components
3. Total the inrush VA of all coils that are starting at the
same time and all loads and coils that are running
(using the regulation chart to give possible units to be
used)
4. Take VA size from step two, go to standard VA size in
chart. Make sure inrush VA from chart is greater than
total VA from step three. (If not go to next larger VA size
and repeat)
If your supply voltage is stable and fluctuates less than 5%
we recommend you use the 90% secondary voltage
column. If your supply voltage is not stable and fluctuates
more than 10% we recommend you use the 95%
secondary voltage column. We recommend that you never
use the 85% secondary voltage column since magnetic
devices lose life expectancy if they are continuously
started at 85% of rated voltage.
Primary Voltage
Secondary Voltage
D1
240 x 480
230 x 460
220 x 440
120
115
110
D5
600
575
550
120
115
110
D12
480
460
440
240
230
220
D24
120
115
110
120
115
110
D31
240 x 480
230 x 460
220 x 440
120/240
115/230
110/220
D32
240/480/600
230/460/575
220/440/550
99/120
95/115
91/110
D37
600
575
550
120/240
115/230
110/220
D50
240/416/480/600
230/400/460/575
220/380/440/550
208/500
99/120/130
95/115/125
91/110/120
85/100/110
D55
120 x 240
115 x 230
110 x 220
120/240
115/230
110/220
D62
600
575
550
240
230
220
D95
208/240/480
200/230/460
220/440
120
115
110
Regulation Chart for Type T
Inrush VA @ 20% power factor
VA
25
50
75
100
150
221
193
271
339
666
298
266
396
499
893
375
339
520
659
1120
171
151
210
266
529
240
215
318
404
731
311
282
430
549
942
200
250
300
350
500
588
1416
1634
1894
3197
815
1910
2184
2592
4104
1041
2388
2709
3261
4981
459
1057
1194
1392
2374
659
1494
1681
2005
3195
866
1936
2169
2621
4019
750
1000
1500
2000
3000
5000
3770
6587
19324
31384
26539
53111
5515
9079
23983
38777
39934
85265
7231
11430
28607
46161
52713
116277
2887
4706
15066
24794
19355
39368
4391
6886
19361
31630
30721
66309
5945
9051
23756
38667
42216
93882
Regulation Chart for Type E
Inrush VA @ 20% power factor
VA
Inrush VA @ 40% power factor
95% Secondary 90% Secondary 85% Secondary 95% Secondary 90% Secondary 85% Secondary
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
25
50
75
100
150
95
164
387
479
755
...
213
487
606
1177
146
277
622
770
1532
60
123
284
346
567
...
168
375
463
930
119
225
798
613
1252
200
250
300
350
500
1260
1530
2030
2920
4230
1883
2327
2981
4586
5984
2419
2995
3800
5981
7707
910
1115
1455
2180
3120
1462
1811
2290
3637
4661
1950
2419
3038
4903
6229
750
1000
1500
2000
3000
5000
7430
10300
19200
27750
31800
86100
11460
16873
30042
45194
82333
148768
14736
21734
39217
60022
108205
202077
5380
7450
14500
21750
26750
72600
8907
13145
23859
36901
66072
126887
11891
17571
32179
50334
89509
175552
Listing
For complete technical specification and selection data
use the Square D Fax-on-Demand system.
Dial 1-800-557-4556, follow prompts, and request
document code 1348, or order catalog 9070CT9901.
Inrush VA @ 40% power factor
95% Secondary 90% Secondary 85% Secondary 95% Secondary 90% Secondary 85% Secondary
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
File
Type
UL
E61239
cUL
E61239
T1500-T5000
CSA
LR37055, Guide 184-N-90
T25-T1000, EO17-EO11
947923, EN 60742/01.89 (TUV ref: 00941-RAG/sg E9371495E01)
T25-T200
9579078, EN 60742/01.89 (TUV ref: 00941-RAG/sg E9471921.02E01)
T250-T1000
9579078, EN 60742/01.89 (TUV ref: 00941-RAG/sg E9471921.02E01)
T1500-T5000
EN (CE)
T25-T5000, EO17-EO11
TRANSFORMERS
2. Total all sealed VA of all operating coils and other loads
VA (Determines minimal VA size required for the circuit)
Voltage Code
12
Square D manufactures two types of industrial control
transformers – a global type and a high regulation type.
FINGERSAFE is a Registered Trademark of Square D Company or related companies.
MultiTap is a Trademark of Square D Company or related companies.
3/00
© 2000 Square D
All Rights Reserved
12-13
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Industrial Control Transformers
Class 9070
Key to Price Column
Headings
Voltage Code
Primary Voltages
Secondary Voltages
Key for Dimensions & Accessory
Square D manufactures a wide variety of voltage combinations for control transformers. The voltage combinations are
expressed as “Voltage Codes” and these codes are embedded within the catalog number of the transformer. Standard
codes are listed, if the voltage combination you require is not listed, call your Square D Distributor for assistance.
Type T
D1a
D31a
240 x 480 240 x 480
120
120/240
I
I
D5a
600
120
I
D37a
600
120/240
I
D24a
120
120
I
D55a
120 x 240
120/240
I
D3
208
120
I
D4
277
120
I
D51
208/277
120
I
D60
277
120/240
I
n/a
$ 57.00
60.00
63.00
83.00
n/a
$ 41.00
49.70
55.00
70.00
n/a
$142.00
148.00
149.00
158.00
n/a
$142.00
148.00
149.00
158.00
n/a
$142.00
148.00
149.00
158.00
n/a
$ 41.00
49.70
55.00
70.00
n/a
$ 41.00
49.70
55.00
70.00
n/a
$142.00
148.00
149.00
158.00
n/a
$142.00
148.00
149.00
158.00
62.00
72.00
80.00
85.00
106.00
107.00
113.00
132.00
138.00
155.00
89.00
110.00
113.00
131.00
143.00
216.00
217.00
219.00
220.00
227.00
216.00
217.00
219.00
220.00
227.00
216.00
217.00
219.00
220.00
227.00
89.00
110.00
113.00
131.00
143.00
89.00
110.00
113.00
131.00
143.00
216.00
217.00
219.00
220.00
227.00
216.00
217.00
219.00
220.00
227.00
147.00
178.00
254.00
309.00
429.00
721.00
215.00
254.00
372.00
413.00
677.00
916.00
202.00
254.00
356.00
413.00
582.00
916.00
255.00
271.00
390.00
423.00
724.00
916.00
255.00
271.00
390.00
423.00
724.00
916.00
255.00
271.00
390.00
423.00
724.00
916.00
202.00
254.00
356.00
413.00
582.00
916.00
202.00
254.00
356.00
413.00
582.00
916.00
255.00
271.00
390.00
423.00
724.00
916.00
255.00
271.00
390.00
423.00
724.00
916.00
UL/CSA/
NOM
VA
CE VA
Type
25
50
75
100
150
25
50
75
100
150
T25
T50
T75
T100
T150
$ 33.50
35.30
41.80
46.90
50.00
200
250
300
350
500
200
160
200
250
300
T200
T250
T300
T350
T500
750
1000
1500
2000
3000
5000
500
630
1000
1500
2000
3000
T750
T1000
T1500
T2000
T3000
T5000
Type T
D2
240 x 480
24
I
D59
240 x 480
12/24
I
D13
120
12/24
I
D23
120/240
24
I
D54
120/240
12/24
I
D14
208
24
I
D25
277
24
I
D36
600
12/24
I
$ 41.00
49.70
55.00
70.00
89.00
$142.00
148.00
149.00
158.00
216.00
$ 41.00
49.70
55.00
70.00
89.00
$ 41.00
49.70
55.00
70.00
89.00
$142.00
148.00
149.00
158.00
216.00
$ 41.00
49.70
55.00
70.00
89.00
$142.00
148.00
149.00
158.00
216.00
$142.00
148.00
149.00
158.00
216.00
T250
T300
T350
T500
T750 q
110.00
113.00
131.00
143.00
202.00
217.00
219.00
220.00
227.00
255.00
110.00
113.00
131.00
143.00
202.00
110.00
113.00
131.00
143.00
202.00
217.00
219.00
220.00
227.00
255.00
110.00
113.00
131.00
143.00
202.00
217.00
219.00
220.00
227.00
255.00
217.00
219.00
220.00
227.00
255.00
T1000 q
254.00
271.00
254.00
254.00
271.00
254.00
271.00
271.00
UL/CSA/
NOM
VA
CE VA
50
75
100
150
200
50
75
100
150
200
T50
T75
T100
T150
T200
250
300
350
500
750
160
200
250
300
500
1000
630
Type
q See Control Transformer Catalog: 9070CT9901 for Dimensions different than digest
Type T
UL/CSA/NOM
VA
CE VA
Type
D15
240 x 480
24/120
I
D12a
480
240
I
D22
480
277
I
D62a
600
240
I
50
75
100
150
200
50
75
100
150
200
T50
T75
T100
T150
T200
$ 41.00
49.70
63.00
70.00
89.00
$ 41.00
49.70
55.00
70.00
89.00
$142.00
148.00
149.00
158.00
216.00
$142.00
148.00
149.00
158.00
216.00
250
300
350
500
750
160
200
250
300
500
T250
T300
T350
T500
T750
113.00
132.00
138.00
155.00
215.00
110.00
113.00
131.00
143.00
202.00
217.00
219.00
220.00
227.00
255.00
217.00
219.00
220.00
227.00
255.00
1000
1500
2000
3000
5000
630
1000
1500
2000
3000
T1000
T1500
T2000
T3000
T5000
254.00
372.00
413.00
677.00
916.00
254.00
356.00
413.00
582.00
916.00
271.00
390.00
423.00
724.00
916.00
271.00
390.00
423.00
724.00
916.00
TRANSFORMERS
a See Page 12-13 for triple ratings on this voltage code.
12
How to Order:
To Order Specify:
k Class Number
k Type Number
k Voltage Code
Catalog Number
Class
Type
Voltage Code
9070
T500
D1
FINGERSAFE is a Registered Trademark of Square D Company or related companies.
