Transient Recovery Voltages (TRVs) for High-Voltage Circuit Breakers Part 1 Denis Dufournet Chair CIGRE WG A3.28 & IEEE WG C37.011, Fellow IEEE San Antonio (USA), 19/09/2013 GRID Content (1/3) Page • • • • • • • Introduction & General Considerations Capacitive Current Switching TRV Types of Fault TRVs TRV Modification Terminal Fault TRV 4 &13 29 45 63 72 − First-pole-to-clear factor − TRV rating & testing − TRV & arcing times 73 88 120 − TRV for generator circuit breakers 138 Short-Line Fault TRV ITRV (Initial TRV) TRV HV Circuit Breakers P 2 148 187 Content (2/3) Page • Out-of-Phase TRV 194 • Three-Phase Line Faults TRV 199 • Shunt Reactor Switching TRV 217 • Transformer Limited Fault TRV 229 • Series Reactor Limited Fault TRV 264 • Influence of Series Capacitors on TRV 271 • Harmonization of TRVs in IEC & IEEE 282 TRV HV Circuit Breakers P 3 Content (3/3) Page • Annexes 306 − A: First-pole-to-clear factor 307 − B: Second-pole-to-clear factor 316 − C: Complement on line faults 321 − D: Equivalent circuit for 3-phase to ground fault 326 − E: Test circuit for kpp = 1.3 329 − F: Bibliography 333 TRV HV Circuit Breakers P 4 Introduction GRID Importance of TRV • The TRV is a decisive parameter that limits the interrupting capability of a circuit breaker. • The interrupting capability of a circuit breaker was found to be strongly dependent on TRV in the 1950’s. • When developing interrupting chambers, manufacturers must verify and prove the TRV withstand specified in the standards for different test duties. • Users must specify TRVs in accordance with their applications. • Type tests in high-power laboratories must be performed in accordance with international standards, in particular with rated values of TRVs. TRV HV Circuit Breakers P 6 “Recent” TRV Studies in International Bodies • TRV Studies by International Working Groups 1993-1996: CIGRE-CIRED WG CC03 “Medium Voltages TRVs“ 1994-1998: IEC SC17A WG21 “Revision Circuit Breaker Standard” 1997-2002: IEC SC17A WG23 “Harmonization TRVs Circuit Breakers ≥ 100kV” 2002-2006: IEC SC17A WG35 “”Revision TRVs Circuit Breakers < 100kV” 2001-2009: IEEE C37-04 & 06 ”Harmonization TRVs Circuit Breakers” 2002-2005: IEEE C37-011 “Revision Application Guide HV Circuit Breakers” 2004-2008: CIGRE WG A3-19 ”Implications of Three-phase Line Faults” 2007-2009: CIGRE WG A3-22 ”Technical Requirements for UHV Equipment” 2009-2011: IEC SC17A MT36 TF ”Introduction UHV TRVs in IEC 62271-100” 2008-2011: IEEE C37-011 ”Revision Application Guide HV Circuit Breakers” 2011-2013: CIGRE WG A3-28 ”Switching Phenomena for UHV & EHV Equipment” TRV HV Circuit Breakers P 7 Main References • A.Greenwood, Electrical Transients in Power Systems. (book) 2nd edition, John Wiley & Sons (1991). • R.Alexander, D.Dufournet, IEEE Tutorial on TRVs (2003-05) http://www.ewh.ieee.org/soc/pes/switchgear/presentations/trvtutorial/T utorialTRVAlexander-Dufournet.pdf • D.Dufournet, TRVs for High-Voltage Circuit Breakers, Presentation at IEEE Switchgear Committee meeting in Calgary (2008-10) http://www.ewh.ieee.org/soc/pes/switchgear/presentations/2008cbtutor ial/Part4_IEEETutorialonTRVHVCircuitBreakers-Dufournet.pdf • CIGRE Technical Brochure N°134, Transient Recovery Voltages in Medium Voltage Networks (1998-12) • CIGRE Technical Brochure N°408, Line fault phenomena and their implications for 3-phase short and long-line fault clearing, (2010-02) TRV HV Circuit Breakers P 8 Main References • A.Janssen, D.Dufournet, “Travelling Waves at Line Fault Clearing and Other Transient Phenomena”, CIGRE Session 2010, Paper A3-102. • CIGRE Technical Brochure 456, “Background of Technical Specifications for Substation Equipment Exceeding 800kV AC”, by CIGRE WG A3-22 (2011-04). • D.Dufournet, A.Janssen, “Transformer Limited fault TRV”, Tutorial at IEEE Switchgear Committee Meeting in San Diego (2012-10) • Denis Dufournet, Joanne (Jingxuan) Hu, High-Voltage Circuit Breakers Seminar Part 2 Transient Recovery Voltages, University of Manitoba, Winnipeg (2012-06) TRV HV Circuit Breakers P 9 Standards & Guides • • • • • • • • • IEC 62271-100, High-Voltage Circuit-Breakers (2012-09) IEC 62271-101, Synthetic testing (2012-10) IEC 62271-110, Inductive load switching (2012-09) IEC 62271-306, Guide to IEC 62271-100, 62271-1 .. (2012-12) ANSI/IEEE C37.04, 04a, 04b, IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers. IEEE Std C37.06-2009, Draft AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis-Preferred Ratings and Related Required Capabilities IEEE Std C37.09, 09b-2010, IEEE Standard Test Procedure for AC HighVoltage Circuit Breakers Rated on a Symmetrical Current Basis. IEEE C37.011, Application Guide for TRV for AC High-Voltage Circuit Breakers” (2011). IEEE C37.013, IEEE Standard for AC High-Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis. TRV HV Circuit Breakers P 10 Historical Perspective • In the second edition of IEC 56 published in 1954, the TRV, defined as "restriking voltage”, was of single frequency. The amplitude factor (or crest value) and the TRV frequency (related to the rate-of-rise) were not specified but had to be evaluated during the tests. • In the third edition of IEC 56, published in 1971, IEC introduced for the first time the term “TRV” and its representation by two or four parameters. The short-line-fault tests were also introduced in this edition. • TRVs requirements were also introduced in 1971 in ANSI C37.0721971 (IEEE Std. 327), with TRV ratings in C37.0722-1971 and TRV Application Guide C37.0721-1971 (IEEE Std. 328). TRV HV Circuit Breakers P 11 Historical Perspective • In the fourth edition of IEC 56, published in 1987, a first-pole-to-clear factor of 1.3 is the only factor specified for rated voltages ≥ 245 kV. − the rate of rise of recovery voltage (RRRV) is doubled to 2.0 kV/µs for terminal fault test duty T100. − ITRV is introduced for rated voltages ≥ 100 kV. • ITRV is introduced in ANSI C37.04 and C37.09 in 1991 (amendments 04i and 09g). • ANSI C37-06 (1997) harmonize partly TRV parameters with those in IEC (e.g. RRRV = 2.0 kV/µs for T100). • As in IEC, line surge impedance is 450 Ω for all rated voltages in ANSI/IEEE C37.04-1999 (instead of 450 Ω for Ur ≤ 242 kV and 360 Ω for Ur ≥ 362 kV). TRV HV Circuit Breakers P 12 Historical Perspective • Further Harmonization of TRVs between IEC and IEEE lead to − Amendments 1 and 2 of IEC 62271-100 (respectively in 2002 and 2006) − Amendments of IEEE C37.04b (2008), IEEE C37.06 (2009) and IEEE C37.09b (2010). Harmonization of IEC and IEEE standards for high-voltage circuit breakers is presented in detail in a specific chapter. TRV HV Circuit Breakers P 13 General considerations on Transient Recovery Voltages GRID General Considerations • The recovery voltage is the voltage which appears across the terminals of a pole of circuit breaker after current interruption. Xs U A B CURRENT Recovery voltage TRANSIENT RECOVERY VOLTAGE TRV HV Circuit Breakers P 15 RECOVERY VOLTAGE General Considerations • Current Interruption Process in SF6 Circuit Breakers Two contacts are separated in each interrupting chamber. An arc is generated, it is cooled and extinguished when current passes through zero. Simulation arc interruption TRV HV Circuit Breakers P 16 General Considerations • During the interruption process, the arc loses rapidly its conductivity as the instantaneous current approaches zero. TRV (kV) I (A) TRV Gas circuit breakers: Within a few microseconds after current zero, arc resistance (RARC) rises to one million ohm in a few microseconds and current stops flowing in the circuit. Interruption when current passes through zero • During the first microseconds after current zero, the TRV withstand is function of the energy balance in the arc: it is the thermal phase of interruption. TRV HV Circuit Breakers P 17 General Considerations • Later, the voltage withstand is function of the dielectric withstand between contacts: it is the dielectric phase of interruption. The breaking operation is successful if the circuit breaker is able to withstand the TRV and the power frequency recovery voltage. The TRV is the difference between the voltages on the source side and on the load side of the circuit breaker. • During type tests, standards require that the recovery voltage is applied during 300 ms after current interruption. TRV HV Circuit Breakers P 18 General Considerations • The nature of the TRV is dependent on the circuit being interrupted, whether primarily resistive, capacitive or inductive, (or some combination). • When interrupting a fault at the circuit breaker terminal (terminal fault) in an inductive circuit, the supply voltage at current zero is maximum. The circuit breaker interrupts at current zero (at a time when the power input is minimum) the voltage on the supply side terminal meets the supply voltage in a transient process called the TRV. TRV frequency is 1 2 LC with L = short-circuit inductance C = supply capacitance. TRV HV Circuit Breakers P 19 Fault General Considerations TRV during inductive current breaking CURRENT Supply voltage TRANSIENT RECOVERY Current and TRV waveforms during interruption of inductive current VOLTAGE Note: voltage polarity not respected on Figure TRV HV Circuit Breakers P 20 General Considerations TRV and recovery voltage in resistive, inductive and capacitive circuits 2,5 2 1,5 CAPACITIVE CIRCUIT 1 0,5 0 0 0,005 0,01 0,015 0,02 -0,5 -1 -1,5 RESISTIVE CIRCUIT -2 TRV HV Circuit Breakers P 21 INDUCTIVE CIRCUIT (with stray capacitance) 0,025 0,03 0,035 General Considerations • Combination of the former basic cases are possible, for example the TRV for mainly active load current breaking is a combination of TRVs associated with inductive and resistive circuits. • They are specified for high-voltage switches only as circuit-breakers are able to interrupt with more severe TRVs (in inductive circuits). TRV HV Circuit Breakers P 22 General Considerations • Fault interruptions are often considered to produce the most onerous TRVs. Shunt reactor switching is one of the exceptions. • TRVs can be oscillatory, triangular, or exponential and can occur as a combination of these forms. • The highest peak TRVs are met during capacitive current and out-ofphase current interruption, • TRVs associated with the highest short-circuit current are obtained during terminal fault and short-line-fault interruption. • In general, a network can be reduced to a simple parallel RLC circuit for TRV calculations. This representation is valid for a short-time period until voltage reflections return from remote buses (see IEEE C37.011-2011) TRV HV Circuit Breakers P 23 General Considerations Equivalent circuit Real network (Vcb) L C R N Lines, each with surge impedance TRV HV Circuit Breakers P 24 Z l c R Z N L: source inductance, lines excepted C: source capacitance, lines excepted General Considerations (Vcb) L R C − The TRV in the parallel RLC circuit is oscillatory (under-damped) if 1 R L/C 2 − The TRV in the parallel RLC circuit is exponential (over-damped) if 1 R L/C 2 TRV HV Circuit Breakers P 25 General Considerations TRV (p.u.) 2 0.5 R / (L / C) 1,8 = 10 4 1,6 2 1,4 1 1,2 0.75 1 0,8 0,6 0,5 0,4 0,3 0,2 0 0 1 2 3 4 5 6 7 8 9 t/RC t / RC Damping of the oscillatory TRV is provided by R, as R is in parallel to L and C (parallel damping) the damping increases when the resistance decreases (the TRV peak increases when R increases). TRV HV Circuit Breakers P 26 General Considerations • Reflection from end of lines When longer time frames are considered, typically several hundreds of micro-seconds, reflections on lines must be considered. VOLTAGE (kV) 900 800 SYSTEM TRV TRV CAPABILITY FOR A STANDARD BREAKER 700 600 500 400 300 200 REFLECTED WAVE 100 0 0 100 200 300 400 500 600 700 800 900 1000 TIME (µs) TRV HV Circuit Breakers P 27 Lines or cables must then be treated as components with distributed elements on which voltage waves travel after current interruption. These traveling waves are reflected and refracted when reaching an open circuit or a discontinuity. General Considerations • The most severe TRV occurs across the first pole to clear of a circuit breaker when it interrupts a three-phase terminal fault with a symmetrical current and when the system voltage is maximum (see section on Terminal fault). • By definition, all TRV values defined in the standards are inherent, i.e. the values that would be obtained during interruption by an ideal circuit breaker without arc voltage. (arc resistance changes from zero to an infinite value at current zero). TRV HV Circuit Breakers P 28 Capacitive Current Switching TRV & Recovery Voltage GRID Capacitive Current Switching U (p.u.) 2,5 2 Recovery voltage 1,5 1 0,5 current interruption Supply voltage 0 -0,5 Example of a single phase interruption at 50 Hz Load voltage -1 -1,5 0,005 0,01 0,015 0,02 0,025 0,03 0,035 Time (s) Capacitive current interruption: recovery voltage has a (1 – cos) waveshape TRV HV Circuit Breakers P 30 Capacitive Current Switching Supply-side voltage Load-side voltage Recovery voltage Current Contact separation Current interruption TRV HV Circuit Breakers P 31 Final current interruption Restrike Capacitive Current Switching U (p.u.) Overvoltage 3 p.u. 3,5 3 2,5 2 p.u. 2 1,5 1 Recovery voltage instant of current interruption 0,5 2 p.u. 0 -0,5 -1 -1,5 0,005 Restrike Reignition 0,01 no overvoltage 0,015 overvoltage 0,02 0,025 Time (s) TRV HV Circuit Breakers P 32 Capacitive Current Switching • Two cases can be distinguished, depending on when the restrike happens: − When it is less than 1/4 of a cycle after current interruption: it is called a reignition, no overvoltage is produced on the circuit during the transient period when the load voltage tend to reach the supply voltage. − When it is more than 1/4 of a cycle after current interruption, it is called a restrike, there is an overvoltage on the circuit during the transient period following the restrike. TRV HV Circuit Breakers P 33 "1-Cos" Waveshape • Special case of series capacitor switching by by-pass switches − By-pass switches must be able to withstand the reinsertion voltage without restrike during the transfer of reinsertion current. TRV HV Circuit Breakers P 34 "1-Cos" Waveshape • Special case of series capacitor switching by by-pass switches − Several transient reinsertion voltage waveshapes can be obtained in service. − The reinsertion voltage waveshape should be determined by systems studies. − For standardization purposes, and in order to cover the greatest number of practical cases, IEC 62271-109 recommends a "1-cos" waveshape having a preferred first time-to-peak of 5,6 ms. − A restrike happens if there is a resumption of current 2.8 ms or later after the initial current interruption. TRV HV Circuit Breakers P 35 Capacitive Current Switching Voltage Jump Circuit with capacitive and inductive components. • The recovery voltage is the sum a 1– cos wave-shape and a high-frequency voltage oscillation on the supply side due to a transient across the short-circuit (inductive) reactance at the time of interruption (explanation on next slide). • There is an initial voltage jump. • It tends to increase the minimum arcing time and therefore to increase the shortest duration between contact separation and the instant of peak recovery voltage. • Interruption is easier when the voltage jump is higher TRV HV Circuit Breakers P 36 A E Capacitive Current Switching Voltage Jump 1 0 1- Supply-side voltage after current interruption, with voltage jump 2- Load-side voltage after current interruption Voltage before current interruption UA TRV HV Circuit Breakers P 37 3- Recovery voltage across circuit-breaker terminals I 1 E E 1 C C 1 Ls C 2 Ls C Three-Phase Capacitive Current Breaking Capacitor Bank with Isolated Neutral ER ES A B CR CS CT ET TRV HV Circuit Breakers P 38 EN N Three-Phase Capacitive Current Breaking Capacitor Bank with Isolated Neutral Recovery voltage for the first pole to interrupt 2,0 VB 1,5 1,0 2.5 p.u. 0,5 VN 0,0 -0 ,0 05 -0,003 -0,00 1 0,00 1 0 ,0 03 0,00 5 0,0 07 0 ,0 09 0,01 1 0,0 13 0 ,0 15 -0,5 -1,0 VA -1,5 Due to neutral voltage shift (VN) after interruption by the first pole, the peak recovery voltage is 2.5 p.u. instead of 2 p.u. for single-phase interruption. TRV HV Circuit Breakers P 39 Three-Phase Capacitive Current Breaking Capacitor Bank with Isolated Neutral Recovery voltage (RV) on each pole uc= 2.5 p.u. kc= 1.25 RV on firstpole-to-clear The recovery voltage is higher on the first pole to clear TRV HV Circuit Breakers P 40 Three-Phase Capacitive Current Breaking Capacitor Bank with Isolated Neutral TRV 3-PHASE CAPACITIVE CURRENT SWITCHING (50Hz) Capacitor bank with isolated neutral Single-phase test with kc= 1,4 2,5 2 TRV (p.u.) The three-phase recovery voltage is considered to be covered during a single phase test with a supply voltage equal to the phase to ground voltage multiplied by 1.4 3 Three-phase test 1,5 1 Single-phase test with kc= 1,25 0,5 0 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5 9 9,5 10 TRV HV Circuit Breakers P 41 T (ms) Three-Phase Line-Charging Current Breaking In the case of line switching The recovery voltage is influenced by phase-toground and phase-to-phase capacitances Equivalence during singlephase test is obtained with a supply voltage equal to the phase-to-ground voltage multiplied by a factor = 1.2 (U is 2.4 p.u.). TRV HV Circuit Breakers P 42 Three-Phase Cable-Charging Current Breaking • Types of cables & equivalent circuits Similar case as overhead lines Same case as capacitor bank with grounded neutral C1/C0=3 Ur ≤ 52kV C1/C0=2 Ur > 52kV Screened cable TRV HV Circuit Breakers P 43 Belted cable Three-Phase Capacitive Current Breaking Single-phase tests to simulate three-phase conditions • Test voltage for single-phase