DE14_P01.FM Page 1 Monday, November 23, 2015 10:00 PM Series Ratings Selection Guide Contents Description Page Series Ratings NQ Series Connected Circuit Breaker Ratings 2 • NF Series Connected Circuit Breaker Ratings 4 • I-Line Series Connected Circuit Breaker Ratings 4 • Fuse/I-Line Circuit Breaker Series Connected Ratings 5 • Homeline Loadcentre Single Row - Short Circuit Current Rating 6 • Homeline Loadcentre Double Row, Indoor Devices - Short Circuit Current Rating 6 • Homeline Loadcentre Outdoor Devices- Short Circuit Current Rating 6 • Canadian QO Loadcentres - Short Circuit Current Rating 7 DE14 SERIES RATINGS • Note: For additional information on Panelboard / Switchboard Short-Circuit Current Ratings please refer to Data Bulletin 2700DB9901. 11/15 DE14-1 DE14_p02.fm Page 2 Monday, November 23, 2015 10:46 PM Series Ratings NQ Panelboards Class 1640 This page contains UL Tested and Certified series combination ratings for panelboards for Canada. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure. NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical) Maximum System Voltage AC ab NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical) Maximum System Voltage AC ab Maximum Square D™ Brand Integral Short or Remote Main Circuit Circuit Breakers and Remote Current Main Fuses Rating 22,000 MG 25,000 LD, HD, JD HG, JG 65,000 LG LJ HJ, JJ 120/240 1P/3W LJ 100,000 DJ 400 A 125,000 HL, JL 18,000 LA/LH (L) 34200MC LA/LH (L) 34225MC LA/LH (L) 34250MC LA/LH (L) 34400MC DE14 SERIES RATINGS QJ 25,000 LD 208Y/120 3P/4W 240/120 V 3P/4W DJ–W 150 A MC 30,000 DJ–W 250 A MC DJ–W 600 A MC Square D™ Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges cdef Type 1 Pole 2 Pole 3 Pole QO (B) QO (B) QO (B) VH QO (B) PL QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) PL QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) GFI QO (B) EPD QO (B) QO (B) VH QO (B) PL QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO(B) VH QO (B) H QO (B) GFI QO (B) EPD QO(B) AFI QO(B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) PL QO (B) GFI QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) PL QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF 15–30 A 15–70 A 15–70 A 15–30 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–70 A 15–30 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–70 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–30 A 15–30 A 15–70 A 15–70 A 15–30 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–70 A — — — 15–20 A 15–20 A 15–20 A 15–70 A — 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A — 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–70 A 15–30 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A — 15–125 A 15–125 A 15–60 A 15–60 A 15–60 A — 15–20 A — 15–125 A 15–125 A 15–60 A 15–60 A 15–60 A — 15–20 A — 15–125 A 15–125 A 15–60 A 15–60 A — 15–20 A — 40–60 A 40–60 A 15–125 A 15–125 A 15–60 A 15–60 A 15–60 A — 15–20 A — 15–125 A 15–125 A 15–100 A 15–30 A 15–60 A — 15–20 A — 15–125 A 150 A 15–60 A 15–60 A — 15–20 A — 15–125 A 150 A 15–60 A 15–60 A — 15–20 A — 15–125 A 15–125 A 15–60 A 15–60 A 15–60 A — 15–20 A — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — QO (B) 15–30 A 15–30 A 15–30 A QO (B) QO (B) VH QO (B) GFI QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) GFI QO (B) AFI QO (B) QO (B) VH QO (B) GFI QO (B) AFI QO (B) QO (B) VH QO (B) GFI QO (B) AFI 15–70 A 15–30 A 15–30 A 15–30 A — 15–20 A 15–20 A 15–20 A 15–70 A — 15–30 A 15–20 A 15–70 A — 15–30 A 15–20 A 15–70 A — 15–30 A 15–20 A 15–125 A 15–125 A 15–60 A 15–60 A — — — — 15–100 A 15–125 A 15–60 A — 15–100 A — 15–60 A — 15–100 A — 15–60 A — — 15–150 A 