Series Ratings
Selection Guide
Contents
Description
Page
Series Ratings
NQ Series Connected Circuit Breaker Ratings
2
•
NF Series Connected Circuit Breaker Ratings
4
•
I-Line Series Connected Circuit Breaker Ratings
4
•
Fuse/I-Line Circuit Breaker Series Connected Ratings
5
•
Homeline Loadcentre Single Row - Short Circuit Current Rating
6
•
Homeline Loadcentre Double Row, Indoor Devices - Short Circuit Current Rating
6
•
Homeline Loadcentre Outdoor Devices- Short Circuit Current Rating
6
•
Canadian QO Loadcentres - Short Circuit Current Rating
7
DE14
SERIES RATINGS
•
Note:
For additional information on Panelboard / Switchboard Short-Circuit Current Ratings please refer to Data Bulletin 2700DB9901.
11/15
DE14-1
DE14_p02.fm Page 2 Monday, November 23, 2015 10:46 PM
Series Ratings
NQ Panelboards
Class 1640
This page contains UL Tested and Certified series combination ratings for
panelboards for Canada. These ratings apply to either an integral main
located in the same enclosure or a remote main located in a separate
enclosure.
NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Maximum
System
Voltage
AC ab
NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Maximum
System
Voltage
AC ab
Maximum Square D™ Brand Integral
Short
or Remote Main Circuit
Circuit
Breakers and Remote
Current
Main Fuses
Rating
22,000
MG
25,000
LD, HD, JD
HG, JG
65,000
LG
LJ
HJ, JJ
120/240
1P/3W
LJ
100,000
DJ 400 A
125,000
HL, JL
18,000
LA/LH (L) 34200MC
LA/LH (L) 34225MC
LA/LH (L) 34250MC
LA/LH (L) 34400MC
DE14
SERIES RATINGS
QJ
25,000
LD
208Y/120
3P/4W
240/120 V
3P/4W
DJ–W 150 A MC
30,000
DJ–W 250 A MC
DJ–W 600 A MC
Square D™ Brand Branch Circuit Breaker Catalog
Designation and Allowable Ampere Ranges cdef
Type
1 Pole
2 Pole
3 Pole
QO (B)
QO (B)
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B) GFI
QO (B) EPD
QO (B)
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO(B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO(B) AFI
QO(B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
15–30 A
15–70 A
15–70 A
15–30 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–70 A
15–30 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–70 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–30 A
15–30 A
15–70 A
15–70 A
15–30 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–70 A
—
—
—
15–20 A
15–20 A
15–20 A
15–70 A
—
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
—
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–70 A
15–30 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
—
15–125 A
15–125 A
15–60 A
15–60 A
15–60 A
—
15–20 A
—
15–125 A
15–125 A
15–60 A
15–60 A
15–60 A
—
15–20 A
—
15–125 A
15–125 A
15–60 A
15–60 A
—
15–20 A
—
40–60 A
40–60 A
15–125 A
15–125 A
15–60 A
15–60 A
15–60 A
—
15–20 A
—
15–125 A
15–125 A
15–100 A
15–30 A
15–60 A
—
15–20 A
—
15–125 A
150 A
15–60 A
15–60 A
—
15–20 A
—
15–125 A
150 A
15–60 A
15–60 A
—
15–20 A
—
15–125 A
15–125 A
15–60 A
15–60 A
15–60 A
—
15–20 A
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
QO (B)
15–30 A
15–30 A
15–30 A
QO (B)
QO (B) VH
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) GFI
QO (B) AFI
QO (B)
QO (B) VH
QO (B) GFI
QO (B) AFI
QO (B)
QO (B) VH
QO (B) GFI
QO (B) AFI
15–70 A
15–30 A
15–30 A
15–30 A
—
15–20 A
15–20 A
15–20 A
15–70 A
—
15–30 A
15–20 A
15–70 A
—
15–30 A
15–20 A
15–70 A
—
15–30 A
15–20 A
15–125 A
15–125 A
15–60 A
15–60 A
—
—
—
—
15–100 A
15–125 A
15–60 A
—
15–100 A
—
15–60 A
—
15–100 A
—
15–60 A
—
—
15–150 A
15–30 A
15–30 A
15–30 A
—
—
—
—
15–150 A
—
—
—
15–100 A
—
—
—
15–150 A
—
—
LG
65,000
LJ
LL
208Y/120
3P/4W
240/120 V
3P/4W
DJ 400 A
100,000
QJ
LJ
240/120 V
3P/4W
22,000
QO (B) VH
QD
ED, FD
KD
240/120 V
3P/4W
25,000
HD, JD
LD
a
b
c
d
e
f
g
h
DE14-2
Maximum Square D™ Brand Integral
Short
or Remote Main Circuit
Circuit
Breakers and Remote
Current
Main Fuses
Rating
Square D™ Brand Branch Circuit Breaker Catalog
Designation and Allowable Ampere Ranges cdef
Type
1 Pole
2 Pole
3 Pole
QO (B)
QO (B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B)
QO (B) VH
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) PL
