Scope of DOI White Paper: The Purpose of this document is to provide clarification on North
Carolina State Code requirements to Code Officials (CEO) who are agents for the Authority
Having Jurisdiction (AHJ).
DOI File #: WP61-11
Edition Date: 09/08/11, Revision 1: 12/05/11
Subject of White Paper: Classification of Building Materials
According to Combustibility
Contents
Page
1.0 Introduction………………………………………………………………………1
2.0 Summary of Code References……………………………………………………2
3.0 Classes of Materials Commonly Encountered in Building Construction………...3
A. Non-Combustible Materials………………………………………………3
B. Combustible Materials……………………………………………………4
C. Fire Retardant Treated Wood…………………………………………….4
D. Intumescent Coatings…………………………………………………….5
4.0 Descriptions of Tests……………………………………………………………..6
A. ASTM E 136……………………………………………………………..6
B. ASTM E 84………………………………………………………………7
C. ASTM E 119……………………………………………………………..8
D. NFPA 286………………………………………………………………..9
5.0 Technical References…………………………………………………………….10
6.0 Photographic Credits…………………………………………………………….10
1.0
Introduction
Chapter 6 of the North Carolina Building Code (NCBC) classifies buildings on the basis
of the combustibility of the materials from which they are constructed. Classifications by
materials are referred to as the “Type of Construction” of the building. Types I and II
construction by definition require all structural (load-bearing) frame members to be non-
File No. WP61-11
Material Combustibility
Page 1
combustible materials, i.e., materials that do not readily burn. Exterior walls in Types
III and IV construction are also required to be non-combustible. Other structural
members in Types III and IV construction and all structural members in Type V
construction may be combustible materials; that is, materials that readily burn.
The amount of fuel available to feed a fire is known as the “fire loading.” Increasing fire
loading increases the heat release and the smoke release of a fire. Higher heat and smoke
release pose a greater hazard to building occupants and increase the difficulty of fighting
a fire. In an effort to limit fire loading, Table 503 of the NCBC limits the height and area
of a building based on construction type and occupancy classification, both of which are
an indication of the amount of combustible materials present in the building. Limiting
the fire loading in a building increases the amount of time occupants have to exit the
building, provides firefighters with more time for rescue, and limits the resources,
including manpower, equipment and water, required to extinguish the fire.
As an aid to the CEO, the remainder of this document deals with the classification of
materials based on combustibility. Emphasis is on testing required to establish noncombustibility, common materials considered to be non-combustible, and materials
which may be substituted for non-combustible materials under certain circumstances.
2.0
Summary of Code References (2012 edition)
 NCBC Section 602 – Defines building construction types on the basis of materials
and fire resistance ratings.
 NCBC Section 603 – Lists exceptions to non-combustible materials in Type I and
Type II Construction.
 NCBC Section 703.4 – Establishes ASTM E 136 as the test required for noncombustibility and references ASTM E 136 for passing criteria. This section also
establishes criteria for classification of composite materials as non-combustible.
 NCBC Section 803.2 – Allows NFPA 286 test as an alternative to ASTM E 84 to
establish combustibility of finish materials, and provides acceptance criteria for the
NFPA 286 test.
 NCBC Section 2303.2 – Defines fire retardant treated wood in terms of an extended
ASTM E 84 test and establishes labeling requirements.
 NCBC Section 2603.9 – Allows passing NFPA 286, UL 1715, or FM 4880 as
alternatives to providing a prescriptive thermal barrier for foam plastics.
 NCFC (Fire Prevention Code) Section 803.4 – Allows use of intumescent coatings
to achieve flame spread requirements in existing buildings, and requires maintenance
of the coating.
File No. WP61-11
Material Combustibility
Page 2
3.0
Classes of Materials Commonly Encountered in Building Construction
A. Non-combustible material – A non-combustible material is a substance that will not
ignite, burn, support combustion, or release flammable vapors when subject to fire or
heat, in the form in which it is used and under conditions anticipated. Any solid
substance complying with either of two sets of passing criteria listed in Section 8 of
ASTM E 136 when the substance is tested in accordance with the procedure specified
in ASTM E 136 is considered to be non-combustible.
