N6223V1 3/09 Rev. A ADEMCO 4204CF SUPERVISED NOTIFICATION APPLIANCE MODULE INSTALLATION AND SETUP GUIDE GENERAL INFORMATION Connections and Settings The ADEMCO 4204CF Supervised Notification Appliance Module adds up to two Class B (Style Y) Supervised Notification Appliance Outputs to compatible ADEMCO Control Panels (for more information on Style Y, see NFPA-72 National Fire Alarm Code Chapter 3: Protected Premises Fire Alarm Systems). Refer to your Control Panel’s installation instructions to determine if it supports this module. Each output is supervised using an EOL20 2K resistor (two resistors supplied). Select and set an address for the 4204CF using its DIP switch settings as shown in Diagram 1. Assign a unique address to the 4204CF so that the control can communicate with it. Refer to the control’s installation instructions to determine which address or range of addresses to use. • For UL commercial and household fire installations, no more than one wire per terminal may be connected. • Use only 14-22AWG wire. Make connections to the control’s keypad wiring by using the 4- position terminal block TB1, or the 4-pin plug (plug cable provided). Make connections to the Notification Appliance Power input and outputs via the module’s 12-position terminal block (TB2). Refer to Diagrams 2, 3, and 4. 1. Only relay 1 (Output A) and relay 3 (Output B) may be programmed for activation. Refer to the control’s Installation Instructions for programming output activation and supervision options. 2. When programming 4204CF output activation options in the control panel, outputs must not be programmed to “Close for 2 Seconds.” Any other option may be used, but do not program the relay to ”Stop” in less than 10 seconds. UL For UL Commercial Fire installations, only one notification appliance module may be used, and only one notification appliance output (A or B) may be used on that module. Each appliance output is rated at 1.2A max. You can power these outputs from the control panel or from a supplementary regulated UL Commercial Fire Alarm (power limited) power supply rated at 8-30VDC. The 4204CF has a built-in cover tamper switch, which allows it to detect and report the removal of its cover to the Control Panel. INSTALLATION Mounting UL SPECIFICATIONS • For dry, indoor use only. Do not install in air-handling spaces. • For all fire (NFPA) and UL Commercial Burglary installations, the 4204CF must be tamper protected or mounted in a tamperprotected cabinet. Physical: 6-7/16” W x 4-1/4” H x 1-1/4” D (163mm x 108mm x 32mm) Electrical: +12V Input Input Voltage: 12VDC nominal (10-14VDC) Input Current: 25mA + 80mA per active output For fire alarm installations, mount the 4204CF inside a UL864 listed cabinet such as the control’s cabinet. Cover tamper supervision is not required; to disable tamper supervision, set DIP switch Position 1 to the ON position. 1. Cover tamper supervision is not supported by all control panels. For other (i.e., non-fire alarm) installations, a separate enclosure is not required. Mount the 4204CF directly on a surface using the slotted holes located on the back of its housing (mounting screws provided). Feed the wires through the slot on the side on the side or through the breakout located on the back of the housing. Cover tamper supervision can be used, if supported by the control panel. 