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) GFI
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) AS
QO (B) GFI
QO (B) AFI
QO (B)
QO (B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QO (B) DF
15–70 A
15–70 A
—
15–30 A
15–30 A
—
15–20 A
15–20 A
15–20 A
15–70 A
15–70 A
—
15–30 A
15–30 A
—
15–20 A
15–20 A
15–20 A
—
—
—
15–70 A
—
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
—
15–30 A
15–30 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–70 A
—
—
—
15–20 A
15–20 A
15–20 A
15–70 A
15–30 A
15–30 A
—
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
—
15–30 A
15–30 A
15–30 A
—
15–20 A
15–20 A
15–20 A
15–70 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–30 A
15–30 A
15–20 A
15–70 A
—
—
15–30 A
15–30 A
—
15–20 A
15–20 A
15–20 A
15–70 A
15–30 A
—
15–30 A
15–30 A
—
15–20 A
15–20 A
15–20 A
15–125 A
15–125 A
15–100 A
15–60 A
15–60 A
—
—
—
—
15–125 A
15–125 A
15–100 A
15–60 A
15–60 A
—
—
—
—
—
—
—
15–125 A
—
15–60 A
15–60 A
—
—
—
15–125 A
—
15–60 A
15–60 A
15–60 A
15–60 A
—
—
—
15–125 A
15–125 A
15–100 A
15–30 A
15–60 A
—
—
—
15–125 A
15–60 A
15–60 A
—
15–60 A
—
—
—
15–125 A
—
15–60 A
15–60 A
15–60 A
—
—
—
—
15–125 A
15–60 A
—
—
—
15–125 A
15–30 A
15–60 A
—
15–125 A
—
15–100 A
15–60 A
15–60 A
—
—
—
—
15–125 A
15–125 A
15–100 A
15–60 A
15–60 A
—
—
—
—
—
15–150 A
—
15–30 A
15–30 A
15–30 A
—
—
—
—
15–150 A
—
15–30 A
15–30 A
15–30 A
—
—
—
15–30 A
15–30 A
15–30 A
—
15–150 A
—
—
—
—
—
15–30 A
15–150 A
15–30 A
15–50 A
15–50 A
15–50 A
—
—
—
—
15–150 A
—
—
—
—
—
—
15–100 A
15–50 A
15–50 A
15–50 A
—
—
—
—
15–30 A
35–150 A
15–30 A
15–50 A
15–50 A
15–50 A
—
—
—
15–100 A
15–50 A
—
—
—
15–100 A
15–30 A
—
—
15–100 A
35–150 A
—
15–50 A
15–50 A
15–50 A
—
—
—
—
15–150 A
—
15–30 A
15–30 A
15–30 A
—
—
—
For shown circuit breakers rated less than this maximum voltage, the indicated short circuit current
rating also applies, but at the voltage rating of the circuit breaker
Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard.
Suffixes HID, and SWD may also be applied to the applicable branch circuit breakers shown
above. Suffix SWN may not be applied in combination with LC main breakers.
Where QO (B) circuit breakers are shown above, QO (B) H, QO (B) VH, and QOH (B) circuit
breakers may also be used.
Where QO (B) GFI circuit breakers are shown above, QO (B) EPD and/or QO (B) EPE circuit
breakers may also be used. QO–EPE only comes in 3 pole construction.
Where QO (B) AFI circuit breakers are shown above, QO (B) CAFI circuit breakers may also be
used.
To achieve selective coordination, the rating of the DJ main circuit breaker must be at least two
times greater than the ampere rating of any branch circuit breaker.
For complete series ratings for Delta Systems please reference NQ/NQM Panelboards
Information Manual 80043–712–06.
11/15
DE14_p03.fm Page 3 Monday, November 23, 2015 10:46 PM
Series Ratings
NQ Panelboards
Class 1640
NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Maximum Square D™ Brand Integral
Short
or Remote Main Circuit
Circuit
Breakers and Remote
Current
Main Fuses
Rating
LA, MA
LC400A
42,000
LC600A
MG
LC400A
LC600A
DJ400A
DJ_W
DJ, DG, DL 150–600 A
EG, FG, KG
65,000
QG
240/120 V
3P/4W
HG, JG
FC_ or KC_22___
FC_ or KC_34___
LG
LJ
LL
FC_ or KC_22___
FC_ or KC_34___
DJ400A
EJ
100,000
LJ
HJ, JJ
11/15
Square D™ Brand Branch Circuit Breaker Catalog
Designation and Allowable Ampere Ranges cdef
Type
1 Pole
2 Pole
3 Pole
Q2L–H
QDL
QO (B)
QO (B) VH
QO (B) GFI
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B) VH
QO (B) GFI
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B) VH
QO (B)
QO (B) VH
QO (B) GFI
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B) VH
QO (B) GFI
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) H
QO (B)
QO (B) VH
QO (B) GFI
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B) EPD
QO (B)
QO (B) GFI
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) GFI
QO (B) PL
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) PL
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) AS
QO (B)
QO (B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) EPD
QO (B) EPE
