ADEMCO 4204CF Supervised Notification

advertisement
N6223V1 3/09 Rev. A
ADEMCO 4204CF
SUPERVISED NOTIFICATION APPLIANCE MODULE
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
Connections and Settings
The ADEMCO 4204CF Supervised Notification Appliance Module adds up
to two Class B (Style Y) Supervised Notification Appliance Outputs to
compatible ADEMCO Control Panels (for more information on Style Y, see
NFPA-72 National Fire Alarm Code Chapter 3: Protected Premises Fire
Alarm Systems). Refer to your Control Panel’s installation instructions to
determine if it supports this module. Each output is supervised using an
EOL20 2K resistor (two resistors supplied).
Select and set an address for the 4204CF using its DIP switch settings as
shown in Diagram 1. Assign a unique address to the 4204CF so that the
control can communicate with it. Refer to the control’s installation
instructions to determine which address or range of addresses to use.
• For UL commercial and household fire installations, no
more than one wire per terminal may be connected.
• Use only 14-22AWG wire.
Make connections to the control’s keypad wiring by using the 4- position
terminal block TB1, or the 4-pin plug (plug cable provided). Make
connections to the Notification Appliance Power input and outputs via the
module’s 12-position terminal block (TB2). Refer to Diagrams 2, 3, and 4.
1. Only relay 1 (Output A) and relay 3 (Output B) may be
programmed for activation. Refer to the control’s
Installation Instructions for programming output activation
and supervision options.
2. When programming 4204CF output activation options in
the control panel, outputs must not be programmed to
“Close for 2 Seconds.” Any other option may be used, but
do not program the relay to ”Stop” in less than 10 seconds.
UL
For UL Commercial Fire installations, only one notification
appliance module may be used, and only one notification
appliance output (A or B) may be used on that module.
Each appliance output is rated at 1.2A max. You can power these outputs
from the control panel or from a supplementary regulated UL Commercial
Fire Alarm (power limited) power supply rated at 8-30VDC.
The 4204CF has a built-in cover tamper switch, which allows it to detect
and report the removal of its cover to the Control Panel.
INSTALLATION
Mounting
UL
SPECIFICATIONS
• For dry, indoor use only. Do not install in air-handling spaces.
• For all fire (NFPA) and UL Commercial Burglary installations,
the 4204CF must be tamper protected or mounted in a tamperprotected cabinet.
Physical: 6-7/16” W x 4-1/4” H x 1-1/4” D
(163mm x 108mm x 32mm)
Electrical:
+12V Input
Input Voltage: 12VDC nominal (10-14VDC)
Input Current: 25mA + 80mA per active output
For fire alarm installations, mount the 4204CF inside a UL864 listed
cabinet such as the control’s cabinet. Cover tamper supervision is not
required; to disable tamper supervision, set DIP switch Position 1 to the
ON position.
1. Cover tamper supervision is not supported by all control
panels. For other (i.e., non-fire alarm) installations, a
separate enclosure is not required. Mount the 4204CF
directly on a surface using the slotted holes located on the
back of its housing (mounting screws provided). Feed the
wires through the slot on the side on the side or through
the breakout located on the back of the housing. Cover
tamper supervision can be used, if supported by the
control panel.
2. Affix the connections level (provided) to the inside of the
4204CF’s cover.
OFF
ON
4204CF ADDRESS SETTINGS
SWITCH
NUMBER
("—" means "OFF")
8
9
10
12
13
14
ON —
ON
—
ON
ON
—
ON
—
ON
—
ON
—
ON —
3
ON ON
—
—
ON ON
—
—
ON ON
—
—
ON ON
—
4
4
ON ON ON ON
—
—
—
ON ON ON ON
—
—
—
—
5
5
ON ON ON ON ON ON ON ON
—
—
—
—
—
1 2
0
1
2
3
4
5
6
—
—
7
—
—
11
—
15
—
FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE
MODULE MAY BE USED, AND ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B)
MAY BE USED ON THAT MODULE.
TB2
4204CF
12
DIP SWITCH
FOR SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING TAMPER
11
10
COVER TAMPER (REED) SWITCH
EITHER OR BOTH
CAN BE USED
4-PIN CONSOLE
PLUG
NC
NC
9
8
7
POLARIZED
NC NOTIFICATION
NC APPLIANCES
5
4
2
TB1
1
16
YEL
BLK
GRN
RED
NOTIFICATION
APPLIANCE
OUTPUT B
2K EOLR
EOL20
NOTIFICATION
APPLIANCE
OUTPUT A
2K EOLR
EOL20
6
3
15
http://www.security.honeywell.com/hsc/resources/wa/index.html
2
POSITIONS 2-5
DETERMINE 4204CF'S ADDRESS:
CONTROL'S INSTRUCTIONS SPECIFY ADDRESS TO
USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED).
