3/10/14 Electrical Plans

advertisement
ELECTRICAL SYMBOLS
FLOOR OUTLET / DEVICES AND SHOWN
SMOKE DETECTOR -RESIDENTIAL
RANGE OUTLET
TRACK LIGHTING UNIT
RECESSED DOWNLIGHT WALLWASH / FLOOD
CEILING MOUNTED EXIT SIGN
WALL MOUNTED EXIT SIGN
EMERGENCY LIGHTING UNIT W/ HEADS
RECESSED REMOTE HEAD
WALL MOUNTED REMOTE HEAD
EMERGENCY LIGHTING UNIT W/O HEADS
CONTROL
SINGLE POLE TOGGLE SWITCH
JUNCTION BOX
STROBE UNIT ( VISIBLE ONLY )
HORN UNIT ( AUDIBLE ONLY )
WALL SPEAKER*
RECESSED CEILING SPEAKER
GUEST ROOM DEVICE - HORN / SMOKE DETECTOR
VOLUME CONTROL*
PULL STATION
TELEVISION OUTLET*
FIRE ALARM CONTROL PANEL
COMMUNICATIONS*
BELL / BUZZER
DOUBLE POLE TOGGLE SWITCH
MOMENTARY CONTACT SWITCH
SPEED CONTROL SWITCH
PUSH BUTTON
DIMMER
3-WAY DIMMER
ELECTRIC THERMOSTAT
GUEST ROOM DEVICE - HORN / STROBE / SMOKE DETECTOR
MICROPHONE OUTLET*
4-WAY TOGGLE SWITCH
KEYED SWITCH
HORN STROBE UNIT ( AUDIBLE & VISIBLE )
CLOCK OUTLET (UNLESS SPECIFIED WIRELESS)
WALL MOUNTED TELEPHONE OUTLET*
SWITCH WITH PILOT
BEAM DETECTOR TRANSMITTER/RECEIVER
WALL MOUNTED JUNCTION BOX
3-WAY TOGGLE SWITCH
SWITCH WITH TIMER
DUCT MOUNTED SMOKE DETECTOR / DAMPER CONTROL
AUNNUNCIATOR
SPRINKLER FLOW SWITCH
SPRINKLER TAMPER SWITCH
VICTORIA CITY HALL
FFE = 974.0
MAGNETIC DOOR HOLD OPEN
MISCELLANEOUS
DEVICES MOUNTED IN COMMON OUTLET
MOTOR CONTROLLER
COMBINATION MOTOR CONTROLLER / DISCONNECT
T
SMOKE DAMPER
CARBON MONOXIDE DETECTOR
AREA OF RESCUE
AIL
DISCONNECT SWITCH
R
ET
PANEL - REFER TO SCHEDULE
Y
NT
TERMINAL CABINET
CO
N
I
P
MOTOR
BIK
U
E
HE
NN
PROPOSED TRANSFORMER
I hereby certify that this plan,
specification, or report was
pre-pared by me or under my
direct supervision and that i am
a duly registered Engineer under
the laws of the state of
Minnesota.
Kaeko Leitch
Reg. No.:
)
AK
RL
GE
TEI
ANE
EL
Date:
S
3 (
ABBREVIATIONS
.N
. RD
CO
1
O. 1
This document is by Brunton
Architects and contains privileged
and confidential information
intended for use by Brunton
Architects personnel only. Any
disclosure or distribution of this
document or information contained
herein, without prior written
consent of Brunton Architects, is
prohibited.
S
1
E0.1
SITE PLAN - ELECTRICAL
SCALE: 1" = 20'-0"
20
SCALE
0
20
NORTH
FEET
PLAN NOTES
1. PROVIDE (2) 4" SCHEDULE 40 PVC CONDUITS FROM TELEPHONE BACKBOARD TO
PROPERTY LINE , CAP AND STAKE. BURY CONDUIT 30" BELOW GRADE, 3'-0" SWEEPS,
NO ELECTRICAL BENDS ALLOWED. BORE CONDUITS UNDER CO. RD. 113 TO APPROXIMATE
LOCATION SHOWN. FIELD VERIFY EXACT LOCATION WITH TELEPHONE UTILITY.