QO (B) GFI
QO (B) AFI
QO (B)
QO (B) H
QO (B) VH
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B)
QO (B) VH
QO (B) H
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) H
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
—
—
15–70 A
15–70 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–30 A
15–20 A
15–20 A
15–20 A
15–30 A
15–30 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–30 A
—
15–20 A
15–20 A
15–20 A
15–70 A
—
—
15–70 A
—
15–30 A
15–20 A
15–20 A
15–20 A
—
15–70 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
—
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
—
—
15–30 A
15–30 A
—
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–30 A
15–70 A
15–70 A
—
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–30 A
15–30 A
—
—
—
15–30 A
15–20 A
15–70 A
—
—
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–70 A
15–70 A
—
—
—
15–20 A
15–20 A
15–20 A
15–70 A
—
—
15–30 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
100–225 A
70–225 A
15–70 A
15–125A
15–60 A
—
—
—
15–125 A
15–60 A
—
—
—
15–30 A
15–30 A
15–125 A
15–60 A
—
—
—
15–125 A
—
—
—
—
15–125 A
—
15–100 A
15–150 A
110–125 A
15–60 A
—
—
—
—
15–125 A
15–60 A
—
—
—
15–125 A
—
15–60 A
15–60 A
—
—
—
15–125 A
—
15–100 A
15–60 A
15–60 A
—
15–60 A
—
—
—
15–100 A
15–30 A
15–125 A
15–125 A
15–100 A
15–60 A
15–60 A
—
—
—
15–125 A
40–60 A
40–60 A
—
—
—
15–30 A
—
15–125 A
15–100 A
—
15–60 A
15–60 A
—
—
—
15–125 A
15–125 A
15–125 A
15–100 A
15–30 A
15–60 A
—
—
—
15–125 A
15–100 A
—
15–60 A
15–60 A
15–60 A
—
—
—
100–225 A
70–225 A
—
15–100 A
15–30 A
—
—
—
15–100 A
15–30 A
—
—
—
15–30 A
—
15–100 A
—
—
—
—
15–150 A
15–30 A
—
—
—
—
15–150 A
—
—
15–150 A
—
—
—
—
15–30 A
15–100 A
—
—
—
—
15–30 A
35–150 A
15–50 A
15–30 A
—
—
—
15–100 A
35–150 A
—
15–50 A
15–50 A
15–50 A
15–30 A
—
—
—
15–100 A
15–30 A
—
15–150 A
—
15–30 A
15–30 A
—
—
—
—
—
15–30 A
15–30 A
15–30 A
15–30 A
—
—
—
—
15–150 A
—
—
—
—
—
15–100 A
—
15–150 A
—
—
—
—
—
—
15–100 A
—
35–150 A
15–30 A
15–50 A
15–50 A
—
—
—
Maximum
System
Voltage
AC ab
Maximum Square D™ Brand Integral
Short
or Remote Main Circuit
Circuit
Breakers and Remote
Current
Main Fuses
Rating
125,000
HL, JL
200,000
FI, KI, HR, JR
240/120 V
3P/4
200 A Max. Class T6,
J Fuses
208Y/120
3P/4W
200,000
400 A Max. Class T3
Fuses
42,000
50,000
400 A Max. Class T3
Fuses
400 A Max. Class T3 Fuses
400 A Max. Class J Fuses
65,000
400 A Max. Class T6 Fuses
240/120 V
3P/4W
100,000
200 A Max. Class
T3 Fuses
200 A Max. Class J or T6
Fuses
200,000
400 A Max. Class T3 Fuses
a
b
c
d
e
f
Square D™ Brand Branch Circuit Breaker Catalog
Designation and Allowable Ampere Ranges cdef
Type
1 Pole
2 Pole
3 Pole
QO (B)
QO (B) H
QO (B) VH
QO (B) PL
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) GFI
QO (B) EPD
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B)
QO (B) GFI
QO (B) EPD
QO (B)
QO (B) GFI
QO (B) EPE
QO (B) EPD
15–70 A
—
—
15–30 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
15–30 A
15–30 A
15–20 A
15–20 A
15–20 A
15–70 A
—
—
15–70 A
15–30 A
—
15–30 A
15–125 A
15–100 A
—
15–60 A
15–60 A
15–60 A
—
—
—
15–125 A
15–60 A
15–60 A
—
—
—
15–125 A
—
—
15–125 A
15–60 A
—
15–60 A
15–100 A
—
35–150 A
15–30 A
15–50 A
15–50 A
—
—
—
15–100 A
—
—
—
—
—
—
15–50 A
15–50 A
15–100 A
15–50 A
15–50 A
15–50 A
QO (B) VH
15–30 A
15–125 A
—
QO (B) VH
QO (B) VH
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QO (B) DF
QO (B) VH
QO (B) AFI
QO (B)
QO (B) VH
QO (B) GFI
QO (B) EPD
QO (B) EPE
QO (B) AFI
QO (B) CAFI
QOT
QO (B) DF
QO (B) EPD
QO (B) EPE
QO (B)
QO (B) GFI
QO (B) EPD
QO (B) EPE
—
15–70 A
—
—
15–20 A
15–20 A
15–20 A
15–70 A
15–20 A
15–70 A
—
15–30 A
15–30 A
—
15–20 A
15–20 A
15–30 A
15–20 A
—
—
15–70 A
15–30 A
15–30 A
—
—
15–125 A
—
—
—
—
—
15–125 A
—
15–125 A
—
15–60 A
15–60 A
—
—
—
15–30 A
—
—
—
15–125 A
15–60 A
15–60 A
—
15–30 A
—
15–50 A
15–50 A
—
—
—
15–150 A
—
15–100 A
15–30 A
—
15–50 A
15–50 A
—
—
—
—
15–50 A
15–50 A
15–100 A
—
15–50 A
15–50 A
For shown circuit breakers rated less than this maximum voltage, the indicated short circuit current
rating also applies, but at the voltage rating of the circuit breaker.
Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard.
Suffixes HID, SWD, and SWN may also be applied to the applicable branch circuit breakers shown
above. Suffix SWN may not be applied in combination with LC main breakers.
Where QO (B) circuit breakers are shown above, QO (B) H, QO (B) VH, and QH (B) circuit
breakers may also be used.
Where QO (B) GFI circuit breakers are shown above, QO (B) EPD circuit breakers may also be
used.
To acheive selective coordiantion, the rating of the DJ main circuit breaker must be at least two
times greater than the ampere rating of any branch circuit breaker.
SERIES RATINGS
Maximum
System
Voltage
AC ab
DE14
NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical)
DE14-3
DE14_p04.fm Page 4 Sunday, December 6, 2015 12:00 PM
Series Ratings
I-Line™ Panelboards
Class 2110 / Refer to Catalog 2110CT9701
This page contains UL Tested and Certified series combination ratings for
panelboards for Canada. These ratings apply to either an integral main
located in the same enclosure or a remote main located in a separate
enclosure.
I-Line Series Connected Circuit Breaker Ratings
(RMS Symmetrical) (continued)
NF Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Max.
Maximum Short
System Circuit
Voltage, Current
AC
Rating
Square D™ Brand
Integral or Remote
Main Circuit Breakers and
Remote Main Fuses
Square D™ Brand
Branch Circuit Breaker Catalog
Designation and Allowable
Ampere Ranges
EG, FH, FG, KH, LH, MH, MX, HG, JG, DG
LG
EG
EJ, FC, FJ, KC, LC, HJ, JJ
120
100,000
DJ, LJ
120/240
EJ, FC, KC, HJ, JJ
240
125,000
HL, JL
FI, KI, LI, LXI, HR, JR, LR
200,000
FI, KI, HR, JR
Class J or T (600 V) 200 A Max Fuses
EG, FG, KH, LH, HG, JG, DG, LG
35,000
EG, HG, JG
EJ, FC, FJ, KC, LC, LX, HJ, JJ, DJ
EJ, FC, KC, HJ, JJ
65,000
LJ
65,000
277
480Y/277
100,000
200,000
18,000
25,000
600Y/347 35,000
50,000
65,000
200,000
EDB, EDB-EPD
EDB
ECB-G3
EDB, EDB-EPD, EGB
EDB, EGB
ECB-G3
EDB, EDB-EPD, EGB, ECB-G3
EDB, EDB-EPD, EGB, EJB
ECB-G3
ECB-G3
EDB, EDB-EPD
ECB-G3
EDB, EDB-EPD, EGB
ECB-G3
EDB, EDB-EPD, EGB,
EGB-EPD
LL
EDB-EPD, EGB-EPD
HL, JL
EDB, EDB-EPD, EGB, EJB
DL, LL
EDB, EGB, EJB
400 A Max Fuses
EDB, EDB-EPD, EGB, EJB
FI, KI, LI, LXI, HR, JR, LR
EDB, EDB-EPD, EGB, EJB
FI, KI, HR, JR
ECB-G3
200 A Max Fuses
EDB, EDB-EPD, EGB, EJB, ECB-G3
HG, JG, MG,
EDB
LG
EDB (15–100 A)
EJ, FI, KH, KI, LC, LE, LX, LI, LXI, HJ, JJ
EDB, EGB
EDB (15–100 A),
LJ
EGB (15–100 A)
LH
(15–70 A) EDB, EGB
LC, LE, LX
EDB, EGB, EJB
HL, JL,
EDB, EGB, EJB
EDB
(15–100 A), EGB
LL
(15–100 A),EJB (15–100 A)
FI, KI, HR, JR
EDB, EGB, EJB
LI, LXI, LR
EJB
Class J or T (600 V) 200 A Max Fuses
EDB, EGB, EJB
.
DE14
SERIES RATINGS
I-Line Series Connected Circuit Breaker Ratings
(RMS Symmetrical)
Max. Short
Square D™ Brand Branch Circuit Breakers
Maximum Circuit
Integral or Remote
System Current
2- or 3-pole Main
Voltage
Rating
Designation
Poles
Circuit Breaker
AC
(RMS
Symm.)
42k
MG
FY
65k
QG, LH
FA, FD
FJ,
QJ
FD
120
1
100k
QJ, LC
FA
LJ
FH
200k
LR
FH, FY
QJ
FA, FD
208Y/120
100k
2, 3
QJ, PH, PJ, RJ
QD, QG
35k
MG
FA
1
KA
FD
1, 2, 3
42k
LA, MA
HD, JD, QD
2, 3
MG
FA
50k
MG
FA (25 A Max.)