14
For the latest warranty information, please go to:
3
POSITION 1
ENABLES/DISABLES COVER TAMPER
ON = TAMPER DISABLED; OFF = TAMPER ENABLED
SHOWN DISABLED (AS SHIPPED).
13
Notification Appliance Power Input
Input Voltage: 12VDC or 24VDC
Input Current: 0mA when both outputs inactive. Up to 2.4A when both
outputs are active.
Notification Appliance Outputs
Output Voltage: Supplied by notification appliance power input
Output Current: Each output must be limited to 1.2A max
Miscellaneous: Outputs are supervised (Style Y) using an EOL20 2K
resistor and are power limited.
A sync module must be used in conjunction with the notification appliances
connected to the 4204CF module.
For a complete list of approved notification appliances, and sync modules, see
the installation instructions for the commercial fire compliant control panel used
with this device.
NFPA-72 Compliant
WARRANTY
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL
WITH WHICH THIS DEVICE IS USED FOR DETAILS REGARDING THE
ENTIRE ALARM SYSTEM.
DIP SWITCH:
WHITE AREAS DENOTE SWITCH HANDLES
UL
NC
NC
SPECIAL APPLICATIONS CIRCUITS
ALARM POLARITY SHOWN
EACH OUTPUT PROVIDES
STYLE Y SUPERVISION
EACH OUTPUT RATED 1.2A MAX
USE NOTIFICATION APPLIANCES
COMPATIBLE WITH POWER SUPPLY
VOLTAGE RATING
POWER FOR NOTIFICATION APPLIANCE OUTPUTS A & B
8-30 VDC OR VFW. UP TO 2.4A DEPENDING ON
NOTIFICATION APPLIANCE CURRENT.
DATA IN FROM CONTROL
GROUND
NOTIFICATION APPLIANCE AND CONSOLE DATA
OUTPUTS ARE POWER-LIMITED.
ALL POWER-LIMITED WIRING MUST BE SEPARATED
FROM NON-POWER-LIMITED AND HIGH-VOLTAGE
WIRING BY 1/4" (6.4mm).
ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED
WHEN POWERED BY THE CONTROL PANEL.
NFPA-72 COMPLIANT.
DATA OUT TO CONTROL
12VDC; SUPPLIES POWER TO MODULE CIRCUITRY (INCLUDING APPLIANCE OUTPUT
RELAY COILS). CURRENT DRAIN AY 12V IS: 25mA + (80mA PER ACTIVE OUTPUT).
Diagram 1. SETTINGS AND CONNECTIONS
4204CF-004-V1
FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE
NOTIFICATION APPLIANCE MODULE MAY BE USED, AND
ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B)
MAY BE USED ON THAT MODULE.
POWER FOR NOTIFICATION APPLIANCE.
DO NOT EXCEED CONTROL'S AUX
POWER CURRENT RATING
SPECIAL
APPLICATIONS
CIRCUITS
+
AUX POWER
+
NOTIFICATION APPLIANCE
OUTPUT A 12VDC
GROUND
GROUND
CONTROL
12V
CONSOLE DATA
4204CF
DATA TO CONTROL
CONSOLE DATA
NOTIFICATION APPLIANCE
OUTPUT B 12VDC
DATA FROM CONTROL
ALL POWER-LIMITED WIRING MUST BE SEPARATED FROM NON-POWER-LIMITED
AND HIGH-VOLTAGE WIRING BY 1/4" (6.4mm).
ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED WHEN POWERED BY THE
CONTROL PANEL.
NFPA-72 COMPLIANT.
4204CF-001-V1
22AWG WIRE MAY BE USED.
MOUNT THE 4204CF WITHIN 3 FEET
OF THE CONTROL. RUN WIRES IN
CONDUIT. CONTROL SUPERVISION
OF WIRING NOT REQUIRED.
Diagram 2. MODULE AND NOTIFICATION APPLIANCES POWERED FROM CONTROL
FOR UL COMMERCIAL FIRE
INSTALLATIONS, ONLY ONE
NOTIFICATION APPLIANCE
MODULE MAY BE USED, AND
ONLY ONE NOTIFICATION
APPLIANCE OUTPUT (A or B)
MAY BE USED ON THAT MODULE.
SUPPLY AC/BATTERY
SUPERVISE
WIRE TO EOLR SUPERVISED
ZONE ON CONTROL
SUPPLEMENTAL
POWER SUPPLY
POWER FOR NOTIFICATION APPLIANCES.
DO NOT EXCEED SUPPLY'S CURRENT RATING.
