Restricted earth-fault protection function block description

advertisement

Restricted earth-fault protection function block description

Document ID: PRELIMINARY VERSION

Budapest, October 2009

Restricted earth-fault protection

User’s manual version information

Version Date Modification Compiled by

Preliminary 30.10.2009. Preliminary version, without technical information Petri

PRELIMINARY VERSION 2/16

Restricted earth-fault protection

CONTENTS

1 Restricted earth-fault protection function ............................................................................4

1.1

Structure of the restricted earth-fault protection algorithm ...........................................4

1.2

The Fourier calculation (Fourier) .................................................................................6

1.3

The zero-sequence current calculation (Zero-sequence current calculation ) ............7

1.4

Directional decision (Directional decision) ...................................................................7

1.5

The zero-sequence differential characteristics (Differential characteristics) ...............8

1.6

The decision logic (Decision logic) ........................................................................... 11

1.7

Technical summary ................................................................................................... 13

1.7.1

Technical data .................................................................................................... 13

1.7.2

The measured values ........................................................................................ 13

1.7.3

The parameters .................................................................................................. 14

1.7.4

The binary input status signals .......................................................................... 15

1.7.5

Binary output status signals ............................................................................... 15

1.7.6

The function block .............................................................................................. 15

1.8

Example for the setting calculation of the zero-sequence differential protection function ................................................................................................................................. 16

PRELIMINARY VERSION 3/16

Restricted earth-fault protection

1 Restricted earth-fault protection function

The restricted earth-fault protection function is basically a low-impedance differential protection function based on zero sequence current components. It can be applied to transformers with grounded neutral. The function compares the measured neutral current and the calculated zero sequence current component of the phase currents and generates a trip command if the difference of these currents is above the characteristics.

1.1 Structure of the restricted earth-fault protection algorithm

Fig.1-1 shows the structure of the restricted earth-fault protection (DIF87N) algorithm.

IprimL1

IprimL2

Preparation

Fourier

IL1

Fourier

IL2

Zero sequence current calculation

-

Directional decision

DIF87N

IprimL3

Fourier

IL3

Binary outputs

IN

Fourier

IN

Differential characteristics magnitude

Decision logic

Measured values

Parameters

Status signals

Figure 1 1 Structure of the restricted earth-fault protection algorithm

The inputs for the preparation are: the sampled values of three primary phase currents, the sampled value of the neutral current.

The outputs of the preparation are: the RMS values of the fundamental Fourier components of the phase currents and that of the neutral current.

The inputs for the DIF87N function are: the RMS values of the fundamental Fourier components of the phase currents and that of the neutral current, parameters, status signal.

The outputs of the DIF87N function are: the binary output status signal, the measured values for displaying.

PRELIMINARY VERSION 4/16

Restricted earth-fault protection

The software modules of the differential protection function:

Fourier calculations

These modules calculate the basic Fourier current components of the phase currents and that of the neutral current individually. These modules belong to the preparatory phase.

Zero sequence current calculation

This module calculates the zero sequence current components based on the Fourier components of the phase currents. These modules belong to the preparatory phase.

Directional decision

This module compares the direction of the neutral current and that of the calculated zero sequence current. In case of small zero sequence components of the high fault currents in the phases, this decision improves the stability of the function.

Differential characteristics

This module performs the necessary calculations for the evaluation of the “percentage d ifferential characteristics” and decides if the differential current is above the characteristic curve of the differential protection function. This curve is the function of the restraint current, which is the maximum of the phase currents and the current of the neutral point. The result of this calculation is needed for the decision logic.

Decision logic

The decision logic module combines the status signals, binary and enumerated parameters to generate the trip command of the function.

The following description explains the details of the individual components.

PRELIMINARY VERSION 5/16

Restricted earth-fault protection

1.2 The Fourier calculation (Fourier)

These modules calculate the basic Fourier current components of the phase currents and that of the neutral current individually. The magnitudes of these currents are matched to each other using the current transformer rated current values. These modules belong to the preparatory phase.

IprimL1

IprimL2

IprimL3

IL1Four

IL2Four

IL3Four

INFour

IN

Fourier

Figure 1 2 Principal scheme of the Fourier calculation

The inputs are the sampled values of: the three phase currents of the primary side (IprimL1, IprimL2, IprimL3) the current measured at the neutral point (IN)

The outputs are the basic Fourer components of the analyzed currents (IL1Four, IL2Four,

IL3Four, INFour).