1
HG, JG
FA, HD
JG
JD, QD
2, 3
QG
FA, FD, QD
LH, MH, PA, PG, RG
HD, JD, QD
FG, FH, MH, MX, PJ
FD
65k
FC, KC, KH, LC, LH
FD, FG
1, 2, 3
LH
FA
LH
LA
MG
HD, JD, KA
LG
HD, JD, KA, LA, LD, MA
2, 3
DG
FH, HD, JD, KA, LA, MA
85k
RL
FH, KH
240
FC, KC, LC, LX
FD, FG, FJ
1
PH, PJ, RJ
QD, QG
2, 3
QJ
FD
2
FJ
FD
FC, KC
FA, FH, FD, FG, FJ
LC, LX
FH, FD, FG, FJ
2, 3
KC, LC, LX
KA
KC, LC
KH
LC
LA, LH, MG
100k
LC
FA
1, 2, 3
HJ, JJ
FA, FH, HD, HG
JJ
JD, JG
LC, LX, MJ, PJ, RJ
HD, HG, JD, JG
MJ
LA, LH
LJ
FH, HD, HG, JD, JG, KA, LA, LD, LG, MA, MG 2, 3
DJ
FH, HD, HG, JD, JG, KA, LA, MA, MG
RL
RG
HL, JL
HD, HG, HJ, FA, H
JL
JD, JG, JJ
PC, PH, PL, RL
HD, HG, JD, JG
240
125k
PC, PL, RL
HH, JJ
2, 3
FI, KI, LI, LXI
HD, HG, HJ
KI, LI, LXI
JD, JG, JJ
a
b
Max. Short
Square D™ Brand Branch Circuit Breakers
Maximum Circuit
Integral or Remote
System Current
2- or 3-pole Main
Voltage
Rating
Designation
Poles
Circuit Breaker
AC
(RMS
Symm.)
FI, KI, LI, LXI
FD, FG, FJ
1
FI, KI
FA, FH, FC, FD, FG, FJ
LI, LXI
FH, FD, FG, FJ
240
200k
LI
FC
2, 3
KI, LI, LXI
KA, QD, QG, QJ
LI
KC
LR
FH, HJ, HL, JJ, JL, LA, LH, QD, QG, QJ
18k
LD
FY
25k
FH, KA
FD
FG, KH, LH
FD
35k
DG
FH, FY
LG
FH, FY
FJ
FD
FC, KC
FA, FH, FY, FD, FG
LC, LX (400 A Max.)
FH
LC, LX (600 A Max.)
FY, FD, FG
65k
LJ
FH, FY
277
1
DJ
FH, FY
LL
FY
DL
FH, FJ
100k
LL
FH, FJ
FI, KI
FA, FH, FY, FD, FG, FJ
HR
FA, FJ, FY
JR
FA, FJ, FY
200k
LI, LXI (400 A Max.)
FH
LI, LXI (600 A Max.)
FY, FD, FG, FJ
LR
FH, FY
22k
MG
FA
KH, LA, MA, MX, PA,
FH
PC, PX, PJ
LA, MA, PA, PC, PX
KA
30k
LA, MA, PA
HD, JD
MG
FA (25 A Max.), FH, KA
MH, MX, PA
HD, JD
HG, JG
FA, HD
JG
JD
35k
LH, MG, PG, RG
HD, JD
LG
FH, HD, JD, KA, LA, LD, MA
DG
FH, HD, JD, KA, LA, MA
MJ
FH (25 A Max.)
42k
RL
RG
50k
MJ
KA, KH
FC, KC
FA, FH
HJ, JJ
FA, FH, HD, HG
JJ
JD, JG
LC, LI, LX, LXI
HD, HG, JD, JG
LC, LX (400 A Max.)
FH
65k
480
KC, LC, LX
KA
LC, LX
LA
LJ
FH, HD, HG, JD, JG, KA, LA, LD, LG, MA
2, 3
DJ
FH, HD, HG, JD, JG, KA, LA, MA
HL, JL
FA, FH, HD, HG, HJ
JL
JD, JG, JJ
JR
FA
LI, LXI (600 A Max.)
KA
100k
FH,
HD,
HG,
HJ,
JD,
JG, JJ, KA, LA, LD, LG,
LL
LJ, MA
200k
25k
35k
480Y/277
65k
200k
18k
25k
35k
600
50k
65k
100k
600Y/347
18k
25k
50k
DL
PC, PH, PL, RL
RL
FI, KI
HR
JR
KI
LI
LR
LXI
FH, KA
FG, KH, LH
FJ
FC, KC
LC, LX (600 A Max.)
FI, KI
LI, LXI (600 A Max.)