1. Passing Criteria #1:
a. Weight loss of the specimen cannot exceed 50%.
b. Temperatures on the surface of the specimen and at the geometric
center of the specimen during the test may not rise more than 54oF
(30oC) above the equilibrium temperature of the furnace measured
prior to introducing the specimen.
c. During the first 30 seconds of the test, there can be no flaming from
the specimen.
2. Passing Criteria #2:
a. If more than 50% of the weight of the specimen is lost, the material
may still be classified as non-combustible provided both of the
following conditions are met.
b. Temperatures on the surface of the specimen and at the geometric
center of the specimen during the test may not rise above the
equilibrium temperature of the furnace measured prior to introducing
the specimen.
c. No flaming from the specimen can occur at any time during the test.
3. Examples of non-combustible materials include:
a. Portland cement concrete, gypsum concrete (normally used in drywall
or poured gypsum floor toppings), or magnesite (magnesium oxide)
concrete having aggregates of sand, gravel, expanded vermiculite,
expanded or vesicular slags, diatomaceous silica, perlite, or pumice.
This class of products includes Portland cement stucco, Portland
cement plaster, and gypsum plaster, as well as concrete.
b. Brick masonry, concrete block masonry, and ceramic tiles.
c. Metals except aluminum (aluminum is classified as limitedcombustible), magnesium and magnesium alloys.
d. Sheet glass, block glass, and uncoated glass fibers.
e. Mineral wool and rock wool.
4. Composite materials may be considered non-combustible if the material has a
structural base of non-combustible material, the combustible surfacing is not
File No. WP61-11
Material Combustibility
Page 3
more than 0.125” thick, and the surfacing has a flame spread less than 50
when tested in accordance with ASTM E 84.
B. Combustible material – Any solid substance that does not comply with either
Passing Criteria #1 or Passing Criteria #2 when tested in accordance with ASTM E
136 is considered to be combustible. Combustible materials will ignite, burn, support
combustion, or release flammable vapors. Wood is by far the most common
combustible material used for structural purposes in building construction.
C. Fire Retardant Treated Wood – “Fire retardant treated wood is any wood product
which, when impregnated with chemicals by a pressure process or other means during
manufacture, shall have, when tested in accordance with ASTM E 84, a listed flame
spread index of 25 or less and show no evidence of significant progressive
combustion when the test is continued for an additional 20-minute period. In
addition, the flame front shall not progress more than 10.5 feet beyond the centerline
of the burners at any time during the test.” (NCBC Section 2303.2)
1. Fire retardant treated wood is a combustible material; even though, when
first introduced, the product was
marketed as “Non-comb” wood.
There are, however, certain
circumstances under which fire
retardant treated wood may be
substituted for non-combustible
materials. For instance, fire
retardant treated wood is allowed in
exterior walls of Type III buildings
when the exterior wall is 2 hour
rated (Section 602.3). Section 603 of the NCBC lists the following locations
where fire retardant treated wood may be substituted for non-combustible
materials in Type I and II Construction.
a. Non-load-bearing partitions with a fire resistance rating of 2 hours or
less.
b. Non-load-bearing exterior walls requiring no fire rating.
c. Roof construction in Type I Construction two stories or less and Type
II Construction of any height, including girders, trusses, framing, and
decking.
d. Roof construction in Type I Construction exceeding two stories in
height when the vertical distance from the upper floor to the roof is 20
feet or more.
File No. WP61-11
Material Combustibility
Page 4
2. Usually, fire retardant treated wood appears darker than untreated wood.
Sometimes the color difference is subtle, and identification by color alone in
not always possible. As a result, labeling of fire retardant treated wood is
required. Labels shall identify the approving agency and the treating
manufacturer. Species of the wood, trade name of the treatment, flame
spread, and smoke developed must also appear on the label.
3. Exposure to weather or moisture can cause leaching of the salts deposited by
the treating chemicals. Leaching salts can increase the flame spread of the
material and facilitate corrosion of metals in contact with the fire retardant
treated wood. Consequently, fire retardant treated wood for exterior use must
be subjected to a Standard Rain Test (ASTM D 2898). Upon passing the test,
the material may be labeled for exterior exposure, and only materials labeled
for exterior exposure should be used in exterior or moist environments,
including locations where condensation is likely to form.