12-14
© 2000 Square D
All Rights Reserved
CP8
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Industrial Control Transformers
Class 9070
Type T MultiTap™
UL/CSA/NOM
VA
CE VA
Type
D18
208/277/380
95/115
II
D20
208/230/460
115
II
D95 a
208/240/480
120
II
D32 a
230/460/575
95/115
II
D33
380/400/415
115/230
I
D50 a
240/416/480/600
99/120/130
IV
D19
208/240/277/380/480
24
III
D52
380/400/415
12/24
I
50
50
T50
$ 57.00
$ 57.00
$157.00
$ 57.00
$ 57.00
$ 96.00
$ 41.00
$157.00
75
75
T75
60.00
60.00
158.00
60.00
60.00
103.00
49.70
158.00
100
100
T100
63.00
63.00
168.00
63.00
63.00
106.00
55.00
168.00
150
150
T150
83.00
83.00
235.00
83.00
83.00
111.00
70.00
235.00
200
200
T200
107.00
107.00
234.00
107.00
107.00
127.00
89.00
234.00
250
160
T250
113.00
113.00
237.00
113.00
113.00
138.00
110.00
237.00
300
200
T300
132.00
132.00
247.00
132.00
132.00
151.00
113.00
247.00
350
250
T350
138.00
138.00
287.00
138.00
138.00
156.00
131.00
287.00
500
300
T500
155.00
155.00
290.00
155.00
155.00
199.00
143.00
290.00
750
500
T750 q
215.00
215.00
320.00
215.00
215.00
231.00
202.00
320.00
1000
630
T1000 q
254.00
254.00
409.00
254.00
254.00
302.00
254.00
409.00
a See page 12-13 for triple ratings on this voltage code.
q See Control Transformer Catalog: 9070CT9901 for Dimensions different than Digest.
Type Dimension Key
A
B
C
Dq
E
F
Slots
Fig.
I
II
III
IV
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
T25 & T50
T25
...
...
3.09
78.5
3.00
76.2
2.58
65.5
3.84
97.5
2.00
50.8
2.50
63.5
.20x.38
5.1x9.7
1
...
...
T25
...
4.00
101.6
3.43
87.1
2.64
67.0
4.80
121.9
2.00
50.8
2.50
63.5
.20x.48 5.1x12.2
2
...
...
T50
T50
4.19
106.4
3.43
87.1
2.89
73.4
4.99
126.7
2.38
60.5
2.81
71.4
.20x.48 5.1x12.2
2
T75 & T100
T50
...
...
3.34
84.8
3.38
85.8
2.89
73.4
4.09
103.9
2.38
60.5
2.81
71.4
.20x.48 5.1x12.2
1
...
...
3.59
91.2
3.75
95.3
3.20
81.3
4.34
110.2
2.88
73.2
3.13
79.5
.20x.38
5.1x9.7
1
T75 & T100
T75
4.88
124.0
3.75
95.3
3.20
81.3
5.68
144.2
2.88
73.2
3.13
79.5
.20x.38
5.1x9.7
2
T150 & T200 T75, T100 & T150
...
...
T250
...
T150
T100
5.25
133.4
3.75
95.3
3.25
82.6
6.05
153.6
2.88
73.2
3.13
79.5
.20x.38
5.1x9.7
2
T300
T200
T200
T150
4.70
119.4
4.50
114.3
3.80
96.5
5.50
139.7
2.56
65.0
3.75
95.3
.20x.38
5.1x9.7
2
T350
T250 & T300
T250
T200 & T250
5.09
129.3
4.50
114.3
3.80
96.5
5.89
149.6
3.00
76.2
3.75
95.3
.20x.38
5.1x9.7
2
T500
T350
T350 & T300
T300
5.46
138.7
4.50
114.3
3.80
96.5
6.26
159.0
3.56
90.4
3.75
95.3
.28x.56 7.1x14.2
2
T750
T500
T500
T350 & T500
5.66
143.8
5.25
133.4
4.43
112.5
6.46
164.0
3.43
87.1
4.38
111.3
.28x.56 7.1x14.2
2
T1000
T750
T750
T750
6.04
153.4
5.25
133.4
4.43
112.5
6.84
173.7
4.31
109.5
4.38
111.3
.28x.56 7.1x14.2
2
T1500
T1000
T1000
T1000
5.81
147.6
7.06
179.3
6.16
156.5
6.61
167.9
4.13
104.9
5.81
147.6
.28x.56 7.1x14.2
2
T2000
T1500
T1500
T1500
7.04
178.8
7.06
179.3
6.16
156.5
7.84
199.1
4.56
115.8
5.81
147.6
.28x.56 7.1x14.2
2
T3000
T2000
T2000
T2000
6.86
174.2
9.00
228.6
8.46
214.9
7.26
184.4
4.63
117.6
7.63
193.8
.44x.69 11.2x17.5
3
T5000
T3000
T3000
T3000
8.73
221.7
9.00
228.6
8.46
214.9
9.13
231.9
6.56
166.6
7.63
193.8
.44x.69 11.2x17.5
3
q Dimension with FINGERSAFE® Covers
D
D
B
A
Accessories
FINGERSAFE® Covers (not supplied with unit)
B
A
Type Accessory Keyq
Type
C
C
I
Description
Price
2 covers per kit
$6.60
N/A
2 covers per kit
9.00
T25-T5000
2 covers per kit
9.20
II
III, IV
FSC-1
T25-T200
T25-T100
N/A
FSC-2
T250-T5000
T150-T5000
FSC-23
N/A
N/A
q Kits must be ordered separately. Also supplied in bulk packages of 100 individual
covers. Add “B” to Type number (available only on FSC-1B and FSC-2B).
F
E
D
E
Figure 2
A
B
Fuse Pullers (use on TF and FB accessory)
Catalog
Price
9070FP-1
$9.50
Jumper Kits
Catalog
Number
C
Type Accessory Key
Description
Price
Two jumpers
per bag
Minimum order
30033-027-54 T250-T5000 T200-T3000 T25-T3000 of 50 kits
$1.60
I
30033-027-53 T25-T200
II
T25-T150
III, IV
N/A
1.60
TRANSFORMERS
F
12
Figure 1
NOTE: Jumpers are supplied with voltage codes that require them. If additional kits are
required, order per above chart.
F
Figure 3
E
FINGERSAFE is a Registered Trademark of Square D Company or related companies.
MultiTap is a Trademark of Square D Company or related companies.
3/00
CP8
Discount
Schedule
© 2000 Square D
All Rights Reserved
12-15
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Industrial Control Transformers
Class 9070
Type TF: Factory Installed Primary and Secondary Fuse Blocks
B
D
A
D1 a
240 X 480
120
I
50
50
TF50
$ 50.00
75
75
TF75
56.00
100
100
TF100
61.00
150
150
TF150
65.00
200
200
TF200
77.00
250
160
TF250
87.00
300
200
TF300
95.00
350
250
TF350
100.00
500
300
TF500
120.00
750
500
TF750
161.00
1000
630
TF1000
194.00
1500
1000
TF1500
269.00
2000
1500
TF2000
324.00
a See Page 12-13 for triple ratings on this voltage code.
UL/CSA
VA
G
C
F
E
CE VA
D2
240 x 480
24
I
$ 56.00
...
70.00
84.00
...
...
129.00
...
158.00
...
...
...
...
Type
D3
208
120
I
$ 56.00
...
70.00
84.00
...
...
129.00
...
158.00
...
...
...
...
D5 a
600
120
I
$ 56.00
...
70.00
84.00
...
...
129.00
...
158.00
...
...
...
...
D20
208/230/460
115
II
$ 82.00
...
89.00
109.00
134.00
...
166.00
...
185.00
...
...
...
...
D23
120/240
24
I
$ 56.00
64.00
70.00
84.00
89.00
116.00
129.00
131.00
158.00
...
...
...
...
Dimensions–Type TF Only
I
25 VA
...
50 VA
...
75 VA
...
...
100 VA
...
150 VA
200 VA
250 VA
300 VA
350 VA
...
...
500 VA
...
750 VA
1000 VA
1500 VA
2000 VA
VA Key
II
...
...
25 VA
...
50 VA
75 VA
...
...
...
100 VA
150 VA
...
200 VA
250 VA
300 VA
...
350 VA
...
500 VA
750 VA
1000 VA
1500 VA
III
...
25 VA
...
50 VA
...
...
75 VA
...
100 VA
...
...
150 VA
200 VA
250 VA
...
300 VA
...
350 VA
500 VA
750 VA
1000 VA
1500 VA
Figure
A
B
C
Dq
E
F
Gf
SLOT
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3.09
4.00
3.09
4.19
3.34
3.59
4.88
3.34
4.88
3.59
3.59
5.25
4.70
5.09
5.09
5.46
5.46
5.46
5.66
6.04
5.81
7.04
3.00
3.43
3.00
3.43
3.38
3.75
3.75
3.38
3.75
3.75
3.75
3.75
4.50
4.50
4.50
4.50
4.50
4.50
5.25
5.25
7.06
7.06
4.00
4.00
4.00
4.25
4.25
4.55
4.55
4.25
4.55
4.55
4.55
4.55
5.10
5.10
5.10
5.10
5.10
5.10
5.73
5.73
7.46
7.46
3.84
4.80
3.84
4.99
4.09
4.34
5.68
4.09
5.68
4.34
4.34
6.05
5.50
5.89
5.89
6.26
6.26
6.26
6.46
6.84
6.61
7.84
2.00
2.00
2.00
2.38
2.38
2.88
2.88
2.38
2.88
2.88
2.88
2.88
2.56
3.00
3.00
3.56
3.56
3.56
3.43
4.31
4.13
4.56
2.50
2.50
2.50
2.81
2.81
3.13
3.13
2.81
3.13
3.13
3.13
3.13
3.75
3.75
3.75
3.75
3.75
3.75
4.38
4.38
5.81
5.81
4.20
4.20
4.20
4.45
4.45
4.75
4.75
4.45
4.75
4.75
4.75
4.75
5.30
5.30
5.30
5.30
5.30
5.30
5.93
5.93
7.66
7.66
.20 x .38
.20 X .48
.20 x .38
.20 X .48
.20 X .48
.20 x .38
.20 x .38
.20 X .48
.20 x .38
.20 x .38
.20 x .38
.20 x .38
.20 x .38
.20 x .38
.20 x .38
.20 x .38
.20 x .38
.20 x .38
.28 X .56
.28 X .56
.28 X .56
.28 X .56
q Dimensions with FINGERSAFE® covers installed.
f Dimensions with fuse pullers installed.