tests: U test k c Ur 3 • Voltage factors in case of effectively grounded neutral systems − Line-charging current kc = 1.2 − Cable-charging current kc = 1.0 (screened cable) = 1.4/ 1.2 (belted cable ≤52kV / >52kV) − Capacitor-bank current kc = 1.0/1.4 grounded/isolated neutral • Voltage factors in case of non-effectively grounded neutral systems − Line-charging current kc = 1.4 − Cable-charging current kc = 1.4 − Capacitor-bank current kc = 1.4 • Voltage factors in the case of fault on another line(s) − Effectively grounded neutral systems kc = 1.4 − Non-effectively grounded neutral systems kc = 1.7 TRV HV Circuit Breakers P 44 Types of Fault TRVs GRID Types of Fault TRVs / Reminder Equivalent circuit Real network (Vcb) L C R N Lines, each with surge impedance TRV HV Circuit Breakers P 46 Z l c R Z N L: source inductance, lines excepted C: source capacitance, lines excepted Types of Fault TRVs / Overdamped TRV Exponential (overdamped) TRV • The exponential part of a TRV occurs when the equivalent resistance of the circuit with N connected lines in parallel Z R = Zeq = 1 is lower or equal to 0.5 Leq / Ceq N where Z1 = positive sequence surge impedance of a line Z0 = zero sequence surge impedance of a line 3 Z0 N = number of lines, Z1 2 Z 0 Leq = equivalent inductance, Ceq = equivalent capacitance. • It typically occurs when one or several lines are on the unfaulted side of the circuit breaker and when the fault is cleared at the circuit breaker terminals. • The rate of rise of recovery voltage is RRRV = Zeq x (di/dt) TRV HV Circuit Breakers P 47 Types of Fault TRVs / Overdamped TRV Three-phase to ground fault (Vcb) • Equivalent inductance L eq when 3 L 0 L1 L1 2 L 0 LLeq L0 3 L1 ZReq Ceq C 9 L1 Leq 1.3 L1 7 see Annex D: 3-phase network representation • Equivalent capacitance Ceq 2 (C1 C0 ) C0 3 TRV HV Circuit Breakers P 48 C0 2 C1 3 Types of Fault TRVs / Overdamped TRV Three-phase to ground fault • Equivalent surge impedance (first pole to clear) Z eq Z 0Z1 3 N Z1 2Z 0 Z0 ZS 2 ZM Z1 Z S Z M ZM Z 0 Z1 3 ZS: self value ZM: mutual value TRV HV Circuit Breakers P 49 3 Z0 Z1 2 Z 0 see Annex D: 3-phase network representation See section on SLF for the calculation of line surge impedance Types of Fault TRVs / Overdamped TRV • TRV for parallel RLC circuit ucb u1 (1 e with t (cosh t sinh t )) ucb is the voltage across the open circuit-breaker u1 = = 2 f = 377 rad/s at 60 Hz and 314 rad/s at 50 Hz I is the short-circuit current (rms) = = 2 I ω Leq TRV HV Circuit Breakers P 50 1 2 Z eq Ceq 2 1 /( Leq Ceq ) Types of Fault TRVs / Overdamped TRV • TRV when Ceq can be neglected ucb u1 (1 e t / ) where Leq Z eq • RRRV ducb dt TRV HV Circuit Breakers P 51 dI 2 I ω Z eq Z eq dt Types of Fault TRVs / Overdamped TRV • Special case of three-phase ungrounded faults − Equivalent inductance − Equivalent capacitance Ceq 2 C1 3 with C1= C0 TRV HV Circuit Breakers P 52 C1 1.5 L eq 3 L1 1 . 5 L1 2 Types of Fault TRVs / Overdamped TRV • This exponential part of TRV is transmitted as traveling waves on each of the transmission lines. Reflected wave(s) returning from open lines or discontinuities contribute also to the TRV. TRV HV Circuit Breakers P 53 Types of Fault TRVs / Overdamped TRV • As an example, the following figure shows the one line diagram of a 550 kV substation. The TRV seen by circuit breaker (A) when clearing the three-phase fault is shown in the next slide. Circuit breaker (B) is open. TRV HV Circuit Breakers P 54 Types of Fault TRVs / Overdamped TRV System TRV with reflected wave VOLTAGE (kV) 900 800 SYSTEM TRV TRV CAPABILITY FOR A STANDARD BREAKER 700 600 500 400 300 200 REFLECTED WAVE 100 0 0 100 200 300 400 500 600 700 800 900 1000 TIME (µs) A reflection occurs from the end of the shortest line after 2 x 81 / 0.3 = 540 µs TRV HV Circuit Breakers P 55 Types of Fault TRVs / Reflected Waves • • • • The exponential part of TRV is transmitted as traveling waves on each of the transmission lines. When a wave reaches a discontinuity on the line (another bus or a transformer termination) a reflected wave is produced, which travels back towards the faulted bus. It takes 6.67 µs for a wave to go out and back to a discontinuity 1km away as the wave travels at 300 000 km/s (speed of light). At a discontinuity transmitted and reflected waves can be described by the following equations: 2 Zb et ei Za Zb Za TRV HV Circuit Breakers P 56 Zb Zb Za er ei Za Zb Types of Fault TRVs / Reflected Waves Zb Za • • A wave that reaches a shortcircuit point (Zb= 0) is reflected with an opposite sign A wave that reaches an open point (Zb is infinite) is reflected with the same sign. The voltage at this point is then doubled. TRV HV Circuit Breakers P 57 2 Zb et ei Za Zb er ei Zb Za Za Zb Types of Fault TRVs / Reflected Waves • Example of TRV resulting from several traveling waves From CIGRE WG A322/28 tutorial in Rio de Janeiro (2012-02) Times in µs and not in ms TRV HV Circuit Breakers P 58 Types of Fault TRVs / Underdamped TRV Oscillatory (underdamped) TRV • An oscillatory TRV occurs generally when a fault is limited by a transformer or a series reactor and no transmission line (or cable) surge impedance is present to provide damping. TRV HV Circuit Breakers P 59 Types of Fault TRVs / Underdamped TRV • To be oscillatory, the equivalent resistance of the source side has to be such that Leq Z Req 0.5 N Ceq Leq = equivalent source inductance Ceq = equivalent source capacitance. • To meet this requirement, only a low number of lines (N) must be connected on the source side. Therefore oscillatory TRVs are specified for − terminal fault test duties T10 and T30 for circuit breakers in transmission systems (Ur 100 kV), − all terminal fault test duties in the case of circuit breakers in distribution or sub-transmission systems (Ur < 100 kV). TRV HV Circuit Breakers P 60 Types of Fault TRVs / Underdamped TRV • Transmission systems (Ur 100 kV) In the large majority of cases, TRV characteristics (peak value and rate-of-rise) for faults with 10% or 30% of rated short-circuit current are covered by the rated values defined in the standards for test duties T10 and T30. TRV HV Circuit Breakers P 61 Types of Fault TRVs / Triangular wave-shape • Triangular-shaped TRVs are associated with short-line faults (see separate chapter on SLF). • After current interruption, the line-side voltage exhibits a characteristic triangular waveshape. • The rate-of-rise of the saw-tooth shaped TRV is function of the line surge impedance and current. The rate-of rise is usually higher than that experienced with exponential or oscillatory TRVs (with the same current), however the TRV peak is generally low. line Circuit breaker TRV HV Circuit Breakers P 62 TRV Modification GRID Current Asymmetry and Circuit Breaker Influence on TRV TRV HV Circuit Breakers P 64 TRV Modification / Current Asymmetry • When interrupting asymmetrical currents, TRV is less severe (lower RRRV and TRV peak) than when interrupting the related symmetrical current because the instantaneous value of the supply voltage at the time of interruption is less than the peak value. SUPPLY VOLTAGE CURRENT TIME TRV HV Circuit Breakers P 65 TRV Modification / Current Asymmetry • Correction factors of the TRV peak and rate of rise of recovery voltage (RRRV) when interrupting asymmetrical currents are given in − IEEE C37.081 “IEEE Guide for Synthetic Fault Testing of AC HighVoltage Circuit Breakers Rated on a Symmetrical Current Basis”. − IEEE C37.081a “Supplement to IEEE Guide for Synthetic Fault Testing 8.3.2: Recovery Voltage for Terminal Faults; Asymmetrical Short-Circuit Current”. − IEC 62271-100 “High-Voltage Circuit-Breakers” (2012-09). − IEC 62271-101 “Synthetic testing” (2012-10): Annex I TRV HV Circuit Breakers P 66 TRV Modification / Current Asymmetry • The RRRV is proportional to the slope of current before interruption (di/dt). Factor F1 gives the correction due to current asymmetry: D F1 1 D X /R 2 with D degree of asymmetry (p.u.) -D interruption after a major loop of current +D interruption after a minor loop of current X/R short-circuit reactance divided by resistance • When time to peak TRV is relatively short (< 500 µs), the correction factor for the TRV peak is also F1. TRV HV Circuit Breakers P 67 TRV Modification / Current Asymmetry • Correction factor for the TRV peak in case of long time to peak TRV (> 500 µs) : TRV HV Circuit Breakers P 68 TRV Modification / Circuit Breaker Influence • During current interruption, the circuit TRV can be modified by a circuit breaker: − by arc resistance, − by the circuit breaker capacitance or opening resistor (if any). • The TRV measured across the terminals of two different types of circuit breakers under identical conditions can be different. • To simplify both rating and application, the power system TRV is calculated ignoring the influence of the circuit breaker. The circuit breaker is