15–30 A 15–30 A 15–30 A — — — — 15–150 A — — — 15–100 A — — — 15–150 A — — LG 65,000 LJ LL 208Y/120 3P/4W 240/120 V 3P/4W DJ 400 A 100,000 QJ LJ 240/120 V 3P/4W 22,000 QO (B) VH QD ED, FD KD 240/120 V 3P/4W 25,000 HD, JD LD a b c d e f g h DE14-2 Maximum Square D™ Brand Integral Short or Remote Main Circuit Circuit Breakers and Remote Current Main Fuses Rating Square D™ Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges cdef Type 1 Pole 2 Pole 3 Pole QO (B) QO (B) VH QO (B) H QO (B) GFI QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) H QO (B) GFI QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QO (B) DF QO (B) GFI QO (B) EPD QO (B) EPE QO (B) QO (B) VH QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) PL QO (B) GFI QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) H QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) GFI QO (B) EPD QO (B) EPE QO (B) PL QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) PL QO (B) GFI QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) GFI QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) AS QO (B) GFI QO (B) AFI QO (B) QO (B) VH QO (B) H QO (B) GFI QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) H QO (B) GFI QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QO (B) DF 15–70 A 15–70 A — 15–30 A 15–30 A — 15–20 A 15–20 A 15–20 A 15–70 A 15–70 A — 15–30 A 15–30 A — 15–20 A 15–20 A 15–20 A — — — 15–70 A — 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A — 15–30 A 15–30 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–70 A — — — 15–20 A 15–20 A 15–20 A 15–70 A 15–30 A 15–30 A — 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A — 15–30 A 15–30 A 15–30 A — 15–20 A 15–20 A 15–20 A 15–70 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–30 A 15–30 A 15–20 A 15–70 A — — 15–30 A 15–30 A — 15–20 A 15–20 A 15–20 A 15–70 A 15–30 A — 15–30 A 15–30 A — 15–20 A 15–20 A 15–20 A 15–125 A 15–125 A 15–100 A 15–60 A 15–60 A — — — — 15–125 A 15–125 A 15–100 A 15–60 A 15–60 A — — — — — — — 15–125 A — 15–60 A 15–60 A — — — 15–125 A — 15–60 A 15–60 A 15–60 A 15–60 A — — — 15–125 A 15–125 A 15–100 A 15–30 A 15–60 A — — — 15–125 A 15–60 A 15–60 A — 15–60 A — — — 15–125 A — 15–60 A 15–60 A 15–60 A — — — — 15–125 A 15–60 A — — — 15–125 A 15–30 A 15–60 A — 15–125 A — 15–100 A 15–60 A 15–60 A — — — — 15–125 A 15–125 A 15–100 A 15–60 A 15–60 A — — — — — 15–150 A — 15–30 A 15–30 A 15–30 A — — — — 15–150 A — 15–30 A 15–30 A 15–30 A — — — 15–30 A 15–30 A 15–30 A — 15–150 A — — — — — 15–30 A 15–150 A 15–30 A 15–50 A 15–50 A 15–50 A — — — — 15–150 A — — — — — — 15–100 A 15–50 A 15–50 A 15–50 A — — — — 15–30 A 35–150 A 15–30 A 15–50 A 15–50 A 15–50 A — — — 15–100 A 15–50 A — — — 15–100 A 15–30 A — — 15–100 A 35–150 A — 15–50 A 15–50 A 15–50 A — — — — 15–150 A — 15–30 A 15–30 A 15–30 A — — — For shown circuit breakers rated less than this maximum voltage, the indicated short circuit current rating also applies, but at the voltage rating of the circuit breaker Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard. Suffixes HID, and SWD may also be applied to the applicable branch circuit breakers shown above. Suffix SWN may not be applied in combination with LC main breakers. Where QO (B) circuit breakers are shown above, QO (B) H, QO (B) VH, and QOH (B) circuit breakers may also be used. Where QO (B) GFI circuit breakers are shown above, QO (B) EPD and/or QO (B) EPE circuit breakers may also be used. QO–EPE only comes in 3 pole construction. Where QO (B) AFI circuit breakers are shown above, QO (B) CAFI circuit breakers may also be used. To achieve selective coordination, the rating of the DJ main circuit breaker must be at least two times greater than the ampere rating of any branch circuit breaker. For complete series ratings for Delta Systems please reference NQ/NQM Panelboards Information Manual 80043–712–06. 