Field Installed Fuse Options
Field-Installable Secondary Fuse Clips
Primary and Secondary Fusing
Type
Type Accessory Key
I
II
III, IV
FB-3A 25-200 25-150 N/A
FB-3B 2502000
2001500
251500
Description
Price
Three pole fuse block for primary
fusing, accomodates 1-1/2" x
$26.40
13/32" midget fuse (2 rejection
and 1 non-rejection)
Three pole fuse block for primary
and secondary fusing, accomodates 1-1/2" x 13/32" midget fuse 26.40
(2 rejection and 1 non-rejection)
Primary Fusing
Type
FB-2A 25-200 25-150 N/A
TRANSFORMERS
2001500
251500
Description
Two pole fuse block for primary
and secondary fusing, accommo- $22.70
dates 1-1/2" x 13/32" midget fuse
(2 rejection)
Two pole fuse block for primary
fusing, accomodates 1-1/2" x 13/ 22.70
32" midget fuse (2 rejection)
D1:240 x 480-120
12
I
CE VA
50
100
150
160
300
500
Catalog Number
9070T50D1SF41
9070T100D1SF41
9070T150D1SF41
9070T250D1SF41
9070T500D1SF41
9070T750D1SF41
II
Price
$ 40.30
52.00
55.00
79.00
113.00
154.00
Description
III, IV
Price
SF25A
25-200 25-150 N/A
Secondary fuse block accommodates 1-1/4" x 1/4" fuse
$6.60
SF25B
2502000
Secondary fuse block accommodates 1-1/4" x 1/4" fuse
6.60
Secondary fuse clip accommodates 1-1/2" x 13/32" midget
fuse
5.40
Secondary fuse clip accommodates 1-1/2" x 13/32" midget
fuse
5.40
2001500
251500
SF41Ac 25-200 25-150 N/A
2002000
252000
Price
Factory Installed Secondary Fuse Clips
UL/CSA VA
50
100
150
250
500
750
Type Accessory Key
SF41Bc N/A
Type Accessory Key
I
II
III, IV
FB-2B 2502000
Type
FB-1A
25-200 25-150 N/A
One pole fuse block for secondary fusing, accomodates 1-1/2" 15.80
x 13/32" midget fuse (1 nonrejection)
FB-1B
2502000
One pole fuse block for secondary fusing, accomodates 1-1/2" 15.80
x 13/32" midget fuse (1 nonrejection)
2001500
251500
c SF41 can be installed on the following voltage codes: D1, D5, D24, D3, D4,
D51, D2, D23, D14, D25, D20, D95, D19.
How to Order:
To Order Specify:
k Class Number
k Type Number
k Voltage Code
k Field Fuse Option
Catalog Number
Class
Type
Voltage Code
9070
TF500
D1
9070
FB-3B
FINGERSAFE is a Registered
Trademark of Square D Company
or related companies.
12-16
© 2000 Square D
All Rights Reserved
CP8
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Proof date: 12/13/99, 2:59 PM
Industrial Control Transformers
Class 9070, 9991
Type E
VA
Type
Make changes: Initials _______________ Date:
_____________
Type EO3D1
Dimensions - See Figure 4
Weight
(lbs.)
60 Hz
50 Hz
A
B
C
E
F
Slot
EO17
EO1
EO18
25
50
75
25
35
75
3.31
3.31
3.78
3.00
3.00
3.38
2.50
2.50
2.81
1.75
2.00
2.19
2.50
2.50
2.81
.20 x .38
.20 x .38
.20 x .38
1.9
2.2
3.5
EO2
EO3
EO4
100
150
300
70
120
240
3.78
4.44
5.56
3.38
3.75
4.50
2.81
3.13
3.75
2.38
2.88
3.25
2.81
3.13
3.75
.20 x .38
.20 x .38
.20 x .38
3.8
6.0
10.5
EO16
EO51
EO61
350
500
750
280
400
500
6.19
6.56
7.94
4.50
5.25
5.25
3.75
4.38
4.38
3.81
3.81
5.13
3.75
4.38
4.38
.20 x .38
.28 x .41
.28 x .41
13.2
17.2
24.5
EO71
EO81
EO91
1000
1500
2000
900
1300
1800
7.94
8.59
9.22
6.00
7.06
7.06
5.00
6.03
6.03
4.75
5.88
6.50
5.00
5.81
5.81
.28 x .63
.44 x .69
.44 x .69
30.5
45.0
56.0
EO10
EO11
3000
5000
3000
5000
9.44
12.06
9.00
9.00
8.38
8.38
5.88
8.50
7.63
7.63
.44 x .69
.44 x .69
72.0
115.0
Type E Stocked Voltages
B
A
C
F
VA
Type
E
Figure 4
60 Hz
Stocked Voltage Codes
50 Hz
Price
EO17
25
25
D1, D2, D3
$ 35.80
EO1
50
35
D1, D2, D7
45.00
EO18
75
75
D1, D2
52.00
EO2
100
70
D1, D2
62.00
EO3
150
120
D1, D7
EO4
300
240
D1, D5, D7
126.00
EO16
350
280
D1, D2
134.00
EO51
500
400
D1, D5, D6
152.00
EO61
750
500
D1, D5
215.00
EO71
1000
900
D1, D5
247.00
EO81
1500
1300
D1
379.00
EO91
2000
1800
D1
459.00
EO10
3000
3000
D1
662.00
EO11
5000
5000
D1
1009.00
70.00
Transformers with Leads
OK TO PRINT: Initials: _______________ Date_____________
Transformers with leads, instead of screw terminals, are available. See the following chart
for VA sizes and voltage combinations. Consult your nearest Square D/Schneider Electric
sales office for further details. Lead length is 25".
Type EL and KL with Leads
Type
VA
Voltage
Price
EL1D9
EL2D9
EL3D9
KL300D9
50
100
150
300
480-120
480-120
480-120
480-120
$ 70.00
94.00
107.00
174.00
Class 9070 Type EL, KL
Dimensions – See Figure 5
Type
Weight
(lbs.)
A
B
C
E
F
G
H
EL1
2.2
25⁄8
3
21⁄2
2
21⁄2
13⁄64
3⁄8
EL2
3.8
3
33⁄8
213⁄16
23⁄8
213⁄16
13⁄64
3⁄8
EL3
6.0
35⁄8
33⁄4
31⁄8
27⁄8
31⁄8
13⁄64
3⁄8
KL300
8.0
31⁄2
41⁄2
33⁄4
29⁄16
33⁄4
13⁄64
3⁄8
Separate NEMA Type 1 Enclosures for Transformers
Figure 5
For Use With
UE7
EO1, EO17, T50
LG1
EO2, EO3, EO4, EO15, EO16, EO18, EO19, T75, T100, T150,
T200, T250, T300, T350, T500
SDG4
EO51, EO61, T750, T1000, EO71
User must drill mounting holes. Refer to pages 13-105 and 13-106 for dimensions.
How to Order:
To Order Specify:
3/00
CP8
Discount
Schedule
Catalog Number
Class
Type
Voltage Code
9070
E051
D1
© 2000 Square D
All Rights Reserved
12
k Class Number
k Type Number
k Voltage Code
TRANSFORMERS
Class 9991 Type
12-17
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Transformer Disconnects
Class 9070
Class 9070 Transformer Disconnect – Improved Design
k Up To 34% Less Panel Space
k UL Listed, File E137621
k CSA certified (NEMA Type 1 only), File LR37055
Transformer disconnects mount inside or outside a control system enclosure and
provide power to auxiliary single-phase loads when the main three-phase
disconnect is either “on” or “off.” The transformer disconnect is normally wired to the
line side of the control panel's main disconnect. This convenient source of 120 V
power can be used for auxiliary or isolated loads, such as panel lighting, portable
power tools, and programmable controller equipment.
The standard enclosure is a lockable NEMA Type 1 for general purpose
applications. The disconnect switch is rated at 45 Amperes, 600 volts, and has an
external handle mechanically interlocked with the enclosure cover. The handle can
lock in the “off” position. There is also a standard fusible and grounded transformer
secondary.
Transformer Disconnects available in NEMA Type 1 Standard,
NEMA Type 12 Standard, and NEMA Type 1 Mini.
Primary fuse holders and secondary fuse holders for branch circuit protection are now standard, complying with National Electric Code
requirements.
NEMA Type 1 Mini Enclosure D1 = 240/480 V-120 V 230/460 V-115 V 220/440 V-110 V 50/60 Hz
Transformer
Continuous
VA
Catalog
Numberq
Price
Enclosure
Dimensions
100
250
500
MN100G0D1
MN250G0D1
MN500G0D1
$ 417.
464.
511.
G0
G0
G0
NEMA Type 1 Standard Enclosure
A
B
C
D
E
F
G
H
I
J
10.3
10.3
10.3
2.0
2.0
2.0
2.65
2.65
2.65
11.3
11.3
11.3
7.0
7.0
7.0
7.81
7.81
7.81
15.25
15.25
15.25
2.09
2.09
2.09
.32
.32
.32
1.0
1.0
1.0
D1 = 240/480 V-120 V 230/460 V-115 V 220/440 V-110 V 50/60 Hz
Transformer
Continuous
VA
Catalog
Numberq
Price
Enclosure
Dimensions
250
500
750
SK250G1D1
SK500G1D1
SK750G1D1
$ 422.
464.
522.
1000
1500
2000
3000
SK1000G1D1
SK1500G2D1
SK2000G2D1
SK3000G2D1
686.
1015.
1154.
1464.