considered to be ideal i.e. without modifying effects on the electrical characteristics of a system, − when conducting its impedance is zero, − at current zero its impedance changes from zero to infinity. TRV HV Circuit Breakers P 69 TRV Modification / Circuit Breaker Influence • When a circuit breaker is fitted with grading capacitors or with line-toground capacitors, these capacitors can reduce significantly the rateof-rise of TRV during short-line faults. • Opening resistors (R) are used to assist interruption by air blast circuit breakers, they are used on some SF6 circuit breakers (Japanese 550kV 1 break & 1100 kV 2 breaks). The RRRV (rate of rise of recovery voltage) is reduced as follows du Z R di Z R I 2 dt Z R dt Z R The resistor (R) is in parallel with the surge impedance of the system (Z). TRV HV Circuit Breakers P 70 Air blast Generator Circuit Breaker with opening resistor TRV Modification / Circuit Breaker Influence Interruption with Opening Resistance R Arc extinction is facilitated by reducing the voltage stress (RRRV) after current interruption, a parallel resistance is used for this purpose TRV HV Circuit Breakers P 71 Terminal Fault TRV GRID Terminal fault TRV First pole to clear factor TRV HV Circuit Breakers P 73 Terminal Fault TRV CURRENT TRANSIENT RECOVERY VOLTAGE Current - TRV - Recovery Voltage TRV HV Circuit Breakers P 74 RECOVERY VOLTAGE Terminal Fault TRV • First Pole to Clear Factor (kpp) − During 3-phase faults interruption, the recovery voltage is higher on the first pole to clear. − The first-pole-to clear factor is the ratio of the power frequency voltage across the first interrupting pole, before current interruption in the other poles, to the power frequency voltage occurring across the pole after interruption in all three poles. − It is the ratio between the recovery voltage (RV) across the first pole to clear and the phase to ground voltage of the system. kpp TRV HV Circuit Breakers P 75 Recovery Voltage Ur 3 Terminal Fault TRV • First Pole to Clear Factor (kpp) kpp Ur 3 ER ES ET TRV HV Circuit Breakers P 76 A Ur 3 B Terminal Fault TRV • When tests are performed on one pole (single-phase tests), the supply voltage must be multiplied by kpp in order to have the recovery voltage that would be met on the first pole during a three-phase interruption. • The first–pole–to-clear factor (kpp) is a function of the grounding arrangements of the system and of the type of fault. For systems with non-effectively grounded neutral, kpp is 1.5. For three-phase to ground faults in systems with effectively grounded neutral, kpp is 1.3 (see Annex A). Note: for UHV systems (rated voltages 1100 & 1200kV) the ratio X0/X1 is close to 2 and the standardized value of kpp is 1.2. • For three-phase ungrounded faults, kpp is 1.5. TRV HV Circuit Breakers P 77 Terminal Fault TRV Three-phase faults in non-effectively grounded systems or three-phase ungrounded faults In these cases, kpp is 1.5 TRV HV Circuit Breakers P 78 Terminal Fault TRV Example of First-Pole-To-Clear Factor (kpp) 3-phase ungrounded fault in effectivelygrounded neutral L i L i When pole A interrupts. voltage eA is maximum = 1 p.u. eB = eC = - 0.5 p.u. TRV HV Circuit Breakers P 79 di eC 0 dt di e eC L B 2 dt e eC di eP eB L eB B dt 2 e eC eP B 0.5 2 e A eP 1 (0.5) 1.5 eB 2 L L First-pole-to-clear factor is 1.5 Terminal Fault TRV Example of First-Pole-To-Clear Factor (kpp) 3-phase to ground fault in non-effectively grounded system When the first pole interrupts: Voltage at neutral point N: EN + ES = Xsc I EN + ET = - Xsc I N ES ES = Emax cos (120°) = -0.5 p.u. ET ET = Emax cos (240°) = -0.5 p.u. then EN = 0.5 p.u. Voltage EA = EN + ER = 1.5 p.u. First-pole-to-clear factor is 1.5 TRV HV Circuit Breakers P 80 B 1 p.u. Xsc kpp= 1.5 Xsc EN = – (ES + ET)/2 ER is maximum = Emax cos(0°) = 1 p.u. A ER Xsc Terminal Fault TRV First-Pole-To-Clear Factor (kpp) Single-phase fault in an effectively grounded system • In this case, kpp is 1.0 as the circuit breaker interrupts under the phaseto-ground voltage. E I3 V3 I2 V2 I1 TRV HV Circuit Breakers P 81 V1 Terminal Fault TRV First-Pole-To-Clear Factor (kpp) Three-phase to ground fault in effectively grounded neutral systems • The value of kpp is dependent upon the sequence impedances from the location of the fault to the various system neutral points (ratio X0/X1). 3X 0 k pp X1 2X 0 where X0 is the zero sequence reactance of the system, X1 the positive sequence reactance of the system. For systems up to 800 kV, the ratio X0/X1 is taken to be 3.0. Hence, for systems with effectively grounded systems kpp is 1.3. TRV HV Circuit Breakers P 82 Terminal Fault TRV Pole-To-Clear Factor Equations for the other clearing poles • In systems with non-effectively grounded neutral, after interruption of the first phase (R), the current is interrupted by the last two poles in series under the phase-to-phase voltage (ES – ET) equal to 3 times the phase voltage ER ES ES - ET ET TRV HV Circuit Breakers P 83 I I Terminal Fault TRV Pole-To-Clear Factor It follows that, in systems with non-effectively grounded neutrals, for the second and third pole to clear: k pp Current in each phase TRV HV Circuit Breakers P 84 3 0.87 2 After interruption of the 3 poles, the recovery voltage is 1 p.u. TRV in each phase Terminal Fault TRV Pole-To-Clear Factor In systems with effectively grounded neutrals, the second pole clears a three-phase to ground fault with a factor k pp 3 X 02 X 0 X 1 X 12 X 0 2X1 See Annex B If X0 / X1 = 3.0 the second pole to clear factor is 1.25. Currents TRV HV Circuit Breakers P 85 TRVs Terminal Fault TRV Pole-To-Clear Factor In systems with effectively grounded neutral, for the third pole-toclear: k pp 1 E I3 V3 I2 V2 I1 TRV HV Circuit Breakers P 86 V1 Terminal Fault TRV Pole-To-Clear Factor Pole-to-clear factors (kp) for each clearing pole 3-phase to ground case Neutral Pole to clear factor X0/X1 first pole 2nd pole 3rd pole isolated infinite 1.5 0.87 0.87 effectively grounded 3.0 1.3 1.27 1.0 see note 1.0 1.0 1.0 1.0 Note: values of the pole-to-clear factor are given for X0/X1 = 1.0 to indicate the trend in the special case of networks with a ratio X0/X1 of less than 3.0. kpp= 1.5 is taken for all systems that are not effectively grounded, it includes (but is not limited to) systems with isolated neutral (it is also taken for three-phase ungrounded faults). TRV HV Circuit Breakers P 87 Terminal fault TRV Rating & Testing TRV HV Circuit Breakers P 88 Terminal Fault TRV Rating Current CURRENT SupplySupply voltage voltage Transient recovery TRANSIENT RECOVERY voltage VOLTAGE TRV HV Circuit Breakers P 89 Terminal Fault TRV Rating • The TRV ratings for circuit breakers are applicable for interruption of three-phase faults with − a rated symmetrical short circuit current − at the rated voltage of the circuit breaker. • In IEC − While three-phase ungrounded faults produce the highest TRV peaks, the probability of their occurrence is very low. Therefore, in IEC 62271-100 the TRV ratings are based on three-phase to ground faults. − TRV parameters are given in subclause 4.102 of IEC 62271100. − For values of fault current other than rated and for line faults, related TRV capabilities are given in subclause 6.104.5 of IEC 62271-100. TRV HV Circuit Breakers P 90 Terminal Fault TRV Rating • In ANSI/IEEE − TRV withstand capabilities are given in ANSI/IEEE C37.04 and IEEE C37.06. − In the case of terminal faults, for circuit-breakers of rated voltages equal or higher than 100 kV, separate Tables give TRVs for three-phase to ground and three-phase ungrounded faults. TRV HV Circuit Breakers P 91 Terminal Fault TRV Rating • ANSI/IEEE C37.06 – Table 10 TRV HV Circuit Breakers P 92 Terminal Fault TRV Rating • ANSI/IEEE C37.06 – Table 11 TRV HV Circuit Breakers P 93 Terminal Fault TRV Rating • For circuit breakers applied on systems 72.5 kV and below, the TRV ratings assume that the system neutrals can be non-effectively grounded. • For circuit breakers applied on systems 245 kV and above, the TRV ratings assume that the system neutrals are effectively grounded. • Standard TRV are defined by two-parameter and four-parameter envelopes. • These envelopes are used to compare − System TRVs − Standard TRVs − Test TRVs TRV HV Circuit Breakers P 94 Terminal Fault TRV Rating • A two-parameter envelope is used for oscillatory (underdamped) TRVs specified in standards for: − circuit breakers rated less than 100 kV, at all values of breaking current, − circuit breakers rated 100 kV and above if the short-circuit current is equal or less than 30% of the rated breaking current. Ur 2 k pp k af 3 u ' uc / 3 uc t d 0.15 t3 (Class S1, cable systems) t d 0.05 t3 (Class S 2, line systems) The test TRV must not cross the delay segment defined by (td , 0) and (t’, u’) TRV HV Circuit Breakers P 95 Terminal Fault TRV Rating • A four-parameter envelope is specified for circuit