Technical Data Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Bulletin Number 140M, 140-CMN Topic Bulletin 140M Motor Protection Circuit Breakers Page 3 Overview 3 Catalog Number Explanation 5 Application Diagrams 7 Bulletin 140M Motor Circuit Protectors 11 Overview 11 Catalog Number Explanation 13 Application Diagrams 15 Specifications 17 Approximate Dimensions 35 Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Motor Protection Circuit Breaker and Motor Circuit Protector Specifications 2 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Bulletin 140M Motor Protection Circuit Breakers Overview Motor Protection Circuit Breakers may provide the following protective and control functions. • Disconnect for Motor Branch Circuit • Branch-Circuit, Short-Circuit Protection (Magnetic Protection) • Overload Protection (Thermal Protection) • Switching (Manual) In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140M-C, D and F Frames: The 140M-C, D and F frame Motor Protection Circuit Breakers may have two cULus Listings - as Manual, Self-Protected Combination Motor Controllers and as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). When UL/CSA listed as Manual, Self-Protected Combination Motor Controllers, the 140M Motor Protection Circuit Breakers provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. At some higher voltages and currents (particularly at 600V), a few of the 140M-C, D and F frame devices are only UL/CSA Listed as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). 140-CMN Frame: The 140-CMN frame Motor Protection Circuit Breakers are UL Listed/CSA Certified as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on UL/CSA Listed Application Ratings - Motor Protection Circuit Breaker (MPCB) Only for the specific ratings of each Motor Protection Circuit Breaker. Standards Compliance and Certifications Standards Compliance IEC/EN60947-1,-2,-4-1,-5-1 IEC/EN60204-1 CSA,C22.2 No.14 UL508 Certifications CE Marked CCC CSACertified cULus Listed (File No. E54612, NLRV(7); E205542, NKJH(7); E197878, DIVQ(7);) ATEX Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 3 Bulletin 140M Motor Protection Circuit Breakers Max.Current Ie Current Rating Short Circuit Protection Standard Magnetic T rip High Magnetic Trip Magnetic Only Trip (MCP) Overload Protection Trip Class Standards Compliance: CSA22.2, No.14 UL508 (Group Installation) UL508 Manual, Self Protected (Type E) UL508 (Overload Protection) IEC60947-1,-2 IEC60947-4-1 CE ATEX (IEC60079-14) CCC Accessories External Rotary Operator Auxiliary Contacts Trip Indication Contacts 4 C-Frame 32 A 0.1…32 A D-Frame 32 A 1.6…32 A F-Frame 45 A 6.3…45 A CMN-Frame 90 A 16…90 A ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ 10 10 10 10 ✓ ✓ (see ratings) ✓ (see ratings) ✓ ✓ ✓ ✓ ✓ (up to 25 A) ✓ (up to 25 A) ✓ ✓ (see ratings) ✓ (see ratings) ✓ ✓ ✓ ✓ ✓ (up to 25 A) ✓ (up to 25 A) ✓ ✓ (see ratings) ✓ (see ratings) ✓ ✓ ✓ ✓ ✓ ✓ (see ratings) — ✓ — — ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 — ✓ — ✓ ✓ — ✓ Bulletin 140M Motor Protection Circuit Breakers Catalog Number Explanation Examples given in this section are not intended to be used for product selection. 140M a Code 140M Code A B – C b 2 c E d a Bulletin Number Description Motor Protection Circuit Breaker e Current Range Description Example A16=0.16 A=.10 B16=1.6 B=1.0 – A63 e – KN f b Frame/Rating Code Description C 32 A Code KN KRY C C=10 C16=16 TE D E D=100 E=1000 D16=160 E16=1600 MT D 32A F 45A f Miscellaneous Description Black Lockable Knob Red/Yellow Lockable Knob Spacing Adapter for SelfProtected Starters (TypeE) STD BusBar Mount, Top – CC g – GJ h c Interrupting Rating/Breaking Capacity Code Description 2 Normal Break 8 Frame Size C,D,F,CMN C,D,F,CMN High Break Code E T d Protection Type Description Adj Thermal/ Fixed Mag(13 x In) Adj Thermal/Fixed Mag (Fixed at 16...20 x In) g Auxiliary Trip Contacts C, D, F Frames 1st Code Description 2nd Code Description Bottom Front Right Side C,D,F X Placeholder X Placeholder C,D,F,CMN A B C 1 N.C. 1 N.O. 1 N.O.+1 N.C. C D E D 2N.O. K E 2N.C. L 1 N.O.+1 N.C. 2 N.O. 2 N.C. 1 N.C. (SC+OL) + 1 N.C. (SC) 1 N.O. (SC+OL) + 1 N.O. (SC) 1 N.C. (SC + OL)+ 1 N.O. (SC) 1 N.O. (SC + OL) + 1 N.C. (SC) 1 N.O. (SC)+1 N.C.(SC) R S 1 N.C.+ 1 N.O. (SC + OL) 1 N.O.+1 N.O.(SC+OL) M N Q g (continued) Auxiliary Trip Contacts CMN Frames Description 1st Code Description 2nd Code Bottom Front Top Front(1) X Placeholder X Placeholder K 1 N.C. (OL)+ 1 N.C.(SC) C 1 N.O.+1 N.C. D 2 N.O. L 1 N.O. (OL)+1 N.O. (SC) E 2 N.C. M 1 N.C. (OL) + 1 N.O. (SC) N 1 N.O. (OL) + 1 N.C. (SC) (1) Cannot be combined with option “h”. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 5 Bulletin 140M Motor Protection Circuit Breakers 1st Code G P 1stCode G P 6 Description Left Side Undervoltage Trip Shunt Trip Description Top Front§ Undervoltage Trip Shunt Trip h UV and Shunt Trips C, D, F Frame 2nd Code Description Voltage J K D C H F A T N B VC M ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE CMN Frame 2nd Code KJ D A 24V AC, 60 Hz 24V AC, 50 Hz 120V AC, 60 Hz 110V AC, 50 Hz 208V AC, 60 Hz 220…230V AC, 50 Hz 240V AC, 60Hz 277V AC, 60 Hz 380…400V AC, 50 Hz 480V AC, 60Hz and415V AC, 50 Hz 600V AC, 60Hz 575V AC, 60Hz and500V AC, 50 Hz 9V DC 12V DC 24V DC 36V DC 48V DC 60V DC 64V DC 72V DC 80V DC Description Voltage 24V AC, 60 Hz and 24V AC, 50 Hz 120V AC, 60 Hz and 110V AC, 50 Hz 240V AC, 60 Hz and 220…230V AC, 50 Hz Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Bulletin 140M Motor Protection Circuit Breakers Application Diagrams Group Installation with MPCBs There is only one Branch Circuit Protective Device (BCPD) for the “Group” Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and other loads to be connected to the same branch-circuit…”. The most restrictive part of the conditions specified for Group Installation is the requirement for the protection of the conductors for each motor circuit. In the U.S. NEC for 2002, a new rule for the conductor sizing was added for devices that are listed and marked “Suitable for use as Tap Conductor Protection”. Below is an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”. Bulletin 140M Motor Protection Circuit Breakers UL/CSA Listed for Group Installation Conductors from the BCPD to each motor must be a minimum of 1/3 the ampacity of the Branch Circuit conductors. Bulletin 140M Motor Protection Circuit Breakers UL/CSA Listed for Tap conductor Protection in Group Installations Conductors from the BCPD to manual motor controller listed as “…Tap Conductor Protection…” must be minimum of 1/10 the rating or setting of the BCPD. Conductors from the controller to the motor must be 125% of the motor FLA. BCPD Branch Circuit Protective Device Group Installation: Single Motor Taps Must be 1/3 the ampacity of the Branch-Circuit conductors Fuses or Circuit Breaker Branch Circuit conductors Tap Conductor Protection in Group Installation: Conductors from BCPD to manual motor controller listed as “…Tap Conductor Protection…” must be minimum of 1/10 the rating or setting of the BCPD Tap Conductor Protection in Group Installation: Conductors to each motor sized normally at 125% of motor FLA Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 7 Bulletin 140M Motor Protection Circuit Breakers Multiple Motor Installation with MPCBs Each Motor has an Individual Branch Circuit Protective Device Bulletin 140M Motor Protection Circuit Breakers (MPCBs) UL/CSA Listed as Type E Manual Self-Protected Combination Motor Controllers or UL/CSA Listed as Circuit Breakers These UL/CSA Listings allow the Bulletin 140M MPCBs to provide the branch-circuit, short-circuit protection (as well as overload protection) for each individual motor circuit. Additional short-circuit protection is not required for the protection of the individual motor circuits, leaving only the requirement for protection of the feeder circuit conductors by an upstream protective device. Below is an example that illustrates installations involving multiple motors, each with its own branch-circuit protection (BCPD). Bulletin 140M-J…L (Inverse Time Circuit Breakers) may provide the branch-circuit protection for each individual motor circuit Feeder Circuit Conductors Bulletin 140M-C…F (Type E Self-Protected Combination Motor Controllers) may provide the branch-circuit protection for each individual motor circuit Conductors to each motor sized normally at 125% FLA 8 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Bulletin 140M Motor Protection Circuit Breakers Type E and Type F Combination Motor Controllers Most of the 140M-C…F motor protection circuit breakers are UL listed as a manual Type E self-protected combination motor controller. Although there are many tests involved, one of the critical tests a self-protected combination motor controller must pass, is to perform 6000 electrical ops. and an additional 4000 mechanical ops. after a short circuit. By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or solid-state motor controller (such as a Bulletin 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller, additional short-circuit protection is not required for the individual motor circuits. A combination of a Bulletin 140M manual self protected combination motor controller and 100-C contactor can be listed as a Type E self-protected combination motor controller. In this case, both the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical operational test. In some cases, this may require over sizing of the Bulletin 140M MPCB or the 100-C contactor to achieve weld free performance and meet the additional life requirements. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 9 Bulletin 140M Motor Protection Circuit Breakers Notes: 10 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Bulletin 140M Motor Circuit Protectors Overview Motor Circuit Protectors may provide the following protective and control functions. • Disconnect for Motor Branch Circuit • Branch-Circuit, Short-Circuit Protection (Magnetic Protection) • Switching (Manual) In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140M-C, D, and F Frames: The 140M-C, D and F frame Motor Circuit Protectors have one UL/CSA Listing - as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). The 140M-C, D and F Frame Motor Circuit Protectors are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193 overload relay, as part of our Bulletin 103T and 107T Self-Protected IEC Combination Starters. These starters are then able to provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. Standards Compliance and Certifications Standards Compliance IEC/EN60947-1,-2,-4-1,-5-1 IEC/EN60204-1 CSA,C22.2 No.14 UL508 Certifications CE Marked CCC cULus Listed (File No. E54612, Guide No. NLRV, NLRV7) Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 11 Bulletin 140M Motor Circuit Protectors Max.Current Ie Current Rating Short Circuit Protection Standards Compliance: CSA22.2, No.14 UL508 (Group Installation) IEC60947-2 CE CCC Accessories External Rotary Operator Auxiliary Contacts Trip Indication Contacts 12 C-Frame 25 A 0.16…2.5 A D-Frame 32A 2.5…32 A F-Frame 45 A 25…45 A ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ (up to 25 A) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Bulletin 140M Motor Circuit Protectors Catalog Number Explanation Examples given in this section are not intended to be used for product selection. 140M a Code 140M Code A B – C b 2 c N d a Bulletin Number Description Motor Circuit Protector e Current Range Description Example A16=0.16 A=.10 B=1.0 B16=1.6 – A63 e – KN f b Frame/Rating Code Description C 25 A D 32A F 45A Code KN KRY C C=10 C16=16 TE D E D=100 E=1000 D16=160 E16=1600 MT f Miscellaneous Description Black Lockable Knob Red/Yellow Lockable Knob Spacing Adapter for SelfProtected Starters (TypeE) STD BusBar Mount, Top – CC g – GJ h c Interrupting Rating/Breaking Capacity Code Description 2 Normal Break 8 High Break Frame Size C,D,F,CMN C,D,F,CMN d Protection Type Description Fixed Mag only (13 x In) Adj Mag only (<13 x In) Adj Mag only (>13 x In) Code N P R g Auxiliary Trip Contacts C, D, F Frames 1st Code Description 2nd Code Description Bottom Front Right Side C,D,F X Placeholder X Placeholder C,D,F,CMN A B C 1 N.C. 1 N.O. 1 N.O.+1 N.C. C D E D 2N.O. K E 2N.C. L 1 N.O.+1 N.C. 2 N.O. 2 N.C. 1 N.C. (SC+OL) + 1 N.C. (SC) 1 N.O. (SC+OL) + 1 N.O. (SC) 1 N.C. (SC + OL)+ 1 N.O. (SC) 1 N.O. (SC + OL) + 1 N.C. (SC) 1 N.O. (SC)+1 N.C.(SC) R S 1 N.C.+ 1 N.O. (SC + OL) 1 N.O.+1 N.O.(SC+OL) M N Q g (continued) Auxiliary Trip Contacts CMN Frames Description 1st Code Description 2nd Code Top Front(1) Bottom Front X Placeholder X Placeholder K 1 N.C. (OL)+ 1 N.C.(SC) C 1 N.O.+1 N.C. D 2 N.O. L 1 N.O. (OL)+1 N.O. (SC) E 2 N.C. M 1 N.C. (OL) + 1 N.O. (SC) N 1 N.O. (OL) + 1 N.C. (SC) (1) Cannot be combined with option “h”. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 13 Bulletin 140M Motor Circuit Protectors 1st Code G P 1stCode G P 14 Description Left Side Undervoltage Trip Shunt Trip Description Top Front§ Undervoltage Trip Shunt Trip h UV and Shunt Trips C, D, F Frame 2nd Code Description Voltage J K D C H F A T N B VC M ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE CMN Frame 2nd Code KJ D A 24V AC, 60 Hz 24V AC, 50 Hz 120V AC, 60 Hz 110V AC, 50 Hz 208V AC, 60 Hz 220…230V AC, 50 Hz 240V AC, 60Hz 277V AC, 60 Hz 380…400V AC, 50 Hz 480V AC, 60Hz and415V AC, 50 Hz 600V AC, 60Hz 575V AC, 60Hz and500V AC, 50 Hz 9V DC 12V DC 24V DC 36V DC 48V DC 60V DC 64V DC 72V DC 80V DC Description Voltage 24V AC, 60 Hz and 24V AC, 50 Hz 120V AC, 60 Hz and 110V AC, 50 Hz 240V AC, 60 Hz and 220…230V AC, 50 Hz Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Bulletin 140M Motor Circuit Protectors Application Diagrams Group Installation with MCPs There is only one Branch Circuit Protective Device (BCPD) for the “Group” Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and other loads to be connected to the same branch-circuit…”. The most restrictive part of the conditions specified for Group Installation is the requirement for the protection of the conductors for each motor circuit. Below is an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”. Bulletin 140M Motor Circuit Protectors UL/CSA Listed for Group Installation Conductors from the BCPD to each motor must be a minimum of 1/3 the ampacity of the Branch Circuit conductors. Motor Circuit Protectors do not provide thermal protection, so a separate overload relay must be used. Therefore, MCPs cannot be UL/CSA Listed for Tap Conductor Protection in Group Installations. BCPD Branch Circuit Protective Device Bulletin 140M-C…F Group Installation: Single Motor Taps Must be 1/3 the ampacity of the Branch-Circuit conductors Fuses or Circuit Breaker Branch Circuit conductors Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 15 Bulletin 140M Motor Circuit Protectors 16 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Specifications IEC Performance Data Cat.No.140M-C2EA63 B10 B16 B25 B40 B63 0.25 0.4 0.63 1 1.6 2.5 4 6.3 3.3 5.2 8.2 13 21 33 52 82 Switching of Standard Three-Phase Motors, AC-3 — 0.06 