A
B
C
D
E
F
G
H
I
J
G1
G1
G1
10.8
10.8
10.8
1.7
1.7
1.7
6.0
6.0
6.0
11.8
11.8
11.8
9.4
9.4
9.4
8.96
8.96
8.96
16.81
16.81
16.81
2.09
2.09
2.09
.32
.32
.32
1.0
1.0
1.0
G1
G2
G2
G2
10.8
13.8
13.8
13.8
1.7
1.7
1.7
1.7
6.0
10.0
10.0
10.0
11.8
14.8
14.8
14.8
9.4
13.4
13.4
13.4
8.96
12.21
12.21
12.21
16.81
23.06
23.06
23.06
2.09
2.09
2.09
2.09
.32
.32
.32
.32
1.0
1.0
1.0
1.0
NEMA Type 12 Standard Enclosuret D1 = 240/480 V-120 V 230/460 V-115 V 220/440 V-110 V 50/60 Hz
Transformer
Continuous
VA
Catalog
Number
Price
Enclosure
Dimensions
250
500
750
SK250A2D1
SK500A2D1
SK750A2D1
$1023.
1066.
1129.
1000
1500
2000
3000
SK1000A2D1
SK1500A2D1
SK2000A2D1
SK3000A2D1
1161.
1277.
1361.
1699.
A
B
C
D
E
F
G
H
I
J
K
A2
A2
A2
13.5
13.5
13.5
2.86
2.86
2.86
6.0
6.0
6.0
14.5
14.5
14.5
16.5
16.5
16.5
13.49
13.49
13.49
25.56
25.56
25.56
2.44
2.44
2.44
4.25
4.25
4.25
15.75
15.75
15.75
.32DIA
.32DIA
.32DIA
A2
A2
A2
A2
13.5
13.5
13.5
13.5
2.86
2.86
2.86
2.86
6.0
6.0
6.0
6.0
14.5
14.5
14.5
14.5
16.5
16.5
16.5
16.5
13.49
13.49
13.49
13.49
25.56
25.56
25.56
25.56
2.44
2.44
2.44
2.44
4.25
4.25
4.25
4.25
15.75
15.75
15.75
15.75
.32DIA
.32DIA
.32DIA
.32DIA
q Catalog numbers shown in bold type are normally stocked items.
t Rated NEMA Type 3R by adding form N3.
D
A
B
C
ON
E
OFF
TRANSFORMERS
1/2"- 3/4"
Knockouts
90¡
I
G
J
12
F
H
1/2"- 3/4" Conduit
Enclosure Type G0, G1, G2
12-18
© 2000 Square D
All Rights Reserved
Enclosure Type A2
CP1
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Transformer Disconnects
Class 9070
Special Voltage Codes (use adder)
Standard Features
k Sizes
k Switch
k Enclosure
k Type TF
Transformer
k
k
k
k
100 through 3000 VA
– 600 V, 45 A 100,000 A Short Circuit Withstand
Integrated Rating When Protected by
Class CC Fuses.
NEMA Type 1
– 230/460-115 V
– Top-mounted Fuse Block
– Accommodates Two Class CC Time Delay
Primary Fuses and One Secondary Fuse
1-1/2" x 13/32"
Knockouts
Conveniently Located
Ground Terminal
External Mounting Flanges with Slotted Holes for “Hook and
Hang” Mounting
90 degrees Access Cover Stop
Voltage
Code
Primary
Voltage
Secondary
Voltage
D3
208
120
D4
277
120
D5
550
575
600
110
115
120
110
D6
380
D17
415
110
D24
110
115
120
110
115
120
Please contact your nearest Square D/Schneider Electric sales office for other voltages.
Cross Reference
Old Square D Number
Old Square D Number
New Square D Number
SK5271M
SK5271N
SK250G1
SK250G1
MN100G0D1
MN250G0D1
SK5271Q,R
SK5271S,J
SK5271T,K
SK250G1
SK500G1
SK750G1
SK250G1D1
SK500G1D1
SK750G1D1
SK5271U
SK5271V
SK5271W
SK5271X
SK1000G1
SK1500G2
SK2000G2
SK3000G2
SK1000G1D1
SK1500G2D1
SK2000G2D1
SK3000G2D1
Type SK transformer disconnects–UL Listed: File E137621: CSA certified: File LR37055.
Factory Modifications For NEMA Type 1 t
Factory
Modification
Forms
Type TF control power transformer with top mounted fuse
block provides wiring ease in minimal space.
Units Stocked with Factory Modifications:
9070SK500G1D1F11
9070SK500G1D1G13
9070SK1000G1D1G13
G13q
Duplex Receptacle, Door-Mounted
$100.00
G0, G1, G2, A2
G14q
Class A Ground Fault Protected Receptacle, Door-Mounted
222.00
G0, G1, G2, A2
G15q
Twist-Lock Receptacle, Door-Mounted
159.00
G1, G2
G16q
Two Duplex Receptacles, Door-Mounted
201.00
G2, A2
E23kc
Electrostatically-Shielded Transformer
100.00
G0, G1, G2, A2
P1
“ON” Red Warning Pilot Light
C
55°C Rise Transformer (standard on SK250G1)
N3
Convert NEMA Type 12 to NEMA Type 3R
34.00
A2
F11c
Additional Fusible Secondary Circuit
37.00
G0, G1, G2, A2
F30
Replace Standard 13/32" x 1-1/2" Class CC
Primary Fuse Holders with 13/16" x 5"
Primary Fuse Holders
80.00
G2, A2
Special Voltages (See Voltage Chart above)
q
k
c
t
b
Available
on Enclosure
Sizes
b
Price
Adder
Description
53.00
G1, G2, A2
106.00
G1, G2, A2
211.00
G1, G1, G2, A2
Not available with other receptacle options.
Consult factory for inrush data.
E23 and F11 not available together in Size 1 enclosure.
Mini enclosure limited to only one modification, restricted to E23, F11, G13 or G14.
Note: If either Form F30 or G16, or the combination of Forms E23 and F11 are ordered on SK250G1 through
SK1000G1, the Size 2 enclosure must be supplied. Therefore, the catalog numbers change to SK250G2 through
SK2000G2 and a list price adder of $106.00 will apply.
How to Order:
To Order Specify:
Catalog Number
Class
Type
VA
Rating
Enclosure(s)
Voltage
Code
Form(s)
9070
SK
1000
G1
D1
P1
12
TRANSFORMERS
k Class Number
k Type Number
k VA Rating
k Enclosure
k Voltage Code
k Form(s)
G13, G14, G15, G16
F30 - Not Shown on Drawing
3/00
CP1
Discount
Schedule
© 2000 Square D
All Rights Reserved
12-19
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Instrument Transformers–600 Volt Class
Voltage Transformers, Current Transformers
Class 4210
Voltage Transformers
k These voltage transformers are designed for line-to-line or line-to-ground connection on the primary voltage
indicated. See the table below to determine the applicable configuration for proper system voltage indication.
k Model 450R is designed for switchboard use. This model features high accuracy and burden capacity for
excellent performance in metering and indication.
k Model 460R is a compact, lightweight design, providing exceptional performance in indicating applications.
k Model 470R is a compact, low cost design optimized for maximum accuracy and performace when used with
POWERLOGIC® circuit monitors.
UR/cUR Recognized. 60 Hz
Model 450R
MODEL 450R
MODEL 460R
Thermal Rating: 500 VA @ 30°C; 300 VA Thermal Rating: 150 VA @ 30°C: 100 VA
@ 55°C.
@ 55°C.
Accuracy 0.3W. X.M & Y: 1.2 Z
Accuracy 0.6W: 1.2 X
Catalog Numberk
Price Each
MODEL 470R
Thermal Rating: 150 VA @ 30°C: 100 VA
@ 55°C.
Accuracy 0.3W: 1.2 X
Catalog Numberk
System
Voltage
Winding
Ratio
Catalog Numberk
Price Each
450R069
450R120
450R208
450R240
450R288
$301.
301.
301.
301.
301.
460R069
460R120
460R208
460R240
460R288
$225.
225.
225.
225.
225.
470R069
470R120
470R208
470R240
470R288
Price Each
$248.
248.
248.
248.
248.
69/120Y
120/208Y
120/208Y
240/416Y
288/500Yq
0.58:1
1:1
1.73:1
2:1
2.4:1
450R300
450R380t
450R480
450R600
314.
345.
314.
314.
460R300
460R380t
460R480
460R600
232.
255.
232.
232.
470R300
470R380t
470R480
470R600
$256.
282.
256.
256.
300/520Y
220/380Y
480/480Yc
600/600Y
2.5:1
3.17:1
4:1
5:1
q Use on 277/480 wye systems
c Use on 480 V delta systems
t Designed for 50 Hz applications
Model 460R
Model 470R
Current Transformers
General Purpose Compact Units UR/cUR Recognized
Window
Size
Catalog Numberk
(without brackets) j
Current Rating
(Amperes)
VA 60 Hz
VA 400 Hz
Accuracy
(At Rated Current)
Rating
Factor
30°C Ambient
Price
Each
11⁄8"
2NR500
2NR600
2NR750
2NR800
2NR101
2NR121
2NR1250
2NR151
2NR201
2NR251
2NR301
50:5
60:5
75:5
80:5
100:5
120:5
125:5
150:5
200:5
250:5
300:5
1.0
1.0
1.5
1.5
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.0
2.0
3.0
3.0
4.0
5.0
5.0
5.0
5.0
5.0
5.0
= 2%
= 2%
= 2%
= 2%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
$27.60
27.60
27.60
27.60
27.60
27.60
27.60
27.60
27.60
27.60
27.60
19⁄16"
5NR101
5NR151
5NR201
5NR251
5NR301
5NR401
5NR501
5NR601
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
2.0
2.5
5.0
5.0
5.0
12.5
12.5
25.0
4.0
5.0
12.5
12.5
12.5
25.0
25.0
50.0
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
32.50
32.50
32.50
32.50
32.50
35.30
35.30
35.30
19⁄16"
54R101
54R151
54R201
54R251
54R301
54R401
54R501
54R601
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
2.0
2.5
5.0
5.0
5.0
12.5
12.5
25.0
4.0
5.0
12.5
12.5
12.5
25.0
25.0
50.0
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
34.40
34.40
34.40
34.40
34.40
38.20
38.20
38.20
21/4"
7RL500
7RL101
7RL151
7RL201
7RL251
7RL301
7RL401
7RL501
7RL601
7RL751
7RL801
7RL102
7RL122
7RL152
50:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1500:5
2.5
2.5
2.5
5.0
5.0
5.0
12.5
12.5
12.5
12.5
12.5
25.0
25.0
25.0
5.0
5.0
5.0
10.0
10.0
10.0
25.0
25.0
25.0
25.0
25.0
50.0
50.0
50.0
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
= 1%
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
39.00
39.00
39.00
39.00
39.00
39.00
39.00
39.00
39.00
39.00
39.00
45.00
45.00
45.00
B
A
C
Dimensions
Model
450R
460R
470R
A
B
C
6
43⁄4
43⁄4
71⁄8
41⁄2
41⁄2
57⁄8
37⁄8
37⁄8
Model 54R
D
TRANSFORMERS
.20 Dia.