11/15 DE14_p03.fm Page 3 Monday, November 23, 2015 10:46 PM Series Ratings NQ Panelboards Class 1640 NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical) Maximum Square D™ Brand Integral Short or Remote Main Circuit Circuit Breakers and Remote Current Main Fuses Rating LA, MA LC400A 42,000 LC600A MG LC400A LC600A DJ400A DJ_W DJ, DG, DL 150–600 A EG, FG, KG 65,000 QG 240/120 V 3P/4W HG, JG FC_ or KC_22___ FC_ or KC_34___ LG LJ LL FC_ or KC_22___ FC_ or KC_34___ DJ400A EJ 100,000 LJ HJ, JJ 11/15 Square D™ Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges cdef Type 1 Pole 2 Pole 3 Pole Q2L–H QDL QO (B) QO (B) VH QO (B) GFI QO (B) AFI QO (B) CAFI QO (B) DF QO (B) VH QO (B) GFI QO (B) AFI QO (B) CAFI QO (B) DF QO (B) VH QO (B) QO (B) VH QO (B) GFI QO (B) AFI QO (B) CAFI QO (B) DF QO (B) VH QO (B) GFI QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) H QO (B) QO (B) VH QO (B) GFI QO (B) AFI QO (B) CAFI QO (B) DF QO (B) EPD QO (B) QO (B) GFI QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) GFI QO (B) PL QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) VH QO (B) H QO (B) GFI QO (B) EPD QO (B) EPE QO (B) PL QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) AS QO (B) QO (B) VH QO (B) H QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) GFI QO (B) EPD QO (B) EPE QO (B) EPD QO (B) EPE QO (B) GFI QO (B) AFI QO (B) QO (B) H QO (B) VH QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) QO (B) VH QO (B) H QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) H QO (B) VH QO (B) PL QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF — — 15–70 A 15–70 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–30 A 15–20 A 15–20 A 15–20 A 15–30 A 15–30 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–30 A — 15–20 A 15–20 A 15–20 A 15–70 A — — 15–70 A — 15–30 A 15–20 A 15–20 A 15–20 A — 15–70 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A — 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A — — 15–30 A 15–30 A — 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–30 A 15–70 A 15–70 A — 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–30 A 15–30 A — — — 15–30 A 15–20 A 15–70 A — — 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–70 A 15–70 A — — — 15–20 A 15–20 A 15–20 A 15–70 A — — 15–30 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 100–225 A 70–225 A 15–70 A 15–125A 15–60 A — — — 15–125 A 15–60 A — — — 15–30 A 15–30 A 15–125 A 15–60 A — — — 15–125 A — — — — 15–125 A — 15–100 A 15–150 A 110–125 A 15–60 A — — — — 15–125 A 15–60 A — — — 15–125 A — 15–60 A 15–60 A — — — 15–125 A — 15–100 A 15–60 A 15–60 A — 15–60 A — — — 15–100 A 15–30 A 15–125 A 15–125 A 15–100 A 15–60 A 15–60 A — — — 15–125 A 40–60 A 40–60 A — — — 15–30 A — 15–125 A 15–100 A — 15–60 A 15–60 A — — — 15–125 A 15–125 A 15–125 A 15–100 A 15–30 A 15–60 A — — — 15–125 A 15–100 A — 15–60 A 15–60 A 15–60 A — — — 100–225 A 70–225 A — 15–100 A 15–30 A — — — 15–100 A 15–30 A — — — 15–30 A — 15–100 A — — — — 15–150 A 15–30 A — — — — 15–150 A — — 15–150 A — — — — 15–30 A 15–100 A — — — — 15–30 A 35–150 A 15–50 A 15–30 A — — — 15–100 A 35–150 A — 15–50 A 15–50 A 15–50 A 15–30 A — — — 15–100 A 15–30 A — 15–150 A — 15–30 A 15–30 A — — — — — 15–30 A 15–30 A 15–30 A 15–30 A — — — — 15–150 A — — — — — 15–100 A — 15–150 A — — — — — — 15–100 A — 35–150 A 15–30 A 15–50 A 15–50 A — — — Maximum System Voltage AC ab Maximum Square D™ Brand Integral Short or Remote Main Circuit