The integer parameters

of the Fourier calculation are listed in Table 1-1.

Parameter name Title Unit Min Max Step Default

Parameters for the current magnitude compensation:

DIF87N_TRPri_IPar_ TR Primary comp. %

DIF87N_TRNeut_IPar_ TR neutral %

20

100

500

1000

1

1

100

500

Table 1 1 The integer parameters of the Fourier calculation

PRELIMINARY VERSION 6/16

Restricted earth-fault protection

1.3 The zero sequence current calculation

(Zero sequence current calculation )

This module calculates the zero sequence current component based on the Fourier components of the phase currents. This module belongs to the preparatory phase.

The inputs are the basic Fourier components of the phase currents (IL1Four, IL2Four,

IL3Four).

The outputs are the Fourier components of the calculated zero sequence current (3IoFour).

IL1Four

IL2Four

IL3Four

3IoFour=IL1Four+

IL2Four+

IL3Four

3IoFour

Figure 1 3 Principal scheme of the zero sequence current calculation

1.4 Directional decision (Directional decision)

This module compares the direction of the neutral current and that of the calculated zero sequence current. In case of small zero sequence component of the high fault currents in the phases, this decision improves the stability of the function.

For the directional decision, the positive directions are drawn in Figure 1 4 . In this system, if

the angle between the calculated zero sequence current 3Io and the measured neutral cu rrent IN is out of the range of ±90 degrees, then the restricted earth fault protection can be blocked, the status signal DIF87N_StDir_GrI_ (Dir.element Start) is set to TRUE value. The blocking is decided in the decision logic of the function, using the binary parameter

DIF87N_DirCheck_BPar_.

PRELIMINARY VERSION 7/16

Restricted earth-fault protection

IL1

IL2

IL3

IN

Figure 1 4 Positive directions for the directional decision

The inputs are the Fourier components of the calculated zero sequence current (3IoFour) and that of the neutral current (INFour).

The binary output status signal

of the directional decision is shown in Table 1 2 .

Binary output signals Signal title Explanation

DIF87N_StDir_GrI_ Dir.element Start

Directional blocking signal of the zero - sequence directional element

Table 1 2 The binary output status signals of the directional decision

3IoFour

INFour

BLOCK

INFour

DIF87N_StDir_GrI_

3IoFour

Figure 1 5 Principal scheme of the directional decision

1.5 The zero sequence differential characteristics

(Differential characteristics)

This module performs the necessary calculations for the evaluation of the “percentage differential characteristics”, and decides if the differential current is above the characteristic curve of the zero sequence differential protection function. This curve is the function of the restraint current, which is the maximum of the phase currents and the current of the neutral point. The result of this calculation is processed in the decision logic.

PRELIMINARY VERSION 8/16

Restricted earth-fault protection

The differential current is calculated using the following formula:

Diff Current IL1Four IL2Four IL3Four INFour

The restraint current is calculated using the following formula:

Bias Current MAX(IL1Fou r , IL2Four , IL3Four , INFour)

Based on these values, the zero sequence differential protection characteristics are shown in

Figure 1-6 .

Diff Current

Slope=

DIF87N_f2_IPar__

DIF87N_f1_IPar_

Bias Current

DIF87N_f2Brk_IPar_

Figure 1-6 The zero sequence differential protection characteristics

IL1Four

IL2Four

IL3Four

INFour

Diff

Current

Slope=

DIF87N_f2_IPar__

DIF87N_f1_IPar_

DIF87N_f2Brk_IPar_

Bias Current

DIF87N_GenTr_GrI_i _

Measured values

Figure 1 7 Principal scheme of the zero sequence differential protection

PRELIMINARY VERSION 9/16

Restricted earth-fault protection

The measured values

of the restricted earth-fault protection function are listed in Table 1 3 .

Measured value Title Dim.

Explanation

DIF87N_Id_OLM_

DIF87N_Bias_OLM_

Diff

Current

Bias

Current

In %

In %

The calculated differential current

The calculated restraint current

Table 1 3 The measured analogue values of the zero sequence differential protection characteristics

The binary output status signal of the differential protection characteristics is shown in

Table 1 4 .