breakers rated 100 kV and above if the short-circuit current is more than 30% of the rated breaking current (cases with over-damped TRVs). u1 Ur 2 k pp 0.75 3 TRV HV Circuit Breakers P 96 uc Ur 2 k pp k af 3 u ' u1 / 2 t 2 4 t1 Terminal Fault TRV Rating The peak value of TRV is defined as follows: U c k af k pp 2 Ur 3 where kpp is the first pole to clear factor kaf is the amplitude factor (ratio between the peak value of TRV and the peak value of the recovery voltage at power frequency). In IEC 62271-100 and IEEE C37.04, kaf is 1.4 at 100% rated breaking current. TRV HV Circuit Breakers P 97 Terminal Fault TRV Rating - Ur < 100 kV TRV envelopes for terminal fault (Ur < 100 kV) VOLTAGE 0.1 I 0.3 I 0.6 I I is the rated short-circuit current TRV HV Circuit Breakers P 98 1.0 I TIME Terminal Fault TRV Rating - Ur < 100 kV • Cable systems and line systems In order to cover all types of networks (distribution, industrial and subtransmission) and for standardization purposes, two types of systems are introduced: − Cable systems Cable systems have a TRV during breaking of terminal fault at 100% of short-circuit breaking current that does not exceed the envelope derived from Table 24 in Edition 1.2 of IEC 62271-100. TRV values are those defined in the former editions of IEC standard for high-voltage circuit breakers. − Line systems Line systems have a TRV during breaking of terminal fault at 100% of short-circuit breaking current defined by the envelope derived from Table 25 in Edition 1.2 of IEC 62271-100. Standard values of TRVs for line systems are those defined in ANSI/IEEE C37.06 for outdoor circuit-breakers. TRV HV Circuit Breakers P 99 Terminal Fault TRV Rating - Ur < 100 kV • Comparison of TRVs for cable systems and line-systems Envelope of Line system TRV Envelope of Cable system TRV Uc t3 The rate of rise of recovery voltage (RRRV) for line systems is approximately twice the value for cable systems TRV HV Circuit Breakers P 100 Terminal Fault TRV Rating - Ur < 100 kV • Classes of Circuit breakers Circuit breaker Ur < 100 kV ClassCS S1 Class SLF ? Cable-system No Class Class S2 LS Direct connection to OH line Yes Direct connection to OH line Yes Line-system Cable-system Class S2 LS Class Short-line fault breaking performance is required only for class S2 TRV HV Circuit Breakers P 101 Terminal Fault TRV Rating - Ur < 100 kV Amplitude factor for terminal fault (Ur < 100 kV) Class S2 circuit breakers 1,9 Amplitude factor (p.u.) 1,8 1,7 1,6 1,5 1,4 1,3 1,2 T10 10% I TRV HV Circuit Breakers P 102 T30 30% I T60 60% I T100 100% I Terminal Fault TRV Rating - Ur < 100 kV RRRV for terminal fault T100 (Ur < 100 kV) Class S2 circuit breakers 1,6 RRRV (kV/µs) 72.5kV 1.47 1,4 1,2 1.33 52kV 1.21 38kV 1.05 1 0,8 0.91 24kV 15kV 0,6 0,4 12,5 TRV HV Circuit Breakers P 103 22,5 32,5 42,5 52,5 62,5 72,5 Ur (kV) Terminal Fault TRV Rating - Ur < 100 kV • Calculation of standard RRRV: circuit breaker 72.5 kV class S2 − Time to peak TRV was taken from ANSI C37.06: T2 106 µs − Time t3 is 88% of T2 (1-COS waveshape): t3 = 93 µs − TRV peak uc is calculated from Ur, kpp and kaf 72.5 2 uc 1.5 1.54 137 kV 3 137 VATR 1.47 kV / µs − RRRV is the ratio of uc and t3 : 93 it is the present value in IEC and IEEE standards. TRV HV Circuit Breakers P 104 Terminal Fault TRV Rating - Ur < 100 kV RRRV for terminal fault T100 (Ur < 100 kV) Class S2 circuit breakers 1,6 RRRV (kV/µs) 72.5kV 1.47 1,4 1,2 1.33 52kV 1.21 38kV 1.05 1kV/µs 1 0,8 0.91 24kV 15kV RRRV 0.4 U r0.305 0,6 20kV 0,4 12,5 TRV HV Circuit Breakers P 105 22,5 32,5 42,5 52,5 62,5 72,5 Ur (kV) Terminal Fault TRV Rating - Ur < 100 kV • RRRV at reduced short-circuit current (Class S2) − Time t3 for T100 is multiplied by the following factors 0.67 for T60 0.40 for T30 and T10 − Compared with the standard value for T100, the RRRV at reduced short-circuit current is divided by the multiplier for time t3 and multiplied by the increase of amplitude factor. − Example: T60 72.5 kV RRRV TRV HV Circuit Breakers P 106 1.47 1.65 2.35 kV / µs 0.67 1.54 Terminal Fault TRV Rating - Ur ≥ 100 kV TRV envelopes for terminal fault (Ur 100 kV) I is the rated short-circuit current Note: time to peak for T60 is shown here according to IEEE, it is half the IEC value TRV HV Circuit Breakers P 107 Terminal Fault TRV Rating - Ur ≥ 100 kV Amplitude factor for terminal fault (Ur 100 kV) according to IEC and IEEE C37.06 kaf (p.u.) 1,8 IEC & IEEE k pp=1.3 1,7 1,6 1,5 IEEE k pp=1.5 1,4 1,3 1,2 1,1 1 10 20 30 40 50 60 70 80 90 100 % Isc Case 10 % Isc: kpp x kaf = 2.46 (IEEE kpp=1.5) and 2.29 (IEC & IEEE kpp=1.3) TRV HV Circuit Breakers P 108 Terminal Fault TRV Rating - Ur ≥ 100 kV Rate-of-rise-of-recovery-voltage for terminal fault (Ur 100 kV) 8 7 RRRV (kV/µs) 6 5 4 3 2 1 T10 TRV HV Circuit Breakers P 109 T30 T60 T100 Terminal Fault TRV Application • A circuit breaker TRV capability is considered to be sufficient if the two or four parameter envelope drawn with rated parameters is equal or higher than the two or four parameter envelope of the system TRV. Voltage System TRV envelope Circuit breaker rated TRV envelope time TRV HV Circuit Breakers P 110 Terminal Fault TRV Application • The parameters that define the circuit breaker TRV capabilities vary with the circuit breaker voltage rating and short-circuit current interrupting level. • The circuit breaker TRV capabilities at 10%, 30%, 60% and 100% of rated short-circuit interrupting current (Isc), corresponding to terminal fault test duties T10, T30, T60 and T100, are given in IEEE Std C37.06. • The circuit breaker TRV withstand capability envelope at any other short-circuit interrupting current below rated can be derived using the multipliers given in Table 1 of IEEE C37.011-011. • TRV studies are sometimes carried out to determine if a system TRV is covered by the circuit breaker TRV capability demonstrated by type tests, either when new circuit breakers are to be installed or following a system change. TRV HV Circuit Breakers P 111 Terminal Fault TRV Application • It is not uncommon that the maximum short-circuit current falls in between 30% and 60% of the circuit breaker rated short-circuit current. • To allow comparison of system TRV and circuit breaker TRV withstand capability and to avoid additional testing, a method of interpolation of TRV capabilities demonstrated by type tests was introduced in the former editions of IEEE C37.011. • Following the introduction of the two-parameter and four-parameter description of TRVs, this method of interpolation in the current range between T30 and T60 (terminal faults with respectively 30% and 60% of Isc) was not clearly stated in the 2005 edition of IEEE C37.011. • Thus, the method of interpolation has been further developed in IEEE C37.011-2011 to define the circuit breaker TRV withstand capability for short-circuit currents in this range between T30 and T60. TRV HV Circuit Breakers P 112 Terminal Fault TRV Application • In standards, it is considered that 30 % of Isc is the maximum shortcircuit current for which a two parameter TRV is applicable for circuit breakers rated 100 kV and above. • The related TRV capability for short-circuit currents between 30 % of Isc and 60 % of Isc is then necessarily a four parameter TRV. • The Working Group in charge of IEEE Guide C37.011 has defined that the TRV capability between T30 and T60 can be considered to have a rate-of-rise (u1/t1) and a first reference voltage (u1) that have intermediate values between those of T30 and T60. TRV HV Circuit Breakers P 113 Terminal Fault TRV Application • TRV parameters (u1, t1, uc, t2) for any terminal fault current between 30 % and 60 % of Isc can be obtained as follows: − u1 and t1 are linearly interpolated between u1 and t1 of T60 and uc and t3 of T30 − uc and t2 are linearly interpolated between uc and t2 of T60 and uc and t3 of T30 • The method of interpolation is illustrated by the Figure shown on the next slide. TRV HV Circuit Breakers P 114 Terminal Fault TRV Application 245kV Breaker TRV Envelope 500 450 T100 T75 400 T60 350 T55 T50 300 kV T45 250 T40 T35 200 T30 150 T10 u1,t1 100 50 0 0 50 100 150 200 250 Time (µs) Example of TRV interpolation for a 245kV circuit breaker TRV HV Circuit Breakers P 115 Terminal Fault TRV Application * When the system TRV has an initial slope that is higher than the value specified for terminal fault type tests, Guide IEEE C37.011 authorizes to combine the TRV withstands demonstrated during terminal fault and short-line-fault (same range of currents). Voltage withstand by a 550kV circuit breaker at 75% rated breaking capability TRV HV Circuit Breakers P 116 Terminal Fault TRV Testing • Tests are required at 100% (T100), 60% (T60), 30% (T30) and 10% (T10) of rated short-circuit current with the corresponding rated TRVs and recovery voltages. • In IEC 62271-100, 3 tests are required with a symmetrical current for each test duty, except