Proof Positive® Copper-Clad Steel

advertisement
Grounding & Bare Copper
Proof Positive®
Copper-Clad
Steel
CONSTRUCTION
AT A GLANCE
CONDUCTOR TYPE 1
Copper-clad steel
Applications
SPECIFICATIONS
• Used as uninsulated hook ups, jumpers,
and grounds in electrical and substation
construction
Southwire’s Proof Positive® Copper-Clad
Steel Conductor meets or exceeds the
following applicable ASTM specifications:
• Suitable for direct burial
•B 910: Annealed Copper-Clad Steel Wire
• Unique serial number provides proof of
ownership for traceability
OPTIONS
• Solid (1 strand)
CONSTRUCTION DETAILS
• Stranded (7 and 19 strands)
•Bare copper-clad steel stranded conductor
• 30% or 40% conductivity, DSA (dead soft
annealed)
• Low carbon (LC) steel
•Center strand is tinned and has a laseretched, unique set of codes that will be
visible for the life of the conductor
•Code is comprised of:
• A license code
• A serial number unique to every foot of
cable
• The website URL which stores the
ownership information
•One strand in the outermost layer of the
construction is also tinned
1
41
Section C
Solid Constructions
Size
(AWG)
0.1285
Weight
(lbs/1000 ft)
Minimum
Breaking Load (lbf)
Short Time Fusing
Current @ 30
Cycles kA
Nominal DC
Resistance @20ºC
(Ω/1000 ft)
in2
cmil
40%*
COND
30%*
COND
40%*
COND
30%*
COND
40%*
COND
30%*
COND
40%*
COND
30%*
COND
0.0130
16512
46.3
45.82
503
566
2.23
1.93
1.572
2.094
6
0.1620
0.0206
26250
73.6
72.8
800
900
3.55
3.07
0.989
1.317
4
0.2043
0.0328
41738
117.0
115.8
1272
1431
5.65
4.89
0.622
0.828
2
0.2576
0.0521
66368
186.1
184.1
2023
2275
8.98
7.77
0.391
0.521
*40% or 30% conductivity of IACS
Stranded Constructions
Size
(AWG)
# of
Wires
Diameter
(inches)
Cross Sectional
Area
Weight
(lbs/1000 ft)
Minimum
Breaking Load (lbf)
Short Time Fusing
Current @ 30
Cycles kA
Nominal DC
Resistance @20ºC
(Ω/1000 ft)
in2
cmil
40%*
COND
30%*
COND
40%*
COND
30%*
COND
40%*
COND
30%*
COND
40%*
COND
30%*
COND
259
257
2513
2827
12.39
10.73
0.286
0.381
7
0.343
0.0720
91612
7 No. 8
7
0.386
0.0908
115586
327
324
3171
3567
15.63
13.54
0.227
0.302
2/0
7
0.410
0.1046
133115
377
373
3652
4108
18.01
15.59
0.197
0.262
7 No. 7
7
0.433
0.1145
145757
413
409
3998
4498
19.72
17.07
0.180
0.240
7 No. 6
7
0.486
0.1443
183708
520
515
5040
5670
24.85
21.52
0.143
0.190
7 No. 5
7
0.546
0.1819
231613
656
649
6354
7148
31.33
27.13
0.113
0.151
4/0
19
0.530
0.1661
211475
601
595
5801
6526
28.60
24.77
0.124
0.166
19 No. 9
19
0.572
0.1953
248660
707
700
6821
7674
33.63
29.13
0.106
0.141
19 No. 8
19
0.643
0.2464
313733
892
883
8606
9682
42.44
36.75
0.084
0.112
*40% or 30% conductivity of IACS
42
Proof PositivE® Copper-CLAD STEEL
7 No. 9
Grounding & Bare Copper
8
Diameter
(inches)
Cross Sectional
Area
Download