Power Quality Management Harmonic Distortion and Variable Frequency Drives Voltage and Current Harmonic Distortion Cause and Effect 23/09/2011 Marek Farbis, Mirus International Inc. 1 We will focus on • • • • • • • • • Introduction: the ideal vs. distorted waveform Definition of harmonics Effects of harmonic distortion What is a cause for harmonic voltage distortion? Definition and calculation of THD VFDs and harmonics Standards and recommendations Harmonic mitigation techniques Applications 23/09/2011 Marek Farbis, Mirus International Inc. 2 Introduction 3-Phase, 480V, 60Hz Power Supply V(A,B) V(B,C) V(C,A) 800 600 400 200 Volts • Electricity generation is normally produced at constant frequencies of 50 Hz or 60 Hz and can be considered practically sinusoidal. • Ideally, an electricity supply should invariably show a perfectly sinusoidal voltage signal at every customer location. • In reality however these signals contain many types of disturbances. 0 -200 -400 -600 -800 0.000 0.002 0.004 Marek Farbis, Mirus International Inc. 0.006 0.008 0.010 Time [sec] 0.012 0.014 0.016 0.018 Introduction • The deviation of the voltage and current waveforms from sinusoidal is described in terms of the waveform distortion, often expressed as harmonic distortion. • In nearly all cases harmonic distortion is produced by a customer’s equipment (nonlinear loads) injecting electrical noise into the power system i.e. Variable Frequency Drives. Marek Farbis, Mirus International Inc. Definition of Harmonics • In a periodic signal the primary, desired frequency is the "Fundamental Frequency“. • The term “harmonics” was originated in the field of acoustics, where it was related to the vibration of a string or an air column at a frequency that is a multiple of the base frequency. • A harmonic component in an AC power system is defined as a sinusoidal component of a periodic waveform that has a frequency equal to an integer multiple of the fundamental frequency of the system. • French mathematician Jean Baptiste Joseph Fourier (1768-1830) found that any function of a variable can be expanded in a series of sines of multiples of the variable. 23/09/2011 Marek Farbis, Mirus International Inc. 7 Harmonics - Components of a Distorted Waveform Fundamental - 60 Hz Distorted Waveform Resultant 1.5 2 2 1 1.5 0.5 1 0 0.5 -0.5 0 -1 -0.5 -1.5 -1 5th Harmonic - 300 Hz -1.5 1.5 -2 Time domain 1 0.5 60 Hz 0 Harmonic Harmonic Spectrum HarmonicSpectrum Spectrum Fundamental ofFundamental %ofof Fundamental %% 100 100 -0.5 -1 80 80 300 Hz 60 60 -1.5 420 Hz 40 40 7th Harmonic - 420 Hz 1.5 20 20 1 0 0 11 1 33 3 55 5 77 7 Harmonic Harmonic ## Harmonic # 99 9 11 11 11 13 13 0.5 13 0 -0.5 Fourier Series Frequency domain -1 f(t) = Ao+A1sin(wt+q1)+A2sin(2wt+q2)+A3sin(3wt+q3) ... 23/09/2011 Marek Farbis, Mirus International Inc. -1.5 8 Why is the harmonic distortion bad? • Effect of penetration in the electrical system affecting adjacent installations. • Thermal effect on electric rotating machines, transformers, capacitors, and cables (extra losses). • Pulsating torques in rotating machines. • Neutral conductor overloading. • Increased risk of faults from overvoltage conditions developed on power factor correction capacitors and resonant conditions. • Unexpected Fuse Operation. • Abnormal operation of electronic relays. • Abnormal operation of solid-state devices. • Lower system power factor preventing effective utilization. 23/09/2011 Marek Farbis, Mirus International Inc. 10 What causes a voltage distortion? • Relationship between System Impedance and Voltage Distortion. 