REVISIONS:
2. NEW 800A SERVICE. E.C. TO PROVIDE CONDUITS AND CONDUCTORS AS REQUIRED.
BORE FEEDERS UNDER CO. RD. 113 AS REQUIRED TO MAKE CONNECTION TO UTILITY
TRANSFORMER.
3. 200A/2P FEEDER TO BAND SHELTER, APPROXIMATELY 150 FEET. FIELD VERIFY EXACT
LOCATION WITH OWNER AND OR ARCHITECT PRIOR TO INSTALLATION. BAND SHELTER
PANEL PROVIDED AND INSTALLED BY OTHERS.
SHEET NO.
E0.1
DATE:
SURFACE FLUORESCENT, NIGHT LIGHT / EMERGENCY
DUCT SMOKE DETECTOR
PROJECT MANAGER:
SURFACE FLUORESCENT
HALF SWITCHED DUPLEX RECEPTACLE
GFCI PROTECTED OUTLET
WEATHER PROOF & WEATHER RESISTANT OUTLET
SPECIAL PURPOSE OUTLET
CHECKED BY:
RECESSED FLUORESCENT, NIGHT LIGHT / EMERGENCY
THERMAL HEAT DETECTOR - FIXED TEMPERATURE
DRAWN BY:
RECESSED FLUORESCENT
QUAD-PLEX RECEPTACLE
THERMAL HEAT DETECTOR -RATE OF RISE
FOX/BJB
WALL MOUNTED FIXTURE NIGHT LIGHT / EMERGENCY
DUPLEX RECEPTACLE
PHOTOELECTRIC SMOKE DETECTOR
SITE PLAN - ELECTRICAL
WALL MOUNTED FIXTURE
DEVICES
CONSULTANT
RECESSED DOWNLIGHT, NIGHT LIGHT / EMERGENCY
FIRE ALARM
PROJECT:
RECESSED DOWNLIGHT
PLAN NOTE
PROJECT NUMBER:
SURFACE FIXTURE, NIGHT LIGHT / EMERGENCY
MOTOR DESIGNATION - REFER TO SCHEDULE
SHEET TITLE:
SURFACE FIXTURE
PHOTO ELECTRIC CONTROL
NURSE CALL
INTERCOM
CARD READER
OCCUPANCY SENSOR
QUAMOCLIT
STREET
LIGHTING FIXTURES
LIGHT FIXTURE TYPE - REFER TO SCHEDULE
F
WORKROOM
109
LIBRARY
106
ELEC.
108
JANITOR 103
E
IT
110
ELEV.
EQUIP
105
MEN
102
D
RECESSED LIGHT FIXTURE SUPPORT DETAIL
SPRINKLER
104
NO SCALE
WOMEN
101
EMERGENCY CONTROL DEVICE DETAIL
LOBBY
100
WEST STAIR
107
N.T.S.
STOR.
111
C
BOOK
DROP
112
B
EAST STAIR
113
CONSULTANT
A
1
2
2.9
3
3.9
4
4.6
5
6
7
I hereby certify that this plan,
specification, or report was
pre-pared by me or under my
direct supervision and that i am
a duly registered Engineer under
the laws of the state of
Minnesota.
Kaeko Leitch
Reg. No.:
Date:
1
E1.1
LIGHTING CONTROL PANEL LCP-01
FIRST FLOOR PLAN - LIGHTING
8
SCALE: 1/8" = 1'-0"
0
8
NORTH
This document is by Brunton
Architects and contains privileged
and confidential information
intended for use by Brunton
Architects personnel only. Any
disclosure or distribution of this
document or information contained
herein, without prior written
consent of Brunton Architects, is
prohibited.
N.T.S.
SCALE
FEET
F
BREAK RM.
216
CONF. RM.
202
WEST STAIR
206
UNISEX
RESTROOM
215
SERVER
ROOM
214
E
LIGHTING CONTROL PANEL LCP-02
COUNCIL
CHAMBERS
203
N.T.S.