Mtg. Hole
(2)
A
H1 BEC
k Catalog Numbers in bold type are normally stock
j Mounting brackets on page 12-24.
Dimensions (inches)
12
Model
2NR
5NR
54R
7RL
A
1.13
1.56
1.56
2.25
B
C
D
E
2.38 –
.94 –
3.50 – 1.06 –
3.50 4.56 1.06 4.00
4.38 – 1.38 –
For additional information including excitation curves, reference Bulletin 4210CT9701 or D-Fax ™ number 197 (Pages 1-20) and 201 (Pages 21-38).
POWERLOGIC is a Registered Trademark of Square D Company or related companies.
12-20
© 2000 Square D
All Rights Reserved
PA1
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Instrument Transformers–600 Volt Class
Torroidal Current Transformers
Class 4210
Relay
Class
115⁄16"
64R101
64R151
64R201
64R251
64R301
64R401
64R501
64R601
64R751
100:5
150:0
200:5
250:5
300:5
400:5
500:5
600:5
750:5
115⁄16"
66R101
66R151
66R201
66R251
66R301
66R401
66R501
66R601
66R751
B-0.1
B-0.2
B-0.5
B-0.9
B-1.8
Rating
Factor
30°C
Ambient
–
–
–
–
–
–
–
–
–
1.2
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
2.4
1.2
1.2
0.6
0.6
0.6
0.3
0.3
0.3
–
–
2.4
1.2
1.2
0.6
0.6
0.3
0.3
–
–
–
–
2.4
1.2
0.6
0.6
0.6
–
–
–
–
–
–
–
1.2
0.6
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
$ 40.10
40.10
40.10
40.10
40.10
46.70
46.70
54.00
55.00
100:5
150:0
200:5
250:5
300:5
400:5
500:5
600:5
750:5
–
–
C10
C10
C10
C10
C20
C20
C20
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
–
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
–
2.4
2.4
1.2
1.2
0.6
0.6
0.3
0.3
–
–
–
2.4
2.4
1.2
0.6
0.6
0.3
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
75.00
75.00
75.00
75.00
75.00
85.00
85.00
94.00
97.00
211⁄32"
74R201
74R251
74R301
74R401
74R501
74R601
74R751
74R801
74R102
74R122
74R152
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1500:5
–
–
–
–
–
–
–
–
–
–
–
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.6
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
–
1.2
2.4
1.2
0.6
0.6
0.6
0.6
0.3
0.3
0.3
–
–
–
–
1.2
1.2
1.2
1.2
0.6
0.6
0.6
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.0
55.00
55.00
55.00
55.00
55.00
55.00
59.00
58.00
63.00
70.00
74.00
211⁄32"
76R201
76R251
76R301
76R401
76R501
76R601
76R751
76R801
76R102
76R122
76R152
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1500:5
C10
C10
C10
C10
C10
C20
C20
C20
C20
C20
C20
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
2.4
1.2
1.2
0.6
0.6
0.6
0.3
0.3
0.3
0.3
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.0
85.00
85.00
85.00
85.00
85.00
85.00
85.00
85.00
108.00
112.00
131.00
4"
100R201
100R301
100R401
100R501
100R601
100R801
100R102
100R122
100R152
100R162
100R202
200:5
300:5
400:5
500:5
600:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
C10
C10
C20
C20
C20
C20
C50
C50
C50
C50
C50
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
–
2.4
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
110.00
110.00
110.00
110.00
110.00
110.00
137.00
137.00
160.00
160.00
160.00
4"
110R201
110R301
110R401
110R501
110R601
110R801
110R102
110R122
110R152
110R162
110R202
200:5
300:5
400:5
500:5
600:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
C20
C20
C20
C50
C50
C50
C100
C100
C100
C100
C100
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
156.00
156.00
156.00
156.00
156.00
177.00
192.00
192.00
207.00
207.00
207.00
53⁄4"
120R201
120R301
120R401
120R501
120R601
120R801
120R102
120R122
120R152
120R162
120R202
120R252
120R302
200:5
300:5
400:5
500:5
600:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
3000:5
C10
C10
C20
C20
C20
C20
C20
C50
C50
C50
C50
C50
C50
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
2.4
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
–
2.4
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
122.00
122.00
122.00
122.00
122.00
127.00
139.00
139.00
150.00
150.00
150.00
177.00
177.00
81⁄8"
140R500
140R101
140R401
140R501
140R601
140R801
140R102
140R122
140R152
140R202
140R252
140R302
140R402
140R502
140R602
50:5
100:5
400:5
500:5
600:5
800:5
1000:5
1200:5
1500:5
2000:5
2500:5
3000:5
4000:5
5000:5
6000:5
–
–
C20
C20
C20
C50
C50
C100
C100
C100
C100
C100
C100
C100
C100
–
–
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
–
2.4
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.0
1.0
256.00
256.00
256.00
256.00
256.00
256.00
275.00
275.00
324.00
324.00
324.00
324.00
344.00
406.00
484.00
Models 64R, 74R
Models 66R, 76R
Models 100R, 110R, 120R and 140R
A
B
B
C
Dimensions (inches)
Model
64R
66R
74R
76R
100R
110R
120R
140R
A
B
C
115⁄16
115⁄16
211⁄32
211⁄32
4
4
53⁄4
81⁄8
43⁄16
43⁄16
411⁄16
411⁄16
7
7
81⁄2
11
11⁄2
31⁄16
15⁄8
31⁄4
21⁄8
27⁄8
21⁄8
3
ANSI Accuracy Classification — 60 Hz
Metering Class
For Ground Fault Sensing
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Price
12
Catalog
k Current
Window Number
(without
Rating
Size
brackets) (Amperes)
j
TRANSFORMERS
Torroidal Current Transformers UR/cUR Recognized 25–400 Hz
k Catalog numbers shown in bold letters are normally stocked items.
j Mounting brackets on page 12-24.
3/00
PA1
Discount
Schedule
© 2000 Square D
All Rights Reserved
12-21
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Instrument Transformers–600 Volt Class
Torroidal Current Transformers, Shorting Terminal Blocks
Class 4210
Torroidal Current Transformers UR/cUR Recognized 25–400 Hz
Models 152R, 170R, 180R, 210R
Window
Size
X1
A
CL B
HI
67⁄8"
CL
B
C
Dimensions (inches)
Model
A
B
C
152R
6.88
12.25
4.12
170R
4.25
6.75
1.31
180R
2.50
4.50
2.12
210R
6.25
9.50
2.87
41⁄4"
Models 200R, 201R, 202R and 203R
8.50
1.0 1.0
3.25
X1
CL
HI
A
21⁄2"
CL
4.62
21⁄2"
8.50
Modelt
Dimension A (Inches)
200R
201R
202R
203R
2.50
3.50
4.50
5.25
21/2"
t Base is included
Shorting Terminal Blocks
3090TB4
3090TB6
Shorting Terminal Block (4-pole)
Shorting Terminal Block (6-pole)
$49.00
56.00
31/2"
12
TRANSFORMERS
41/2"
51/4"
Catalog
Numberk
(without
brackets)j
152R500
152R101
152R151
152R201
152R251
152R301
152R401
152R501
152R601
152R801
152R102
152R122
152R152
152R162
152R202
152R252
152R302
152R402
170R201
170R251
170R301
170R401
170R501
170R601
170R751
170R801
170R102
170R122
170R152
170R162
170R202
170R252
180R101
180R151
180R201
180R251
180R301
180R401
180R501
180R601
180R751
180R801
180R102
180R122
180R152
210R122
210R162
210R202
210R252
210R302
210R402
200R101
200R151
200R201
200R251
200R301
200R401
200R501
200R601
201R101
201R151
201R201
201R251
201R301
201R401
201R501
201R601
201R751
201R801
202R101
202R151
202R201
202R251
202R301
202R401
202R501
202R601
202R751
202R801
202R102
203R101
203R151
203R201
203R251
203R301
203R401
203R501
203R601
203R751
203R801
203R102
203R122
203R152
203R162
203R202
203R252
203R302
12-22
PA1
B-0.2
B-0.5
B-0.9
B-1.8
C10
C20
C50
C50
C50
C100
C100
C100
C200
C200
C200
C400
C400
C400
C400
C400
C400
C800
–
–
–
–
–
–
C10
C10
C10
C10
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
C100
C100
C100
C200
C200
C200
C50
C50
C100
C100
C100
C200
C200
C200
C20
C50
C50
C100
C100
C100
C200
C200
C200
C200
C20
C20
C50
C50
C50
C100
C100
C100
C200
C200
C200
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.6
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
1.2
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.6
0.6
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
2.4
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
–
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
2.4
1.2
0.6
0.6
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
–
2.4
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
2.4
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
–
–
–
2.4
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
–
2.4
1.2
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
–
–
–
2.4
2.4
1.2
0.6
0.6
0.3
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
1.2
1.2
0.6
0.3
0.3
0.3
0.3
2.4
2.4
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
–
2.4
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
–
–
–
2.4
2.4
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
–
–
–
–
2.4
1.2
1.2
0.6
0.6
0.6
0.6
0.3
0.3
–
–
–
–
–
2.4
1.2
1.2
0.6
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
2.4
1.2
1.2
0.6
0.3
0.3
0.3
–
2.4
2.4
1.2
1.2
0.6
0.3
0.3
0.3
0.3
–
–
2.4
1.2
1.2
0.6
0.8
0.3
0.3
0.3
0.3
C20
C20
C20
C20
C50
C50
C100
C100
C100
C100
C200
C200
C200
C200
C200
C200
C200
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
2.4
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
2.4
2.4
1.2
1.2
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
–
2.4
2.4
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.33
1.33
1.33
1.33
Relay
Class
50:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
3000:5
4000:5
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1500:5
1200:5
1600:5
2000:5
2500:5
3000:5
4000:5
100:5
150:0
200:5
250:5
300:5
400:5
500:5
600:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
3000:5
j Mounting brackets on page 12-24
© 2000 Square D
All Rights Reserved
B-0.1
Rating
Factor
30°C
Ambient
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.0
1.0
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Current
Rating
(Amperes)
Discount
Schedule
ANSI Accuracy Classification – 60 Hz
Metering Class
Price
$418.