0.09 0.18 0.25 0.37 0.75 1.5 0.04 0.09 0.18 0.25 0.55 0.75 1.5 2.2 0.09 0.12 0.18 0.37 0.75 1.1 2.2 3.0 0.09 0.18 0.25 0.55 1.1 1.8 3.0 4.0 Back-Up Fuses gG, gL, only if Icc3 Icu A25 A40 C10 10 130 C16 16 208 C20 20 260 C25 25 325 C29 29 406 C32 32 448 2.2 4.0 6.3 7.5 4.0 7.5 10 13 5.5 10 11 17 5.5 11 15 22 7.5 13 18.5 25 7.5 15 20 25 ⋆ ⋆ ⋆ 50 63 80 50 80 80 80 63 100 100 80 80 63 100 100 80 80 63 125 125 100 100 80 125 125 100 100 80 100 100 100 100 4 100 100 50 50 4 100 65 10 10 3 65 50 6 6 3 65 15 6 6 3 50 15 6 6 3 50 15 6 6 3 100 100 100 100 4 100 100 50 50 4 100 50 6 6 3 50 15 6 6 3 50 15 6 6 3 25 15 6 6 3 25 15 6 6 3 Rated Operational Current, Ie Magnetic Release Current [A] [A] A16 0.16 2.1 230/240V 400/415V 500V 690V [kW] [kW] [kW] [kW] — 0.02 0.06 0.06 230/240V 400/415V 440/460V 500V 690V [A] [A] [A] [A] [A] ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ 230/240V 400/415V 440/460V 500V 690V [kA] [kA] [kA] [kA] [kA] 100 100 100 100 100 230/240V 400/415V 440/460V 500V 690V [kA] [kA] [kA] [kA] [kA] 100 100 100 100 100 ⋆ ⋆ ⋆ 16 20 35 Ultimate Short Circuit Breaking Capacity, Icu 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 8 8 8 Rated Service Short Circuit Breaking Capacity, Ics 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 8 8 8 ⋆ No back-up fuse required. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 17 Specifications Rated Operational Current, Ie Magnetic Release Current [A] [A] 230/240V 400/415V 500V 690V [kW] [kW] [kW] [kW] 230/240V 400/415V 440/460V 500V 690V [A] [A] [A] [A] [A] 230/240V 400/415V 440/460V 500V 690V [kA] [kA] [kA] [kA] [kA] 230/240V 400/415V 440/460V 500V 690V [kA] [kA] [kA] [kA] [kA] Cat.No.140M-D8EC10 C16 C20 C25 C29 4.0 6.3 10 16 20 25 29 52 82 130 208 260 325 406 Switching of Standard Three-Phase Motors, AC-3 0.37 0.75 1.5 2.2 4.0 5.5 5.5 7.5 0.75 1.5 2.2 4.0 7.5 10 11 13 1.1 2.2 3.0 6.3 10 11 15 18.5 1.8 3.0 4.0 7.5 13 17 22 25 Back-Up Fuses gG, gL, only if Icc3 Icu B25 2.5 33 B40 B63 ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ 100 100 125 80 100 100 125 ⋆ ⋆ ⋆ ⋆ 80 80 80 100 20 35 50 50 63 63 63 80 Ultimate Short Circuit Breaking Capacity, Icu 100 100 100 100 100 100 100 65 100 100 100 100 100 100 65 50 100 100 100 100 50 50 50 25 100 100 100 100 50 50 50 25 10 10 10 6 6 6 6 6 Rated Service Short Circuit Breaking Capacity, Ics 100 100 100 100 100 100 100 50 100 100 100 100 50 25 25 25 100 100 100 100 50 25 25 20 100 100 100 100 50 25 25 20 10 10 10 6 4 4 4 4 C10 10 130 C16 16 208 7.5 15 20 25 2.2 4.0 6.3 7.5 4.0 7.5 10 13 5.5 10 11 17 6.3 11 15 22 7.5 15 20 30 13 22 30 40 ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ 125 125 100 80 80 80 80 63 100 100 100 80 100 100 100 80 100 100 100 80 125 125 125 100 125 125 125 100 65 50 25 25 6 100 100 65 50 10 100 100 65 50 10 100 100 65 50 10 100 100 65 50 10 100 65 65 50 10 100 65 50 50 10 50 25 20 20 4 100 50 50 50 10 100 50 50 50 10 100 50 50 50 10 100 50 50 50 10 100 50 50 50 6 100 50 50 50 6 ⋆ No back-up fuse required. 18 Cat.No.140M-F8EC20 C25 C32 20 25 32 260 325 416 C32 32 448 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 C45 45 585 Specifications Cat.No. 140-CMN… -4000 -6300 [A] 25 40 63 Rated Operational Current, Ie [A] 350 560 890 Magnetic Release Current Switching of Standard Three-Phase Motors, AC-3 230/240V ‡ [kW] 5.5/7.5 10/11 13/20 400/415V ‡ [kW] 7.5/13 15/22 25/32 500V ‡ [kW] 11/15 18.5/25 30/40 690V ‡ [kW] 15/22 25/30 37/55 Back-Up Fuses gG, gL, only if Icc3 Icu 230/240V [A] ⋆ ⋆ ⋆ 400/415V [A] 160 160 160 500V [A] 160 160 160 690V [A] 160 160 160 Ultimate Short Circuit Breaking Capacity, Icu 230/240V [kA] 100 100 50 400/415V [kA] 50 30 20 500V [kA] 30 20 10 690V [kA] 15 8 4 Rated Service Short Circuit Breaking Capacity, Ics 230/240V [kA] 100 100 50 400/415V [kA] 50 30 8 500V [kA] 30 15 6 690V [kA] 15 8 4 -2500 -9000 90 1260 22/25 37/45 45/55 63/75 ⋆ 160 160 160 50 20 10 4 50 8 6 4 ⋆ No back-up fuse required. ‡ Power ratings: Preferred values according to IEC 60072-1. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 19 Specifications Cat.No.140M-C2NA16 A25 A40 A63 B10 [A] 0.16 0.25 0.4 0.63 1 Rated Operational Current, Ie [A] 2.1 3.3 5.2 8.2 13 Magnetic Release Current Switching of Standard Three-Phase Motors, AC-3 230/240V [kW] — — 0.06 0.09 0.18 400/415V [kW] 0.02 0.04 0.09 0.18 0.25 500V [kW] 0.06 0.09 0.12 0.18 0.37 690V [kW] 0.06 0.09 0.18 0.25 0.55 Back-Up Fuses gG, gL, only if Icc3 Icu 230/240V [A] ⋆ ⋆ ⋆ ⋆ ⋆ 400/415V [A] ⋆ ⋆ ⋆ ⋆ ⋆ 440/460V [A] ⋆ ⋆ ⋆ ⋆ ⋆ 500V [A] ⋆ ⋆ ⋆ ⋆ ⋆ 690V [A] ⋆ ⋆ ⋆ ⋆ ⋆ Ultimate Short Circuit Breaking Capacity, Icu 230/240V [kA] 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 440/460V [kA] 100 100 100 100 100 500V [kA] 100 100 100 100 100 690V [kA] 100 100 100 100 100 Rated Service Short Circuit Breaking Capacity, Ics 230/240V [kA] 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 440/460V [kA] 100 100 100 100 100 500V [kA] 100 100 100 100 100 690V [kA] 100 100 100 100 100 B16 1.6 21 B25 2.5 32 0.25 0.55 0.75 1.1 0.37 0.75 1.1 1.8 ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ 16 20 100 100 100 100 10 100 100 100 100 8 100 100 100 100 8 100 100 100 100 8 ⋆ No back-up fuse required. 