D. Intumescent Coatings – Liquid applied in either the shop or the field, intumescent
coatings encapsulate the material to which they are applied. When exposed to heat,
intumescent coatings char and swell, increasing in volume and decreasing in density,
thereby creating an insulating effect.
1. There are two types of intumescents.
a. Soft char intumescents produce a light char
when heated that acts as an insulator due to
poor heat conduction characteristics. In
addition, hydrates in these products liberate
water vapor in the presence of heat,
producing a cooling effect. Expansion
pressures associated with these products
are low, and soft char intumescents are,
consequently, best suited for coatings.
b. Hard char intumescents typically contain
sodium silicates or graphite, which create a
heavy char with substantial expansion
pressure associated with volume increase.
Often, these materials are used for
firestopping materials and sometimes for
coatings.
2. The wide variety of intumescent coatings on the
market may be used in several different
applications. Whatever the application, the
product must be subjected to the appropriate
File No. WP61-11
Material Combustibility
Page 5
testing for the intended use. Uses of intumescent coatings and appropriate
testing include the following:
a. When applied to specific structural elements and the coated element is
tested in accordance with ASTM E 119, some intumescent coatings
are capable of maintaining a fire resistance rating on certain materials,
primary of which is structural steel. These coatings are typically
referred to in marketing literature as “fire resistive” coatings.
b. Coatings used to achieve a flame spread are generally referred to as
“fire retardant” coatings. Products in this class may be tested to
ASTM E 84. More commonly, alternative tests allowed by the NCBC,
including UL 1715, NFPA 286, and FM 4880 are preferred by the
manufacturers. Passing one of these three tests allows the coating to
be used as an alternative to a prescriptive thermal barrier or ignition
barrier when applied to foam plastic insulations, as well as for
increasing the flame spread of an interior finish material.
c. When used as an alternative to fire retardant treated wood, fire
retardant coatings, applied to the same material intended for field use,
must pass the same extended ASTM E 84 test as fire retardant treated
wood. (See item 3C above.) Protection of metal fasteners must also be
addressed.
3. Intumescent coatings are vulnerable to environmentally induced deterioration,
and must be maintained. Abraded areas must be touch coated as soon as
possible after damage is incurred, and coatings must be re-applied periodically
in accordance with the manufacturer’s recommendations. Therefore, use of
these coatings in areas that are not accessible after completion of the project is
not recommended.
4.0
Descriptions of Tests
A. ASTM E 136 – Standard Test for Behavior of Materials in a Vertical Tube
Furnace at 750oC
File No. WP61-11
Material Combustibility
Page 6
1. ASTM E 136 is the test specified by the code as required to establish a
material as a non-combustible material. This test does not apply to laminated
or coated materials. Aluminum will not pass an E 136 test; therefore,
aluminum cannot be classified as non-combustible.
2. A tube furnace is pre-heated to a temperature of 750oC. A
pre-weighed material specimen is, then, lowered into the
furnace with a thermocouple attached to the surface and a
thermocouple located at the geometric center of the specimen.
Testing continues until both thermocouples have stabilized at a maximum
reading or until one of the acceptance criteria is violated. (See item 3.0A for
acceptance criteria.)
B. ASTM E 84 – Standard Method for Surface Burning Characteristics of Building
Materials
1. ASTM E 84 is specified by the code as the test to assess the contribution of
surface finishes on walls and ceilings to fire loading. ASTM E84 does not
measure heat transmission to determine fire resistance ratings or if the
material should be classified as non-combustible.
2. The test is a comparative test intended to measure the propagation of flame
from an ignition source along a specified length of the material and compare
the distance of propagation to a reference material, red oak. ASTM E84 is an
industry standard for defining how a product performs when tested for surface
flame spread. The result of the test is based on a scale that compares the
surface burning to select grade red oak, which is rated 100. A product that has
a flame spread of 25 has a surface burning spread 25% of red oak. A test
report for a product may also include the smoke developed index, which is
required to be less than 450.
