Frequency Response – Issue Paper California ISO Frequency Response Issue Paper August 7, 2015 Market and Infrastructure Policy CAISO/M&ID/JC 1 August 7, 2015 Frequency Response – Issue Paper California ISO Table of Contents 1. Purpose of this initiative .................................................................................................................... 3 2. Background ......................................................................................................................................... 4 2.1. Primary Response to a Frequency Disturbance........................................................................ 4 2.2. Frequency Response Trend in North America .......................................................................... 7 2.3. ISO Frequency Response Capabilities ....................................................................................... 9 3. Details of ISO Frequency Response Obligation under BAL-003-1 .......................................... 11 4. Considerations for the ISO.............................................................................................................. 12 5. Initiative Schedule ............................................................................................................................ 14 6. Next Steps ......................................................................................................................................... 14 CAISO/M&ID/JC 2 August 7, 2015 Frequency Response – Issue Paper California ISO 1. Purpose of this initiative On January 16, 2014, the Federal Energy Regulatory Commission (FERC) approved1 Reliability Standard BAL-003-12 (Frequency Response and Frequency Bias Setting), submitted by the North American Reliability Corporation (NERC). With the approval of this standard, NERC created a new obligation for balancing authorities including the ISO to demonstrate sufficient frequency response to disturbances in system frequency. The purpose of this initiative is to ensure that the ISO can comply with the new NERC requirements. NERC’s BAL-003-1 Frequency Response and Frequency Bias Setting Purpose: To require sufficient Frequency Response from the BA to maintain Interconnection Frequency within predefined bounds by arresting frequency deviations and supporting frequency until the frequency is restored to its scheduled value. To provide consistent methods for measuring Frequency Response and determining the Frequency Bias Setting. Requirement R1 of BAL-003-1 requires that each BA or Frequency Response Sharing Group (FRSG) must achieve an annual Frequency Response Measure that is equal to or more negative than its “Frequency Response Obligation” to ensure sufficient Frequency Response. To assess each balancing authority’s performance, on an annual basis NERC will select between 20 and 30 disturbance events within the year and measure the balancing authority’s response to each disturbance.3 In 2013, there were 25 such events. Compliance with BAL-003-1 will begin December 1, 2016.4 NERC has established a methodology for calculating frequency response obligations. NERC determines a balancing authority’s obligation by first determining the obligation for the interconnection as a whole and then assigning a share to each balancing authority based on its share of the total generation and load of the interconnection. As a balancing authority in the Western Electricity Coordinating Council (WECC), the ISO will have between 24% and 30% of WECC’s total frequency response 1 See FERC Order No. 794 Docket No. RM13-11-000 See Reliability Standard BAL-003-1 3 Event selection details are covered within this NERC filing. 4 The standard goes into effect on April 1, 2016, but NERC will not begin measuring compliance until December 1, 2016. 2 CAISO/M&ID/JC 3 August 7, 2015 Frequency Response – Issue Paper California ISO obligation. WECC’s obligation5 is 906 MW/0.1 Hz and therefore the ISO’s obligation is 218 MW/0.1 Hz. Compliance with the frequency response obligation is based on actual performance, rather than procurement of frequency response capability. Accordingly, this standard requires the ISO to demonstrate that resources provided sufficient frequency response during frequency disturbance events. At the same time, in order to be prepared for unpredictable frequency events, the ISO will need some procedure to ensure that sufficient frequency response is available to meet the ISO’s share of WECC’s obligation whenever such an event occurs. This paper summarizes the ISO’s current capability to respond to frequency response events and considers whether this capability will enable the ISO to comply with the new standard. The ISO seeks stakeholder input on how best to meet the new requirement and on the frequency response capabilities of emerging technologies such as wind, solar and energy storage devices. 2. Background This section provides general background on frequency response and the difference between primary, secondary and tertiary frequency controls. The new NERC standard addresses the primary frequency control referred to as “frequency response.” This section also describes the ISO’s current capabilities for primary, secondary and tertiary response. 