HG, JG
JG
LG
MG, PG, RG
MG
HJ, JJ
JJ
LJ
PJ, RJ
LC
HL, JL
JL
LL
PK
LR
FI, KI
HR
JR
KI
KI, LI
LI
LR
MG
MJ
HL, JL
FH, HD, HG, HJ, JD, JG, JJ, KA, LA, MA
HJ, JJ
RG
FA, FH, FC, HD, HG, HJ
FA, HD, HG, HJ, HL
HD, HG, HJ, HL, JD, JG, JJ, JL
JD, JG, JJ, KA
FC, KA, KC, LA, HJ, HL, JJ, JL
FH, HJ, HL, JJ, JL, LA, LH
KA, HJ, HL, JJ, JL
FD
FD
FD
FD, FG
FD, FG
FD, FG, FJ
FD, FG, FJ
FA, HD
JD
HD, JD, LD
HD, JD
FA
FA, HD, HG
JD
HD, HG, JD, JG, LD, LG, MA
MG
FH, HD, HG, HJ, JD, JG, JJ, LA
FA (30 MAX), HD, HG, HJ
JD, JG, JJ
HD, HG, HJ, JD, JG, JJ, LD, LG, LJ, MA
HJ, JJ, MJ
HJ, JJ
HD, HG, HJ
FA, HD, HG, HJ, HL
FA, HD, HG, HJ, HL, JD, JG, JJ, JL
JD, JG, JJ
FH
LA
HL, JL
FA (25 A max.)
FA (30 A max.)
FJ
2, 3
1
NOTE: LD, LG, LH, and LL breakers are only available in 3 pole configurations.
Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard.
Obsolete. Contact your local Schneider Electric representative or distributor for the replacement circuit breaker.
DE14-4
11/15
DE14_p05.fm Page 5 Sunday, November 15, 2015 8:33 AM
Series Ratings
I-Line™ Panelboards
Class 2110
Fuse/I-Line Circuit Breaker Series Connected Ratings
120/240 1Ø 208Y/120
100,000
240
65,000
Remote Main Fuse
Maximum
Amperage
1200 A
800 A
600 A
1200 A
800 A
600 A
1200 A
800 A
600 A
240
100,000
800 A
1200 A
1600/2000 A
4000 A
600 A
240
200,000
800 A
1200 A
1600/2000 A
4000 A
400 A
600 A
480
100,000
800 A
1200 A
1600 A
2000 A
4000 A
200 A
400 A
600 A
480
200,000
800 A
a
600
100,000
600
200,000
1200 A
1600/2000 A
30 A
200 A
400 A
600 A
1200 A
600 A
800 A
Square D™ Brand Branch Circuit Breakers
Fuse Class
Designation a
L, T (300 V)
T (600 V)
J, RK5
L, T (300 V)
T (600 V)
J, RK5
L, T (300 V)
T (600 V)
J, RK5
L, T (600 V)
RK5
J
T (600 V)
T (300 V)
L
L
T (600 V)
L
L
J, T (600 V)
RK5
J
T (600 V)
T (300 V)
L
L
T (600 V)
L
L
J, T (600 V)
J, RK5
J, T (600 V)
RK5
L, T (600 V)
L
T (600 V)
L
L
L
RK5
J
T(600V)
J
T (600V)
RK5
T (300 V)
T (600 V)
L
L
L
CC
J
J, T (600 V)
R
L
J
T (600 V)
QD, QG
QD, QG
QD, QG
QD
QD
QD
QD, QG (2-pole)
QD, QG (2-pole)
QD, QG (2-pole)
FA, FH, KA, KH, KC, LA, LH, MA, MH, MX, PG
FH, KA, KH, LA, LH, MA, MH, MX, PG, HD, HG, HJ, HL, JD, JG, JJ, JL
HD, HG, HJ, HL, JD, JG, JJ, JL
FH, KA, KH, LA, LH, MA, MH, MX, PG
PG
FH,KA,KH,LA,LH,MA,MH,MX,PG
FH, KH, LA, LH, MA, MH, MX, PG
HD, HG, HJ, HL, JD, JG, JJ, JL
KH, MA, MH, MX, PG
HD, HG, HJ, HL, JD, JG, JJ, JL
FA( 3-pole only), FH, FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL
FH, FC, HD, HG, HJ, HL, JD, JG, JJ, JL KH, KC, LA, LH, LC, MA, MH, MX, NC, NX, PG, PJ, PL
HD, HG, HJ, HL, JD, JG, JJ, JL
FH, FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL
PG, PJ, PL
FH,FC, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL
FC, KH, KC, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL
HD, HG, HJ, HL, JD, JG, JJ, JL
NA, NC, NX, PJ, PL
HD, HG, HJ, HL, JD, JG, JJ, JL
HD, HG, HJ, HL, JD, JG, JJ, JL
HJ, HL, JJ, JL
FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ
FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ
FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ
FC, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ
HJ, HL, JJ, JL
KC, LC, MA, MH, MX, NA, PG, PJ
KC, LC, MH,MG, MJ, MX, NA, PG, PJ
HJ, HL, JJ, JL
HJ, HL
FA, FH, FC, HJ, HL, JJ, JL, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL
FA, FH, FC, HJ, HL, JJ, JL, KA, KH, KC, LA, LH, MA, MH, MX, NA, NC, NX
FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL
KA, KH, KC, LA, LH, MA, MH, MX, NA, NC, NX
KC, LA, LH, LC, MA, MH, MX, MG, MJ, NC, NX, PG, PJ,
PG, PJ, PL
KA, KH, KC, LA, LH, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL
KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL
KC, LC, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL
NA, NC, NX
HG, JG ( molded case switches )
HD, HG, HJ, HL, JD, JG, JJ, JL
HJ, HL, JJ, JL
MG, MJ
MG, MJ
MG, MJ
MG, MJ
Series rating valid for 2-pole or 3-pole circuit breakers.