3. A full length, full width specimen is attached to the ceiling of a nominally 24
foot long by 18 inch wide duct with a gas burner at one end. Airflow,
calibrated to spread the flame
the full length of a red oak
specimen in 5 ½ minutes, is
introduced, and the burner
ignited. Distance the flame
spreads in 10 minutes is
measured, and flame spread is
calculated from formulas
included in the test standard.
4. For fire retardant treated wood the test is extended an additional 20 minutes,
subject to the acceptance criteria specified in Section 2303.2 of the NCBC.
File No. WP61-11
Material Combustibility
Page 7
C. ASTM E 119 – Standard Test Methods for Fire Tests of Building Construction
and Materials
1. Fire resistance ratings required by the NCBC for wall assemblies, floor/ceiling
assemblies, roof/ceiling assemblies and individual structural members are
established by or based on testing in accordance with ASTM E 119. The term
“assembly” refers to a collection of components, structural and non-structural,
arranged in a specific way. Fastening of components in an assembly is limited
to the tested fastening method and arrangement. Ratings on assemblies may
be required by the code to prevent structural collapse, to compartmentalize a
building, to protect an element of an egress system, or some combination of
the three. Individual structural members, beams and columns, are typically
required to be rated in certain types of construction to prevent structural
collapse.
2. An assembly or structural member is placed in a flat furnace in either the
horizontal or vertical position, depending on in service use. If the specimen is
a load-bearing element, a specific load
is imposed on the specimen. The
specimen is, then, subjected to a
controlled flame introduced from one
side of the assembly, simulating
exposure conditions during in-service
use and producing temperatures
increasing to a maximum along a
specific time-temperature relationship.
Columns are exposed to the heat
source on all sides to simulate actual
in-service use. Testing continues until
one of the following three failure
modes is observed:
a. Structural collapse occurs.
b. The temperature measured on
the unexposed surface of the assembly exceeds 250oF. This criterion
is a measure of heat transmission through the assembly.
c. Cotton waste placed on the unexposed side of the assembly ignites.
This criterion is a measure of the passage of flame and hot gases
through the assembly.
File No. WP61-11
Material Combustibility
Page 8
3. Classification of the assembly is reported in hours based on the duration of the
test.
D. NFPA 286 – Fire Tests for Evaluating Contribution of Wall and Ceiling Interior
Finish to Room Fire Growth (a.k.a. the Room Corner Test)
1. As stated in the title of the standard, NFPA 286 is intended to evaluate the
contribution of interior surface finishes to a fire. To this purpose, the NCBC
allows NFPA 286 as an alternative to ASTM E 84. Chapter 26 of the NCBC
also allows passage of the room corner test as an alternative to providing a
thermal barrier between foam plastics and occupied interior spaces. A
modified version of NFPA 286 has been developed by the foam plastic
insulation industry as an alternative to ignition barriers in non-storage attics
and crawl spaces. ICC has adopted this modified test as part of their
evaluation criteria AC 377 for foam plastic insulation. UL 1715 is a test
protocol similar to NFPA 286 used for the same purposes.
2. A room is constructed in an indoor laboratory from wood framing, light gage
metal framing, or concrete block. The room door opening remains an opening
without a door. Interior walls and ceiling of the room are covered with the
test material. A gas burner of specific height is placed in one corner of the
room, and thermocouples are located at specific locations within the room.
Duration of the test is 15 minutes. For the first five minutes the burner is
operated at an output of 40 kW. After five minutes the burner output is
increased to 160 kW and remains at 160kW for the final ten minutes of the
test.
3. NFPA 286 has a specific definition of flashover, but specifies no acceptance
criteria. Acceptance criteria are specified in Section 803.2.1 of the NCBC,
one of which is the room must not flashover during the 160 kW exposures.
File No. WP61-11
Material Combustibility
Page 9
5.0
Technical References
A.
Wikipedia - http://en.wikipedia.org/wiki/Intumescent
B.
Answers.com - http://www.answers.com/topic/noncombustible-material-1
6.0
Photographic Credits
A.
www.alpinepainting.com
B.
www.alertinsulation.com
C.
www.pathnet.org
D.
www.independent.com
E.
www.buildinggreen.com
F.
www.westernfire.com
G.
www.harvel.com
H.
www.contegointernational.com
File No. WP61-11
Material Combustibility
Page 10
Related documents
Download