Circuit Breakers and Remote Current Main Fuses Rating 125,000 HL, JL 200,000 FI, KI, HR, JR 240/120 V 3P/4 200 A Max. Class T6, J Fuses 208Y/120 3P/4W 200,000 400 A Max. Class T3 Fuses 42,000 50,000 400 A Max. Class T3 Fuses 400 A Max. Class T3 Fuses 400 A Max. Class J Fuses 65,000 400 A Max. Class T6 Fuses 240/120 V 3P/4W 100,000 200 A Max. Class T3 Fuses 200 A Max. Class J or T6 Fuses 200,000 400 A Max. Class T3 Fuses a b c d e f Square D™ Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges cdef Type 1 Pole 2 Pole 3 Pole QO (B) QO (B) H QO (B) VH QO (B) PL QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) GFI QO (B) EPD QO (B) AFI QO (B) CAFI QO (B) DF QO (B) QO (B) GFI QO (B) EPD QO (B) QO (B) GFI QO (B) EPE QO (B) EPD 15–70 A — — 15–30 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A 15–30 A 15–30 A 15–20 A 15–20 A 15–20 A 15–70 A — — 15–70 A 15–30 A — 15–30 A 15–125 A 15–100 A — 15–60 A 15–60 A 15–60 A — — — 15–125 A 15–60 A 15–60 A — — — 15–125 A — — 15–125 A 15–60 A — 15–60 A 15–100 A — 35–150 A 15–30 A 15–50 A 15–50 A — — — 15–100 A — — — — — — 15–50 A 15–50 A 15–100 A 15–50 A 15–50 A 15–50 A QO (B) VH 15–30 A 15–125 A — QO (B) VH QO (B) VH QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QO (B) DF QO (B) VH QO (B) AFI QO (B) QO (B) VH QO (B) GFI QO (B) EPD QO (B) EPE QO (B) AFI QO (B) CAFI QOT QO (B) DF QO (B) EPD QO (B) EPE QO (B) QO (B) GFI QO (B) EPD QO (B) EPE — 15–70 A — — 15–20 A 15–20 A 15–20 A 15–70 A 15–20 A 15–70 A — 15–30 A 15–30 A — 15–20 A 15–20 A 15–30 A 15–20 A — — 15–70 A 15–30 A 15–30 A — — 15–125 A — — — — — 15–125 A — 15–125 A — 15–60 A 15–60 A — — — 15–30 A — — — 15–125 A 15–60 A 15–60 A — 15–30 A — 15–50 A 15–50 A — — — 15–150 A — 15–100 A 15–30 A — 15–50 A 15–50 A — — — — 15–50 A 15–50 A 15–100 A — 15–50 A 15–50 A For shown circuit breakers rated less than this maximum voltage, the indicated short circuit current rating also applies, but at the voltage rating of the circuit breaker. Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard. Suffixes HID, SWD, and SWN may also be applied to the applicable branch circuit breakers shown above. Suffix SWN may not be applied in combination with LC main breakers. Where QO (B) circuit breakers are shown above, QO (B) H, QO (B) VH, and QH (B) circuit breakers may also be used. Where QO (B) GFI circuit breakers are shown above, QO (B) EPD circuit breakers may also be used. To acheive selective coordiantion, the rating of the DJ main circuit breaker must be at least two times greater than the ampere rating of any branch circuit breaker. SERIES RATINGS Maximum System Voltage AC ab DE14 NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical) DE14-3 DE14_p04.fm Page 4 Sunday, December 6, 2015 12:00 PM Series Ratings I-Line™ Panelboards Class 2110 / Refer to Catalog 2110CT9701 This page contains UL Tested and Certified series combination ratings for panelboards for Canada. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure. I-Line Series Connected Circuit Breaker Ratings (RMS Symmetrical) (continued) NF Series Connected Circuit Breaker Ratings (RMS Symmetrical) Max. Maximum Short System Circuit Voltage, Current AC Rating Square D™ Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses Square D™ Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges EG, FH, FG, KH, LH, MH, MX, HG, JG, DG LG EG EJ, FC, FJ, KC, LC, HJ, JJ 120 100,000 DJ, LJ 120/240 EJ, FC, KC, HJ, JJ 240 125,000 HL, JL FI, KI, LI, LXI, HR, JR, LR 200,000 FI, KI, HR, JR Class J or T (600 V) 200 A Max Fuses EG, FG, KH, LH, HG, JG, DG, LG 35,000 EG, HG, JG EJ, FC, FJ, KC, LC, LX, HJ, JJ, DJ EJ, FC, KC, HJ, JJ 65,000 LJ 65,000 