Binary output signals Signal title Explanation

DIF87N_GenTr_GrI_i General Trip_i

Internal general trip signal of the differential characteristics

Table 1 4 The binary output status signals of the zero sequence differential protection characteristics

The parameters of the differential protection characteristics are explained in the following tables.

The integer parameters

of the differential protection characteristics are listed in Table 1 5 .

Parameter name Title Unit Min Max Step Default

Base sensitivity:

10 50 1 30 DIF87N_f1_IPar_ Base sensitivity

Slope of the second section of the characteristics:

%

DIF87N_f2_IPar_ Second part

Break point of the characteristic line:

- 50 100 1 70

DIF87N_f2Brk_IPar_ Break point - 100 200 1 125

Table 1 5 The integer parameters of the zero sequence differential protection characteristics

The binary input signal serves to increase the base sensitivity by 4 times. The conditions of increasing are defined by the user, applying the graphic equation editor.

Binary input signal Explanation

DIF87N_UnSens_GrO_

Output status of a graphic equation defined by the user to increase the base sensitivity by 4 times

Table 1 6 The binary input signal of the zero sequence differential protection characteristics

PRELIMINARY VERSION 10/16

Restricted earth-fault protection

1.6 The decision logic (Decision logic)

The decision logic module combines the status signals, binary and enumerated parameters to generate the trip command of the function.

DIF87N_StDir_GrI_

DIF87N_DirCheck_BPar_

DIF87N_Blk_GrO_

DIF87N_GenTr_GrI_i

DIF87N_Oper_EPar

AND

OR NOT

AND

DIF87N_GenTr_GrI

_

Figure 1 8 The logic scheme of the restricted earth-fault protection function

Binary input signals Signal title Explanation

DIF87N_GenTr_GrI_i

DIF87N_StDir_GrI_

General Trip_i

Dir.element Start

Internal general trip signal of the differential characteristics

Directional blocking signal restricted earth-fault protection function

Table 1 7 The binary input status signals of the zero sequence differential protection characteristics

The restricted earth-fault protection function has a binary input signal, which serves the purpose of disabling the function . The conditions of disabling are defined by the user applying the graphic equation editor.

Binary input signal Explanation

DIF87N_Blk_GrO

Output status of a graphic equation defined by the user to disable the differential protection function.

Table 1 8 The binary input signal of the restricted earth-fault protection function

The binary output signals of the restricted earth-fault protection function are listed in Table

1 9 .

Binary output signals Signal title Explanation

DIF87N_GenTr_GrI_

DIF87N_StDir_GrI_

General Trip

Dir.element Start

General trip signal of the zero sequence differential protection characteristics

Directional blocking signal of the restricted earth-fault protection function

Table 1 9 The binary output status signals of the zero sequence differential protection characteristics

PRELIMINARY VERSION 11/16

Restricted earth-fault protection

The enumerated parameter

of the restricted earth-fault protection function is shown in Table

1 10 :

Default Parameter name Title Selection range

Parameter to enable the zero sequence differential protection function:

DIF87N_Oper_EPar_ Operation Off,On On

Table 1 10 The enumerated parameters of the restricted earth-fault protection function

The Boolean parameter

of the restricted earth-fault protection function is shown in Table

1 14 :

Parameter name Title

DIF87N_DirCheck_BPar_ Directional check

Default Explanation

True

Enabling the directional checking of the measured and calculated zero sequence currents

Table 1 11 The Boolean parameters of the restricted earth-fault protection function

The restricted earth-fault protection function generates a trip signal if the differential current as the function of the bias current is above the differential characteristic lines and the function is not blocked and the operation of the function is enabled by parameter setting.

Blocking can be caused by the directional decision if it is enabled by parameter setting and the angle of the currents is in the blocking area or the user has composed a blocking graphic equation, and the conditions result a TRUE value for the blocking.

PRELIMINARY VERSION 12/16

Restricted earth-fault protection

1.7 Technical summary

1.7.1 Technical data

Function

Operating characteristic

Reset ratio

Unrestrained differential setting

Base sensitivity

Operate time

Reset time

*To be defined by types tests

Effective range* Accuracy*

1.7.2 The measured values

The measured values

of the restricted earth-fault protection function are listed in Table 1 12 .

Measured value Title Dim.

