N6223 6/96 No. 4204CF S U P E R V I S E D N O T I F I C AT I O N A P P L I A N C E M O D U L E INSTALLATION INSTRUCTIONS GENERAL INFORMATION Connections and Settings The 4204CF Supervised Notification Appliance Module adds up to 2 Class B (Style Y) Supervised Notification Appliance Outputs to compatible ADEMCO Control Panels (for more information on Style Y, see NFPA 72 National Fire Alarm Code Chapter 3: Protected Premises Fire Alarm Systems). Refer to your control panelÕs installation instructions to determine if it supports this module. Each output is supervised using a model 610-7 2K EOL resistor (2 resistors supplied). Select and set an address for the 4204CF using its DIP switch settings as shown in Diagram 1. Assign a unique address to the 4204CF so that the control can communicate with it. Refer to the controlÕs Installation Instructions to determine which address or range of addresses to use. Make connections to the control's keypad wiring by using the 4-position terminal block TB1, or the 4-pin plug (plug cable provided). Make connections to the Notification Appliance Power input and outputs via the moduleÕs 12 position terminal block (TB2) (refer to Diagrams 2, 3 & 4). Each appliance output is rated at 1.2A max. You can power these outputs from the Control Panel or from a supplementary UL864 commercial fire listed (power limited) power supply rated at 8-30 VDC (regulated)/VFW (full wave rectified, unfiltered). ✓ The 4204CF connects to the control via the control's keypad wiring. From the Control Panel's keypad wiring, the 4204CF receives output activation commands and sends output supervision status back to the Control Panel. The 4204CF has a built-in cover tamper switch, which allows it to detect and report the removal of its cover to the Control Panel. SPECIFICATIONS (163mm x 108mm x 32mm) Electrical +12V Input Input Voltage: +12VDC (10-14VDC) Input Current: 25mA + 80mA per active output For fire alarm installations, mount the 4204CF inside a U.L. 864 listed cabinet such as the controlÕs cabinet or the supplementary power supply cabinet (if used). Cover tamper supervision is not required; to disable tamper supervision, set DIP switch Position 1 to the ON position. Notification Appliance Power Input Input Voltage: 8-30 VDC or VFW Input Current: 0 mA when both outputs inactive. Up to 2.4A when both outputs are active 1. Cover tamper supervision is not supported by all control panels. For other (i.e. non-fire alarm) installations, a separate enclosure is not required. Mount the 4204CF directly on a surface using the slotted holes located on the back of its housing (mounting screws provided). Feed the wires through the slot on the side or through the breakout located on the back of the housing. Cover tamper supervision can be used, if supported by the control panel. 2. Affix the connections label (provided) to the inside of the 4204CFÕs cover. Notification Appliance Outputs Output Voltage: Supplied by notification appliance power input Output Current: Each output must be limited to 1.2A max Miscellaneous: Outputs are supervised (Style Y) using 610-7 2K EOL resistor and are power limited. Refer to the instructions for the notification power supply used for a list of compatible indicating devices. 4204CF ADDRESS SETTINGS ("—" means "OFF") ➞ ON 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 ON — ON — ON — ON — ON — ON — ON — ON — 3 ON ON — — ON ON — — ON ON — — ON ON — — 4 ON ON ON ON — — — — ON ON ON ON — — — — 5 ON ON ON ON ON ON ON ON — — — — — — — — ➞ ➞ ➞ ➞ 2 3 4 5 POSITIONS 2-5 DETERMINE 4204CF’s ADDRESS: CONTROL’S INSTRUCTIONS SPECIFY ADDRESS TO USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED) SWITCH POSITION ➞ ON 1 ▲ { ➞ OFF SETTINGS ▲ ➞ 6 4 ➞ TB1 13 14 15 16 YEL BLK GRN RED ▲ NC NC TB2 NOTIFICATION APPLIANCE OUTPUT B 2K EOLR #610-7 + POLARIZED NOTIFICATION APPLIANCES NOTIFICATION APPLIANCE – OUTPUT A 2K EOLR + #610-7 NC NC 3 ➞ EITHER OR BOTH CAN BE USED ➞ – NC NC 5 4-PIN CONSOLE PLUG 2 ➞ 7 COVER TAMPER (REED) SWITCH 8 DIP SWITCH FOR SETTING DEVICE ADDRESS AND ENABLING/ DISABLING TAMPER 9 10 11 12 DIP SWITCH: WHITE AREAS DENOTE SWITCH HANDLES 1 POSITION 1 ENABLES/DISABLES COVER TAMPER ON = TAMPER DISABLED SHOWN DISABLED (AS SHIPPED) OFF = TAMPER ENABLED 6-7/16Ó W x 4-1/4Ó H x 1-1/4Ó D Physical INSTALLATION Mounting ✓ 1. Only relay 1 (Output A) and relay 3 (Output B) may be programmed for activation. Refer to the controlÕs Installation Instructions for programming output activation and supervision options. 