277 480Y/277 100,000 200,000 18,000 25,000 600Y/347 35,000 50,000 65,000 200,000 EDB, EDB-EPD EDB ECB-G3 EDB, EDB-EPD, EGB EDB, EGB ECB-G3 EDB, EDB-EPD, EGB, ECB-G3 EDB, EDB-EPD, EGB, EJB ECB-G3 ECB-G3 EDB, EDB-EPD ECB-G3 EDB, EDB-EPD, EGB ECB-G3 EDB, EDB-EPD, EGB, EGB-EPD LL EDB-EPD, EGB-EPD HL, JL EDB, EDB-EPD, EGB, EJB DL, LL EDB, EGB, EJB 400 A Max Fuses EDB, EDB-EPD, EGB, EJB FI, KI, LI, LXI, HR, JR, LR EDB, EDB-EPD, EGB, EJB FI, KI, HR, JR ECB-G3 200 A Max Fuses EDB, EDB-EPD, EGB, EJB, ECB-G3 HG, JG, MG, EDB LG EDB (15–100 A) EJ, FI, KH, KI, LC, LE, LX, LI, LXI, HJ, JJ EDB, EGB EDB (15–100 A), LJ EGB (15–100 A) LH (15–70 A) EDB, EGB LC, LE, LX EDB, EGB, EJB HL, JL, EDB, EGB, EJB EDB (15–100 A), EGB LL (15–100 A),EJB (15–100 A) FI, KI, HR, JR EDB, EGB, EJB LI, LXI, LR EJB Class J or T (600 V) 200 A Max Fuses EDB, EGB, EJB . DE14 SERIES RATINGS I-Line Series Connected Circuit Breaker Ratings (RMS Symmetrical) Max. Short Square D™ Brand Branch Circuit Breakers Maximum Circuit Integral or Remote System Current 2- or 3-pole Main Voltage Rating Designation Poles Circuit Breaker AC (RMS Symm.) 42k MG FY 65k QG, LH FA, FD FJ, QJ FD 120 1 100k QJ, LC FA LJ FH 200k LR FH, FY QJ FA, FD 208Y/120 100k 2, 3 QJ, PH, PJ, RJ QD, QG 35k MG FA 1 KA FD 1, 2, 3 42k LA, MA HD, JD, QD 2, 3 MG FA 50k MG FA (25 A Max.) 1 HG, JG FA, HD JG JD, QD 2, 3 QG FA, FD, QD LH, MH, PA, PG, RG HD, JD, QD FG, FH, MH, MX, PJ FD 65k FC, KC, KH, LC, LH FD, FG 1, 2, 3 LH FA LH LA MG HD, JD, KA LG HD, JD, KA, LA, LD, MA 2, 3 DG FH, HD, JD, KA, LA, MA 85k RL FH, KH 240 FC, KC, LC, LX FD, FG, FJ 1 PH, PJ, RJ QD, QG 2, 3 QJ FD 2 FJ FD FC, KC FA, FH, FD, FG, FJ LC, LX FH, FD, FG, FJ 2, 3 KC, LC, LX KA KC, LC KH LC LA, LH, MG 100k LC FA 1, 2, 3 HJ, JJ FA, FH, HD, HG JJ JD, JG LC, LX, MJ, PJ, RJ HD, HG, JD, JG MJ LA, LH LJ FH, HD, HG, JD, JG, KA, LA, LD, LG, MA, MG 2, 3 DJ FH, HD, HG, JD, JG, KA, LA, MA, MG RL RG HL, JL HD, HG, HJ, FA, H JL JD, JG, JJ PC, PH, PL, RL HD, HG, JD, JG 240 125k PC, PL, RL HH, JJ 2, 3 FI, KI, LI, LXI HD, HG, HJ KI, LI, LXI JD, JG, JJ a b Max. Short Square D™ Brand Branch Circuit Breakers Maximum Circuit Integral or Remote System Current 2- or 3-pole Main Voltage Rating Designation Poles Circuit Breaker AC (RMS Symm.) FI, KI, LI, LXI FD, FG, FJ 1 FI, KI FA, FH, FC, FD, FG, FJ LI, LXI FH, FD, FG, FJ 240 200k LI FC 2, 3 KI, LI, LXI KA, QD, QG, QJ LI KC LR FH, HJ, HL, JJ, JL, LA, LH, QD, QG, QJ 18k LD FY 25k FH, KA FD FG, KH, LH FD 35k DG FH, FY LG FH, FY FJ FD FC, KC FA, FH, FY, FD, FG LC, LX (400 A Max.) FH LC, LX (600 A Max.) FY, FD, FG 65k LJ FH, FY 277 1 DJ FH, FY LL FY DL FH, FJ 100k LL FH, FJ FI, KI FA, FH, FY, FD, FG, FJ HR FA, FJ, FY JR FA, FJ, FY 200k LI, LXI (400 A Max.) FH LI, LXI (600 A Max.) FY, FD, FG, FJ LR FH, FY 22k MG FA KH, LA, MA, MX, PA, FH PC, PX, PJ LA, MA, PA, PC, PX KA 30k LA, MA, PA HD, JD MG FA (25 A Max.), FH, KA MH, MX, PA HD, JD HG, JG FA, HD JG JD 35k LH, MG, PG, RG HD, JD LG FH, HD, JD, KA, LA, LD, MA DG FH, HD, JD, KA, LA, MA MJ FH (25 A Max.) 42k RL RG 50k MJ KA, KH FC, KC FA, FH HJ, JJ FA, FH, HD, HG JJ JD, JG LC, LI, LX, LXI HD, HG, JD, JG LC, LX (400 A Max.) FH 65k 480 KC, LC, LX KA LC, LX LA LJ FH, HD, HG, JD, JG, KA, LA, LD, LG, MA 2, 3 DJ FH, HD, HG, JD, JG, KA, LA, MA HL, JL FA, FH, HD, HG, HJ JL JD, JG, JJ JR FA LI, LXI (600 A Max.) KA 100k FH, HD, HG, HJ, JD, JG, JJ, KA, LA, LD, LG, LL LJ, MA 200k 25k 35k 480Y/277 65k 200k 18k 25k 35k 600 50k 65k 100k 600Y/347 18k 25k 50k DL PC, PH, PL, RL RL FI, KI HR JR KI LI LR LXI FH, KA FG, KH, LH FJ FC, KC LC, LX (600 A Max.) FI, KI LI, LXI (600 A Max.) HG, JG JG LG MG, PG, RG MG HJ, JJ JJ LJ PJ, RJ LC HL, JL JL LL PK LR