23/09/2011 Marek Farbis, Mirus International Inc. 11 Harmonic voltage distortion is caused by the flow of harmonic currents through system impedance. ZTh Relationship between System Impedance and Voltage Distortion. ZCh cable xfmr Harmonic Current Source UTILITY ZSh ZSh CUSTOMER/UTILITY ZTh ZCh Sinusoidal Voltage Source VS VL Ih Non-linear Load ~ VS = Ih x ZSh VFD1 VT <- The voltage will be the least distorted nearest to the source. Ohm’s Law: V h = Ih x Z h VT = Ih x (ZSh+ZTh) <- Voltage Distortion at the Transformer at h VL = Ih x (ZSh+ZTh+ZCh) <- more distorted nearer the load, as the harmonic current flows through larger amounts of impedance. Where: ZSh – impedance of the source at harmonic h, Where: Zh – impedance at hth harmonic, ZTh – impedance of the transformer at harmonic h, ZChpower – impedance of cables at harmonic h, Ih – current of travels hth harmonic, While current only along the path of the non-linear load, voltage Vh – voltage of hthall harmonic, distortion affects loads connected to that particular bus or phase. 23/09/2011 Marek Farbis, Mirus International Inc. 12 Total Harmonic Distortion • “Fundamental Current” refers to the current carried in the fundamental frequency, Ih1 (60 Hz). • “current Total Harmonic Distortion” refers to the ratio of all harmonic currents to the fundamental current. hmax iTHD 2 I h h2 I h1 100% Ratio of the root-sum-square (RSS) value of the harmonic content of the current to the RMS value of the fundamental current. 23/09/2011 Marek Farbis, Mirus International Inc. 13 Standard Variable Frequency Drive (PWM) DIODE BRIDGE IGBT ‘S = FAST KNIFE SWITCHES IGBT = Insulated-Gate Bipolar Transistor CONTROL VOLTAGE & FREQUENCY 23/09/2011 Marek Farbis, Mirus International Inc. 14 VFD, 6-Pulse Rectifier Current Waveform VFD input current 300.0 200.0 Current [Amps] 100.0 0.0 0.017 0.022 0.027 0.032 -100.0 -200.0 -300.0 23/09/2011 time [msec] Marek Farbis, Mirus International Inc. 15 VFD, 6-Pulse Rectifier and Harmonics For simple diode bridge rectifiers: h=n·p±1 h = harmonic number p = # of pulses in rectification scheme n = any integer (1, 2, 3, etc.) ia % Fund. . 100 When, p = 6 60 40 20 h=n·6±1 h = -- 5,7,--,11,13,--,17,19... 23/09/2011 80 0 1 3 5 7 9 11 13 15 17 19 21 23 25 harmonic Current Waveform and Spectrum Marek Farbis, Mirus International Inc. 16 Harmonic distortion limits • IEEE Standard 519 – 1992 – IEEE Recommended Practices and Requirements for Harmonic Control in Power Systems. • IEEE Standard C57.110 – 1986 – IEEE Recommended Practice for Establishing Transformer Capability When Supplying Nonsinusoidal Load Currents. 23/09/2011 Marek Farbis, Mirus International Inc. 17 IEEE Standard 519 General Overview Introduced in 1981 (Latest revision 1992) ‘Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems’ o Sets limits for voltage and current distortion at Point of Common Coupling. o Recognizes responsibility of both User and Utility. Widely adopted in N. America Becoming more common globally 23/09/2011 Marek Farbis, Mirus International Inc. 18 IEEE Standard 519-1992, “Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems” Definition of Terms Point of Common Coupling (PCC) UTILITY XFMR ZSh A point of metering, or any point as long as both the utility and the consumer can either access the point for direct measurement of the harmonic indices meaningful to both or can estimate the harmonic indices at point of interference. CUSTOMER/UTILITY XFMR ZTh ZCh1 ZCh2 VFD1 Within an industrial plant the PCC is the point between the nonlinear load and the other loads. 