20 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Specifications Rated Operational Current, Ie Magnetic Release Current 230/240V 400/415V 500V 690V 230/240V 400/415V 440/460V 500V 690V 230/240V 400/415V 440/460V 500V 690V 230/240V 400/415V 440/460V 500V 690V Cat.No.140M-D8NB25 B63 B40 C10 C16 C25 [A] 2.5 4.0 6.3 10 16 25 [A] 32 52 82 130 208 325 Switching of Standard Three-Phase Motors, AC-3 [kW] 0.37 0.75 1.5 2.2 4.0 5.5 [kW] 0.75 1.5 2.2 4.0 7.5 11 [kW] 1.1 2.2 3.0 6.3 10 15 [kW] 1.8 3.0 4.0 7.5 13 22 Back-Up Fuses gG, gL, only if Icc3 Icu [A] ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ 100 [A] [A] ⋆ ⋆ ⋆ ⋆ 80 100 ⋆ ⋆ ⋆ ⋆ 80 80 [A] [A] 20 35 50 50 63 63 Ultimate Short Circuit Breaking Capacity, Icu [kA] 100 100 100 100 100 100 [kA] 100 100 100 100 100 65 [kA] 100 100 100 100 50 50 [kA] 100 100 100 100 50 25 [kA] 10 10 10 6 6 6 Rated Service Short Circuit Breaking Capacity, Ics [kA] 100 100 100 100 100 100 [kA] 100 100 100 100 50 25 [kA] 100 100 100 100 50 25 [kA] 100 100 100 100 50 25 [kA] 10 10 10 6 4 4 C32 32 448 Cat.No.140M-F8NC25 C32 C45 25 32 45 325 416 585 7.5 15 20 25 6.3 11 15 22 7.5 15 20 30 13 22 30 40 ⋆ 125 125 100 80 100 100 100 100 80 125 125 125 125 100 125 125 125 125 100 65 50 25 25 6 100 100 65 50 10 100 65 65 50 10 100 65 50 50 10 50 25 20 20 4 100 50 50 50 10 100 50 50 50 6 100 50 50 50 6 ⋆ No back-up fuse required. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 21 Specifications Rated Operational Current, Ie Magnetic Release Current 230/240V 400/415V 500V 690V 230/240V 400/415V 440/460V 500V 690V 230/240V 400/415V 440/460V 500V 690V 230/240V 400/415V 440/460V 500V 690V Cat.No.140M-C2TA16 A25 A40 A63 B10 B16 B25 [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 [A] 3.2 5.2 8.2 13 21 32 52 Switching of Standard Three-Phase Motors, AC-3 [kW] — — 0.06 0.09 0.18 0.25 0.37 [kW] 0.02 0.04 0.09 0.18 0.25 0.55 0.75 [kW] 0.06 0.09 0.12 0.18 0.37 0.75 1.1 [kW] 0.06 0.09 0.18 0.25 0.55 1.1 1.8 Back-Up Fuses gG, gL, only if Icc3 Icu [A] ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ [A] ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ [A] ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ [A] ⋆ ⋆ ⋆ ⋆ ⋆ 16 20 [A] Ultimate Short Circuit Breaking Capacity, Icu [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 8 8 Rated Service Short Circuit Breaking Capacity, Ics [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 8 8 B40 4.0 82 B63 6.3 130 C10 10 208 C16 16 260 0.75 1.5 2.2 3.0 1.5 2.2 3.0 4.0 2.2 4.0 6.3 7.5 4.0 7.5 10 13 ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ ⋆ 80 80 80 63 ⋆ ⋆ 35 50 63 80 50 100 100 100 100 8 100 100 100 100 4 100 100 50 50 4 100 50 10 10 3 100 100 100 100 8 100 100 100 100 4 100 100 50 50 4 100 15 6 6 3 ⋆ No back-up fuse required. 22 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Specifications Cat.No.140M-D8TC16 C20 [A] 16 20 Rated Operational Current, Ie [A] 260 325 Magnetic Release Current Switching of Standard Three-Phase Motors, AC-3 230/240V‡ [kW] 4.0 5.5 400/415V‡ [kW] 7.5 10 [kW] 10 11 500V‡ [kW] 13 17 690V‡ Back-Up Fuses gG, gL, only if Icc3 Icu 230/240V [A] ⋆ ⋆ 400/415V [A] 80 100 440/460V [A] 80 100 500V [A] 80 80 690V [A] 63 63 Ultimate Short Circuit Breaking Capacity, Icu 230/240V [kA] 100 100 400/415V [kA] 100 65 440/460V [kA] 50 25 500V [kA] 50 25 690V [kA] 6 6 Rated Service Short Circuit Breaking Capacity, Ics 230/240V [kA] 100 100 400/415V [kA] 25 25 440/460V [kA] 25 25 500V [kA] 25 25 690V [kA] 4 4 Cat.No.140M-F8TC25 C32 25 32 416 585 6.3 11 15 22 7.5 15 20 30 ⋆ ⋆ 100 100 100 80 125 125 125 100 100 65 65 50 10 100 65 65 50 10 100 50 50 50 6 100 50 50 50 6 ⋆ No back-up fuse required. ‡ Consult your local Rockwell Automation sales office or Allen-Bradley distributor. General Data Cat.No. 140M-C Rated Insulation Voltage Ui IEC,SEV,VDE0660 [V] UL,CSA [V] Rated Impulse Withstand Voltage Uimp Pollution degree Main circuits Uimp/Overvoltage Category Auxiliary circuits Uimp/Overvoltage Category Rated Frequency [Hz] Utilization Category IEC60947-2 (Circuit breaker) IEC60947-4-1 (Motor starter) Lifespan Mechanical [operations] Electrical (Ie max.) [operations] Switching Frequency [operations/h] 140M-D 140M-F 140-CMN 690 600 690 600 3 6kV/III 6kV/III 50/60 3 6kV/III 6kV/III 40…60 A AC-3 A AC-3 (except 90 A) 100000 100000 30000 30000 max.25 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 30000 5000 max.20 23 Specifications Cat.No. 140M-C Ambient Temperature Storage [°C] Operation [°C] Climatic resistance Moisture change climate (600068-2-30) Dry heat (60086-2-2) Moisture heat (60068-2-3) Site Altitude [m] Protection Class Resistance to Shock, Transport (60068-2-27) Resistance to Vibration, Operation (60068-2-6) Rated Thermal Current Ith up to 40°C ambient temperature [A] up to 60°C ambient temperature [A] Rated Supply Current Ie [A] Dependence on Temperature 40°C [A] 50°C [A] 60°C [A] 70°C [A] Overload Protection Characteristics