Earth Fault Detection

advertisement
- Earth Fault Detection: Basics in Theory
Version 1.2 dated 03.11.2008 -
Generator Protection
Earth Fault Detection
Basics in Theory
Author:
Ingo Kühnen (Graduate Engineer)
___________________________
Woodward Power Solutions GmbH
Krefelder Weg 47
47906 Kempen, Germany
Kempen, 03.11.2008
page 1 of 12
- Earth Fault Detection: Basics in Theory
1.1
Version 1.2 dated 03.11.2008 -
Star Point Treatment of Generators
Due to the fact that the outgoing utility transformers are delta connected, i.e. separated
from the neutral earthing system of medium voltage side, the rating of earth fault
currents of the MV - System (10.5kV) only depends on the star point treatment of the
generators.
The following star point treatments of generators are feasible:
1. isolated, i.e. unearthed star point
2. compensated star point, i.e. star point earthed via Peterson earth fault neutralizer
3. indirectly earthed star point, i.e.
a.)
earthed via reactor or transformer or
b.)
earthed via resistor
4. directly, i.e. solidly earthed star point.
This document is to compare the different methods of treating generator star points –
taking into account the requirements and conditions of the majority of power stations.
page 2 of 12
- Earth Fault Detection: Basics in Theory
As to 1.
Version 1.2 dated 03.11.2008 -
Isolated Star Point
The rating of the earth fault currents at isolated star points is mainly depending on the
cable capacities of the network system, because of the fact that the earth fault circuit is
only closed via cable capacities and earth fault location. Consequently, this method is
only feasible, provided that the cable capacities within the network are relatively high
and do not vary, which may particularly apply to cable network systems that are
strongly intermeshed and quite complex. In most of the power stations, however, these
conditions are not prevailing since the various existing operating modes and switching
states on their own will result in very different network cable capacities. In case of an
earth fault of one conductor, the system voltage of the remaining two healthy
conductors against earth will increase by the factor √3, thus achieving the line-to-line
voltage. The following shall apply:
IE = 3 ⋅ I0 ≈ 3 ⋅ U Δ ⋅ ω ⋅ CE
U
Ž,healthy conductor
with IE:
CE:
ω:
As to 2.
≈ 3 ⋅ UŽ= UΔ
earth fault current at earth fault location
earthing capacitance = zero-capacitance of the network
2πf = angular frequency
Compensated Star Point
In this case, cable capacities of the entire network system are largely compensated
through the inductance of a Petersen earth fault neutralizer. In case of an earth fault,
the residual currents still available then, are very low. These currents are frequently
detected by means of watt hour metering. This method of star point treatment is even
more dependent on the cable capacities of the network system though the rating of
cable capacities will additionally determine the rating of the Petersen earth fault
neutralizer.
Consequently, this method of star point treatment is inapplicable, as well.
page 3 of 12
- Earth Fault Detection: Basics in Theory
As to 3a)
Version 1.2 dated 03.11.2008 -
Star Point earthed via Reactor or Transformer
By earthing the generator star point via reactor, it is possible to determine the value for
the earth fault current. When this method is applied, the earth fault current will only
depend on the network system’s cable capacity as shown hereafter:
IE ≈
⇒
⎛
3 ⋅ UΔ j ⋅ ⎜ ωC E −
⎝
⎛
1 ⎞
IE ≈ 3 ⋅ U Δ ⋅ ⎜ ωCE −
⎟
3ωL D ⎠
⎝
U
Ž,healthy conductor
with IE:
LD
CE:
ω:
1 ⎞
⎟
3ωL D ⎠
≤ 14
. ⋅ UŽ
earth fault current at earth fault location
inductance of reactor or transformer
earthing capacitance of the network
2πf = angular frequency
In case of an one phase earth fault the system voltage of the remaining two healthy
conductors against earth will increase by approximation of a max. factor 1.4 due to
earth fault factor fE. It is also possible to connect a reactor or a transformer with the
generator bus bar and operate the generator star points separately. The reactor (or the
transformer) will then be acting as a so-called star point creator. In this case, it is
necessary to determine a defined load for the reactor (or transformer).