23/09/2011 MOTOR1 Marek Farbis, Mirus International Inc. ZCh3 ZCh4 VFD2 MOTOR3 MOTOR2 19 IEEE Standard 519-1992, “Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems” Definition of Terms Point of Common Coupling (PCC) UTILITY XFMR ZSh A point of metering, or any point as long as both the utility and the consumer can either access the point for direct measurement of the harmonic indices meaningful to both or can estimate the harmonic indices at point of interference. CUSTOMER/UTILITY XFMR ZTh ZCh1 ZCh2 Within an industrial plant the PCC is the point between the nonlinear load and the other loads. 23/09/2011 Rarely convenient to measure on Utility Side. VFD1 MOTOR1 Marek Farbis, Mirus International Inc. ZCh3 ZCh4 VFD2 MOTOR3 MOTOR2 20 IEEE Standard 519-1992, “Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems” Definition of Terms The harmonic current limits are based on the size of the load with respect to the size of the power system to which the load is connected. UTILITY XFMR Short-Circuit Ratio (ISC/IL): Ratio of the short-circuit current (ISC) available at the PCC to the maximum fundamental load current (IL). CUSTOMER/UTILITY XFMR ZTh IL Maximum Load Current (IL): Recommended to be the average current of the maximum demand for the preceding 12 months. ZCh2 VFD1 MOTOR1 23/09/2011 Marek Farbis, Mirus International Inc. ISC ZSh ZCh1 ZCh3 ZCh4 VFD2 MOTOR3 MOTOR2 21 IEEE Standard 519-1992, “Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems” Recommended Current Distortion Limits Table 10.3, p72 Current Distortion Limits for General Distribution Systems (120 V Through 69,000 V) Maximum Harmonic Current Distortion in Percent of IL Individual Harmonic Order (Odd Harmonics) ISC/IL <11 11h<17 17h<23 23h<35 35h TDD <20* 4.0 2.0 1.5 0.6 0.3 5.0 20<50 7.0 3.5 2.5 1.0 0.5 8.0 50<100 10.0 4.5 4.0 1.5 0.7 12.0 100<1000 12.0 5.5 5.0 2.0 1.0 15.0 >1000 15.0 7.0 6.0 2.5 1.4 20.0 Where: ISC = maximum short-circuit current at PCC. IL = maximum demand load current (fundamental frequency component) at PCC. TDD = Total Demand Distortion (harmonic current distortion calculated in % of maximum demand load current) THD = Total Harmonic Distortion (calculated based on actual load) 23/09/2011 Marek Farbis, Mirus International Inc. 22 IEEE Standard 519-1992, “Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems” Recommended Voltage Distortion Limits Table 10.2, p70 Low-Voltage System Classification and Distortion Limits Special Applications1 General System Dedicated System2 Notch Depth 10% 20% 50% THD (voltage) 3% 5% 10% 16 400 22 800 36 500 Notch Area (AN)3 NOTE: The Value AN for other than 480 V systems should be multiplied by V/480 1 Special applications include hospitals and airports. 2 A dedicated system is exclusively dedicated to the converter load. 3 In volt-microseconds at rated voltage and current. 23/09/2011 Marek Farbis, Mirus International Inc. 23 IEEE Standard 519-1992, “Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems” Current Distortion Criteria • Intended to limit for the harmonic current injection from individual customers, so they will not cause unacceptable voltage distortion levels. – Current harmonics will distort voltage in proportion to impedance of power system. • Short circuit current, ISC is a measure of system impedance. – Higher ISC means lower impedance, therefore lower voltage distortion. • Short circuit ratio, ISC/IL allows for higher distortion levels at lighter loads. – As the size of the user load decreases with respect to the size of the system, the % of harmonic current that the user is allowed to inject into the utility increases. 