Ambient Temperature [°C] Compensation Phase-loss Protection Trip class Magnetic Release Release current(+/-20%) Total Power loss Pv Circuit Breaker at rated load [W] operating temperature Main Disconnect Switch Application Application Conditions 24 140M-D 140M-F -40…+80 140-CMN -25…+80 -25…+60 23°C/83% relative humidity and 40°C/92% relative humidity, 56 cycles 100°C, relative humidity <50%, 7 days 40°C, relative humidity 93%, 56 days to 2000 N.N. IP2X, when wired 30 g,11ms,all axes 5g 0.1…32 0.1…32 0.1…32 1.6…32 1.6…32 1.6…32 6.3…45 6.3…45 6.3…45 30g,11 ms 16…90 16…90 16…90 no reduction no reduction no reduction 15% current reduction of the upper rated current Ie IEC 60947-4-1Motor protection (except Cat.Nos.140M-C2N,140M-D8N,140M-F8N) IEC60947 -20…+60 Differential release 10 (except Cat.Nos.140M-C2N,140M-D8N,140M-F8N) fixed setting fixed setting 13…14 x Ie max. (for 140M-C2E,140M-D8E,140M-F8E,140M-C2N,140M-D8N,140M-F8N) 16…21 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T) Ie max. = maximum values of setting ranges 6…11.5 6…11.6 9…16 10 fixed setting 14 x Ie max. 33 Yes, with accessories For utilization outside North America, assemblies (of products) shall comply to the IEC61439-1 requirements 140M manual motor starters are intended for use in closed areas without hazardous operating conditions such as dust or explosive or corrosive gases. Enclosures of appropriate manner need to be in place to protect devices in such environments. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Specifications Cat.No. 140M-C… Conformity to Standards Approvals 140M-… 140M-F… IEC60947-1;-2;-4-1; EN60947-1;-2;-4-1; UL508; CSA22.2, No.14 CE,UL,CSA 140-CMN IEC60947-1;-2; EN60947-1;-2; UL508; CSA22.2, No.14 CE,UL,CSA Terminal Parts Type of terminals Screwdriver 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor Tightening torque PozidrivNo.2/BladeNo.3 1…6/No.16…10 1…4/No.16…10 1…6/No.16…10 1…6/No.16…10 1.5…6/No.16…8 1.5…6/No.16…8 1…6/No.16…10 1…6/No.16…10 2…2.5/18…22 [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [Nm]/[lb•in] Cat.No. PozidrivNo.2/BladeNo.3 2.5…25/No.14…4 2.5…25/No.14…4 2.5…25/No.14…4 2.5…25/No.14…4 16…25/No.14…4 16…25/No.14…4 2.5…10/No.14…8 2.5…10/No.14…8 3…3.5/27…30 2.5…35 2.5…35 4…50/12…2 4…50/12…2 6…10/55…90 140M-RC… Terminal Parts Type of terminals 2…3.5 Screwdriver 0.2…0.6 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] 0.5…2.5/— 0.5…2.5/— 0.5…2.5/No.18…12 0.5…2.5/No.18…12 1…4/No.16…12 1…4/No.16…12 Accessories for Bulletin 140M Motor Protection Circuit Breakers Rated Thermal Current Ith at 40°C ambient temperature [A] at 60°C ambient temperature [A] Contact Class Coordination According to NEMA AC (UL/CSA Standards) DC Back-Up Fuses gG, gL [A] [V] Rated Supply Current AC-15 [A] DC-13 [V] [A] Auxiliary Contact Blocks for Front Mounting Cat.No.140M-C-AFA…,140M-C-AFAR… Auxiliary Contact Blocks for Right-Side Mounting Cat.No.140M-C-ASA…,140M-C-ASAR… 5 4 10 6 B300 Q300 10 120 3 120 0.5 B600 Q600 10 240 3 240 0.25 24 4 24 2 240 1.5 240 0.25 24 6 24 2 120 5 120 0.5 415 2 415 0.15 690 0.7 Terminal Parts Type of terminals Screwdriver PozidrivNo.2/BladeNo.3 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 25 Specifications 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor Tightening torque Auxiliary Contact Blocks for Front Mounting Cat.No.140M-C-AFA…,140M-C-AFAR… 0.5…1.5/18…14 0.75…1.5/18…14 0.75…1.5/18…14 0.75…1.5/18…14 0.75…1.5/18…14 0.75…1.5/18…14 1.2…1.5/10.6…13 [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [N•m]/[lb•in] Auxiliary Contact Blocks for Right-Side Mounting Cat.No.140M-C-ASA…,140M-C-ASAR… 0.5…2.5/18…14 0.75…2.5/18…14 0.75…2.5/18…14 0.75…2.5/18…14 0.75…2.5/18…14 0.75…2.5/18…14 1.2…1.5/10.6…13 Undervoltage Trip for Left-Side Mounting Cat.No.140M-C-UX… Undervoltage Trip with 2 Auxiliary Contacts for Left-Side Mounting Cat.No.140M-C-UC… Shunt Trip for Left-Side Mounting Cat.No.140M-C-SN… 0.85…1.1 x Us 0.7…0.35 x Us 0.85…1.1 x Us 0.7…0.35 x Us 0.7…1.1 x Us min. max. 21V 50 Hz,24V 60 Hz 600V 50 Hz 21V 50 Hz,24V 60 Hz 600V 50 Hz 21V 50 Hz, 24V 60 Hz 600V 50 Hz 100% 100% AC: 100%; DC: max. 5 sec. Pull-in Hold 8.5VA, 8 W 4VA, 2 W 8.5VA, 8 W 4VA, 2 W 8.5VA, 8 W 4VA, 2 W Actuating Voltage Pull-in Drop-out Rated Control Voltage On-Time Coil Rating Terminal Parts Type of terminals Screwdriver 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor Tightening torque PozidrivNo.2/BladeNo.3 [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [N•m]/[lb•in] 0.5…2.5/No.18…14 0.75…2.5/No.18…14 0.75…2.5/No.18…14 0.75…2.5/No.18…14 0.75…2.5/No.18…14 0.75…2.5/No.18…14 1.2…1.5/10.6…13.3 Compact Busbar Feeder Terminal 140M-C-WTN 140M-F-WTE 140M-C-WTEN Rated Thermal Current Ith at 60°C ambient temperature 64 64 120 — — — 4…25/10…4 — — 4…25/10…4 2.5…50/ 12…1/0 — — 2.5…25/ 14…4 5…6/45…54 — — 3…3.5/ 27…31 [mm2]/[AWG] 2.5…25/14…4 1.conductor [mm2]/[AWG] 2.5…25/14…4 4…50/12…1/0 1.conductor [mm2]/[AWG] 2.5…25/14…4 [N•m]/[lb•in] 3…3.5/27…31 Compact Busbar Feeder Block 140M-C140M-C140M-F140M-FWBEL1,L2,L3 WBET1,T2,T3 WBEL1,L2,L3 WBET1,T2,T3 