RECEPTION
212
PLAN NOTES
AV RM.
201
GENERAL NOTES
LOBBY
200
6. LIGHTING IN THIS AREA TO BE CONTROLLED VIA DIMMABLE DAYLIGHT HARVESTING.
SUPPLIER AND/OR MANUFACTURER TO DETERMINE MOUNTING LOCATIONS AND
QUANTITIES. SEE NOTE 7.
OFFICE
209
OFFICE
210
ADMIN.
OFFICE
211
A
F. A NUMBER NEXT TO A LIGHT FIXTURE REPRESENT THE CIRCUIT NUMBER. THE
LETTER NEXT TO A LIGHT FIXTURE IS THE SWITCH DESIGNATION.
1
1.2
2
2.9
3
3.9
4
4.6
5
6
6.8
7
7. LCD-203 DIMMING DAYLIGHT HARVESTING SYSTEM. BT-203 POWER PACK HAS (3)
NORMALLY OPEN RELAYS, 620VA, AT 120 OR 277 VAC. POWER PACKS ARE USED TO
INCREASE LOAD CAPACITY TO 20A IN EACH ZONE. VERIFY PLACEMENT OF DEVICES
WITH FACTORY. MANUFACTURER - WATTSTOPPER. LS-5C SWITCH.
8. ROUTE HOME RUN THRU LIGHTING CONTROL LCP-01. SEE DETAIL THIS SHEET.
9. RECESSED GROUND MOUNTED FLAG FLOOD LIGHT. MOUNT FLOOD 36" FROM FLAG POLE.
10. ROUTE HOME RUN THRU LIGHTING CONTROL PANEL LCP-02. SEE DETAIL THIS SHEET.
2
E1.1
SECOND FLOOR PLAN - LIGHTING
SCALE: 1/8" = 1'-0"
8
SCALE
0
8
FEET
NORTH
SHEET NO.
E1.1
DATE:
OFFICE
208
CONF. RM.
207
PROJECT MANAGER:
B
CHECKED BY:
E. CONCEAL RACEWAY WHERE EVER POSSIBLE. WHEN EXPOSED RACEWAY MUST BE USED
IN FINISHED AREAS, IT SHALL BE A SURFACE RACEWAY SYSTEM SUCH AS PANDUIT OR
WIREMOLD, PER SPEC SECTION 26 05 33.
C
FOX/BJB
5. LIGHTING IN THIS AREA TO BE CONTROLLED VIA COMBINATION OCCUPANCY SENSOR(S),
WALL SWITCH AND DIMMABLE DAYLIGHT HARVESTING. SUPPLIER AND/OR
MANUFACTURER TO DETERMINE MOUNTING LOCATIONS AND QUANTITIES. SEE NOTE 7.
D. WHEN NOTED "EQUAL MANUFACTURE", "OR EQUAL", "APPROVED EQUAL", OR OTHER
SIMILAR TERMS, IT IS UNDERSTOOD TO MEAN THE ENGINEER'S AND ARCHITECT'S
APPROVAL. HAVING PRIOR APPROVAL ON A MANUFACTURE ONLY, DOES NOT RELIEVE
THE MANUFACTURE OF MEETING WHAT IS SPECIFIED. THE FINAL ACCEPTANCE OR
REJECTION WILL BE BASED ON REVIEW OF THE SHOP DRAWINGS BY THE ENGINEER
AND ARCHITECT.
DRAWN BY:
4. 2000W, 120V EMERGENCY LIGHTING INVERTER PROVIDED AND INSTALLED BY DIV. 26.
SURE-LITES CFMT020.