2.1. Primary Response to a Frequency Disturbance Frequency response is the initial or primary response of resources and load to arrest and quickly recover from changes in system frequency. During normal operating conditions, system frequency is close to scheduled frequency (typically 60 Hz) and is essentially the same throughout an interconnection. All balancing authorities within an interconnected electric system are responsible to provide frequency response capability to support system frequency in the event of a disturbance. The loss of a major resource can cause system frequency to decline to unacceptable operating levels, risking unintentional tripping of load and damage to large steam turbines. Historically, frequency response – the primary and most immediate response to the disturbance – has mainly been provided by the governor response of conventional turbine generators, which comprised the vast majority of generating resources, and frequency responsive loads. In contrast, resources such as wind and solar generating facilities, storage devices and non-frequency responsive loads typically do not have the automatic governor 5 Subject to changes by NERC CAISO/M&ID/JC 4 August 7, 2015 Frequency Response – Issue Paper California ISO response common to conventional generators. With modern inverters, however, these resources can provide inertia6 and frequency response. Following a disturbance, the total frequency response from all resources will support a balancing authority’s ability to meet its frequency response obligation to the interconnection. When a balancing authority loses a resource, it causes a sudden drop in frequency which is detected by the governors on other resources within the interconnection. The governors then provide immediate support to stabilize frequency by increasing the amount of energy their respective resources deliver to the grid. Similarly, frequency responsive loads such as motors and inductive loads consume less power in response to a frequency drop. Figure 1 illustrates how primary frequency control (frequency response), in conjunction with secondary control (i.e., automatic generation control or regulation service) and tertiary control (i.e., market or operator dispatch) work to restore scheduled frequency following a disturbance. 6 Inertia is a characteristic of massive spinning turbines, which has the effect of slowing or inhibiting a change in frequency. Whereas frequency response can be thought of as the response of resources to a change in frequency, inertia works to moderate the initial magnitude of the frequency change. CAISO/M&ID/JC 5 August 7, 2015 Frequency Response – Issue Paper California ISO Figure 1 - Frequency Response 7 Source- NERC Frequency Response Initiative An example of such a decline is illustrated in Figure 2, including points relevant to measuring frequency response. 7 See NERC Frequency Response Initiative CAISO/M&ID/JC 6 August 7, 2015 Frequency Response – Issue Paper California ISO Figure 2 - Frequency Response Frequency FREQ 60.02 Point A 1-Minute after T0 T0 60.00 Hz 59.98 59.96 Point B 59.94 Point C 59.92 59.90 0 4 8 12 16 20 24 28 32 36 40 44 48 52 56 60 64 68 72 76 80 84 88 92 96 Seconds Point A indicates system frequency just prior to a disturbance, which occurs at time T 0. Within the first 30 seconds following the disturbance, balancing authorities within the interconnection provide frequency response to arrest system frequency (i.e., from T0 to point C) and stabilize the system (i.e., between Point C and one minute after T0). 2.2. Frequency Response Trend in North America Since the 1960s generation technology has transitioned from almost exclusively hydro and steam turbine generators to a more diverse fleet of resource types operating today. This transition has contributed to the reduction of conventional governor response and as the resource fleet undergoes a rapid transition the ISO expects governor response to continue to decline. Different unit types exhibit different governing response characteristics8. Nuclear units exhibit little to no governor response, while large hydro plants generally exhibit a significant response in the correct direction. NERC published the Frequency Response Initiative Report 8 See IEEE Power & Energy Society’s PES-TR13 Report CAISO/M&ID/JC 7 August 7, 2015 Frequency Response – Issue Paper California ISO 20129 with the intention of achieving a better understanding of the factors influencing frequency performance across North America. Apart from the change in generating resource mix to more non-conventional resources, several economic reasons exist for conventional generating units to operate in ways that prevent effective governor response. For example, if a unit operates at its maximum capability, regardless of control mode the unit cannot provide additional power in response to a downward disturbance in frequency. Another example is outer-loop megawatt control, which inhibits governor response by slowly adjusting the governor load reference in order to maintain a preselected megawatt level, for example, to maintain the resource’s day-ahead energy schedule. The National Renewable Energy Laboratory (NREL) has noted10 general concern exists among power system operators and utilities regarding the degradation of frequency response in North America over the past two decades. The decline is attributed to several factors. These factors include the withdrawal of primary or governor response shortly after an event, insufficient inservice governors on conventional generation, and the unknown and changing nature of load frequency characteristics. The NREL report also notes increased penetration of inverter-based, or non-synchronous, generation technologies, which lack conventional governor controls. As a result, dynamic performance changes due to increased wind and solar generation, combined with reduced frequency response capability of the fleet, may further