T100 that is performed as follows − 3 tests with symmetrical current and − 3 tests with asymmetrical current (when interrupting asymmetrical currents, the rate-of-rise and peak value of TRV are reduced but the energy in the arc is higher). • In IEEE Std C37.09 − for each test duty T10, T30, T60: 2 tests are required with symmetrical current and 1 test with asymmetrical current. − test duty T100 is performed as in IEC TRV HV Circuit Breakers P 117 Terminal Fault TRV Testing • During testing, the envelope of the test TRV (in red) must be equal or higher than the specified TRV envelope (in blue). U (kV) Envelope of prospective test TRV uc A C Prospective test TRV B u1 Reference line of specified TRV u' Delay line of specified TRV 0 td t' t1 t2 t (µs) This procedure is justified as it allows to compare TRVs in the two regions where a restrike is likely: during the initial part of the TRV where the RRRV is maximum and in the vicinity of the peak voltage (uc). TRV HV Circuit Breakers P 118 Terminal Fault TRV Initial TRV • In a network, the initial part of the TRV may have a high-frequency oscillation of small amplitude. • This ITRV (Initial Transient Recovery Voltage) is due to reflections from the first major discontinuity along the busbar. • It may influence the thermal phase of interruption. • In most cases the ITRV withstand capability is proven during short-linefault tests. More information is given in the chapter dedicated to ITRV TRV HV Circuit Breakers P 119 Terminal fault TRV & Arcing Times TRV HV Circuit Breakers P 120 Terminal Fault TRV & Arcing Time Arcing time 1,5 Contacts separation 1 Interruption at 2nd passage through zero Current 0,5 Arcing time = 13 ms 0 0 0,005 0,01 0,015 0,02 0,025 0,03 0,035 0,04 0,045 Time -0,5 1st passage through zero -1 -1,5 TRV HV Circuit Breakers P 121 0,05 Terminal Fault TRV & Arcing Times In the case of periodic phenomena, durations can be expressed in milliseconds or in electrical degrees. For a system frequency of 50 Hz, the duration of one half loop is 10 ms, it corresponds to 180° el., it follows that 18° el. = 1ms For a system frequency of 60 Hz the duration of one half loop is 8.33 ms so 18° el. = 0.83 ms TRV HV Circuit Breakers P 122 1,5 1 0,5 10 ms 0 0 0,002 0,004 0,006 0,008 0,01 0,012 0,014 0,016 0,018 0,02 -0,5 -1 -1,5 One period at 50 Hz Terminal Fault TRV & Arcing Times Current Arcing time 1st pole Arcing time last poles One period (360°) at 60Hz is 16.7 ms One period (360°) at 50Hz is 20 ms TRV HV Circuit Breakers P 123 Contacts separation 1st pole clears last poles clear Minimum & Maximum Arcing Times • Case 1: Reference case with contact separation at 29.67ms Example three-phase fault interruption Fr = 50 Hz Pole 3 interrupts first Arcing time pole 3 = 8.4ms (minimum arcing time) System with non-effectively grounded neutral TRV HV Circuit Breakers P 124 Minimum & Maximum Arcing Times • Case 2: Contact separation advanced by 3.33ms (60°) = 26.34ms Arcing time pole 1 = 8.4ms Pole 1 interrupts first with the same arcing time as in Case 1 by pole 3 i.e. same breaking conditions in terms of arcing times TRV HV Circuit Breakers P 125 Minimum & Maximum Arcing Times • Case 3: Contact separation advanced by 2.33ms (42°) = 27.34ms Arcing time pole 1 = 15.7ms = 8.4ms + 7.3ms = 8.4ms + 132° maximum arcing time Pole 3 interrupts first with the longest arcing time for a first pole to clear Arcing time pole 3 = 10.7ms = 8.4ms + 42° The range of arcing times for the first pole to clear is 42° TRV HV Circuit Breakers P 126 Minimum & Maximum Arcing Times Three-phase faults grounded systems ungrounded faults in non-effectively or three-phase 20000 Example with fr = 50 Hz tarc min = 12 ms 10000 Iarc Current (A) 0 Contact separation -10000 18° -20000 Iarc -30000 Contact separation -40000 tarc max = 19,33 ms -50000 0 5 10 15 20 Time (ms) TRV HV Circuit Breakers P 127 25 30 35 40 Minimum & Maximum Arcing Times (50Hz) Three-phase faults in noneffectively grounded systems or three-phase ungrounded faults time [ms] 0 5 10 15 20000 20 25 30 35 40 Tmin = 12 ms 15000 Minimum arcing time (blue phase) Tmin = 12 ms 10000 Iarc current [A] 5000 0 Contact separation delayed by 18° el. (or 1 ms) Contact separation -5000 -10000 18° el. -15000 -20000 time [ms] 0 5 10 15 20 25 30 20000 15000 current [A] 10000 5000 Iarc 0 -5000 -10000 Contact separation -15000 -20000 TRV HV Circuit Breakers P 128 T max = 19.33 ms 35 40 Arcing time 1st phase (red phase) = 14.33 ms (Tmin + 60° - 18° = Tmin + 42°) Maximum arcing time (blue phase) = 19.33 ms (14.33 ms + 90° = Tmin + 132°) Minimum & Maximum Arcing Times (60Hz) Three-phase faults in noneffectively grounded systems or three-phase ungrounded faults time [ms] 0 5 10 15 20 25 30 35 40 20000 Tmin = 12 ms 15000 current [A] 10000 5000 Minimum arcing time (blue phase) Tmin = 12 ms Iarc 0 Contact separation -5000 Contact separation delayed by 18° el. (or 0.83 ms) -10000 18° el. -15000 -20000 time [ms] 0 5 10 15 20 25 30 20000 15000 current [A] 10000 5000 Iarc 0 -5000 -10000 Contact separation -15000 -20000 TRV HV Circuit Breakers P 129 T max = 18.1 ms 35 40 Arcing time 1st phase (red phase) = 13.94 ms (Tmin + 60° - 18° = Tmin + 42°) Maximum arcing time (blue phase) = 18.1 ms (13.94 ms + 90° = Tmin + 132°) Terminal Fault Arcing times Three-Phase Short-Circuit Current Interruption Three-phase fault in network with isolated neutral (Ur < 245kV) Current ER A B ES ET Contact separation Time Interruption of current in a first pole, followed ¼ cycle later by interruption of the two other poles in series Breaking Tests HV Circuit-Breakers – Denis Dufournet Terminal Fault Arcing Times Three-Phase Short-Circuit Current Interruption Three-phase fault in network with effectively grounded neutral (Ur ≥ 245kV) Voltages Currents ER A B ES ET Contact separation The three poles interrupt at separate current zeros with different arcing times Breaking Tests HV Circuit-Breakers – Denis Dufournet Arcing Times and TRVs / Fr = 60 Hz Three-phase faults in non-effectively grounded systems or three-phase ungrounded faults 0.87 90° Maximum arcing time 0.87 1.5 Currents = Tmin + 132° = Tmin + 6.1 ms TRVs (pole factor) Three-phase faults in effectively grounded systems 1.27 120° Maximum arcing time = Tmin + 162° = Tmin + 7.5 ms 1.3 TRV HV Circuit Breakers P 132 1.0 Arcing Times and TRVs / Fr = 50 Hz Three-phase faults in non-effectively grounded systems or three-phase ungrounded faults 0.87 90° Maximum arcing time 0.87 1.5 Currents = Tmin + 132° = Tmin + 7.3 ms TRVs (pole factor) Three-phase faults in effectively grounded systems 1.27 120° Maximum arcing time = Tmin + 162° = Tmin + 9 ms 1.3 TRV HV Circuit Breakers P 133 1.0 Terminal Fault TRV & Arcing Times Pole to clear factor Arcing time ° el. Reference = Minimum arcing time first pole TRV HV Circuit Breakers P 134 Minimum arcing time + 180° -18° Terminal Fault TRV & Arcing Times at 60Hz Pole to clear factor Arcing times in ms FR = 60 Hz Arcing time ° el. 0 1.95 3.55 4.15 5.5 5.55 Reference = Minimum arcing time first pole to clear TRV HV Circuit Breakers P 135 6.1 7.5 ms Terminal Fault TRV & Arcing Times Pole to clear factor Single-phase "umbrella" test with kpp=1.3 Increased stress ° el. Reference = Minimum arcing time first pole Minimum arcing time + 180° -18° TRV HV Circuit Breakers P 136 Terminal Fault TRV & Arcing Times 1,5 Contacts separation 1 Current Single-phase tests with minimum & maximum arcing time 0,5 Minimum arcing time = 13 ms 0 0 0,005 0,01 0,015 0,02 0,025 0,03 0,035 0,04 0,045 0,05 Time -0,5 -1 -1,5 1,5 Contacts separation 1 Current Mximum arcing time = 22 ms = 13 ms + 10 ms - 1 ms = 13ms + 180° el. - 18° el. 0,5 0 0 Example with F=50Hz 0,005 0,01 0,015 0,02 0,025 0,03 0,04 0,045 Time -0,5 restrike with arcing time 12 ms -1 -1,5 TRV HV Circuit Breakers P 137 0,035 0,05 Terminal Fault TRV Generator Circuit Breakers TRV HV Circuit Breakers P 138 Generator Circuit Breakers TRV • Special TRV requirements are applicable for generator circuit breakers installed between a generator and a transformer. • Two types of faults need to be considered A1 TRV HV Circuit Breakers P 139 System-source fault B1 Generator-source fault Generator Circuit Breakers TRV • For the two types of fault, the TRV has an oscillatory waveshape and the first-pole-to-clear factor is 1.5 in order to cover three-phase ungrounded faults. • TRV parameters, i.e. peak voltage uc, rate-of-rise (RRRV) and time delay, are listed in ANSI/IEEE C37.013. TRV for system-source faults • RRRV for system-source faults is 3 to 5 times higher than the value specified for distribution or sub-transmission circuit breakers ANSI/IEEE C37.04. This is due to the fact that the TRV frequency is dominated by the natural frequency of the step-up transformer. • IEEE has defined TRV parameters in several ranges of transformer rated power. TRV HV Circuit Breakers P 140 Generator Circuit Breakers TRV • TRV