REVISIONS:
C. ELECTRICAL CONTRACTOR TO UPDATE PANEL INDEXES UPON COMPLETION.
FIRST AND SECOND FLOOR LIGHTING
3. THIS LIGHT CONNECTED THRU WATTSTOPPER ELCU EMERGENCY CONTROL DEVICE.
SEE DETAIL THIS SHEET. SUPPLIER AND/OR MANUFACTURER TO DETERMINE MOUNTING
LOCATIONS AND QUANTITIES
ROOF
ACCESS
205
B. REUSE EXISTING RACEWAY WHENEVER POSSIBLE.
PROJECT NUMBER:
2. LIGHTING IN THIS ROOM TO BE CONTROLLED VIA COMBINATION OCCUPANCY SENSOR(S)
AND LIGHT SWITCHES. SUPPLIER AND / OR MANUFACTURE TO DETERMINE MOUNTING
LOCATIONS & QUANTITIES.
A. PROVIDE A CONSTANT HOT TO ALL NIGHT LIGHTS, EXIT SIGNS, & EMERGENCY LIGHTS.
SHEET TITLE:
1. LIGHTING IN THIS ROOM TO BE CONTROLLED BY OCCUPANCY SENSOR(S). SUPPLIER
AND/ OR MANUFACTURE TO DETERMINE MOUNTING LOCATIONS & QUANTITIES.
PROJECT:
EAST STAIR
213
GENERAL NOTES
PLAN NOTES
A. COORDINATE RECEPTACLE HEIGHTS ABOVE OR IN CABINETS WITH ARCHITECTURAL
PLANS.
1. DUAL CHANNEL ALUMINUM POWER POLE, PANDUIT PCPA. E.C. TO PROVIDE AND INSTALL
POLE AND MAKE 120V CONNECTION TO OWNER SUPPLIED FURNITURE.
B. ELECTRICAL CONTRACTOR TO UPDATE PANEL INDEXES UPON COMPLETION.
2. MULTI-SERVICE FLUSH FLOOR BOX PROVIDED AND INSTALLED BY E.C. WITH DEVICES
AS INDICATED. WIREMOLD RFB4. FIELD VERIFY EXACT LOCATION WITH OWNER PRIOR
TO INSTALLATION.
D. AMOUNT AND PLACEMENT OF NAC PANELS ARE TO BE DETERMINED BY THE FIRE
ALARM EQUIPMENT SUPPLIER. EACH NAC PANEL IS TO HAVE A SMOKE DETECTOR
WITHIN 5' OF THE PANEL.
E. REMOTE TEST SWITCHES FOR DUCT SMOKE DETECTORS ARE TO BE GROUPED IN A
READILY ACCESSIBLE LOCATION IN EACH AREA.
F. MAKE 120V CONNECTION TO SMOKE FIRE DAMPERS. DAMPERS TO LOOSE POWER UPON
ACTIVATION OF FIRE ALARM SYSTEM. DAMPERS TO BE POWERED OPEN WHEN FIRE
ALARM PANEL HAS BEEN RESET.
G. WHEN NOTED "EQUAL MANUFACTURE", "OR EQUAL", "APPROVED EQUAL" OR OTHER
SIMILAR TERMS, IT IS UNDERSTOOD TO MEAN THE ENGINEER'S AND ARCHITECT'S
APPROVAL. HAVING PRIOR APPROVAL ON A MANUFACTURE ONLY, DOES NOT RELIEVE
THE MANUFACTURE OF MEETING WHAT IS SPECIFIED. THE FINAL ACCEPTANCE OR
REJECTION WILL BE BASED ON REVIEW OF THE SHOP DRAWINGS BY THE ENGINEER
AND ARCHITECT.
H. CONCEAL RACEWAY WHERE EVER POSSIBLE. WHEN EXPOSED RACEWAY MUST BE USED
IN FINISHED AREAS, IT SHALL BE A SURFACE RACEWAY SYSTEM SUCH AS PANDUIT OR
WIREMOLD, PER SPEC SECTION 26 05 33.
4. FIELD VERIFY EXACT TV DEVICE AND RECEPTACLE MOUNTING HEIGHT AND LOCATION
WITH OWNER PRIOR TO INSTALLATION.
E
6. E.C. TO PROVIDE AND INSTALL SWITCHED GFCI RECEPTACLE UNDER SINK FOR DISPOSAL.
DISPOSAL PROVIDED AND INSTALLED BY OTHERS.
WORKROOM
109
ELEV.