458.
493.
515.
531.
549.
578.
597.
619.
648.
679.
699.
724.
737.
761.
791.
819.
859.
84.
84.
84.
84.
84.
84.
88.
88.
115.
115.
143.
143.
143.
143.
65.
65.
65.
65.
65.
65.
65.
65.
71.
71.
91.
91.
97.
324.
324.
324.
368.
368.
411.
427.
427.
427.
427.
427.
427.
427.
427.
349.
349.
349.
349.
349.
359.
359.
359.
370.
389.
304.
304.
304.
313.
313.
319.
319.
323.
323.
330.
365.
269.
269.
269.
269.
269.
269.
269.
269.
275.
275.
275.
275.
287.
287.
287.
287.
287.
k Catalog Numbers shown in bold letters are normally stocked items.
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Instrument Transformers – 600 Volt Class
Multi-Ratio, Rectangular, Split Core CTs
Class 4210
Multi-Ratio Current Transformers
Models 151R and 312R
X5
X4
X3
X2
Torroidal Current Transformers UR/cUR Recognized
60 Hz-Model 312R, 25–400 Hz-Model 151R
X1
Window
Size
Catalog
Numberk
(without
brackets)j
Currentc
Rating
(Amperes)
Relay
Class
41⁄2"
312R601
312R122
312R202
312R302
312R402
600:5MR
1200:5MR
2000:5MR
3000:5MR
4000:5MR
67⁄8"
151R601
151R122
151R202
151R302
151R402
600:5MR
1200:5MR
2000:5MR
3000:5MR
4000:5MR
A
CL B
HI
CL
B
C
ANSI Accuracy Classification – 60 Hz
Metering Class
B-0.1
B-0.2
B-0.5
B-0.9
B-1.8
Rating
Factor
30°C
Ambient
C100
C200
C400
C400
C400
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
1.5
1.5
1.5
1.5
1.33
$ 466.
533.
608.
653.
693.
C200
C400
C400
C400
C800
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
1.33
1.33
1.33
1.33
1.33
772.
901.
972.
1012.
1041.
Price
c See chart at left for multi-ratio (MR) taps.
Rectangular Window Current Transformers UR/cUR Recognized 50–400 Hz
Dimensions (inches)
A
B
C
151R
6.88
12.25
4.12
312R
4.50
11.00
2.38
Window
Size
Catalog
Numberk
(without
brackets)j
Current
Rating
(Amperes)
B-0.1
B-0.2
B-0.5
B-0.9
21⁄8"
X
41⁄4"
260R101
260R151
260R201
260R301
260R401
260R601
260R801
260R122
260R162
260R202
260R252
260R302
260R402
100:5
150:5
200:5
300:5
400:5
600:5
800:5
1200:5
1600:5
2000:5
2500:5
3000:5
4000:5
1.2
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
2.4
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
–
–
–
–
–
–
–
–
–
–
–
–
–
33⁄4"
X
77⁄16"
560R401
560R501
560R601
560R751
560R801
560R102
560R122
560R152
560R162
560R202
560R252
560R302
560R322
560R402
560R502
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
3000:5
3200:5
4000:5
5000:5
1.2
0.6
0.6
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
1.2
0.6
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.4
2.4
1.2
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Multi-Ratio Taps (Models 151, 312, 781, 786)
Nominal Ratio
Current Ratioq (Amperes)
600:5
600/500/450/400/300/250/200/150/100/50:5
1200:5
1200/1000/900/800/600/500/400/300/200/100:5
2000:5
2000/1600/1500/1200/1100/800/500/400/300:5
3000:5
3000/2500/2200/2000/1500/1200/1000/800/500/300:5
4000:5
4000/3500/3000/2500/2000/1500/1000/500
q Taps in accordance with ANSI C57.13 and NEMA SG-4.
B
E
A
260R
Price
B-1.8
Rating
Factor
30˚ C
Ambient
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.0
1.0
1.0
$178.
178.
178.
178.
178.
178.
204.
235.
235.
256.
256.
256.
298.
–
–
2.4
1.2
1.2
1.2
0.6
0.6
0.6
0.6
0.3
0.3
0.3
0.3
0.3
–
–
2.4
2.4
2.4
1.2
1.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
143.
143.
143.
143.
143.
145.
145.
145.
145.
150.
150.
150.
160.
160.
175.
Split-Core Current Transformers Model 270R is UR/cUR Recognized 60 Hz
C
D
Window
Size
Catalog
Numberk
(without
brackets)j
Current
Rating
(Amperes)
B-0.1
B-0.2
B-0.5
B-0.9
39⁄16" x
83⁄16"
270R401
270R501
270R601
400:5
500:5
600:5
–
–
–
–
–
–
–
–
–
39⁄16" x
83⁄16"
270R801
270R102
270R122
270R152
270R162
270R202
270R252
270R302
270R402
270R502
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
3000:5
4000:5
5000:5
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
2.4
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
31⁄2" x
61⁄4"
273201
273251
273301
273401
273501
273601
273801
273102
273122
273162
273202
273252
273302
273402
200:5
250:5
300:5
400:5
500:5
600:5
800:5
1000:5
1200:5
1600:5
2000:5
2500:5
3000:5
4000:5
...
...
2.4
2.4
2.4
2.4
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
...
...
...
...
...
2.4
2.4
1.2
1.2
1.2
1.2
1.2
1.2
1.2
Dimensions (inches)
Model
ANSI Accuracy Classification – 60 Hz
Metering Class
A
B
C
D
E
2.13
4.25
2.12
4.88
7.25
270R
3.56
8.81
3.00
9.25
13.06
273
3.50
6.25
3.27
9.25
11.28
560R
3.75
7.45
1.13
5.53
11.13
ANSI Accuracy Classification — 60 Hz
Metering Class
Price
B-1.8
Rating
Factor
30°C
Ambient
–
–
–
–
–
–
1.33
1.33
1.33
$447.
447.
447.
–
2.4
2.4
2.4
2.4
1.2
1.2
1.2
1.2
1.2
–
–
–
–
–
2.4
2.4
1.2
1.2
1.2
–
–
–
–
–
–
–
2.4
1.2
1.2
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.0
1.0
1.0
387.
427.
427.
427.
427.
457.
457.
479.
502.
564.
...
...
...
...
...
...
...
2.4
2.4
2.4
1.2
1.2
1.2
1.2
...
...
...
...
...
...
...
...
...
...
2.4
2.4
1.2
1.2
...
...
...
...
...
...
...
...
...
...
...
...
2.4
1.2
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.33
1.00
1.00
369.
369.
369.
369.
369.
447.
369.
396.
396.
396.
422.
422.
443.
475.
3/00
PA1
Discount
Schedule
12
j Mounting brackets on page 12-24.
k Catalog Numbers shown in bold type are normally stocked items.
TRANSFORMERS
Model
© 2000 Square D
All Rights Reserved
12-23
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Instrument Transformers – 600 Volt Class
Bushing Current Transformers, Auxiliary Current Transformers,
Mounting Brackets–Class 4210
Bushing Current Transformers 50–400 Hz
Models 780R, 781R, 785R, 786R
9.88
T
251
6.5
H2
Window
Size
9.88
H1
251
61⁄2"
Model
T (inches)
780R
781R
785R
786R
3.38
3.38
6.75
6.75
Model 81X
10-32 Studs
61⁄2"
.75
19
6.38
162
61⁄2"
5.88
3.25
149
83
Mounting Brackets
Bracket
Price
2NR
MB-1
$ 3.90
5NR
MB-1
3.90
7RL
MB-7
5.00
54R
Included
...
64R
MB-10
3.70
66R
MB-12
5.30
74R
MB-16
5.30
76R
MB-18
5.30
81X
MB-81
11.70
100R
MB-31
11.70
110R
MB-32
11.70
120R
MB-31
11.70
140R
MB-32
11.70
151R
MB-32
11.70
152R
MB-32
11.70
170R
MB-30
11.70
180R
MB-9
7.10
200R
Included
...
201R
Included
...
202R
Included
...
203R
Included
210R
MB-32
260R
Not Available
...
270R
Not Available
...
273
Not Available
...
61⁄2"
Current c
Rating
(Amperes)
Relay
Class
ANSI Accuracy Classification – 60 Hz
Metering Class
B-0.1
B-0.2
B-0.5
B-0.9
B-1.8
Rating
Factor
30°C
Ambient
Price
780R500
780R750
780R101
780R151
780R201
50:5
75:5
100:5
150:5
200:5
–
C10
C10
C20
C20
–
1.2
2.4
0.6
0.6
–
2.4
2.4
1.2
1.2
–
–
–
–
2.4
–
–
–
–
–
–
–
–
–
–
2.0
2.0
2.0
2.0
2.0
$207.
207.
207.
207.
207.
780R251
780R301
780R401
780R501
780R601
250:5
300:5
400:5
500:5
600:5
C20
C50
C50
C50
C100
0.6
0.3
0.3
0.3
0.3
0.6
0.6
0.3
0.3
0.3
1.2
1.2
0.6
0.6
0.3
2.4
1.2
1.2
0.6
0.6
–
2.4
1.2
1.2
0.6
2.0
2.0
2.0
2.0
2.0
207.
207.
207.
207.
207.
780R751
780R801
780R102
780R122
780R152
750:5
800:5
1000:5
1200:5
1500:5
C100
C100
C100
C200
C200
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.6
0.3
0.3
0.3
2.0
2.0
2.0
2.0
2.0
223.
223.
223.
223.
223.