Note:
•
•
•
•
The fuse used in this CSA/UL test is an envelope (umbrella) fuse. This fuse is designed as a “worst case’’ fuse. Thus, no matter what manufacturer’s fuse is used, the Square D™ brand circuit
breaker is protected.
The line side fused switch may be in a separate enclosure or in the same enclosure as the loadside circuit breaker. A line side fused switch may be a submain, integral main, or remote main. A
load side circuit breaker may be a branch, submain, or an integral main used on the load side of a remote main. This series combination short circuit current rating shall not exceed that of the
line side fused switch. The charts apply to Square D™ brand load side circuit breakers only. However, the line side fuse ratings are independent of the fuse manufacturer.
Not applicable to Corner Grounded Systems.
Limiters used in Square D™ brand DSL and DSL II fused power circuit breakers are not class L fuses and do not have series ratings.
11/15
DE14-5
SERIES RATINGS
Max. Short Circuit
Current Rating
(RMS Symm.)
DE14
Maximum System
Voltage AC
DE14_p06.fm Page 6 Sunday, November 15, 2015 8:34 AM
Series Ratings
Canadian Homeline Loadcentres
Single Row - Short Circuit Current Rating
Tenant Square D™ Circuit Breaker
(Remote only)
Interrupting
Rating RMS
Symmetrical
Amperes at 240 V
Line Side Fuse
or Square D™ Circuit Breaker
(Remote only)
Poles
10,000
22,000
25,000
42,000
42,000
65,000
100,000
42,000
—
QO(B)-VH (125)
QD (225)
QOH(B)
LA, MA
LH, MG, PG
Class R, J, T6, T3, L (1200)
LA, MA
QG (225)
LH, MG, PG, RG (2000)
QJ (225)
MJ, PJ, RJ (2000), Class R, J, T6, T3, L (1200)
—
2
2
2
2,3
2,3
2,3
2,3
2
2,3
2
2,3
65,000
100,000
Catalog
Designation
Poles
—
—
—
—
QO(B)-VH
QO(B)-VH
QOH(B)
QD
—
—
—
—
QD
QD, QG
Schneider Electric Branch Circuit Breaker
Current
Rating
Amperes
Max.
Catalog
Designation
—
2
125
2
225
2
225
2
Current Rating Amperes
Max.
1 Pole
2 Pole
CHOM ¥
50
125 ¶
CHOMT
30
50
CHOM ¥
50
100 ¶
CHOMT
30
50
CHOM ¥
50
125 ¶
CHOMT
30
50
225
¶ Loadcentres with 100 A mains rating are limited to 100 A maximum integral main circuit breaker and 70 A maximum branch circuit.
¥ Catalog designation CHOM includes suffixes AFI, EPD and GFI Circuit Breakers.
The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s)
MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See loadcentre wiring diagram for circuit breaker types.
Double Row, Indoor Devices - Short Circuit Current Rating
Interrupting
Rating RMS
Symmetrical
Amperes at
Vac Max
Line Side Fuse
or Square D™
Circuit Breaker
(Integral or Remote)
Fuse
Class
Catalog
Designation
•
42,000 at 240
—
LA, MA
65,000 at 240
—
LH, MG, PG
Sub Service Square D™
Circuit Breaker
(Integral or Remote)
Line Side Fuse
or Square D™
Circuit Breaker
(Integral or Remote)
Schneider Electric
Branch Circuit Breaker
Catalog
Current
Catalog
Rating Designation
Poles Designation Poles Amperes
•
Max.
•
Current
Rating
Amperes
Max.
Interrupting
Rating RMS
Symmetrical
Amperes at
Vac Max
Fuse
Class
Catalog
Designation
•
1
2
Pole Pole
QO(B)-VH
42,000 at 240
—
LA, MA
65,000 at 240
—
LH, MG, PG,
RG (2000)
Sub Service Square D™
Circuit Breaker
(Integral or Remote)
Schneider Electric
Branch Circuit Breaker
Current
Rating
Catalog
Current
Catalog
Amperes
Rating Designation
Poles Designation Poles Amperes
Max.
•
Max.
•
1
2
Pole Pole
QD
CHOM (§)
R, J,
100,000 at 240 T3, T6,
L (1200
2,3
2
50
100
125
QO(B)-VH
QOH(B)
CHOMT
—
30
50
R, J,
100,000 at 240 T3, T6,
L (1200
2,3
MJ, PJ,
RJ (2000)
2
225
CHOM (§)
50
200
CHOMT
30
50
QD, QG
(§) Catalog designation CHOM includes suffixes AFI, BB, EPD and GFI circuit breakers.
DE14
SERIES RATINGS
Outdoor Devices - Short Circuit Current Rating
Interrupting
Rating RMS
Symmetrical
Amperes at 240 V Max.