EQUIP
105
ELEC.
108
7. MULTI-OUTLET ASSEMBLY (PANDUIT T-70) MOUNTED AT APPROXIMATELY 18" A.F.F. WITH
DEVICES AS INDICATED, UNLESS NOTED OTHERWISE. DEVICES AND COVERPLATES TO BE
OF SAID MANUFACTURER SO THAT COLOR OF DEVICES AND RACEWAY MATCH.
MEN
102
D
STOR.
111
WOMEN
101
WEST STAIR
107
9. 12"L, 4"H, 1/4" THICK COPPER BUS BAR WITH (1) #6 BARE GROUND BACK TO MDP-1.
PROVIDED AND INSTALLED BY E.C.
J. CHECKOUT & START UP OF VFD'S ARE BY DIV. 23.
11. DEVICES TO BE MOUNTED IN BACK OF CABINET. FIELD VERIFY EXACT MOUNTING
REQUIREMENTS WITH CABINET SUPPLIER.
12. E.C. TO PROVIDE AND INSTALL (2) 4" EMT CONDUITS FROM SERVER ROOM 214 TO CEILING
SPACE IN IT 110 FOR COMMUNICATIONS CABLES. STUB CONDUITS 4" A.F.F. PROVIDE
BUSHINGS ON BOTH ENDS. CONCEAL ALL CONDUITS.
13. E.C. TO MAKE 120V POWER CONNECTION TO AUTO DOOR. DOOR PROVIDED AND
INSTALLED BY OTHERS.
IT
110
SPRINKLER
104
8. ALL 120V, 20A DUPLEX RECEPTACLES IN BREAK ROOM TO BE GFCI MOUNTED AT 44" A.F.F.
UNLESS OTHERWISE NOTED.
10. FLOOR BOX PROVIDED AND INSTALLED BY E.C. FIELD VERIFY EXACT LOCATION WITH
OWNER PRIOR TO INSTALLATION. STEEL CITY 665-AV2 FLOOR BOX.
L. ELECTRICAL CONTRACTOR SHALL SIZE CONDUCTORS AS REQUIRED BY N.E.C. FOR
VOLTAGE DROP COMPENSATION.
JANITOR
103
5. MAKE 120V CONNECTION TO DISHWASHER, CORD PROVIDED WITH UNIT INSTALLED
BY E.C.
I. IN RACEWAYS WITH MULTIPLE CIRCUITS, THE NUMBER NEXT TO THE RECEPTACLE
INDICATES THE CIRCUIT NUMBER. A SEPARATE NEUTRAL IS TO BE INSTALLED FOR
EACH HOMERUN.
K. ALL SPECIAL SYSTEM CABLES TO BE RAN IN A RACEWAY UNLESS INSTALLED ABOVE
ACCESSIBLE CEILINGS.
LIBRARY
106
3. E.C. TO MAKE 120V POWER CONNECTION TO HAND DRYER. DRYER PROVIDED AND
INSTALLED BY OTHERS. FIELD VERIFY EXACT LOCATION AND MOUNTING HEIGHT PRIOR
TO INSTALLATION.
LOBBY
100
C
BOOK
DROP
112
B
EAST STAIR
113
A
CONSULTANT
C. EACH RECEPTACLE DESIGNATED GFCI IS TO HAVE A TEST & RESET BUTTON WITHIN
SIGHT OF THE RECEPTACLE.
F
14. E.C. TO PROVIDE AND INSTALL (1) 3/4" CONDUIT BETWEEN COMMUNICATIONS PORTIONS
OF FLOOR BOXES.
1. INSTALL SWITCH, LIGHT AND GFCI RECEPTACLE IN ELEVATOR PIT NEAR ACCESS.
2. 60A, 1 PH. PANEL ELEV-1 FOR ELEVATOR RELATED ELECTRICAL DEVICES. SEE PANEL
SCHEDULE.
16. E.C. TO PROVIDE AND INSTALL (2) 4" EMT CONDUITS FROM TELEPHONE BOARD TO
SERVER ROOM 214 FOR COMMUNICATIONS CABLES. STUB CONDUITS 4" A.F.F. PROVIDE
BUSHINGS ON BOTH ENDS. CONCEAL ALL CONDUITS.