2. Affix the connections level (provided) to the inside of the 4204CF’s cover. OFF ON 4204CF ADDRESS SETTINGS SWITCH NUMBER ("—" means "OFF") 8 9 10 12 13 14 ON — ON — ON ON — ON — ON — ON — ON — 3 ON ON — — ON ON — — ON ON — — ON ON — 4 4 ON ON ON ON — — — ON ON ON ON — — — — 5 5 ON ON ON ON ON ON ON ON — — — — — 1 2 0 1 2 3 4 5 6 — — 7 — — 11 — 15 — FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE MODULE MAY BE USED, AND ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B) MAY BE USED ON THAT MODULE. TB2 4204CF 12 DIP SWITCH FOR SETTING DEVICE ADDRESS AND ENABLING/DISABLING TAMPER 11 10 COVER TAMPER (REED) SWITCH EITHER OR BOTH CAN BE USED 4-PIN CONSOLE PLUG NC NC 9 8 7 POLARIZED NC NOTIFICATION NC APPLIANCES 5 4 2 TB1 1 16 YEL BLK GRN RED NOTIFICATION APPLIANCE OUTPUT B 2K EOLR EOL20 NOTIFICATION APPLIANCE OUTPUT A 2K EOLR EOL20 6 3 15 http://www.security.honeywell.com/hsc/resources/wa/index.html 2 POSITIONS 2-5 DETERMINE 4204CF'S ADDRESS: CONTROL'S INSTRUCTIONS SPECIFY ADDRESS TO USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED). 14 For the latest warranty information, please go to: 3 POSITION 1 ENABLES/DISABLES COVER TAMPER ON = TAMPER DISABLED; OFF = TAMPER ENABLED SHOWN DISABLED (AS SHIPPED). 13 Notification Appliance Power Input Input Voltage: 12VDC or 24VDC Input Current: 0mA when both outputs inactive. Up to 2.4A when both outputs are active. Notification Appliance Outputs Output Voltage: Supplied by notification appliance power input Output Current: Each output must be limited to 1.2A max Miscellaneous: Outputs are supervised (Style Y) using an EOL20 2K resistor and are power limited. A sync module must be used in conjunction with the notification appliances connected to the 4204CF module. For a complete list of approved notification appliances, and sync modules, see the installation instructions for the commercial fire compliant control panel used with this device. NFPA-72 Compliant WARRANTY REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED FOR DETAILS REGARDING THE ENTIRE ALARM SYSTEM. DIP SWITCH: WHITE AREAS DENOTE SWITCH HANDLES UL NC NC SPECIAL APPLICATIONS CIRCUITS ALARM POLARITY SHOWN EACH OUTPUT PROVIDES STYLE Y SUPERVISION EACH OUTPUT RATED 1.2A MAX USE NOTIFICATION APPLIANCES COMPATIBLE WITH POWER SUPPLY VOLTAGE RATING POWER FOR NOTIFICATION APPLIANCE OUTPUTS A & B 8-30 VDC OR VFW. UP TO 2.4A DEPENDING ON NOTIFICATION APPLIANCE CURRENT. DATA IN FROM CONTROL GROUND NOTIFICATION APPLIANCE AND CONSOLE DATA OUTPUTS ARE POWER-LIMITED. ALL POWER-LIMITED WIRING MUST BE SEPARATED FROM NON-POWER-LIMITED AND HIGH-VOLTAGE WIRING BY 1/4" (6.4mm). ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED WHEN POWERED BY THE CONTROL PANEL. NFPA-72 COMPLIANT. DATA OUT TO CONTROL 12VDC; SUPPLIES POWER TO MODULE CIRCUITRY (INCLUDING APPLIANCE OUTPUT RELAY COILS). CURRENT DRAIN AY 12V IS: 25mA + (80mA PER ACTIVE OUTPUT). Diagram 1. SETTINGS AND CONNECTIONS 4204CF-004-V1 FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE MODULE MAY BE USED, AND ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B) MAY BE USED ON THAT MODULE. POWER FOR NOTIFICATION APPLIANCE. DO NOT EXCEED CONTROL'S AUX POWER CURRENT RATING SPECIAL APPLICATIONS CIRCUITS + AUX POWER + NOTIFICATION APPLIANCE OUTPUT A 12VDC GROUND GROUND CONTROL 12V CONSOLE DATA 4204CF DATA TO CONTROL CONSOLE DATA NOTIFICATION APPLIANCE OUTPUT B 12VDC DATA FROM CONTROL ALL POWER-LIMITED WIRING MUST BE SEPARATED FROM NON-POWER-LIMITED AND HIGH-VOLTAGE WIRING BY 1/4" (6.4mm). ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED WHEN POWERED BY THE CONTROL PANEL. NFPA-72 COMPLIANT. 4204CF-001-V1 22AWG WIRE MAY BE USED. MOUNT THE 4204CF WITHIN 3 FEET OF THE CONTROL. RUN WIRES IN CONDUIT. CONTROL SUPERVISION OF WIRING NOT REQUIRED. Diagram 2. MODULE AND NOTIFICATION APPLIANCES POWERED FROM CONTROL FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE MODULE MAY BE USED, AND ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B) MAY BE USED ON THAT MODULE. SUPPLY AC/BATTERY SUPERVISE WIRE TO EOLR SUPERVISED ZONE ON CONTROL SUPPLEMENTAL POWER SUPPLY POWER FOR NOTIFICATION APPLIANCES. DO NOT EXCEED SUPPLY'S CURRENT RATING. NOTE: WHEN NOTIFICATION APPLIANCE POWER IS DISRUPTED, THE EOL RELAY WILL DISRUPT MODULE POWER CAUSING THE CONTROL TO DETECT A 4204CF SUPERVISION FAULT AUX POWER + NOTIFICATION APPLIANCE OUTPUT A 12VDC 4204CF DATA TO CONTROL CONSOLE DATA DATA FROM CONTROL LENGTH (FEET) 125 200 300 500 NOTIFICATION APPLIANCE OUTPUT B 12VDC REFER TO CONTROL'S INSTALLATION INSTRUCTIONS FOR THE MAX COMBINED LENGTH OF ALL WIRE RUNS THAT CAN BE CONNECTED TO THE CONTROL. FOR FIRE ALARM INSTALLATIONS, CONTROL MUST BE PROGRAMMED TO SUPERVISE WIRING WHEN THE 4204CF IS MOUNTED MORE THAN 3 FEET FROM THE CONTROL OR FROM THE SUPPLEMENTARY POWER SUPPLY. HOMERUN WIRES BACK TO CONTROL LIMIT WIRE RUN LENGTH AS FOLLOWS: #22 #20 #18 #16 SPECIAL APPLICATIONS CIRCUITS GROUND CONSOLE DATA GAUGE EOL RELAY MUST BE USED WHEN 4204CF MOUNTED MORE THAN 3 FEET FROM POWER SUPPLY FOR FIRE ALARM INSTALLATION. MOUNT RELAY NEAR 4204CF. SYSTEM SENSOR MODEL No. EOLR-1 MAY BE USED WITH 12V SUPPLY. + 12V GROUND CONTROL USE REGULATED UL COMMERCIAL FIRE LISTED SUPPLY. 8-30 VDC. ALL POWER-LIMITED WIRING MUST BE SEPARATED FROM NON-POWER-LIMITED AND HIGH-VOLTAGE WIRING BY 1/4" (6.4mm). ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED WHEN POWERED BY THE CONTROL PANEL. NFPA-72 COMPLIANT. 4204CF-002-V1 Diagram 3. MODULE POWERED FROM CONTROL, NOTIFICATION APPLIANCES POWERED FROM SUPPLEMENTARY SUPPLY FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE MODULE MAY BE USED, AND ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B) MAY BE USED ON THAT MODULE. SUPPLY AC/BATTERY SUPERVISION SUPPLEMENTAL POWER SUPPLY WIRE TO EOLR SUPERVISED ZONE ON CONTROL POWER FOR MODULE AND NOTIFICATION APPLIANCES. MOUNT THE 4204CF WITHIN 3 FEET OF THE POWER SUPPLY. RUN WIRES IN CONDUIT + SPECIAL APPLICATIONS CIRCUIT NOTIFICATION APPLIANCE OUTPUT A 12VDC + 12V GROUND GROUND CONTROL CONSOLE DATA DATA TO CONTROL CONSOLE DATA DATA FROM CONTROL HOMERUN WIRES BACK TO CONTROL. 22AWG WIRE MAY BE USED, LIMIT WIRE RUN LENGTH TO 1000 FEET. REFER TO CONTROL'S INSTALLATION INSTRUCTIONS FOR THE MAX COMBINED LENGTH OF ALL WIRE RUNS THAT CAN BE CONNECTED TO THE CONTROL. FOR FIRE ALARM INSTRUCTIONS, CONTROL MUST BE PROGRAMMED TO SUPERVISE WIRING WHEN 4204CF MOUNTED MORE THAN 3 FEET FROM CONTROL. USE REGULATED, UL COMMERCIAL FIRE ALARM POWER SUPPLY RATED FOR 12 VDC ONLY. 4204CF NOTIFICATION APPLIANCE OUTPUT B 12VDC ALL POWER-LIMITED WIRING MUST BE SEPARATED FROM NON-POWER-LIMITED AND HIGH-VOLTAGE WIRING BY 1/4" (6.4mm). ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED WHEN POWERED BY THE CONTROL PANEL. NFPA-72 COMPLIANT. 4204CF-003-V1 Diagram 4. MODULE AND NOTIFICATION APPLIANCES POWERED FROM SUPPLEMENTARY POWER SUPPLY 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright 2009 Honeywell International Inc. www.security.honeywell.com ÊN6223V1BŠ N6223V1 3/09 Rev. A