2. When programming 4204CF output activation options in the control panel, outputs must not be programmed to ÒClose for 2 Seconds.Ó Any other option may be used, but do not program the relay to ÓStopÓ in less than 10 seconds. + – FOR NOTIFICATION } POWER APPLIANCE OUTPUTS A & B - ALARM POLARITY SHOWN - EACH OUTPUT PROVIDES STYLE Y SUPERVISION - EACH OUTPUT RATED 1.2A MAX - USE NOTIFICATION APPLIANCES COMPATIBLE WITH NOTIFICATION APPLIANCES POWER SUPPLY VOLTAGE RATING 8-30 VDC OR VFW. UP TO 2.4A DATA IN DEPENDING ON NOTIFICATION FROM CONTROL APPLIANCE CURRENT CONNECTIONS (–) GROUND DATA OUT NOTIFICATION APPLIANCE TO CONTROL AND CONSOLE DATA (+) 12VDC; SUPPLIES POWER TO OUTPUTS ARE POWER MODULE CIRCUITRY (INCLUDING LIMITED APPLIANCE OUTPUT RELAY COILS). CONNECTIONS CURRENT DRAIN AT 12V IS: 25 mA + (80mA PER ACTIVE OUTPUT) Diagram 1. SETTINGS AND CONNECTIONS POWER FOR NOTIFICATION APPLIANCES. DO NOT EXCEED CONTROL'S AUX POWER CURRENT RATING + AUX POWER GROUND GROUND CONSOLE DATA DATA FROM CONTROL ▲ CONSOLE DATA } } 4204CF DATA TO CONTROL ▲ CONTROL – +12V NOTIFICATION APPLIANCE OUTPUT A 12VDC NOTIFICATION APPLIANCE OUTPUT B 12VDC 22AWG WIRE MAY BE USED. MOUNT THE 4204CF WITHIN 3 FEET OF THE CONTROL. RUN WIRES IN CONDUIT. CONTROL SUPERVISION OF WIRING NOT REQUIRED. Diagram 2. MODULE AND NOTIFICATION APPLIANCES POWERED FROM CONTROL SUPPLY AC/BATTERY SUPERVISION WIRE TO EOLR SUPERVISED ZONE ON CONTROL SUPPLEMENTAL POWER SUPPLY } NOTE: WHEN NOTIFICATION APPLIANCE POWER IS DISRUPTED, THE EOL RELAY WILL DISRUPT MODULE POWER CAUSING THE CONTROL TO DETECT A 4204CF SUPERVISION FAULT + AUX POWER GROUND GROUND CONSOLE DATA ▲ CONTROL – +12V ▲ CONSOLE DATA DATA TO CONTROL 4204CF DATA FROM CONTROL USE UL COMMERCIAL FIRE LISTED SUPPLY. 8-30 VDC OR VFW POWER FOR NOTIFICATION APPLIANCES. DO NOT EXCEED SUPPLY’S CURRENT RATING EOL RELAY MUST BE USED WHEN 4204CF MOUNTED MORE THAN 3 FEET FROM POWER SUPPLY FOR FIRE ALARM INSTALLATION. MOUNT RELAY NEAR 4204CF. SYSTEM SENSOR MODEL A77-716B MAY BE USED WITH 12V SUPPLY } } NOTIFICATION APPLIANCE OUTPUT A NOTIFICATION APPLIANCE OUTPUT B REFER TO CONTROL’S HOMERUN WIRES BACK TO CONTROL. LIMIT WIRE RUN LENGTH AS FOLLOWS: INSTALLATION INSTRUCTIONS FOR GAUGE LENGTH (FEET) THE MAX COMBINED LENGTH OF ALL WIRE RUNS THAT CAN BE #22 125 CONNECTED TO THE CONTROL #20 200 #18 300 #16 500 FOR FIRE ALARM INSTALLATIONS, CONTROL MUST BE PROGRAMMED TO SUPERVISE WIRING WHEN THE 4204CF IS MOUNTED MORE THAN 3 FEET FROM THE CONTROL OR FROM THE SUPPLEMENTARY POWER SUPPLY. Diagram 3. MODULE POWERED FROM CONTROL, NOTIFICATION APPLIANCES POWERED FROM SUPPLEMENTARY SUPPLY SUPPLY AC/BATTERY SUPERVISION WIRE TO EOLR SUPERVISED ZONE ON CONTROL } SUPPLEMENTAL POWER SUPPLY +12VDC GROUND CONSOLE DATA ▲ CONSOLE DATA DATA TO CONTROL POWER FOR MODULE AND NOTIFICATION APPLIANCES. MOUNT THE 4204CF WITHIN 3 FEET OF THE POWER SUPPLY. RUN WIRES IN CONDUIT – GROUND ▲ CONTROL + USE UL COMMERCIAL FIRE LISTED SUPPLY RATED FOR 12VDC ONLY 4204CF DATA FROM CONTROL } } NOTIFICATION APPLIANCE OUTPUT A 12VDC NOTIFICATION APPLIANCE OUTPUT B 12VDC HOMERUN WIRES BACK TO CONTROL. 22AWG WIRE MAY BE USED, LIMIT WIRE RUN LENGTH TO 1000 FEET. REFER TO CONTROL’S INSTALLATION INSTRUCTIONS FOR THE MAX COMBINED LENGTH OF ALL WIRE RUNS THAT CAN BE CONNECTED TO THE CONTROL. FOR FIRE ALARM INSTALLATIONS, CONTROL MUST BE PROGRAMMED TO SUPERVISE WIRING WHEN 4204CF MOUNTED MORE THAN 3 FEET FROM CONTROL Diagram 4. MODULE AND NOTIFICATION APPLIANCES POWERED FROM SUPPLEMENTARY POWER SUPPLY ALARM DEVICE MANUFACTURING COMPANY A DIVISION OF PITTWAY CORPORATION 165 Eileen Way, Syosset, New York 11791 Copyright 1996 Pittway Corporation N6223 6/96