3. INSTALL 120V FROM LIGHTED KEYED SWITCH AT FIRST LEVEL UP TO MOTORIZED
DAMPER AT TOP OF ELEVATOR SHAFT ABOVE ROOF. VERTICAL DISTANCE
APPROXIMATELY 40'-0". E.C. TO INTERLOCK FIRE DAMPER AT TOP OF ELEVATOR SHAFT
WITH LIGHTED SWITCH AT ELEVATOR LOBBIES SO THAT INDICATOR LIGHT COMES ON
WHEN DAMPER REACHES 80% OPEN. FLUSH MOUNTED SWITCH PROVIDED AND
INSTALLED BY E.C., DAMPER BY OTHERS.
17. E.C. TO PROVIDE AND INSTALL 4' x 4' x 3/4" AD PLYWOOD BACKBOARD PAINTED WITH 3
COATS FIRE RETARDANT PAINT. DOUBLE DUPLEX RECEPTACLE FOR EQUIPMENT POWER,
GROUND AS REQUIRED. (2) 4" SCHEDULE 40 PVC CONDUITS FROM TELEPHONE
BACKBOARD TO LOCATION SHOWN ON SHEET E0.1, CAP AND STAKE. BURY CONDUIT 30"
BELOW GRADE, 3'-0" SWEEPS, NO ELECTRICAL BENDS ALLOWED.
4. ADDRESSABLE SMOKE DETECTOR W/ ADDRESSABLE BASE AT THE ELEVATOR LOBBIES.
CONNECT TO FIRE ALARM CONTROL PANEL.
18. FLOOR BOX PROVIDED AND INSTALLED BY E.C. FIELD VERIFY EXACT LOCATION WITH
OWNER PRIOR TO INSTALLATION. STEEL CITY 665-AV2 FLOOR BOX. E.C. TO MAKE
120V CONNECTION TO OWNER SUPPLIED FURNITURE.
5. ELEVATOR CONTROLLER.
6. ELEVATOR MACHINE - 208V, 3-PHASE, 25 HP.
7. 200A FUSIBLE ELEVATORBDISCONNECT SWITCH W/ AUXILIARY CONTACTS. FUSE SIZE TO
BE COORDINATED W/ FEEDER OVERCURRENT DEVICE SO AS TO TRIP BEFORE FEEDER
PROTECTION. COORDINATE W/ EQUIPMENT SUPPLIER REGARDING NAMEPLATE
REQUIREMENTS. AUXILIARY CONTACTS ARE FOR CONNECTING THE EMERGENCY
BATTERY LOWERING IF SUPPLIED W/ELEVATOR.
8. EXTEND CIRCUITS TO ELECTRIC PANEL IN THE ELEVATOR EQUIPMENT ROOM, INSTALL (4)
20A, SINGLE-POLE CIRCUIT BREAKERS FOR THE FAN AND LIGHTING, RECEPTACLE IN THE
ELEVATOR PIT, RECEPTACLE IN THE ELEVATOR ROOM, AND FOR THE LIGHTS IN THE
ELEVATOR CAR. PROVIDE (1) 110A, 3-POLE CIRCUIT BREAKER FOR ELEVATOR MACHINE.
9. INSTALL INSIDE OF CONTROL PANEL DISCONNECT LOCKABLE IN "OFF" POSITION FOR
CAR/FAN LIGHT CIRCUIT.
10. EXHAUST FAN CONTROLLED BY REVERSE ACTING T'STAT.
11. E.C. TO PROVIDE AND INSTALL RACEWAY AND CAT 5E CABLE FROM ELEVATOR CONTROL
PANEL BACK TO TELEPHONE BACKBOARD.
12. ADDRESSABLE SMOKE DETECTOR W/ ADDRESSABLE & W/ RELAY BASE IN ELEVATOR
EQUIPMENT ROOM. CONNECT TO 120V LEG OF SMOKE/FIRE DAMPERS IN ELEVATOR
EQUIPMENT ROOM AND TO FIRE ALARM CONTROL PANEL.