This method of star point earthing via reactor or transformer is thus applicable for most
of the power plant network systems.
page 4 of 12
- Earth Fault Detection: Basics in Theory
As to 3b)
Version 1.2 dated 03.11.2008 -
Generator Star Point earthed via Resistor RE
By earthing the generator star point via a resistor, it is possible to control the attitude of
the protection system in comparison to the isolated star point method. The resistor
defines the amount of the earth fault current and is only slightly dependent on the
network system’s cable capacities. The mostly low resistances RN of a less extensive
unmeshed network are usually negligible. The following shall apply:
IE ≈
⎛ 1
⎞
+ jω ⋅ C E ⎟
⎝ 3R E
⎠
3 ⋅ UΔ ⎜
2
⇒
⎛ 1 ⎞
2
IE ≈ 3 ⋅ U Δ ⋅ ⎜
⎟ + (ω ⋅ C E )
⎝ 3R E ⎠
U
Ž,healthy conductor
with IE:
RE
CE:
ω:
≤ 14
. ⋅ UŽ
earth fault current at earth fault location
earthing resistance
earthing capacitance of the network
2πf = angular frequency
In that case, too, if there is an earth fault of one phase conductor the system voltage
of the two healthy conductors against earth will increase by approximation of a max.
factor 1.4 due to earth fault factor fE. Proportionate to this, the load affecting the
insulation of these conductors as well as connected voltage transformers etc. will
increase accordingly. Therefore this method of star point treatment is also applicable.
As to 4.
Solidly earthed generator star point
By means of this star point treatment, in the event of external earth faults, high one
phase short-circuit currents result, which might be a multiple of the generator’s
nominal current. These voltages are too high for the generator windings. The following
shall apply:
IK" ,1P ≈ IK" ,3P ⋅
at a ratio of
3
X
2+ 0
X1
X0
≤ 5.2 for the effectively earthed network.
X1
page 5 of 12
- Earth Fault Detection: Basics in Theory
Version 1.2 dated 03.11.2008 -
To sum up:
After consideration of the different star point treatments of the generators, for the most
power stations only the indirect methods such as
− earthing of the generator star point via an neutral earthing resistor RE
− earthing of the generator star point via a neutral earthing reactor or neutral earthing
transformer with a defined load
− earthing of the busbar of the generators via a neutral earthing transformer as a star
point creator with a defined load
turned out to be practicable.
page 6 of 12
- Earth Fault Detection: Basics in Theory
1.2
Version 1.2 dated 03.11.2008 -
Star Point Treatment via a Neutral Earthing Resistor RE
When comparing the various possibilities of generator star point treatment dealt with in
chapter 1.1, the way of earthing generator star points via a neutral earthing resistor
seems to be the most practicable one since this method offers economic advantages
and can normally rather easily be retrofitted and it is more independent with regard to
subsequent system extensions or modifications.
In the figure 1.2-1 below, the star point treatment of the generator by means of a
neutral earthing resistor RE is illustrated in a diagram.
T2
G
3∼
T2
G
3∼
G1
G2
star point
star point
T1
T1
QE
QE
ϑ>
RE
TE
Figure 1.2-1
Diagram of the generator star point treatment by means of a neutral
earthing resistor RE
with:
RE
earthing resistance with temperature supervision ϑ>
RE ≈ 254 Ω, IRE(10s) ≈ 25A rated for a period of 10s
and I RE(cont.) = 10A continuously, URE = 11 kV/√3
QE:
single-phase vacuum contactor of the series 12, 400A,
with very short switching times
TE:
cable type current transformer for backup earth fault detection
at neutral earthing resistor RE
25/1A with 2.5VA, for max. 120min. at 110% IN
T1,T2: cable type current transformers for earth fault detection within
the generators (restricted earth fault: 64REF), data as TE
page 7 of 12
- Earth Fault Detection: Basics in Theory
Version 1.2 dated 03.11.2008 -
In general, only one generator star point connected to the bus bar is grounded via the
neutral earthing resistor. This applies to each MV busbar section.
With the aid of the appropriate single-phase vacuum contactor QE, the star point of the
generator that was connected first to the MV switchgear, is switched to the neutral
earthing resistor RE. During this, only the star point of the generator that was initially
connected will be earthed via the neutral earthing resistor RE. In case that the
generator circuit breaker of the generator whose star point was connected with, the
neutral earthing resistor is switched off by the corresponding star point contactor and
the neutral earthing resistor will be switched over to the contactor of that generator in
operation, whose circuit breaker will be closed next.
As regards circuitry, it has to be ensured, that not more than only one generator star
point will be earthed via the neutral earthing resistor since otherwise it might happen
that transient currents of the third harmonic would flow between the generator star
points.
To protect the system against ferroresonance (these are oscillations in electric circuits
provoked by capacities and inductance in the iron core, whereby there is not always a
stable operating point produced in the power voltage diagram, as the inductance
depends on the current and therefore modifies the inherent frequency of the oscillating
circuit!) in case of ungrounded generators (floating), the tertiary windings(open delta /
e-n winding) of the voltage transformers are switched in an open triangle and are
burdened with a resistor.
page 8 of 12
- Earth Fault Detection: Basics in Theory
Version 1.2 dated 03.11.2008 -
Protection in case of external earth faults
In the event of a station earth fault beyond the generator protection range, the earth
fault current IE that is primary determined by the dimension of the neutral earthing
resistance (and only secondary by the cable capacities of the network) will be flowing
through the earth fault source. In case of selectivity, it is possible to separate the faulty
segment by means of staggering and IDMT earth fault relays.