FI, KI HR JR KI KI, LI LI LR MG MJ HL, JL FH, HD, HG, HJ, JD, JG, JJ, KA, LA, MA HJ, JJ RG FA, FH, FC, HD, HG, HJ FA, HD, HG, HJ, HL HD, HG, HJ, HL, JD, JG, JJ, JL JD, JG, JJ, KA FC, KA, KC, LA, HJ, HL, JJ, JL FH, HJ, HL, JJ, JL, LA, LH KA, HJ, HL, JJ, JL FD FD FD FD, FG FD, FG FD, FG, FJ FD, FG, FJ FA, HD JD HD, JD, LD HD, JD FA FA, HD, HG JD HD, HG, JD, JG, LD, LG, MA MG FH, HD, HG, HJ, JD, JG, JJ, LA FA (30 MAX), HD, HG, HJ JD, JG, JJ HD, HG, HJ, JD, JG, JJ, LD, LG, LJ, MA HJ, JJ, MJ HJ, JJ HD, HG, HJ FA, HD, HG, HJ, HL FA, HD, HG, HJ, HL, JD, JG, JJ, JL JD, JG, JJ FH LA HL, JL FA (25 A max.) FA (30 A max.) FJ 2, 3 1 NOTE: LD, LG, LH, and LL breakers are only available in 3 pole configurations. Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard. Obsolete. Contact your local Schneider Electric representative or distributor for the replacement circuit breaker. DE14-4 11/15 DE14_p05.fm Page 5 Sunday, November 15, 2015 8:33 AM Series Ratings I-Line™ Panelboards Class 2110 Fuse/I-Line Circuit Breaker Series Connected Ratings 120/240 1Ø 208Y/120 100,000 240 65,000 Remote Main Fuse Maximum Amperage 1200 A 800 A 600 A 1200 A 800 A 600 A 1200 A 800 A 600 A 240 100,000 800 A 1200 A 1600/2000 A 4000 A 600 A 240 200,000 800 A 1200 A 1600/2000 A 4000 A 400 A 600 A 480 100,000 800 A 1200 A 1600 A 2000 A 4000 A 200 A 400 A 600 A 480 200,000 800 A a 600 100,000 600 200,000 1200 A 1600/2000 A 30 A 200 A 400 A 600 A 1200 A 600 A 800 A Square D™ Brand Branch Circuit Breakers Fuse Class Designation a L, T (300 V) T (600 V) J, RK5 L, T (300 V) T (600 V) J, RK5 L, T (300 V) T (600 V) J, RK5 L, T (600 V) RK5 J T (600 V) T (300 V) L L T (600 V) L L J, T (600 V) RK5 J T (600 V) T (300 V) L L T (600 V) L L J, T (600 V) J, RK5 J, T (600 V) RK5 L, T (600 V) L T (600 V) L L L RK5 J T(600V) J T (600V) RK5 T (300 V) T (600 V) L L L CC J J, T (600 V) R L J T (600 V) QD, QG QD, QG QD, QG QD QD QD QD, QG (2-pole) QD, QG (2-pole) QD, QG (2-pole) FA, FH, KA, KH, KC, LA, LH, MA, MH, MX, PG FH, KA, KH, LA, LH, MA, MH, MX, PG, HD, HG, HJ, HL, JD, JG, JJ, JL HD, HG, HJ, HL, JD, JG, JJ, JL FH, KA, KH, LA, LH, MA, MH, MX, PG PG FH,KA,KH,LA,LH,MA,MH,MX,PG FH, KH, LA, LH, MA, MH, MX, PG HD, HG, HJ, HL, JD, JG, JJ, JL KH, MA, MH, MX, PG HD, HG, HJ, HL, JD, JG, JJ, JL FA( 3-pole only), FH, FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL FH, FC, HD, HG, HJ, HL, JD, JG, JJ, JL KH, KC, LA, LH, LC, MA, MH, MX, NC, NX, PG, PJ, PL HD, HG, HJ, HL, JD, JG, JJ, JL FH, FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL PG, PJ, PL FH,FC, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL FC, KH, KC, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL HD, HG, HJ, HL, JD, JG, JJ, JL NA, NC, NX, PJ, PL HD, HG, HJ, HL, JD, JG, JJ, JL HD, HG, HJ, HL, JD, JG, JJ, JL HJ, HL, JJ, JL FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ FC, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ HJ, HL, JJ, JL KC, LC, MA, MH, MX, NA, PG, PJ KC, LC, MH,MG, MJ, MX, NA, PG, PJ HJ, HL, JJ, JL HJ, HL FA, FH, FC, HJ, HL, JJ, JL, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL FA, FH, FC, HJ, HL, JJ, JL, KA, KH, KC, LA, LH, MA, MH, MX, NA, NC, NX FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL KA, KH, KC, LA, LH, MA, MH, MX, NA, NC, NX KC, LA, LH, LC, MA, MH, MX, MG, MJ, NC, NX, PG, PJ, PG, PJ, PL KA, KH, KC, LA, LH, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL KC, LC, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL NA, NC, NX HG, JG ( molded case switches ) HD, HG, HJ, HL, JD, JG, JJ, JL HJ, HL, JJ, JL MG, MJ MG, MJ MG, MJ MG, MJ Series rating valid for 2-pole or 3-pole circuit breakers. Note: • • • • The