13. ADDRESSABLE CONTROL MODULE WITHIN 36" OF ELEVATOR SHUNT TRIP CIRCUIT
BREAKER. CONNECT TO FIRE ALARM CONTROL PANEL AND TO ELEVATOR SHUNT
TRIP CIRCUIT BREAKER.
I hereby certify that this plan,
specification, or report was
pre-pared by me or under my
direct supervision and that i am
a duly registered Engineer under
the laws of the state of
Minnesota.
15. E.C. TO PROVIDE AND INSTALL (1) 2" EMT CONDUITS FROM SERVER ROOM 214 TO CEILING
SPACE IN IT 110 FOR COMMUNICATIONS CABLES. STUB CONDUITS 4" A.F.F. PROVIDE
BUSHINGS ON BOTH ENDS. CONCEAL ALL CONDUITS.
1
2
2.9
3
3.9
4
4.6
5
6
7
Kaeko Leitch
Reg. No.:
FIRST FLOOR PLAN - POWER
1
E2.1
Date:
8
SCALE: 1/8" = 1'-0"
0
SCALE
8
NORTH
This document is by Brunton
Architects and contains privileged
and confidential information
intended for use by Brunton
Architects personnel only. Any
disclosure or distribution of this
document or information contained
herein, without prior written
consent of Brunton Architects, is
prohibited.
FEET
19. (1) 2" CONDUIT FROM FLOOR BOX TO BACKBOARD LOCATED IN IT ROOM. CONCEAL ALL
CONDUIT, PROVIDE AND INSTALL BUSHINGS AS REQUIRED. STUB CONDUITS UP 4" A.F.F.
FLOOR BOX PROVIDED AND INSTALLED BY E.C. FIELD VERIFY EXACT LOCATION WITH
OWNER PRIOR TO INSTALLATION. STEEL CITY 665-AV2 FLOOR BOX.
20. CEILING FAN PROVIDED AND INSTALLED BY DIV. 26. BIG ASS FANS ISIS IS08, 120V,
SINGLE-PHASE, 10A WITH CONTROLLER.
21. PROVIDE RECEPTACLE FOR MICROWAVE. VERIFY EXACT MOUNTING HEIGHT WITH
ARCHITECT AND OR OWNER PRIOR TO INSTALLATION.
F
CONF. RM.
202
22. E.C. TO PROVIDE AND INSTALL FLIP UP, TABLETOP UNIT. ELECTI- CABLE ASSEMBLIES
INTERACT JR, BRUSH ALUMINUM FINISH. VERIFY EXACT LOCATION WITH ARCHITECT
AND OR OWNER PRIOR TO INSTALLATION. (2) POWER,(2) DATA, 72" POWER CORD
PROVIDED WITH UNIT.
BREAK RM.
216
WEST STAIR
206
UNISEX
RESTROOM
215
23. E.C. TO PROVIDE AND INSTALL (1) 1" CONDUIT FROM FLOOR BOX TO TV BOX. CONCEAL
ALL CONDUIT, PROVIDE AND INSTALL BRUSHING AS REQUIRED. FIELD VERIFY EXACT
LOCATION WITH OWNER PRIOR TO INSTALLATION. CONCEAL ALL CONDUIT.
24. E.C. TO PROVIDE AND INSTALL (1) 3" EMPTY CONDUIT FROM LOCATION SHOWN TO
AV ROOM 201. STUB CONDUITS UP 4" AF.F. FIELD VERIFY EXACT LOCATIONS WITH
OWNER PRIOR TO INSTALLATION.
SERVER
ROOM
214
E
COUNCIL
CHAMBERS
203
25. E.C. TO MAKE 120V POWER CONNECTION TO EXTERIOR CABINET. CABINET PROVIDED
AND INSTALLED BY OTHERS. ROUTE HOME FUN THRU LCP-01. FIELD VERIFY EXACT
LOCATION, MOUNTING HEIGHT, AND POWER REQUIREMENTS WITH OWNER AND OR
ARCHITECT.