120 1.conductor Tightening torque 26 [A] Compact Busbar 140M-C 140M-F -W… -W… 64 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 IEC120/UL115 for use with 140M-C-W for use with 140M-C-W for use with 140M-C-W 2.5…3/ 23…27 4…50/10…4 4…25/10…4 2.5…25/ 14…4 for use with 140M-F-W for use with 140M-F-W for use with 140M-F-W 5…6/45…54 Specifications Accessories for Bulletin 140M Screwless Cat.No. 140M-RC… Terminal Parts Type of terminals 2…3.5 Screwdriver 0.2…0.6 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor [mm2]/[AWG] [mm2]/[AWG] 0.5…1.5/— 0.5…1.5/— 0.5…1.5/No.18…14 0.5…1.5/No.18…14 0.5…1.5/No.18…14 0.5…1.5/No.18…14 [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] Weights Description Motor Protection Circuit Breakers Weight [g] 317 373 782 315 365 782 315 365 782 1845 10 Auxiliary Contacts 15 Undervoltage Trip Trip Contact Blocks Shunt Trip 31 108 110 116 94 31 94 Cat.No. 140MC-C2E-… 140M-D8E-… 140MC-F8E-… 140M-C2N-… 140M-D8N-… 140M-F8N-… 140M-C2T-… 140M-D8T-… 140M-F8T-… 140-CMN-… 140M-C-AFA10 140M-C-AFA01 140M-C-AFA11 140M-C-AFA20 140M-C-ASA… 140M-C-AFAR10A… 140M-C-ASAR…M… 140M-C-ASAM11 140-CA… 140M-C?UX… 140M-C-SN… 140M-C-UC… 140-CUV… 140-CT… 140-CRT… Description Weight [g] Cat.No. Anti-Tamper Cover 2 140M-C-CA Lockable Twist Knob 5 140M-C-KN1 140M-C-KRY1 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 27 Specifications Locking Tag 30 140M-C-M3 140M-C-DN66 Door Coupling Handle 123 Extension Shaft 46 140M-C-DS Legend Plate 4 140M-C-DFC… 51 172 27 48 69 90 30 55 80 105 6 140M-C-WTEN 140M-F-WT 140M-C-W452N 140M-C-W453N 140M-C-W454N 140M-C-W455N 140M-C-W542N 140M-C-W543N 140M-C-W544N 140M-C-W545N 140-KBH2 Feeder Terminal Compact Busbars Top Hat Rail Adapter 140M-C-NRY66 Accessories for Bulletin140-CMN Circuit Breakers Cat.No.140-CRT,140-CUV Cat.No.140-CT Trip Contact Block for Flush Mounting on Cat.No. 140-CMN Undervoltage Trip and Shunt Trip for Flush Mounting on Cat.No. 140-CMN Circuit Breakers Circuit Breakers Rated Thermal Current Ith up to 40°C ambient temperature up to 60°C ambient temperature NEMA contact class (UL/CSA-Approval) [A] [A] 10 6 AC DC B600 Standard Pilot Duty R300 Light Pilot Duty 2 2 Make/Breakmax.voltage 432VA 72 VA 480V 28VA 28VA 250V 16A 16A Back-Up Fuse gG, gL Rated Current Ie [V] [A] [V] [A] AC-15: DC-13: 230 3 24 2 400 2.5 48 0.6 500 1.5 110 0.2 690 0.75 230 0.1 AC-14: 440 0.04 DC13: 24 1.5 24 1.5 110 1.5 48 0.5 230 1.0 60 0.4 Terminals Screwdriver 1.conductor 2.conductor 1.conductor 2.conductor Tightening torque 28 [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [N•m]/[lb•in] 0.75…2.5/No.18…14 0.75…2.5/No.18…14 0.75…2.5/No.18…14 0.75…2.5/No.18…14 1…1.5/8.8…10.3 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 0.75…2.5/No.18…14 0.75…2.5/No.18…14 0.75…2.5/No.18…14 0.75…2.5/No.18…14 1…1.5/8.8…10.3 400 1.0 110 0.2 500 0.75 Specifications min. max. Cat.No.140-CUV… Undervoltage Trip Unit for Right-Side Mounting on Cat. No. 140-CMN Circuit Breakers 0.8…1.1 x Us 0.7…0.35 x Us 100% ED 12V50Hz/14V60Hz 600V50Hz Cat.No.140-CRT... Shunt Trip for Flush Mounting on Cat. No. 140-CMN Circuit Breakers 0.7…1.1 x Us — 100% ED 12V50Hz/14V60Hz 600V50Hz [VA/W] [VA/W] 11/8 4/1 12/7 6/2 Fine-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5 Coarse-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5 [N•m] 1…1.5 1…1.5 [AWG] No. 18….14 No. 18….12 [lb•in] 8.8…10.3 8.8…10.3 Pick-up Drop-out Operating Voltage Duty cycle Control Voltage Coil Performance Pick-up Drop-out Terminals Terminal type Tightening torque Coarse-stranded Tightening torque Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 29 Specifications Cut-off Current Icc asymmetrical Icc symmetrical ID Îs The Bulletin 140-M limits solid short-circuit current ICC (prospective short-circuit current). ID is the maximum cut-off current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagrams as a function of the progressive system short-circuit current. Figure 1 - Bulletin140M-C Circuit Breaker (Maximum Cut-Off Current) 140M-C2E, -C2N, -C2T Max. Cut-Off Current, Ue = 400…415V 100 0.25 0.3 Peak current [kA] 0.5 10 20 A 0.7 29 / 32 A 25 A 0.8 16 A 10 A 6.3 A 0.9 4.0 A 0.95 1 2.5 A cos φ 1.0 A 0.1 0.1 1 10 Prospective current [kA r.m.s] 30 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 100 Specifications Figure 2 - Bulletin140M-D Circuit Breaker (Maximum Cut-Off Current) 140M-D8E, -D8N, -D8T Max. Cut-Off Current, Ue = 400…415V 100 0.25 0.3 Peak current [kA] 0.5 29 / 32 A 25 A 16 / 20 A 0.7 10 0.8 10 A 6.3 A 0.9 4.0 A 0.95 2.5 A 1 cos φ 0.1 0.1 10 1 100 Prospective current [kA r.m.s] Figure 3 - Bulletin140M-F Circuit Breaker (Maximum Cut-Off Current) 140M-F8E, -F8N, -F8T Max. Cut-Off Current, Ue = 400…415V 100 0.2 0.3 45 A 32 / 25 A 20 A 16 A Peak current [kA] 0.5 0.7 10 10 A 0.8 0.9 0.95 1 cos φ 0.1 0.1 1 10 100 Prospective current [kA r.m.s] Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 31 Specifications Figure 4 - Bulletin140M-C Circuit Breaker (Maximum Let-through Energy) 140M-C2E, -C2N, -C2T Max. Let-Through-Energy, Ue = 400…415V 1.00E+06 1 