parameters for System-Source Faults Table 5a– TRV parameters for system - source faults Inherent TRV Transformer Rating T2 -Time to - Peak E2 -Peak Voltage TRV Rate (MVA) (µs) (kV) (kV / µs) Line Column 1 Column 2 Column 3 Column 4 1 10 - 50 0.68 V 1.84 V 3.2 2 51 - 100 0.62 V 1.84 V 3.5 3 101 - 200 0.54 V 1.84 V 4.0 4 201 - 400 0.48 V 1.84 V 4.5 5 401 - 600 0.43 V 1.84 V 5.0 6 601 - 1000 0.39 V 1.84 V 5.5 7 1001 or more 0.36 V 1.84 V 6.0 TRV HV Circuit Breakers P 141 Generator Circuit Breakers TRV • TRV for system-source faults (Cont’d) In IEEE C37.013-1993, the WG introduced time t3 (coming from IEC) to define precisely the determination of the TRV rate. E2 is equal to 1.84 V where V is the rms value of the rated maximum voltage and the value 1.84 is equal to 2 x 1.5 (= first-pole-to-clear3 factor) x 1.5 (= amplitude factor) T2 t3 E2 0.85 0.85 TRV rate TRV HV Circuit Breakers P 142 Generator Circuit Breakers TRV TRV for system-source faults (Cont’d) • The RRRV can be significantly reduced if a capacitor is installed between the circuit breaker and the transformer. It is also reduced in the special cases where the connection between the circuit breaker and the transformer(s) is made by cable(s) [29]. TRV RATE FOR SYSTEM FED FAULTS TRANSFORMER 50MVA<<=100MVA 3,6 3,4 TRV RATE (kV/µs) 3,2 3 81MVA 100MVA 2,8 2,6 65,5MVA 2,4 2,2 2 0 2000 4000 6000 CABLE CAPACITANCE (pF) TRV HV Circuit Breakers P 143 8000 10000 12000 Generator Circuit Breakers TRV TRV for system-source faults (Cont’d) • When a capacitance is added between the circuit breaker and the step-up transformer, the TRV peak is increased (explanation: see general considerations). E2 MULTIPLIER FOR SYSTEM FED FAULTS TRANSFORMER 50MVA<<=100MVA TRV peak increase (p.u.) 1,3 1,25 E2 MULTIPLIER (p.u.) 65.5 MVA 1,2 81 MVA 1,15 100 MVA 1,1 1,05 Capacitance (pF) 1 0 2000 4000 6000 8000 CABLE CAPACITANCE (pF) TRV HV Circuit Breakers P 144 10000 12000 Generator Circuit Breakers TRV • TRV for generator-source faults RRRV for generator-source faults is roughly 2 times the values specified for distribution or sub-transmission circuit breakers. “Table 6a – TRV parameters for generator - source faults Inherent TRV Generator Rating T2 -Time - to – Peak E2 -Peak Voltage TRV Rate (MVA) (µs) (kV) (kV / µs) Line Column 1 Column 2 Column 3 Column 4 1 10 - 50 1.44 V 1.84 V 1.5 2 51 - 100 1.35 V 1.84 V 1.6 3 101 - 400 1.20 V 1.84 V 1.8 4 401 - 800 1.08 V 1.84 V 2.0 5 801 or more 0.98 V 1.84 V 2.2 TRV HV Circuit Breakers P 145 Generator Circuit Breakers TRV • TRV in case of asymmetrical currents − Due to the large time constants of generators and transformers (high X/R), generator circuit breakers are required to interrupt currents with a high percentage of dc component (high asymmetry). − The rate-of rise and peak value of TRV during interruption of currents with large asymmetry are significantly reduced. − In this case, the stress is mainly due to the current amplitude and the energy in the arc (mechanical and thermal stresses), and to a lesser extent to the TRV. − The more severe TRV stress is obtained during interruption of symmetrical currents. TRV HV Circuit Breakers P 146 Terminal Fault TRV / Summary • First-pole-to-clear factor − Effectively earthed systems kpp = 1.3 (1.2 for UHV) − Non-effectively earthed systems kpp = 1.5 • Rating − TRV with 2 or 4 parameters − Classes S1 and S2 for rated voltages < 100 kV • Testing circuit breakers ≥ 100 kV − RRRV: 7 – 5 – 3 – 2 kV/µs for resp. T10, T30, T60, T100s − Interrupting window: 162° (kpp = 1.3) or 132° (kpp = 1.5) • Generator circuit breakers TRV HV Circuit Breakers P 147 higher RRRV for T100s Short-Line-Fault (SLF) TRV HV Circuit Breakers P 148 Introduction • The severity of SLF with its associated very fast rate-of-rise-ofrecovery-voltage (RRRV) was identified at the end of the 1950’s. • First SLF tests were performed in 1956-1958 in the USA (G.E.), also at Mettlen substation (CH), Fontenay (EDF High Power Laboratories) and CESI. The aim was to compare theoretical studies and experiments. • The first published paper on SLF is considered to be by W.F. Skeats, C.H. Titus, W.R. Wilson (G.E.) in Transactions AIEE, submitted in April 1957 and published in February 1958. • In Europe, a paper by Michel Pouard (EDF) was published in the Bulletin de la Société Française des Electriciens in Nov. 1958. TRV HV Circuit Breakers P 149 Introduction Paper in Power Apparatus and Systems, Part III, Transactions of the American Institute of Electrical Engineers. Publication in February 1958 TRV HV Circuit Breakers P 150 Test laboratory line used by General Electric in 1957 to test air-blast circuit-breakers. It was 1.6km long, short-circuit power of the source was 50kA under 31kV. Introduction • During the general meetings of CIGRE, SLF was first mentioned during the session of 1958. Two reports were presented during the CIGRE session of 1960 (by France and Switzerland). • IEC introduced for the first time short-line-fault (SLF) requirements in 1971. • SLF TRVs were introduced also in ANSI/IEEE C37.072 in 1971. TRV HV Circuit Breakers P 151 Introduction • The requirement of a SLF interrupting capability had and still has a great influence on the design of high-voltage circuit breakers. It was already the case with air blast type that had to be fitted with opening resistors for SLF interruption. • SLF is also a critical test duty for SF6 type circuit breakers. Sufficient pressure build-up and mass flow rate are necessary for SF6 circuit breakers to interrupt at current zero. TRV HV Circuit Breakers P 152 Short-Line-Fault (SLF) • • Short-line faults occur from a few hundred meters up to several kilometers down the line. − L90: short-line fault with 90% of rated short-circuit current − L75: short-line fault with 75% of rated short-circuit current After current interruption, the line-side voltage exhibits a characteristic triangular waveshape. U line Circuit breaker TRV, neglecting the contribution from the supply-side TRV HV Circuit Breakers P 153 Short-Line-Fault (SLF) • The circuit-breaker interrupts the current, at a passage through zero, the supply voltage and the di/dt are both maximum (in amplitude). The voltage on the circuit-breaker terminals (U0) is a fraction of the supply voltage Us0. LS Us0 Supply side Voltage (point B) LL line U0 At the time of interruption Us0 = (LS + LL ) di/dt U0 = LL di/dt where di/dt is the current derivative at current zero Example Ur = 245kV U s0 U0 Line side Voltage (point C) TRV HV Circuit Breakers P 154 2 Ur 3 200 kV 90 L90 : U 0 U s 0 1 20 kV 100 Short-Line-Fault (SLF) • • As the TRV is at high frequency, the line must be treated as a transmission line with distributed elements. The line side voltage oscillates as travelling waves are transmitted with positive and negative reflections at the open breaker and at the fault, respectively. After current interruption The supply voltage varies much more slowly than the line-side voltage The TRV is mainly due to the voltage variation on the line side. Line-side voltage (point C) TRV HV Circuit Breakers P 155 Supply side voltage (point B) Short-Line-Fault (SLF) • Supply-side and line-side voltages Current t Supply-side voltage Um U=0 t Uo UL Line-side voltage Um: supply voltage at the time of interruption Uo: voltage on circuit breaker terminals at the time of interruption Example L75: Ur = 245kV : Um= 200 kV, Uo= 50 kV, UL= 80 kV TRV HV Circuit Breakers P 156 SLF / Evolution of Line Voltage Voltage profile at current zero (t=0), Voltage decreases linearly towards 0 at the fault point It is considered to be sum of two voltage waves moving in opposite directions. TL = Travel time for wave to travel from one end of line to the other and back. TRV HV Circuit Breakers P 157 SLF / Evolution of Line Voltage Traveling waves that reach the fault point are reflected with an opposite polarity. Traveling waves that reach the open point, at the circuit breaker terminal, are reflected with the same polarity. Voltage at any location on the line is the sum of each component. TRV HV Circuit Breakers P 158 SLF / Evolution of Line Voltage TRV HV Circuit Breakers P 159 SLF / Evolution of Line Voltage Voltage on the line after current interruption VOLTAGE (p.u.) 2 tL/4 0.5 tL 3 tL/4 tL 1.5 tL 0 TIME Voltage at x = 0.75 L -2 TRV HV Circuit Breakers P 160 Voltage half-way to the fault x = 0.5 L Voltage at circuit-breaker Terminal x = 0 SLF / Evolution of Line Voltage Voltage on Circuit Breaker line-side terminal Line side Voltage (p.u.) 1,5 1 0,5 0 0 0,25 0,5 0,75 1 1,25 1,5 1,75 2 -0,5 -1 -1,5 Time / TL Damping is neglected, in practice at time TL voltage is -0.6 to -0.8 p.u. TRV HV Circuit Breakers P 161 SLF TRV Voltage (kV) TRV Supply voltage Line voltage Time (µs) TRV HV Circuit Breakers P 162 SLF / RRRV • The rate-of-rise of recovery voltage (RRRV) on the line side is function of the slope of current before