fuse used in this CSA/UL test is an envelope (umbrella) fuse. This fuse is designed as a “worst case’’ fuse. Thus, no matter what manufacturer’s fuse is used, the Square D™ brand circuit breaker is protected. The line side fused switch may be in a separate enclosure or in the same enclosure as the loadside circuit breaker. A line side fused switch may be a submain, integral main, or remote main. A load side circuit breaker may be a branch, submain, or an integral main used on the load side of a remote main. This series combination short circuit current rating shall not exceed that of the line side fused switch. The charts apply to Square D™ brand load side circuit breakers only. However, the line side fuse ratings are independent of the fuse manufacturer. Not applicable to Corner Grounded Systems. Limiters used in Square D™ brand DSL and DSL II fused power circuit breakers are not class L fuses and do not have series ratings. 11/15 DE14-5 SERIES RATINGS Max. Short Circuit Current Rating (RMS Symm.) DE14 Maximum System Voltage AC DE14_p06.fm Page 6 Sunday, November 15, 2015 8:34 AM Series Ratings Canadian Homeline Loadcentres Single Row - Short Circuit Current Rating Tenant Square D™ Circuit Breaker (Remote only) Interrupting Rating RMS Symmetrical Amperes at 240 V Line Side Fuse or Square D™ Circuit Breaker (Remote only) Poles 10,000 22,000 25,000 42,000 42,000 65,000 100,000 42,000 — QO(B)-VH (125) QD (225) QOH(B) LA, MA LH, MG, PG Class R, J, T6, T3, L (1200) LA, MA QG (225) LH, MG, PG, RG (2000) QJ (225) MJ, PJ, RJ (2000), Class R, J, T6, T3, L (1200) — 2 2 2 2,3 2,3 2,3 2,3 2 2,3 2 2,3 65,000 100,000 Catalog Designation Poles — — — — QO(B)-VH QO(B)-VH QOH(B) QD — — — — QD QD, QG Schneider Electric Branch Circuit Breaker Current Rating Amperes Max. Catalog Designation — 2 125 2 225 2 225 2 Current Rating Amperes Max. 1 Pole 2 Pole CHOM ¥ 50 125 ¶ CHOMT 30 50 CHOM ¥ 50 100 ¶ CHOMT 30 50 CHOM ¥ 50 125 ¶ CHOMT 30 50 225 ¶ Loadcentres with 100 A mains rating are limited to 100 A maximum integral main circuit breaker and 70 A maximum branch circuit. ¥ Catalog designation CHOM includes suffixes AFI, EPD and GFI Circuit Breakers. The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See loadcentre wiring diagram for circuit breaker types. Double Row, Indoor Devices - Short Circuit Current Rating Interrupting Rating RMS Symmetrical Amperes at Vac Max Line Side Fuse or Square D™ Circuit Breaker (Integral or Remote) Fuse Class Catalog Designation • 42,000 at 240 — LA, MA 65,000 at 240 — LH, MG, PG Sub Service Square D™ Circuit Breaker (Integral or Remote) Line Side Fuse or Square D™ Circuit Breaker (Integral or Remote) Schneider Electric Branch Circuit Breaker Catalog Current Catalog Rating Designation Poles Designation Poles Amperes • Max. • Current Rating Amperes Max. Interrupting Rating RMS Symmetrical Amperes at Vac Max Fuse Class Catalog Designation • 1 2 Pole Pole QO(B)-VH 42,000 at 240 — LA, MA 65,000 at 240 — LH, MG, PG, RG (2000) Sub Service Square D™ Circuit Breaker (Integral or Remote) Schneider Electric Branch Circuit Breaker Current Rating Catalog Current Catalog Amperes Rating Designation Poles Designation Poles Amperes Max. • Max. • 1 2 Pole Pole QD CHOM (§) R, J, 100,000 at 240 T3, T6, L (1200 2,3 2 50 100 125 QO(B)-VH QOH(B) CHOMT — 30 50 R, J, 100,000 at 240 T3, T6, L (1200 2,3 MJ, PJ, RJ (2000) 2 225 CHOM (§) 50 200 CHOMT 30 50 QD, QG (§) Catalog designation CHOM includes suffixes AFI, BB, EPD and GFI circuit breakers. DE14 SERIES RATINGS Outdoor Devices - Short Circuit Current Rating Interrupting Rating RMS Symmetrical Amperes at 240 V Max. Line Side Square D™ Circuit