Half-Cycle (50Hz) Let-through energy [A2s] 1.00E+05 25 A 20 A 16 A 29 / 32 A 10 A 1.00E+04 6.3 A 4.0 A 1.00E+03 2.5 A 1.6 A 1.00E+02 0.1 1 10 100 Prospective current [kA r.m.s] Figure 5 - Bulletin140M-D Circuit Breaker (Maximum Let-through Energy) 140M-D8E, -D8N, -D8T Max. Let-Through-Energy, Ue = 400…415V 1.00E+06 1 Half-Cycle (50Hz) 32 A 29 A Let-through energy [A2s] 1.00E+05 25 A 20 / 16 A 10 A 1.00E+04 6.3 A 4.0 A 1.00E+03 2.5 A 1.00E+02 0.1 1 10 Prospective current [kA r.m.s] 32 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 100 Specifications Figure 6 - Bulletin140M-F Circuit Breaker (Maximum Let-through Energy) 140M-F8E, -F8N, -F8T Max. Let-Through-Energy, Ue = 400…415V 1.00E+06 45 A 32 A 25 A 20 A 16 A Let-through energy [A2s] 1 Half-Cycle (50Hz) 1.00E+05 10 A 1.00E+04 1.00E+03 1.00E+02 0.1 1 10 100 Prospective current [kA r.m.s] Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 33 Specifications Time-Current Characteristic Figure 7 - Motor Protection Circuit Breakers Time-Current Characteristic 10 000 1h 1 000 100 1 Tripping time [s] Release Time [s] 10 1 2 0.1 0.01 0.001 0.8 1 2 4 6 10 20 40 60 100 Multiple of set current IeF Multiple of the set current IeF 140-CMN Motor Protector 140M-C, -D, -F Motor Protection Circuit Breakers Thermal Release Trip Current The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an ambient temperature of 20 °C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single phasing. The overload characteristic is also valid for transformer protection. Magnetic Release Trip Current The instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13…14 times the maximum value of setting range. (Transformer protection up to 20 x Ie max.) At a lower setting it is correspondingly higher. Current Setting IeF The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC947-4-1. If a different value is prescribed (e.g., reduced Ie for cooling medium having a temperature higher than 40 °C or a place of installation higher than 2000 m above sea level), the setting current is equal to the reduced rated current Ie of the motor. 34 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes Figure 8 - Cat. No. 140M-C, -D Cat. No. 140M-C2… § § § § Cat. No. 140M-D8… § § § § Mounting on 35 mm DIN Rail Undervoltage/shunt trip Auxiliary contact (front mounted) § Auxiliary contact (side mounted) Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 35 Approximate Dimensions Figure 9 - Cat. No. 140M-F Cat. No. 140M-F8… § § § § Mounting on 35 mm DIN Rail Undervoltage/shunt trip Auxiliary contact (front mounted) § Auxiliary contact (side mounted) Figure 10 - Cat. No. 140M-RC, Screwless Cat. No. 140M-RC… § § § § Mounting on 35 mm DIN Rail Undervoltage/shunt trip Auxiliary contact (front mounted) § Auxiliary contact (side mounted) 36 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Figure 11 - Mounting position/safety clearance of Cat. No. 140M-C…, 140M-D…, 140M-F… Cat. No. 140M-C/D… Cat. No. 140M-F… ° 90 ° 30° 12 90 0° Minimum distance to grounded parts or walls Figure 12 - Cat. No. 140M-C-TE1 Type E adapter on Cat. No. 140M-C2E… Figure 13 - Cat. No. 140M-C-TE1 Type E adapter on Cat. No. 140M-D8E… Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 37 Approximate Dimensions Figure 14 - Cat. No. 140M-C-TE1 Type E adapter on Cat. No. 140M-F8E… Figure 15 - Screw Adapter 140M-C-N45 for 140M-C2/D8 and 140M-F8 . . 38 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 . Approximate Dimensions Figure 16 - Cat. No. 140M-C with Busbar § Compact Busbar Feeder Terminal IEC Compact Busbar Feeder Terminal UL type E and IEC Mounting on 35 mm DIN Rail § Top Hat Rail Adapter 10 mm Figure 17 - 140M-C-SHS Screw Adapter > 10 (25/64) 205 (8-5/64) 215 (8-31/64) 245 (9-41/64) Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 140M-C 140M-D / 140U-D 140M-F 39 Approximate Dimensions Figure 18 - 140M-C-D…66 4.5 min. 100 3.5 1.5...5 35...45 b 53.5 53.5 140M-C-DS 140M-C-DSL a c1 + 5 mm 4...8 c2 4.5 + 5 mm 2.4 Cat. No. 140M-C 140M-D 140M-F With Cat. No. 140-M-C-DS Shaft a b 117…338 105.5 ±5 126…347 114.5 ±5 148.6…369.6 137.1 ±5 c1 49.5 49.5 59.35 c2 40.5 40.5 50.35 a 117…438 126…497 148.6…519 With Cat. No. 140-M-C-DSL Shaft b c1 105.5 ±5 49.5 114.5 ±5 49.5 137.1 ±5 59.35 Figure 19 - 140M-C-WBE 40 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 c2 40.5 40.5 50.35 Approximate Dimensions Figure 20 - Cat. No. 198E… Ø Ø Ø Figure 21 - 140-CMN Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 41 Approximate Dimensions Figure 22 - 140-CD… 1.5…5 (0.059…0.197) 5 (0.197) min. 100 (3.94) 3.5 (1.38) 3.5…4.5 (1.38…1.77) ±5 (0.197) 169 (6.65) 53.5 (2.10) 53.5 (2.10) 180…402 (7.09…50.83) ±5 (0.197) 4…8 (0.157…0.314) 90 ° 90 ° ° 90 30° 70 70 Figure 23 - Mounting position/safety clearance of Cat. No. 140-CMN 42 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 43 Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 140M-TD002B-EN-P - January 2015 Supersedes Publication 140M-TD002A-EN-P January 2015 Copyright © 2015 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.