interruption and of the surge impedance of the line: du di RRRV Z ZI 2sI dt dt Z L C Z is the surge impedance of the line (450 ohm) L and C are respectively the self inductance and the capacitance of the line per unit length I fault current (kA) ω pulsation s multiplier = 0.20 (f = 50Hz) or 0.24 (f = 60 Hz), du/dt in kV/µs TRV HV Circuit Breakers P 163 at 50 Hz Z 2 0.2 10 6 SLF / Line Surge Impedance • Assumptions: conductors of infinite length, the electrical field and magnetic field do not penetrate the ground. • Self surge impedance D = 2 h with h = height of line r = radius of conductor Ln = natural logarithm µ0 = magnetic constant = 4π×10−7 H/m = electric constant = 8.854×10−12 F/m with Z L D 2h 60 Ln 60 Ln C r r (1) • Mutual surge impedance (ZM) between 2 conductors is given by (1) where D is the distance between one conductor and the image of the other conductor, and r represents the distance between the two conductors (see next slide). • A matrix equation is done in case of multi-conductors circuits with self and mutual couplings. Modal analysis done by digital calculations gives the relevant modes of travelling waves (see Annex C in [39] and [47]). TRV HV Circuit Breakers P 164 SLF / Line Surge Impedance • Distances to consider for mutual surge impedance calculation d12 Bundle 1 Bundle 2 Bundle 3 D12 Ground D Z M 12 60 Ln 12 d12 Image of bundle of conductors 2 TRV HV Circuit Breakers P 165 SLF / Line Surge Impedance • Factors that influence the surge impedance − Geometry of a conductor − Arrangement of the conductors in relation to the towers and the ground (single or double circuits..) − Frequency of the TRV: Z decreases by 4% when the frequency increases from 1 to 100 kHz. − In case of bundled conductors, they can clash if the current is high enough. The surge impedance is higher after conductor clashing and reach the value for a single conductor: 450 Ω. − Line height: the surge impedance of lines increases with the conductor height above ground. − Earth resistivity: the surge impedance increases by 5.7% at 1kHz and 3.2% at 100 kHz when earth resistivity changes from 10 to 1000 Ω-m. − Tower footing resistance: if it rises from 0 to 10 Ω the surge impedance increases by about 2%. TRV HV Circuit Breakers P 166 Short-line-fault • Percentage of SLF (or M) V I S LG XS TRV HV Circuit Breakers P 167 IL VLG XS XL Short-line-fault • The transmission line parameters are given in terms of the effective surge impedance ( Zeff) of the faulted line and a peak factor (d) d uL uO uL u L Z eff di / dt 2 / v uo X L I L 2 uO d 2 Z eff XL v XL is the line reactance per unit length v is the velocity of light (0.3 km/µs), is the line length is 2 system power frequency (314 or 377 rad/s for 50 or 60 Hz) TRV HV Circuit Breakers P 168 SLF / Voltage at Current Zero U0 X L IL US X S IS U0 US IL M IS M XS XS XL or M X L X S M X S U0 X L M IS U0 X S M X S IS U 0 1 M X S I S 1 M U S U 0 1 M U S TRV HV Circuit Breakers P 169 SLF / Line-side Contribution to TRV • The rated values for the line surge impedance Z and the peak factor d are defined in standards as follows: Z 450 d U L / U 0 1.6 • The line side voltage contribution to TRV is defined as a triangular wave as follows (where IS is the rated short-circuit current) : U L 1.6 (1 M ) 2 Ur 3 du di Z Z M IS dt dt 2 the first peak UL decreases when M increases the rate-of-rise of recovery voltage increases with M • • There is a critical value of the short-line-fault current for which the circuit breaker has more difficulty to interrupt. The critical value of M is close to 90% for SF6 circuit breakers (generally in the range 90%-95%). it is between 75% and 80% for air blast circuit breakers. TRV HV Circuit Breakers P 170 Short-line-fault • The following Table gives the comparison of current and voltage stresses during test duties L90 and L75, respectively at 90% and 75% of rated short-circuit current, for a circuit-breaker 245kV 40kA 50Hz. • The current and RRRV are higher during L90, but the (first) peak voltage is higher during L75. • In practice, L90 is usually the most severe test duty. L90 L75 Current (kA) 36 30 RRRV (kV/µs) 7.2 6 UL (kV) 32 80 RRRV: rate of rise of recovery voltage Voltage on the line side only is considered TRV HV Circuit Breakers P 171 UL= first peak voltage SLF / Comparison of Test Duties 140 120 4.8 kV/µs 100 U (kV) Ur = 245kV L60 80 Isc = 40kA fr = 50Hz L75 6 kV/µs 60 40 L90 7.2 kV/µs 20 0 0 5 10 15 20 25 30 35 T (µs) When current decreases (longer line), the slope decreases but the peak value increases. It is generally considered that for SF6 circuit breakers interruption is more influenced by the voltage slope (RRRV). TRV HV Circuit Breakers P 172 Short-line-fault • The TRV seen by the circuit breaker is the sum of a contribution from the line side (eL) and a contribution from the supply side (eS): e e L eS with (in a first approximation) eS 2 M (TL t d ) where 2M = RRRV (T100) x M = 2 kV/µs x M TL is the time to peak of the line side TRV td is the time delay of TRV on the source side TRV HV Circuit Breakers P 173 Short-line-fault • Example of calculation of SLF TRV : L90 245 kV 50 kA 50 Hz Fault current = 0.9 x 50 = 45 kA (assuming time delay tdL= 0 µs) TRV HV Circuit Breakers P 174 Short-line-fault • This rate-of-rise of TRV during SLF is much higher than the values that are met during terminal fault interruption: Test duty RRRV (kV/µs) I (kA) F (Hz) SLF L90 50 kA 10.8 45 60 SLF L90 50 kA 9 45 50 SLF L90 40 kA 8.64 36 60 Terminal fault T60 3 30 50/60 Terminal fault T100 2 50 50/60 For SLF, this table gives the RRRV of the line side voltage TRV HV Circuit Breakers P 175 SLF / Line Characteristics • Standard values of lines characteristics for SLF IEC values are shown, ANSI/IEEE values cover rated voltages up to 800kV TRV HV Circuit Breakers P 176 Short-Line-Fault Influence of an Additional Capacitor TRV HV Circuit Breakers P 177 SLF / Influence of an Additional Capacitor • The SLF performance can be increased by adding a capacitor, either between terminals or phase to ground (see figure). • A capacitor has two effects: − it decreases the oscillation frequency and the RRRV of the line side contribution to TRV; − it increases the time delay of the line side contribution to TRV. XS VLG TRV HV Circuit Breakers P 178 C.B. XL SLF / Influence of an Additional Capacitor 60 [ kV ] 50 40 30 1 2 3 20 10 0 0 4 (file t r v 2 .pl4 ; x - v ar t ) v :P 0 0 8 v :P 1 v :P 4 16 [ u s] 20 v :P 1 0 TRV without capacitor TRV HV Circuit Breakers P 179 12 TRV with capacitor (capacitance increase from 1 to 3) SLF / Influence of an Additional Capacitor − Equation of the line-side contribution to TRV up to the first peak: e(t ) Z (di / dt ) t Z C Z C e t / Z C − If the capacitor is connected phase to ground on the line side, the reduction of the line side RRRV can be estimated by a simple calculation, as detailed in the next slide, with Cadd additional line-to-ground capacitance; L line inductance; Z line surge impedance; CL total line capacitance = L/Z2; Ce equivalent line capacitance: capacitance which, together with the inductance L, gives the line frequency of oscillation TRV HV Circuit Breakers P 180 SLF / Influence of an Additional Capacitor − By definition of Ce fL 1 2 LCe 2u *L − The period of oscillation is equal to du du and Z I L 2 dt L dt L Z fL − It follows that 4X L and with u *L 2 X L I L 2 4L 4 CL Ce 2 2 0.4 CL 2 Z If an additional capacitance is added at the line entrance, the RRRV on the line side is reduced in the same manner as the line frequency of oscillation. TRV HV Circuit Breakers P 181 SLF / Influence of an Additional Capacitor − The RRRV on the line side is then 2 LCe du Z IL dt 2 L(Ce Cadd ) Ce du Z IL dt Ce Cadd CL du Z IL 2 dt C L 2.5 Cadd TRV HV Circuit Breakers P 182 Short-Line-Fault Influence of an Opening Resistor TRV HV Circuit Breakers P 183 SLF / Breaking with Opening Resistor • Some circuit breakers, mainly air-blast, have an opening resistor to assist a short-circuit interruption. • It was introduced to improve the SLF breaking capability of air-blast circuit breakers, but it has been used also to facilitate the interruption of fast TRVs by some SF6 circuit breakers. TRV HV Circuit Breakers P 184 SLF / Breaking with Opening Resistor • In case of SLF, the RRRV (or du/dt) is modified as follows: du Z R di Z R I dt Z R dt Z R where R = value of opening resistor Z = line surge impedance I = short-circuit current TRV HV Circuit Breakers P 185 2 Short-Line--Fault TRV / Summary • Very fast RRRV (rate-of-rise of recovery voltage) − Product of fault current derivative by surge impedance − Standard value of surge impedance = 450 Ω • Triangular waveshape due to travelling waves • Test duties L90 and L75 (+ L60 is some cases) − Single-phase tests that cover all SLF conditions • SLF performance improved by − additional capacitor (or opening resistor) TRV HV Circuit Breakers P 186