780R162
780R202
780R252
780R302
780R402
1600:5
2000:5
2500:5
3000:5
4000:5
C200
C200
C200
C200
C200
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.0
2.0
2.0
2.0
1.5
233.
233.
233.
233.
248.
781R601
781R122
781R202
781R302
781R402
600:5 MR
1200:5 MR
2000:5 MR
3000:5 MR
4000:5 MR
C100
C200
C200
C200
C200
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.3
0.3
0.3
0.3
0.6
0.3
0.3
0.3
0.3
2.0
2.0
2.0
2.0
1.5
278.
293.
304.
304.
320.
785R500
785R750
785R101
785R151
785R201
50:5
75:5
100:5
150:5
200:5
C10
C20
C20
C50
C50
2.4
1.2
1.2
0.6
0.6
2.4
1.2
1.2
0.6
0.6
–
–
2.4
1.2
1.2
–
–
–
2.4
2.4
–
–
–
_
2.4
2.0
2.0
2.0
2.0
2.0
377.
377.
377.
377.
377.
785R251
785R301
785R401
785R501
785R601
250:5
300:5
400:5
500:5
600:5
C50
C100
C100
C100
C200
0.3
0.3
0.3
0.3
0.3
0.6
0.3
0.3
0.3
0.3
1.2
0.6
0.3
0.3
0.3
1.2
0.6
0.6
0.6
0.3
2.4
1.2
1.2
0.6
0.6
2.0
2.0
2.0
2.0
2.0
377.
377.
377.
377.
377.
785R751
785R801
785R102
785R122
785R152
750:5
800:5
1000:5
1200:5
1500:5
C200
C200
C200
C400
C400
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.0
2.0
2.0
2.0
2.0
377.
405.
405.
405.
405.
785R162
785R202
785R252
785R302
785R402
1600:5
2000:5
2500:5
3000:5
4000:5
C400
C400
C400
C400
C400
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.0
2.0
2.0
2.0
1.5
405.
423.
423.
423.
451.
786R601
786R122
786R202
786R302
786R402
600:5 MR
1200:5 MR
2000:5 MR
3000:5 MR
4000:5 MR
C200
C400
C400
C400
C400
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
2.0
2.0
2.0
2.0
1.5
448.
476.
493.
493.
522.
c See chart on Page 12-23 for multi-ratio (MR) taps.
Auxiliary Current Transformer
Catalog Number
(without brackets)
81X05000100
81X05000200
81X05000250
81X05000500
81X07500500
81X10000500
81X12500500
81X15000500
Ratio
Price
5:1
5:2
5:2.5
5:5
7.5:5
10:5
12.5:5
15:5
$425.
425.
425.
425.
425.
425.
425.
425.
Model 81X Accuracy 0.3B0.1, B0.2, B0.5@60 Hz, RF=1.5@30°C
...
11.70
12
TRANSFORMERS
Model
Catalog
Number
12-24
© 2000 Square D
All Rights Reserved
PA1
Discount
Schedule
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type
Over 600 Volts
Class 7432
601 Volts thru 15,000 Volts – Three Phase – Indoor
All transformers are built with 220°C insulation and 150°C temperature rise. For
115°C rise add 10% to price and F to catalog number. For 80°C rise add 20% to price
and B to catalog number. Check with factory to verify dimensional changes and weights.
For copper windings add 20%
kV
Class
Code
Primary
Secondary
2.4
30 kV B.I.L
13
14
15
16
17
2400s
2400s
2400s
2400s
2400s
208Y/120
480Y/277
240s
480s
600s
5
30 kV B.I.L
18
19
20
21
22
23
25
26
27
28
29
30
31
4160s
4160s
4160s
4160s
4160s
4160Y/2400
4160Y/2400
4160/2400
4800s
4800s
4800s
4800s
4800s
208Y/120
480Y/277
240s
480s
600s
240s
480s
600s
208Y/120
480Y/277
240s
480s
600s
15
60 kV B.I.L
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
7200s
7200s
7200s
7200s
7200s
12000s
12000s
12000s
12000s
12000s
12470s
12470s
12470s
12470s
12470s
12470Y/7200
12470Y/7200
12470Y/7200
13200s
13200s
13200s
13200s
13200s
13200Y/7620
13200Y/7620
13200Y/7620
13800s
13800s
13800s
13800s
13800s
208Y/120
480Y/277
240s
480s
600s
208Y/120
480Y/277
240s
480s
600s
208Y/120
480Y/277
240s
480s
600s
240s
480s
600s
208Y/120
480Y/277
240s
480s
600s
240s
480s
600s
208Y/120
480Y/277
240s
480s
600s
Standard high voltage taps: 4-2.5%, 2AN and 2BN. For 4-2.5% FCBN, add BN to catalog
number.
Catalog
Number
kVA
Price
PE6D
Weight
(Pounds)
Mounting
Enclosurec
See Page 12-8
2.4 kV and 5 kV Voltage Class 60 Hz 150°C Rise
112.5
150
225
300
112T(
150T(
225T(
300T(
)H
)H
)H
)H
$14201.
17446.
23474.
28324.
1400
1600
1900
2100
Floor
Floor
Floor
Floor
28-D
28-D
29-D
29-D
500
750j
1000j
500T( )H
750T( )H
1000T( )H
33077.
41419.
51410.
3200
3900
7400
Floor
Floor
Floor
31-D
31-D
33-F
1500j
2000j
2500j
1500T( )H
2000T( )H
2500T( )H
61789.
70907.
85748.
9000
10900
12200
Floor
Floor
Floor
33-F
34-F
34-F
)H
)H
)H
)H
)H
$16274.
20011.
27257.
31816.
38800.
2000
2200
2800
3300
5000
Floor
Floor
Floor
Floor
Floor
30-D
30-D
31-D
31-D
32-F
750j
1000j
1500j
750T( )H
1000T( )H
1500T( )H
46075.
58588.
67027.
6000
7400
9000
Floor
Floor
Floor
33-F
33-F
33-F
2000j
2500j
3000j
2000T( )H
2500T( )H
3000T( )H
78570.
90986.
117176.
10900
12200
15400
Floor
Floor
Floor
34-F
34-F
35-F
15 kV Voltage Class 60 Hz 150°C Rise
112.5
150
225
300
500
112T(
150T(
225T(
300T(
500T(
j Dimensions and prices listed for 480 volt secondary only. For 240 volt or 208 volt, contact your nearest
Square D/Schneider Electric sales office.
601 Volts thru 15,000 Volts – Single Phase – Indoor
All transformers are built with 220°C insulation and 150°C temp. rise. or 115°C rise add 10% to price and F to catalog number. For 80°C rise add 20%
to price and B to catalog number, and check with factory for dimensional changes.
Catalog
Number
Price
PE6D
Weight
(Pounds)
Mounting
Enclosurec
See Page 12-8
2.4 kV Voltage Class 60 Hz 150°C Rise
167
250
333
167S( )H
250S( )H
333S( )H
$15148.
19751.
24261.
1500
2200
3000
Floor
Floor
Floor
167S( )H
250S( )H
333S( )H
$16259.
21104.
25826.
Code
Primary
Secondary
2.4
14
25
2400
2400
120/240
277
5
30 kV B.I.L
13
15
16
24
26
27
2400/4160Y
4800
4160
2400/4160Y
4800
4160
120/240
120/240
120/240
277
277
277
15
60 kV B.I.L
17
18
28
29
19
20
21
22
23
30
31
32
33
34
4160/7200Y
7200
4160/7200Y
7200
7200/12470Y
7620/13200Y
12470
13200
13800
7200/12470Y
7620/13200Y
12470
13200
13800
120/240
120/240
277
277
120/240
120/240
120/240
120/240
120/240
277
277
277
277
277
28-D
29-D
29-D
5 kV Voltage Class 60 Hz 150°C Rise
167
250
333
kV
Class
1500
2200
3200
Floor
Floor
Floor
28-D
29-D
29-D
2400
3400
5000
Floor
Floor
Floor
31-D
31-D
31-D
15 kV Voltage Class 60 Hz 150°C Rise
167
250
333
167S( )H
250S( )H
333S( )H
$18712.
24235.
28945.
c Enclosures for indoor use only. Letters in parenthesis refer to enclosure styles on page 12-8. Transformers suitable
for outdoor use available on special order.
Consult your nearest Square D/Schneider Electric sales office.
Lugs: Furnished by customer.
f Dimensions – DO NOT use for construction. Contact your nearest Square D/Schneider Electric sales office for
certified prints.
Special Notes
1. Distribution class lightning arresters are recommended as good practice, but are not included in the above prices.
Arrester addition may affect dimensions. Contact your nearest Square D/Schneider Electric sales office.
2. For 15 kV transformers requiring bottom entrance or exit, a separate compartment is required for adequate termination space and clearance. Transformers 1500 kVA and above with top entrance or exit may require a separate
compartment to provide adequate wiring space. Contact your nearest Square D/Schneider Electric sales office, for
special requirements.
3. If transformer requires a 94" high enclosure for switchgear line-up, or if special enclosure is required, contact your
nearest Square D/Schneider Electric sales office.
4. For 95 kV BIL consult your nearest Square D/Schneider Electric sales office. (May affect dimensions).
3/00
PE6D
Discount
Schedule
To Complete Catalog Number
To complete the single phase or three phase catalog
numbers on this page, select the voltage you require from
the chart above. Insert the voltage code number in place
of the ( ) in the catalog number. Ex.1000 kVA, 3 Ø, 60 Hz,
150˚C temp. rise, 60 kV BIL, NEMA sound level, ventilated
enclosure, 13.2 kV delta 480Y/277 = 100051H with 22.5% full capacity taps. 2AN and 2BN. The correct catalog
number for a 167 kVA, 2400/4160Y-120/240, 1 Ø 60 Hz
unit is 167S13H. The unit would be supplied with 2-2.5%
above and 2–2.5% full capacity below normal taps on the
primary.
© 2000 Square D
All Rights Reserved
12
kVA
TRANSFORMERS
Standard high voltage taps: 4-2.5%, 2AN and 2BN. For 4-2.5% FCBN, add BN to catalog number.