NOTE:
WHEN NOTIFICATION APPLIANCE POWER IS DISRUPTED,
THE EOL RELAY WILL DISRUPT MODULE POWER CAUSING
THE CONTROL TO DETECT A 4204CF SUPERVISION FAULT
AUX POWER
+
NOTIFICATION APPLIANCE
OUTPUT A 12VDC
4204CF
DATA TO CONTROL
CONSOLE DATA
DATA FROM CONTROL
LENGTH (FEET)
125
200
300
500
NOTIFICATION APPLIANCE
OUTPUT B 12VDC
REFER TO CONTROL'S INSTALLATION INSTRUCTIONS FOR THE MAX COMBINED LENGTH
OF ALL WIRE RUNS THAT CAN BE CONNECTED TO THE CONTROL.
FOR FIRE ALARM INSTALLATIONS, CONTROL MUST BE PROGRAMMED TO SUPERVISE
WIRING WHEN THE 4204CF IS MOUNTED MORE THAN 3 FEET FROM THE CONTROL OR
FROM THE SUPPLEMENTARY POWER SUPPLY.
HOMERUN WIRES BACK TO CONTROL
LIMIT WIRE RUN LENGTH AS FOLLOWS:
#22
#20
#18
#16
SPECIAL APPLICATIONS CIRCUITS
GROUND
CONSOLE DATA
GAUGE
EOL RELAY MUST BE USED WHEN 4204CF
MOUNTED MORE THAN 3 FEET FROM POWER
SUPPLY FOR FIRE ALARM INSTALLATION.
MOUNT RELAY NEAR 4204CF. SYSTEM
SENSOR MODEL No. EOLR-1 MAY BE
USED WITH 12V SUPPLY.
+ 12V
GROUND
CONTROL
USE REGULATED UL COMMERCIAL FIRE
LISTED SUPPLY. 8-30 VDC.
ALL POWER-LIMITED WIRING MUST BE SEPARATED FROM NON-POWER-LIMITED
AND HIGH-VOLTAGE WIRING BY 1/4" (6.4mm).
ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED WHEN POWERED BY THE
CONTROL PANEL.
NFPA-72 COMPLIANT.
4204CF-002-V1
Diagram 3. MODULE POWERED FROM CONTROL, NOTIFICATION APPLIANCES POWERED FROM SUPPLEMENTARY SUPPLY
FOR UL COMMERCIAL FIRE
INSTALLATIONS, ONLY ONE
NOTIFICATION APPLIANCE
MODULE MAY BE USED, AND
ONLY ONE NOTIFICATION
APPLIANCE OUTPUT (A or B)
MAY BE USED ON THAT MODULE.
SUPPLY AC/BATTERY
SUPERVISION
SUPPLEMENTAL
POWER SUPPLY
WIRE TO EOLR SUPERVISED
ZONE ON CONTROL
POWER FOR MODULE AND
NOTIFICATION APPLIANCES.
MOUNT THE 4204CF WITHIN
3 FEET OF THE POWER SUPPLY.
RUN WIRES IN CONDUIT
+
SPECIAL APPLICATIONS
CIRCUIT
NOTIFICATION APPLIANCE
OUTPUT A 12VDC
+ 12V
GROUND
GROUND
CONTROL
CONSOLE DATA
DATA TO CONTROL
CONSOLE DATA
DATA FROM CONTROL
HOMERUN WIRES BACK TO CONTROL.
22AWG WIRE MAY BE USED, LIMIT WIRE RUN
LENGTH TO 1000 FEET. REFER TO CONTROL'S
INSTALLATION INSTRUCTIONS FOR THE MAX
COMBINED LENGTH OF ALL WIRE RUNS THAT
CAN BE CONNECTED TO THE CONTROL.
FOR FIRE ALARM INSTRUCTIONS, CONTROL
MUST BE PROGRAMMED TO SUPERVISE
WIRING WHEN 4204CF MOUNTED MORE
THAN 3 FEET FROM CONTROL.
USE REGULATED, UL COMMERCIAL
FIRE ALARM POWER SUPPLY RATED
FOR 12 VDC ONLY.
4204CF
NOTIFICATION APPLIANCE
OUTPUT B 12VDC
ALL POWER-LIMITED WIRING MUST BE SEPARATED FROM NON-POWER-LIMITED
AND HIGH-VOLTAGE WIRING BY 1/4" (6.4mm).
ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED WHEN POWERED BY THE
CONTROL PANEL.
NFPA-72 COMPLIANT.
4204CF-003-V1
Diagram 4. MODULE AND NOTIFICATION APPLIANCES POWERED FROM SUPPLEMENTARY POWER SUPPLY
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright 2009 Honeywell International Inc.
www.security.honeywell.com
ÊN6223V1BŠ
N6223V1 3/09 Rev. A