Protection in case of internal earth faults
In case of an internal earth fault, the stator earth fault relay of the defective generator
will disconnect the defective generator only.
The cable type current transformers T1 and T2 are applied to detect earth faults within
the generator’s protection range, in particular for the detection of stator earth faults
(ANSI - Code: 64REF).
These cable type current transformers must have the same transmission ratio and
shall be connected anti-parallel, as shown in figure 1.2-2.
MRI
Figure1.2-2
S1
T2 S2
S2
T1 S1
B2
B1
Diagram illustrating the wiring of protection devices for the stator earth
fault protection
During faultless condition and in case of an earth fault occurring outside of the
protection range of current transformers T1 and T2, the current rating is approximately
the same. Anti-parallel connection of the transformers leads to the neutralization of the
currents.
An earth fault within the protection range of the two current transformers T1 and T2
results in the addition of the currents. For this purpose, the earth fault relays are
adjusted as to disconnect the generator circuit breaker after maximum 1 sec. at
detected currents of more than 4A or soonest possible at an earth fault current of more
than 16A.
In case of a stator earth fault on an ungrounded generator the earth current limited by
the resistor will flow to the grounded generator in operation. By interconnecting the
ring core c.t. on the main connectors (L1, L2, L3) and the ring core c.t. on the star
point side, only the earth current of the defective generator will be detected by its own
earth fault relay.
page 9 of 12
- Earth Fault Detection: Basics in Theory
Version 1.2 dated 03.11.2008 -
The current on the earth fault relay of the non-defective but grounded generator is zero
due to the anti-parallel connection of the ring core c.t.’s and does therefore not cause
a fault.
Protection of the Neutral Earthing Resistor RE
The cable type current transformer TE is used to detect residual currents in the current
path of the resistor. Should the preceding earth fault relays of the station not pick-up in
case of an external fault, an appropriate earth fault relay has to be provided in order to
prevent the neutral earthing resistor’s overload. According to the rating of the neutral
earthing resistor, this earth fault relay will be adjusted as to pick-up after 10s at the
latest.
To protect the resistor from overheat, the neutral earthing resistor is furthermore
equipped with an overtemperature detection facility. This element is another back-up
protection that may only lead to tripping if no other earth fault relay picks-up.
A prerequisite for both, tripping of the back-up overload protection and tripping of the
back-up overtemperature protection is the separation of the generator’s star point from
the neutral earthing resistor. In that case, the system earth fault protection should
operate for a certain maximum time. After expiry of this time the generators should be
isolated from the grid since earth fault protection can no longer be ensured.
page 10 of 12
- Earth Fault Detection: Basics in Theory
Version 1.2 dated 03.11.2008 -
Prerequisites for the use of star point treatment via Neutral Earthing Resistor RE
in Power Stations
− The generator star points have to be lead out and accessible.
− It is only permitted to earth that generator via neutral earthing resistor RE which is
connected first to the power station. It is never permitted to earth more than one
generator star points via the earthing resistor RE since this might lead to
undesirable transient currents between the generator star points related hereto.
Therefore the neutral earthing vacuum contactors have to be interlocked.
− All relevant network elements as insulation of conductors, voltage transformers etc.
must be capable of withstanding the increased voltage generated between the
healthy phases and earth during an earth fault.
page 11 of 12
- Earth Fault Detection: Basics in Theory
1.3
Version 1.2 dated 03.11.2008 -
Dimensioning of the Neutral Earthing Resistor RE
The earth fault current which is defined by the neutral earthing resistor RE is limited by
the following circumstances:
− On one hand, the earth fault current within the total direct-connected network has to
be at least high enough to energize the selective earth fault relays and the back-up
protection relays.
− On the other hand, the earth fault current should be maintained low enough to avoid
further damages resulting from the earth fault current.
This means that the rating of the neutral earthing resistance results from the current’s
pick-up values of the earth fault relay, taking into account the fact that earth fault
currents must not become too high to maintain damages that might occur as slight as
possible.
After due consideration on principles for the adjustment of these pick-up values there
should be a minimal earth fault current of 80A. The earthing resistor has to be
dimensiond for this earh fault current rating. The following shall apply:
RE ≤
UΔ
3 ⋅ IEmin
⇒
RE = 254Ω dimensioned for IE ≈ 25A at 10sec. (10A continuously)
with RE:
IE, min:
UΔ:
rating of the neutral earthing resistance
minimum defined earth fault current
11 kV
If vacuum contactors with low switching times far below 1s are selected for switching
off the neutral earthing resistor, the resistor can be dimensioned for a load time of 10s
(having regard to maximal staggering times of approximately 3sec.).
page 12 of 12
Related documents
Download