Breaker Catalog Designation or Fuse Class 42,000 65,000 100,000 42,000 65,000 100,000 LA, MA LH, MG, PG Class R, J, T3, T6, L(1200) LA, MA LH, MG, PG, RG (2000) MJ, PJ, RJ, (2000), Class R, J, T6, T3, L(1200) Tenant Square D™ Circuit Breaker (Remote only) Poles (Max. A rating) • 2, 3 2, 3 Catalog Designation (Ampere Max.) • QO(B)-VH (125) QO(B)-VH (125) QOH(B) QD (225) QD, QG (225) Schneider Electric Branch Circuit Breaker Current Rating Amperes Max. Poles Catalog Designation • 1 Pole 2 Pole 2 CHOM (§) CHOMT 50 30 100 50 2 CHOM (§) CHOMT 50 30 200 50 • See circuit breaker for voltage and interrupting rating. See loadcentre marking for acceptable circuit breakers. (§) CHOM includes suffixes AFI, BB, EPD and GFI. The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement branch or main circuit breaker, or service disconnect MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See loadcentre interior for circuit breaker types. DE14-6 11/15 DE14_p07.fm Page 7 Sunday, November 15, 2015 8:34 AM Series Ratings Canadian QO Loadcentres Table 14.1 Interrupting Rating RMS Symmetrical Amperes at Vac Max. Line Side Fuse or Square D™ Circuit Breaker (Integral or Remote) Fuse Class Catalog Designation • Poles Current Rating Amperes Max. Sub Service Square D™ Circuit Breaker (Integral or Remote) Catalog Designation • Poles Catalog Designation • Poles QO...H 2 QO...VH QOH QH QO QOT QO QOT QO QO 1,2,3 2 1,2,3 1,2,3 1 1,2 1 1,2,3 1,2 100 QO 1,2,3 125 QO QOT 1,2 1 Current Rating Amperes Max. f5,000 at 240 10,000 at 240 22,,000 at 240 42,000 at 240 65,000 at 240 10,000 at 240 QOM...VH QO(B)...VH QO...VH 22,000 at 240 22,000 at 240 42,000 at 240 42,000 at 240 65,000 at 240 65,000 at 240 R R J, T6 T3 R T3, T6, J 2 2 3 2 3 3 3 2 2 225 200 100 100 100 400 400 200 600 QO...VH QO(B)...VH 3 2 Square D™ Branch Circuit Breaker Current Rating Amperes Max. 1 Pole 2 pole 3 Pole 15-100 15-30 15-30 10-70 15-30 10-70 15-30 10-70 10-70 15-200 40-125 15-30 10-200 10-100 15-30 10-100 10-200 10-100 10-100 10-100 10-70 10-100 10-100 10-70 15-30 10-125 Table 14.2 Line Side Fuse or Square D™ Circuit Breaker (Integral or Remote) Catalog Designation • Poles Current Rating Amperes Max. 25,000 at 240 65,000 at 240 QD QG 2,3 2,3 225 225 100,000 at 240, 2 pole and 208Y/120, 3 Pole QJ 2,3 225 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 200 400 1,000 400 800 1,000 1,200 1,600 2,000 800 1,200 1,600 2,000 600 800 1,200 100,000 at 240 Fuse Class J, T3, T6 LA MA LH MG MH PG PA RG MJ PJ PH RJ 42,000 at 240 65,000 at 240 65,000 at 240, 9 pole or 100,000 at 240, 2 pole and 208Y/120, 3 pole R, J T6 T3, L Sub Service Square D™ Circuit Breaker (Integral or Remote) Catalog Designation • QD Poles 2,3 Current Rating Amperes Max. 225 Square D™ Branch Circuit Breaker Catalog Designation • QO QO...VH QO...H 240 V 1 Ø QO...GFI QO...EPD QO...PL QO...AS QO...AFI QOT Current Rating Amperes Max. Poles 1,2,3 3 1 Pole 2 pole 3 Pole 15-70 15-200 15-30 35-100 2 1,2 1,2 1,2,3 1,2,3 1 1 15-100 15-30 15-30 15-30 15-30 15-20 15-30 15-60 15-60 15-60 15-30 15-30 15-30 240 Vac 3 Phase 4 Wire Delta: When wired for Delta system, phase “B” must be 208 V to neutral, Circuit breaker poles connected to phase “B” must be rated 240 V. Single pole circuit breakers must not be connected to phase “B”. The Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement branch or main circuit breaker, or service disconnect MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types. DE14 f 240 Vac, 3 phase 3 wire Grounded “B” phase. • See circuit breaker for voltage and interrupting rating. SERIES RATINGS Interrupting Rating RMS Symmetrical Amperes at Vac Max. 11/15 DE14-7