complicate integration of renewable generation. There are several logical reasons why frequency response is declining. Among them are: 9 Steam turbine-generators operating on traditional “sliding pressure” control; Significant penetration of non-traditional generation, primarily wind and solar generation; Proportionally fewer frequency-responsive large motor loads, as the US becomes less of an industrial economy; Variable speed drives on motors do not provide traditional load damping; Some combustion turbine generator designs actually have a positive frequency characteristic, i.e., their output MWs go down when frequency drops. As frequency drops, turbine and compressor speeds drop, airflow decreases, with correspondingly less available for combustion. The manufacturer intentionally reduces fuel input when frequency drops to prevent overheating. This phenomenon reportedly contributed to a blackout in Malaysia in 1996; Generators having less inertia (less mass per MW of output); Fewer resources are carrying frequency responsive spinning reserves as the rules for the distribution of reserves have been relaxed; and See NERC Frequency Response Initiative Report 2012 See Western Wind and Solar Integration Study Phase 3 – Frequency Response and Transient Stability 10 CAISO/M&ID/JC 8 August 7, 2015 Frequency Response – Issue Paper California ISO Power plant control interaction removing or withdrawing governor action due to outer loop control which may be due to focus on plant performance with generation set points. The automatic generation control (AGC) function can also reduce the frequency response of a resource. If AGC perceives a resource’s response to a frequency excursion as a deviation from an economic or market-determined set-point, it would attempt to reverse the frequency response and return the resource to its economic target. 2.3. ISO Frequency Response Capabilities The ISO currently meets frequency response through various system characteristics and products as summarized in the table below. For example, inertial response is a characteristic of the system typically provided by the rotating mass of conventional generation. During a frequency disturbance, the inertia of these resources naturally counteracts and thus reduces the magnitude of the deviation in frequency. This does not require action by either the system operator or a governor; it is inherent to the nature of the unit characteristics. Over time, as nonconventional generation replaces conventional generation, the ISO fleet as a whole may lose natural inertial response. Primary response is provided by governor control of synchronous generators and frequency responsive loads. Currently, the WECC has specified “droop” settings for conventional generators. The droop setting of the governor determines the MW amount a generator responds for each unit of frequency change. This response is instantaneous and automatic from each resource and does not require operator action. However there is no corresponding requirement for non-conventional generators. For primary response, the ISO currently does not have a procurement target. Generators can provide primary frequency response if they are operating below their maximum operating capacity and have available headroom. The ISO’s procurement of spinning reserves ensures that generators have headroom in case of a contingency.11 Secondary response is provided by resources under automatic generation control. The response is slower than primary response, but still may occur within seconds to minutes. The ISO procures regulation up and down to maintain balance between supply and demand within each 5 minute dispatch interval. These resources are on automatic generation control and can also serve as secondary frequency response. Tertiary response requires system operator dispatch control. This occurs within minutes after the start of the event. The ISO deploys spinning and non-spinning reserves to address contingencies and frequency disturbances. 11 See ISO tariff Appendix K for spinning reserve minimum governor characteristics. CAISO/M&ID/JC 9 August 7, 2015 Frequency Response – Issue Paper California ISO Response Type Inertial response Provided by • Comes from motors, pumps, and conventional generators • It is more a characteristic of the system • As the ISO loses more conventional generator, will have less inertial response Primary response • Comes largely from conventional generators with governor response installed and tuned based on WECC requirements Secondary response Tertiary Response • Comes from generation under automatic generation control • Comes from generators dispatched through operator control. • Most intermittent do not have technology Response Time • Response in seconds • Autonomous (not ISO controlled) response in seconds • ISO controlled response in minutes • ISO controlled response in minutes The ISO Procurement • The ISO does not explicitly procure • The ISO does not explicitly procure, but resources with available headroom may respond, such as spinning reserves • Upward and downward regulation • Dispatch of real-time imbalance energy and deployment of spinning and non-spinning reserves CAISO/M&ID/JC 10 August 7, 2015 Frequency Response – Issue Paper California ISO 3. Details of ISO Frequency Response Obligation under BAL-003-1 Currently, the ISO does not explicitly procure frequency response capability. The ISO assumes it is provided through adherence to the WECC standard for governor droop settings and the automatic governor response of interconnected generating resources.12 Compliance with