ELEC-E8406 Electricity Distribution and Markets Research Assignment: Voltage Drop Instructor: John Millar Group #2 Mathias Westerholm 294515 Markus Ukkonen 226415 Verner Püvi 466505 Kennet Bexar 296801 Camila Barragán 545604 The task was to determine the percentage error in the voltage drop calculation between using the approximate formula and the more accurate formula, as defined below. This was to be done for a bare overhead line section of varying lengths, with a single load at the end, and a power factor of 0.9. Approximate formula Lagging power factor ππ ≈ √3 β πΌ(π cos π + ππ πππ) Leading power factor ππ ≈ √3 β πΌ(π cos π − ππ πππ) More accurate formula Lagging power factor (ππΌ cos π − π πΌ sin π)2 ππ = √3 β (π πΌ cos π + ππΌπ πππ + ) 2ππΏπ,π Leading power factor ππ = √3 β (π πΌ cos π − ππΌπ πππ + (ππΌ cos π + π πΌ sin π)2 ) 2ππΏπ,π To perform the calculations, a Raven conductor with the following characteristics was selected: DC @20°C (ohm/km) Ampacity 240 (A) Resistance AC @25°C AC @50°C (ohm/km) (ohm/km) AC @75°C (ohm/km) 0.521679 0.534803 0.646357 0.708696 Reactance Inductive @25°C Inductive @50°C Inductive @75°C (ohm/km) (ohm/km) (ohm/km) 0.341224 0.374034 0.380596 The resistance and reactance values used were those at 75°C, since the cable will be running close to its thermal limits, and thus temperatures are expected to be on the high end of the operating range. The load at the end of the line was determined under the assumptions that it put the cable close to its thermal limit (I = 240 A), that the supply (bus-bar) end voltage was 20.5 kV, and that the line length gave a voltage drop of 7% (Vr = 20.5 kV – 7%β20.5 kV). This means that voltage drops above 7% (namely 10%, 15% and 20%) will cause overloading of the cable. The formulas used can be seen below: π = √3ππΏπΏ πΌπ π = √3ππΏπΏ πΌπ cos π π = √3 β 19.065 ∗ 103 β 240 β 0.9 = 7.13 ππ A load of 7.13 MW would put the conductor at its thermal limit at 7% voltage drop. Voltage drop calculations Once the load was determined, the next step was to determine the line lengths that gave voltage drops of 1%, 3%, 5%, 7%, 10%, 15% and 20%. This was done for a lagging power factor of 0.9, and using the approximate formula. The results can be seen in the following table. Line lengths (km) Voltage drop 0.65 1% 1.92 3% 3.135 5% 4.295 7% 5.94 10% 8.41 15% 10.555 20% Using these particular line lengths, voltage drop was calculated using approximate and more accurate formula, for a lagging and a leading power factor of 0.9 The final results (not including the iterations) are shown in the following table. Calculations can be found in Appendix 1 (Excel file). Lagging power factor / simple formula Vr (V) I (amps) Vd (V) Vd(%) Lagging power factor / accurate formula Vr I (amps) Vd (V) Vd(%) Error Vd (V) 20295.9955 225.4544 204.0045 1.00% 20295.9937 225.4544 204.0063 1.00% 0.0009% 19884.9460 230.1149 615.0546 3.00% 19884.9293 230.1151 615.0712 3.00% 0.0027% 19474.5762 234.9639 1025.4308 5.00% 19474.5289 234.9644 1025.4782 5.00% 0.0046% 19065.0022 240.0116 1435.0372 7.00% 19064.9072 240.0128 1435.1322 7.00% 0.0066% 18449.3592 248.0206 2050.8883 10.00% 18449.1574 248.0233 2051.0902 10.01% 0.0098% 17426.1640 262.5834 3074.1924 15.00% 17425.6749 262.5908 3074.6821 15.00% 0.0159% 16400.4575 279.0057 4099.5776 20.00% 16400.4555 279.0058 4099.5796 20.00% 0.0000% Leading power factor / simple formula Vr (V) I (amps) Vd (V) Vd(%) Leading power factor / accurate formula Vr I (amps) 20380.7111 224.5173 119.2889 0.58% 20380.0459 224.5246 20143.4895 227.1613 356.5106 1.74% 20137.4724 227.2292 19911.0912 229.8127 588.9092 2.87% 19894.4534 230.0049 19683.8739 232.4655 816.1284 3.98% 19651.4710 19351.9443 236.4528 1148.0683 5.60% 18829.4383 243.0142 1670.5693 8.15% 18348.3755 249.3857 2151.6246 10.50% Vd (V) Vd(%) 119.9541 Error Vd (V) 0.59% 0.5546% 362.5277 1.77% 1.6598% 605.5471 2.95% 2.7476% 232.8488 848.5321 4.14% 3.8188% 19286.3737 237.2567 1213.6465 5.92% 5.4034% 18684.7961 244.8955 1815.2218 8.85% 7.9689% 18097.3641 252.8446 2402.6362 11.72% 10.4473% The errors between the approximate formula and the accurate formula can be observed in the following figure. Percentage error Percentage error in voltage drop calculation between approximate formula and more accurate formula. 15.0% 10.0% 5.0% Lagging power factor 0.0% 0.65 1.92 3.135 Leading power factor 4.295 5.94 8.41 10.555 Length of line (km) Corresponding to Vd of 1%, 3%, 5%, 7%, 10%, 15%, and 20% Observations and conclusions Various things can be pointed out from the results. The more obvious one is that, contrary to what was expected, the difference between the approximate and the accurate formula is practically negligible for a lagging power factor, even at voltage drops higher than 10%. The error does slightly increase as the voltage drop increases, except for the voltage drop of 20%, which is an anomaly in the pattern. For a leading power factor, on the other hand, the difference between the results of both formulas is bigger, reaching even an error of 10% for a leading power factor voltage drop of around 11% (length line corresponding to 20% voltage drop in a line with lagging power factor). Thus the approximate equation should be used with a lot of caution, if ever be used at all, for a leading power factor. It must also be reminded that as voltage drops, the voltage at the receiving end is lower, and can easily reach limits where the current goes higher than the rated ampacity of the cable (see figure below). This fact should cautiously be considered during the design phase of the network. Voltage at receiving end (V) Drop in Vr as a function of line length: lagging PF 21000.0000 20000.0000 19000.0000 18000.0000 17000.0000 Ampacity limit crossed 16000.0000 15000.0000 0 2 4 6 Line length 8 10 12