23/09/2011 Marek Farbis, Mirus International Inc. 24 Effect of a Stiff Source, ISC/IL > 100 400 Hp VFD vTHD = 2 % 23/09/2011 Marek Farbis, Mirus International Inc. iTHD = 127 % 25 Effect of a Weak Source, ISC/IL = 8 400 Hp VFD vTHD = 16 % 23/09/2011 Marek Farbis, Mirus International Inc. iTHD = 25 % 26 Load Level contribution to Harmonics • A load’s maximum contribution to harmonic distortion is at rated load. – Harmonic current in Amps at full load is highest even if iTHD might be higher at lighter loads. IEEE Std 519 uses TDD (Total Demand Distortion) for this purpose. – If IEEE Std 519 limits can be met at full load, then both voltage distortion and harmonic overheating would be satisfied at all load levels. • More practical to use a load’s rated current as the Demand Current. 23/09/2011 Marek Farbis, Mirus International Inc. 27 WHAT METHODS ARE USED TODAY TO MITIGATE HARMONIC CURRENTS GENERATED BY PWM VFD’S ? 1.) DO NOTHING. 2.) ADD AC LINE REACTORS OR DC LINK CHOKES 3.) TUNED TRAP FILTER 4.) LOW PASS FILTERS 5.) 18-PULSE VFD’S 6.) VFD/CW ACTIVE FRONT ENDS (AFE). 7.) VFD WITH PARALLEL ACTIVE HARMONIC FILTER 8.) MIRUS LINEATOR™ AUHF. 23/09/2011 Marek Farbis, Mirus International Inc. 28 LINEATOR™ Advanced Universal Harmonic Filter with 600V-480V AUTOXFMR 23/09/2011 Marek Farbis, Mirus International Inc. 35 APPLICATIONS 23/09/2011 Marek Farbis, Mirus International Inc. 36 Case Study, Current Distortion McQuay 400Hp VFD Chiller with Mirus Lineator. Competitive 500Hp VFD chiller with 5% AC Line reactor. 400.0 250.0 350.0 200.0 300.0 150.0 250.0 200.0 100.0 150.0 50.00 100.0 50.00 A 0.000 A 0.000 -50.00 -50.00 -100.0 -150.0 -100.0 -150.0 -200.0 -250.0 -200.0 -300.0 -350.0 -250.0 -400.0 7/20/2011 1:33:27.264 PM 16.669 (ms) 3 ms/Div 7/20/2011 1:33:27.281 PM 7/20/2011 1:39:39.267 PM 16.672 (ms) 3 ms/Div A1 W aveform 163.27 Arms, 7.69 %THD A1 W aveform 216.05 Arms, 42.81 %THD 100 100 80 7.7 % THD at 65% Load = 5% TDD 60 80 40 20 20 1 5 23/09/2011 10 15 20 25 30 35 40 45 50 7/20/2011 - 1:33:27.264 PM 42.8 % THD at 65% Load = 27.8% TDD 60 40 0 7/20/2011 1:39:39.284 PM 0 1 5 10 15 20 25 30 35 40 45 50 7/20/2011 - 1:39:39.267 PM Marek Farbis, Mirus International Inc. 37 Case Study, Voltage Distortion result McQuay 400Hp VFD chiller with Mirus Lineator. Competitive 500Hp VFD chiller with 5% AC Line reactor. 800.0 600.0 600.0 400.0 400.0 200.0 200.0 V 0.000 V 0.000 -200.0 -200.0 -400.0 -400.0 -600.0 -600.0 -800.0 7/20/2011 1:33:27.264 PM 16.669 (ms) 3 ms/Div 7/20/2011 1:33:27.281 PM 8/23/2011 11:54:34.219 AM 16.669 (ms) 3 ms/Div U1 W aveform 587.71 Vrms, 0.86 %THD U1 W aveform 466.20 Vrms, 3.55 %THD 100 100 80 80 60 60 40 40 20 20 0 1 5 23/09/2011 8/23/2011 11:54:34.236 AM 10 15 20 25 30 35 40 45 50 7/20/2011 - 1:33:27.264 PM 0 1 5 10 15 20 25 30 35 40 45 50 8/23/2011 - 11:54:34.219 AM Marek Farbis, Mirus International Inc. 38 Summary • By drawing non-sinusoidal current, VFD’s generate harmonics. • The flow of harmonic currents through the power system impedance creates voltage distortion. • Excessive voltage distortion will cause equipment malfunction. • IEEE Std 519 harmonic limits can be met by application of appropriately designed harmonic treatment. • Harmonic treatment method must perform in ‘Real World’ conditions and when supplied by generator. 23/09/2011 Marek Farbis, Mirus International Inc. 39 How to Ensure your VFD Installation Meets IEEE 519 Limits • Perform harmonic survey to Or determine existing conditions • Obtain harmonic spectrum of • Specify LINEATOR™ FOR ALL LARGER VFD load from manufacturer APPLICATION • Use modeling software to analyze various treatment methods and system conditions • Analyze impact on Generator or UPS • Anticipate effect of future system or load changes 23/09/2011 Marek Farbis, Mirus International Inc. 40 Thank you 23/09/2011 Marek Farbis, Mirus International Inc. 41