the new standard will be measured based upon actual response of generators and load. Therefore, any solution adopted by the ISO and stakeholders must ensure obligated units respond appropriately. If the standard were in place today, the ISO’s 2016 share of frequency response for the loss of two Palo Verde units would be approximately 775 MW of upward response. Every year NERC will establish each BA’s frequency response obligation, which is an all hours (24x7) requirement.13 The ISO has therefore opened the present initiative to determine how best to meet the new obligation. Figure 3 compares the ISO’s frequency response performance with the new obligation had this been in place for 2013. Figure 3 - 2013 Frequency Response 12 13 Automatic response by generator governors is different from AGC. See BAL-003-1 Attachment A for NERC’s methodology CAISO/M&ID/JC 11 August 7, 2015 Frequency Response – Issue Paper California ISO 4. Considerations for the ISO Compliance with NERC BAL-003-1 will begin on December 1, 2016. Therefore the ISO will need to implement any changes proposed in this initiative that require market software changes by the ISO’s fall 2016 software release. The ISO has several tariff provisions relating to frequency response. These tariff provisions include The ISO tariff section 4.5.6.1 states: “Participating Generators shall, in relation to each of their Generating Units, meet all Applicable Reliability Criteria, including any standards regarding governor response capabilities, use of power system stabilizers, voltage control capabilities and hourly Energy delivery. Unless otherwise agreed by the ISO, a Generating Unit must be capable of operating at capacity registered in the ISO Controlled Grid interconnection data, and shall follow the voltage schedules issued by the ISO from time to time.” Appendix A to the ISO tariff defines Applicable Reliability Criteria to mean: “The Reliability Standards and reliability criteria established by NERC and WECC and Local Reliability Criteria, as amended from time to time, including any requirements of the NRC.” o Considerations for the ISO: These two tariff provisions refer to the WECC standard on governor droop settings for synchronous generators; they do not address non-synchronous generators. Appendix K to the ISO tariff requires resources certified to provide spinning reserve to respond immediately and automatically in proportion to frequency deviations through the action of a governor or other control system in accordance with the minimum governor performance requirements.14 o Considerations for the ISO: This addresses primary frequency response but does not quantify amount of frequency response to address the new NERC standard The ISO will therefore need to develop procedures and associated tariff provisions to ensure that sufficient frequency response capability is available in each operating hour to enable the ISO to demonstrate compliance with the new obligation. 14 See ISO tariff Appendix K CAISO/M&ID/JC 12 August 7, 2015 Frequency Response – Issue Paper California ISO The ISO is analyzing 2013 and 2014 events to identify gaps within present capabilities in meeting the frequency response obligation. This includes examining actual governor response and breaking out this analysis by (1) generators providing spinning reserves, and (2) other generators that are online. In addition, the ISO is evaluating whether our current procurement of spinning reserves can meet the new frequency response obligation. One consideration is that a generator may not be capable of providing as much frequency response capacity as spinning reserve capacity. Consequently, the ISO may have to modify spinning reserve procurement to ensure it obtains an adequate quantity of frequency response. Another option could be for the ISO to develop a separate market product to explicitly procure frequency response and ensure generator headroom. However, the ISO likely cannot implement a separate frequency response product by December 1, 2016. It would still have to implement another measure, such as using spinning reserves, as an interim solution. The ISO seeks stakeholder input on the following questions: 1. How should the ISO ensure there is sufficient frequency response capability on the system in all hours to satisfy the new requirement? 2. Should the ISO develop a market product to procure frequency response? 3. If the ISO cannot develop a product in time for the fall 2016 release, what interim solution would be appropriate? For example, using existing or modifying spinning reserve procurement. 4. WECC standards apply only to synchronous generators. Should the ISO explore a requirement that non-synchronous generators have primary frequency response capability? CAISO/M&ID/JC 13 August 7, 2015 Frequency Response – Issue Paper California ISO 5. Initiative Schedule Date Fri 8/7/15 Thu 8/13/15 Thu 8/27/15 Mon 9/14/15 Tue 9/22/15 Tue 10/06/15 Wed 10/30/15 Early November Mid November Mid to Early December Mid December Early January Wed 2/3/2016 Thu 2/4/2016 Event Issue paper posted Stakeholder call Stakeholder comments due Straw proposal posted Stakeholder meeting Stakeholder comments due Revised straw proposal posted Stakeholder call Stakeholder comments due Draft final proposal posted Stakeholder call Stakeholder comments due Board of Governors meeting 6. Next Steps The ISO will discuss this issue paper with stakeholders on a conference call on August 13, 2015. Stakeholders should submit written comments by August 27, 2015 to InitiativeComments@caiso.com. CAISO/M&ID/JC 14 August 7, 2015