12-25
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type
Over 600 Volts–Three Phase
Class 6010
Most switches are supplied as fusible disconnects. The fuse access
door is mechanically interlocked with the switch operating mechanism,
permitting entry to the fuses only when the switch is open. Key-interlock
on the fuse access door or switch operating mechanism, allows
interlocking with other devices.
Distribution class lightning arresters, when required, are located below
the fuses in the incoming line section. Line-side cable entry is at the top
or bottom of the switch. For service voltages above 4.8 kV, an 18" pull
box on the top of the switch is required to provide sufficient room for
stress-cones when cable entry is at the top.
Where switching and overcurrent protection are provided elsewhere, a
full-height air-filled terminal chamber (22" wide) can be provided in place
of the HVL switch as the incoming section.
Primary Switch Ratings, Type HVL
Type
Switch
Manual
Non-Fused
Model III POWER-ZONE Package Unit Substations
General
Model III Power-Zone Package Unit Substations incorporate into one
pre-assembled, unitized module an HVL switch, Dry-Type transformer
and Molded-Case circuit breaker distribution section. All components
are manufactured by Square D and the complete package substation is
engineered and tested as one integral unit by Square D, assuring the
user of a fully coordinated design for maximum reliability.
The Model III is only 36" deep and 85" high, so it will pass through most
existing doorways.
Ventilation is toward the front, at the top of the transformer section, so
the unit can be installed against a wall or in a corner without alteration or
derating.
Model III Power-Zone package unit substations are ideal for renovations
requiring increased electrical demand as well as for high rise
applications and new construction requiring multiple zones and a small
footprint.
75 kVA Through 500 kVA
TRANSFORMERS
Model III Power-Zone Package Unit Substations are available in sizes
from 75 kVA through 500 kVA with three phase primary voltages of 2400
volts through 13,800 volts. When equipped with fan cooking, kVA ratings
as high as 667 kVA are available, AA/FA. Secondary voltages for 600 V
delta, 480 V delta, 480Y/277, 208Y/120 and 240 V delta are available.
The transformer is built with 220°C insulation. 150°C, 115°C or 80°C
Rise units are offered. Largest 80°C Rise size available is 300 kVA. The
secondary circuit breaker distribution section may be equipped with an
individually mounted secondary main breaker or an I-LINE® distribution
panelboard. Branch circuit breakers as small as 15 A single pole FY or
FA Frame (11⁄2 inches mounting height) to as large as 1200 A NA Frame
3-pole circuit breakers (15 inches mounting height) may be installed.
ME/NE Frame Electronic Trip breakers and I-LIMITER® High
interrupting capacity current limiting circuit breakers may also be used.
Switch Ratings
Continuous Interrupt Momentary Asym.
10 Cycle
600 A
600 A
61,000 A
Fault
Close
Asym.
5 kV BIL
15 kV
BIL
40,000 A
60 kV
95 kV
Transformer Section
Special Barrel-wound dry-type transformers employing Resinencapsulated VPIc techniques are used to achieve the low-loss,
compact design necessary for the space-saving package substation
concept. Sizes from 75 through 500 kVA are made. Class H, 220°C
insulation is used throughout. Temperature rise is 150°C as standard,
although 80°C or 115°C low-temperature premium transformers are
available through 300 kVA. Aluminum windings are standard with
copper as an option, (500 kVA, 115°C rise transformers are available
with copper windings only.) Four full capacity 21⁄2% taps are provided—
two above normal voltage and two below.
Fan-cooling is optional. When selected, it increases the self-cooled
rating of the transformer an additional 331⁄3%. The Model 98 digital
temperature controller is used on all fan-cooled units. This system
provides precision control through the use of three high accuracy
thermocouple type temperature sensors–one in each phase.
The controller has a membrane front panel for displaying the
temperature for all three phases with individual readings. The hottest
phase temperature is automatically displayed. The Model 98 features
simple three button operation with fan, alarm and trip function controlled
by hottest phase temperature. The Model 98 is POWERLOGIC
compatible.
Basic Insulation Levels
kV Class
Primary Voltages
BIL
1.2
All 600 V and Below Secondary
10 kV
4 kV
2.5
2400 V
20 kV
10 kV
5.0
4160 V, 4800 V
30 kV
12 kV
7.2
6900 V, 7200 V
30 kV
12 kV
8.7
8320 V
45 kV
19 kV
12, 12.47, 13.2, 13.8 kV
60 kV
31 kV
15.0
600 Hz Test Volt
c Vacuum-Pressure Impregnation
12
Incoming Line Section
Most Model III Power-Zone Package Unit Substations are supplied with
a Square D type HVL Load Interrupter switch. This switch uses a storedenergy spring mechanism to provide Quick-Make, Quick-Break
operation. A direct acting, permanently attached handle gives positive
indication of the switch position—up for closed, down for open— just as
in Square D’s line of safety switches. A viewing window is provided for
positive confirmation of blade position.
12-26
© 2000 Square D
All Rights Reserved
3/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Dry Type
Over 600 Volts–Three Phase
Class 6010
POWER-ZONE® Model III Package Unit Substations
Distribution Section
I-LINE Branch Breaker Data
I-LINE® Mounted Molded Case Circuit Breakers
Type
Molded Case Circuit Breakers are group mounted in an I-LINE
panelboard section offering the inherent ease of installation for which the
plug-on I-LINE circuit breaker has become known. All circuit breakers
are quick-make, quick-break, thermal-magnetic, permanent trip type
and are factory calibrated and sealed for accurate overcurrent response
and maximum short-circuit strength. ME and NE breakers are available
with solid-state logic trip elements. Current-limiting high interrupting
capacity. FI, KI and LI breakers are also available. Breakers may be
safely back-fed for use as main breakers. All circuit breakers are UL
listed and carry integrated equipment rating when used exclusively with
other Square D breakers in intended assembly.
Instead of a panelboard, molded case circuit breakers can be
individually mounted as a Main Breaker for separately installed
equipment. All circuit breakers are quick-make, quick-break, thermalmagnetic, permanent trip molded case circuit breakers and are factory
calibrated and sealed for accurate overcurrent response and maximum
short-circuit strength.
L/R
Interrupting Rating, Kilo Amperes
(RMS Symmetrical)
R
1P
2P
3P
120
240
277
480
600
100
3
3
3
3
3
41⁄2
41⁄2
41⁄2
41⁄2
41⁄2
41⁄2
41⁄2
k
k
k
k
k
kf
18
10
18
...
65
...
...
10
18
18
65
200
14
...
14
...
25
...
...
...
14
14
25
200
...
...
...
14
18
100
225
...
...
...
...
...
...
3
3
41⁄2
41⁄2
41⁄2
9
41⁄2
41⁄2
41⁄2
41⁄2
41⁄2
9
k
k
kf
kf
kf
k
...
...
...
...
...
...
10
22
25
65
200
65
...
...
...
...
...
...
...
...
25
35
200
65
...
...
22
25
100
25
Q4
LA
LH
LIa
MEq
400
...
...
...
...
...
6
6
6
12
9
6
6
6
12
9
k
k
k
k
k
...
...
...
...
...
22
42
65
200
65
...
...
...
...
...
...
30
35
200
65
...
22
25
...
25
MA
MH
MEq
800
...
...
...
9
9
9
9
9
9
k
k
k
...
...
...
42
65
65
...
...
...
30
65
65
22
25
25
NA
NC
NEq
1200
...
...
...
15
15
15
15
15
15
k
k
k
...
...
...
100
125
125
...
...
...
50
100
100
25
65
65
Q2
Q2-H
KA
KH
KIa
MEq
Breakers shown in table on right as mounting “L/R” may be mounted on
either left-hand or right-hand side of panelboard section. Those shown
as “R” mount on right-hand side only.
Mounting Ht. (IN)
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
...
FY
FA 240 V
FA 480 V
FA 600 V
FH
FIa
I-LINE panels are available in 800 A and 2000 A main bus ratings.
Maximum mounting space is 401⁄2" each side (total of 81").
Individually Mounted Main Breakers
Frame
Size
(Amps)
a Current limiting I-LIMITER circuit breakers.
f R only on 2000 A main bus I-LINE.
q Electronic trip.
Main Circuit Breaker Data
Frame Size
(Amps)
Type
225
400
800
1000
1000
1200
1200
1200
MEL
MEL
MEL
MAL
MHL
NAL
NCL
NEL
Circuit breakers that may be individually mounted as main
disconnecting devices include the ME and NE frame solid-state
electronic trip circuit breakers as well as MA, MH, NA and NC frame
units as detailed on right.
Interrupting Rating
RMS Kilo Amperes Symmetrical
240 V
480 V
600 V
Ampere
Rating
(Amps)
65
65
65
42
65
100
125
125
65
65
65
30
50
50
100
100
25
25
25
25
25
25
65
65
100-225
250-400
450-800
125-1000
125-1000
600-1200
600-1200
600-1200
Available Secondary Metering
POWER METER or POWER LOGIC METER, potential transformers,
current transformers.
Dimensions and Weights
2.00
51
2.00
Model 98
Compartment
Meter
Compartment
51
5.75
Removable
Cover
34.00
864
1-inch Minimum Rear Clearance Recommended.
For Rear Transformer Removal, 30-inch Aisle Required.
Grill under Removable Cover
146
12.00
305
36.00
914
51
L.V.
2.00
51
85.38
6.00
6.00
152
152
2169
3.00
76
10.00
2.00 254
51
5.00
H.V.
38.00
48.00
965
1219
86.00
Lifting
Jacks
6.00
152
127
4.00
L.V.
102
36.00
914
2184
Split for
Shipment
32.00
Front View
813
kVA
Weight
(Aluminum
Windings)
75
1121⁄2
150
225
300
500
3200
3350
3600
4400
4700
5000
8.00
203
12
2023
TRANSFORMERS
Top Conduit Entrance
79.63
Viewing
Window
NOTE: High voltage is shown on the left.
High voltage on the right is also available.
2.00
H.V.
Bottom Conduit Entrance
Contact your nearest Square D/Schneider Electric sales office for pricing assistance.
I-LIMITER, I-LINE and POWER-ZONE are Registered Trademarks of Square D Company or related companies.
3/00
© 2000 Square D
All Rights Reserved
12-27