Explanation

DIF87N_Id_OLM_

DIF87N_Bias_OLM_

Diff

Current

Bias

Current

In %

In %

The calculated differential current

The calculated restraint current

Table 1 12 The measured analogue values of the restricted earth-fault protection function

The parameters of the restricted earth-fault protection function are explained in the following tables.

PRELIMINARY VERSION 13/16

Restricted earth-fault protection

1.7.3 The parameters

The enumerated parameter

of the restricted earth-fault protection function is shown in Table

1 13 :

Parameter name Title Selection range

Parameter to enable the zero sequence differential protection function:

DIF87N_Oper_EPar_ Operation Off,On

Default

On

Table 1 13 The enumerated parameters of the restricted earth-fault protection function

The Boolean parameter

of the restricted earth-fault protection function is shown in Table

1 14 :

Parameter name Title

DIF87N_DirCheck_BPar_ Directional check

Default Explanation

True

Enabling the directional checking of the measured and calculated zero sequence currents

Table 1 14 The Boolean parameters of the restricted earth-fault protection function

The integer parameters

of the restricted earth-fault protection function are listed in Table

1 15 .

Min Max Step Default Parameter name Title Unit

Parameters for the current magnitude compensation:

DIF87N_TRPri_IPar_ TR Primary comp.

DIF87N_TRNeut_IPar_ TR neutral

Base sensitivity:

%

%

% DIF87N_f1_IPar_ Base sensitivity

Slope of the second section of the characteristics:

DIF87N_f2_IPar_ Second part

Break point of the characteristic line:

DIF87N_f2Brk_IPar_ Break point

-

-

20

100

10

50

100

500

1000

50

100

200

1

1

1

1

1

100

500

30

70

125

Table 1 15 The integer parameters of the restricted earth-fault protection function

Floating-point parameters

The restricted earth-fault protection function has no floating-point parameters.

Timer parameters

The restricted earth-fault protection function has no timers.

PRELIMINARY VERSION 14/16

Restricted earth-fault protection

1.7.4 The binary input status signals

The restricted earth-fault protection function has a binary input signal, which serves the purpose of disabling the function . The conditions of disabling are defined by the user, applying the graphic equation editor.

The other binary input signal serves to increase the base sensitivity by 4 times. The conditions of increasing the base sensitivity are defined by the user, applying the graphic equation editor.

Binary input signal

DIF87N_Blk_GrO

DIF87N_UnSens_GrO_

Explanation

Output status of a graphic equation defined by the user to disable the differential protection function.

Output status of a graphic equation defined by the user to increase the base sensitivity by 4 times

Table 1 16 The binary input signal of the restricted earth-fault protection function

1.7.5 Binary output status signals

The binary output status signals of the restricted earth-fault protection function are listed in

Table 1-17.

Signal title Explanation Binary output signals

DIF87N_GenTr_GrI_ General Trip

General trip signal of the restricted earth-fault protection function

Table 1 17 The binary output status signals of the restricted earth-fault protection function

1.7.6 The function block

The function block of the restricted earth fault protection function is shown in Figure 1 9 . This

block shows all binary input and output status signals that are applicable in the graphic equation editor.

Figure 1 9 The function block of the restricted earth-fault protection function

PRELIMINARY VERSION 15/16

Restricted earth-fault protection

1.8 Example for the calculation of settings of the zero sequence differential protection function

As an example, the transformer data:

Sn = 25 MVA

U1/U2 = 120/22 kV/kV

Y(d)y6

Current transformers:

CT1

CT2

600/1 A/A

800/1 A/A

CTN 250/1 A/A

The selected base current is the primary rated current of the transformer: 120 A. If a lower current value is selected, the zero sequence differential protection becomes more sensitive.

REF on the secondary side:

I1np = 120 A

I2np = 656 A

INp = 656 A

The setting parameters:

On the secondary side of the CT I2n = 0.82 A

On the secondary side of the CTIN = 2.6 A

Parameter name Title Setting value

DIF87N_TRPri_IPar_

DIF87N_TRNeut_IPar_

TR Primary comp.

TR neutral

82%

260%

The base sensitivity refers to the selecte d “base current” expressed in %, the slope is the ratio of the differential current and the bias current expressed in %.

MICROENER - 49 rue de l'Université 93160 Noisy le Grand France - +33 (0)1 48 15 09 09 - info@microener.com

PRELIMINARY VERSION 16/16