Line Side Square D™ Circuit Breaker
Catalog Designation or Fuse Class
42,000
65,000
100,000
42,000
65,000
100,000
LA, MA
LH, MG, PG
Class R, J, T3, T6, L(1200)
LA, MA
LH, MG, PG, RG (2000)
MJ, PJ, RJ, (2000), Class R, J, T6, T3, L(1200)
Tenant Square D™ Circuit
Breaker
(Remote only)
Poles
(Max. A rating)
•
2, 3
2, 3
Catalog
Designation
(Ampere Max.)
•
QO(B)-VH (125)
QO(B)-VH (125)
QOH(B)
QD (225)
QD, QG (225)
Schneider Electric Branch Circuit Breaker
Current Rating
Amperes Max.
Poles
Catalog
Designation
•
1 Pole
2 Pole
2
CHOM (§)
CHOMT
50
30
100
50
2
CHOM (§)
CHOMT
50
30
200
50
• See circuit breaker for voltage and interrupting rating. See loadcentre marking for acceptable circuit breakers.
(§) CHOM includes suffixes AFI, BB, EPD and GFI.
The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement branch or main
circuit breaker, or service disconnect MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See loadcentre
interior for circuit breaker types.
DE14-6
11/15
DE14_p07.fm Page 7 Sunday, November 15, 2015 8:34 AM
Series Ratings
Canadian QO Loadcentres
Table 14.1
Interrupting
Rating RMS
Symmetrical
Amperes at
Vac Max.
Line Side Fuse or Square D™ Circuit Breaker
(Integral or Remote)
Fuse Class
Catalog
Designation
•
Poles
Current Rating
Amperes Max.
Sub Service Square D™ Circuit Breaker
(Integral or Remote)
Catalog
Designation
•
Poles
Catalog
Designation
•
Poles
QO...H
2
QO...VH
QOH
QH
QO
QOT
QO
QOT
QO
QO
1,2,3
2
1,2,3
1,2,3
1
1,2
1
1,2,3
1,2
100
QO
1,2,3
125
QO
QOT
1,2
1
Current Rating
Amperes Max.
f5,000 at 240
10,000 at 240
22,,000 at 240
42,000 at 240
65,000 at 240
10,000 at 240
QOM...VH
QO(B)...VH
QO...VH
22,000 at 240
22,000 at 240
42,000 at 240
42,000 at 240
65,000 at 240
65,000 at 240
R
R
J, T6
T3
R
T3, T6, J
2
2
3
2
3
3
3
2
2
225
200
100
100
100
400
400
200
600
QO...VH
QO(B)...VH
3
2
Square D™ Branch Circuit Breaker
Current Rating
Amperes Max.
1 Pole
2 pole
3 Pole
15-100
15-30
15-30
10-70
15-30
10-70
15-30
10-70
10-70
15-200
40-125
15-30
10-200
10-100
15-30
10-100
10-200
10-100
10-100
10-100
10-70
10-100
10-100
10-70
15-30
10-125
Table 14.2
Line Side Fuse or Square D™ Circuit Breaker
(Integral or Remote)
Catalog
Designation
•
Poles
Current Rating
Amperes Max.
25,000 at 240
65,000 at 240
QD
QG
2,3
2,3
225
225
100,000 at 240,
2 pole and
208Y/120, 3 Pole
QJ
2,3
225
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
200
400
1,000
400
800
1,000
1,200
1,600
2,000
800
1,200
1,600
2,000
600
800
1,200
100,000 at 240
Fuse Class
J, T3, T6
LA
MA
LH
MG
MH
PG
PA
RG
MJ
PJ
PH
RJ
42,000 at 240
65,000 at 240
65,000 at 240,
9 pole or
100,000 at 240,
2 pole and
208Y/120, 3 pole
R, J
T6
T3, L
Sub Service Square D™ Circuit Breaker
(Integral or Remote)
Catalog
Designation
•
QD
Poles
2,3
Current Rating
Amperes Max.
225
Square D™ Branch Circuit Breaker
Catalog
Designation
•
QO
QO...VH
QO...H
240 V 1 Ø
QO...GFI
QO...EPD
QO...PL
QO...AS
QO...AFI
QOT
Current Rating
Amperes Max.
Poles
1,2,3
3
1 Pole
2 pole
3 Pole
15-70
15-200
15-30
35-100
2
1,2
1,2
1,2,3
1,2,3
1
1
15-100
15-30
15-30
15-30
15-30
15-20
15-30
15-60
15-60
15-60
15-30
15-30
15-30
240 Vac 3 Phase 4 Wire Delta: When wired for Delta system, phase “B” must be 208 V to neutral, Circuit breaker poles connected to phase “B” must be rated 240 V. Single pole circuit breakers must
not be connected to phase “B”.
The Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement branch or main circuit breaker, or
service disconnect MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit
breaker types.
DE14
f 240 Vac, 3 phase 3 wire Grounded “B” phase.
• See circuit breaker for voltage and interrupting rating.
SERIES RATINGS
Interrupting
Rating RMS
Symmetrical
Amperes at
Vac Max.