EAST STAIR
213
AV RM.
201
LOBBY
200
PROJECT:
ELEVATOR PLAN NOTES
RECEPTION
212
14. ADDRESSABLE PRIMARY AND ALTERNATE CONTROL MODULES WITHIN 36" OF
ELEVATOR CONTROLLER. CONNECT TO FIRE ALARM CONTROL PANEL AND TO THE
ELEVATOR CONTROLLER. CONNECTIONS TO ELEVATOR CONTROLLER BY ELEVATOR
INSTALLER.
REVISIONS:
ROOF
ACCESS
205
1
3
E2.1
SPECIAL SYSTEMS OUTLET
ENLARGED ELEVATOR PLAN - ELECTRICAL
SCALE: 1/4" = 1'-0"
4
SCALE
0
4
FEET
NORTH
1.2
2
2.9
3
3.9
2
E2.1
4
4.6
5
SECOND FLOOR PLAN - POWER
SCALE: 1/8" = 1'-0"
8
SCALE
0
8
NORTH
6
6.8
7
FEET
SHEET NO.
NO SCALE
E2.1
DATE:
CHECKED BY:
DRAWN BY:
A
FOX/BJB
CONF. RM.
207
OFFICE
210
FIRST AND SECOND FLOOR POWER AND SPECIAL SYSTEMS
B
OFFICE
209
PROJECT NUMBER:
OFFICE
208
SHEET TITLE:
ADMIN.
OFFICE
211
PROJECT MANAGER:
C
CONSULTANT
I hereby certify that this plan,
specification, or report was
pre-pared by me or under my
direct supervision and that i am
a duly registered Engineer under
the laws of the state of
Minnesota.
Kaeko Leitch
Reg. No.:
Date:
This document is by Brunton
Architects and contains privileged
and confidential information
intended for use by Brunton
Architects personnel only. Any
disclosure or distribution of this
document or information contained
herein, without prior written
consent of Brunton Architects, is
prohibited.
ELECTRICAL POWER RISER DIAGRAM
N.T.S.
FIRE ALARM RISER DIAGRAM
N.T.S.
PLAN NOTES
PROJECT:
1. CABLE TRAY. SEE SPECIFICATIONS FOR REQUIREMENTS. CABLE TRAY PROVIDED AND
INSTALLED BY DIV. 26.
REVISIONS:
F
D
C
C
B
A
B
A
1
1.2
2
2.9
3
3.9
4
5
6
6.8
2
2.9
3
3.9
4
4.6
5
6
7
DOOR ENTRY DETAIL
7
N.T.S.
1
E3.1
ROOF PLAN - ELECTRICAL
SCALE: 1/16" = 1'-0"
16
SCALE
0
16
FEET
NORTH
2
E3.1
FIRST FLOOR PLAN - CABLETRAY
SCALE: 1/16" = 1'-0"
16
SCALE
SHEET TITLE:
1
ELECTRICAL POWER RISER DIAGRAM
FIRE ALARM RISER DIAGRAM
ROOF PLAN - ELECTRICAL
D
SHEET NO.
0
16
FEET
NORTH
E3.1
DATE:
PROJECT MANAGER:
CHECKED BY:
E
DRAWN BY:
E
FOX/BJB
PROJECT NUMBER:
F
CONSULTANT
I hereby certify that this plan,
specification, or report was
pre-pared by me or under my
direct supervision and that i am
a duly registered Engineer under
the laws of the state of
Minnesota.
Kaeko Leitch
Reg. No.:
Date:
PROJECT:
This document is by Brunton
Architects and contains privileged
and confidential information
intended for use by Brunton
Architects personnel only. Any
disclosure or distribution of this
document or information contained
herein, without prior written
consent of Brunton Architects, is
prohibited.
SHEET NO.
E3.2
DATE:
PROJECT MANAGER:
CHECKED BY:
DRAWN BY:
FOX/BJB
ELECTRICAL SCHEDULES
SHEET TITLE:
PROJECT NUMBER:
REVISIONS: