Prices as of April 27, 2016. Check Web site for most current prices. Recommendations for Overcurrent Protection UL and CSA (North American) Standards UL and CSA (North American) Standards North American standards, including UL 508, National Electric Code 450, and the Canadian Electrical Code, Part 1, require overcurrent protection on all control circuit transformers. There are two options for overcurrent protection: Option 1 (Primary only Protection) Provide an overcurrent device in the primary circuit rated to the current of the transformer. The overcurrent limits are as follows: • Primary 9 Amps or more: no more than 125% of rated current • Primary 2 to 9 Amps: no more than 167% of rated current • Primary less than 2 Amps: no more than 300% of rated current for power circuits; no more than 500% of rated current for control circuits Note: This method is considered less desirable, as start-up inrush to the transformer can frequently surpass the current rating of the device and result in nuisance interruptions. Option 2 (Primary and Secondary Protection) The second option is to install overcurrent devices in both the primary and secondary circuits of the transformer. In this option, the secondary device must be rated no more than 125% of rated current of the transformer and the primary no more than 250%. The Canadian Electrical Code permits 300% overcurrent on the primary for this option. In both options listed, it is recommended that time delay fuses be considered to avoid unnecessary interruptions. REFERENCES: UL 508 UL 845 NEC 430-72 NEC 450-3 CEC Part 1, 26-256 Book 3 (14.3) eTX-14 Transformers 1-800-633-0405 Prices as of April 27, 2016. Check Web site for most current prices. Recommendations for Overcurrent Protection UL and CSA (North American) Standards, continued HCTR Current Limiting Class CC Fuses Part Number HCTR-25 HCTR-5 HCTR-75 HCTR1 HCTR1-25 HCTR1-5 HCTR2 HCTR2-5 HCTR3 HCTR3-5 HCTR4 HCTR5 HCTR6 HCTR7-5 HCTR8 HCTR10 HCTR15 HCTR20 HCTR25 HCTR30 PRIMARY (UL and CSA) To assist in the selection of fuses, the following chart recommends the maximum primary fuse rating in amperes. The first number shown is the maximum overcurrent protection when the primary current is less than 2 amps and the overcurrent protection device is rated for 300%. The second number (shown in brackets) is recommended when the primary is less than 2 amps and the overcurrent device is to be rated at 500% of rated current. Where only one number is indicated, the primary is 2 amps or more and one rating of overcurrent protection is shown as optimal. Choose the next higher fuse rating if these numbers do not correspond with standard fuse selections. Recommended Maximum Primary Fuse Ratings in Amps Where Primary Current is less than 2 Amps. Primary Overload Voltage Protection 50 115 120 220 208 230 240 277 380 440 460 480 300% 500% 300% 500% 300% 500% 300% 500% 300% 500% 300% 500% 300% 500% 300% 500% 300% 500% 300% 500% 300% 500% 1.25 (2.0) 1.25 (2.0) 0.6 (1.125) 0.6 (1.125) 0.6 (1.0) 0.6 (1.0) 0.5 (0.8) 0.3 (0.6) 0.3 (0.5) 0.3 (0.5) 0.3 (0.5) AMP Rating Pcs/Pkg Weight Price 0.25 0.5 0.75 1 1.25 1.5 2 2.5 3 3.5 4 5 6 7.5 8 10 15 20 25 30 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb $93.00 $82.00 $107.00 $84.00 $104.00 $83.00 $83.00 $93.00 $84.00 $102.00 $89.00 $87.00 $93.00 $102.00 $93.00 $90.00 $83.00 $90.00 $88.00 $91.00 Wiring Accessories Multi-wire Connectors Sensor Cables and Connectors M12 Junction Blocks Panel Interface Connectors Wiring Duct Cable Ties Wire Bulk Multi-conductor Cables Wire Management Products Power Supplies Hammond Transformers VA RATING 1.8 (3.2) 1.8 (3.2) 1 .0 (1.6) 1.0 (1.8) 0.8 (1.6) 0.8 (1.5) 0.8 (1.25) 0.5 (0.8) 0.5 (0.8) 0.4 (0.8) 0.4 (0.75) 2.5 (4.0) 2.25 (4.0) 1.25 (2.25) 1.4 (2.25) 1.25 (2.0) 1.25 (2.0) 1.0 (1.8) 0.75 (1.25) 0.6 (1.125) 0.6 (1.0) 0.6 (1.0) 8.0 – 8.0 – 4.0 – 4.0 – 4.0 – 3.5 – 5.0 – 3.5 (6.25) 3.2 (5.6) 3.2 (5.0) 3.0 (5.0) Power Distribution Blocks DC Converters 100 150 250 350 500 750 1000 1500 2000 3000 5000 5.0 – 5.0 – 4.5 (7.5) 5.0 (8.0) 4.5 (7.5) 4.0 (7.0) 3.5 (9.0) 2.5 (4.5) 2.25 (3.5) 2.25 (3.5) 2.0 (3.5) Terminal Blocks ZIPLink Connection System Note: S ee HCTR fuse catalog page for characteristic curves. 75 3.5 4.0 (6.5) – 3.5 4.0 (6.5) – 2 .0 3.2 (3.2) (5.6) 2.0 3.5 (3.5) (6.0) 1.8 3. 2 (3.2) (5.0) 1.8 3.0 (3.0) (5.0) 1.6 2.5 (4.5) (6.25) 1.125 1.8 (1.8) (3.2) 1 .0 1.6 (1.6) (2.8) 0.8 1.6 (1.6) (2.5) 0.8 1.5 (1.5) (2.5) Company Information 10.0 – 10.0 – 6.0 – 6.0 – 6.0 – 5.0 – 5.0 – 5.6 (9.0) 5.0 (8.0) 4.5 (8.0) 4.5 (7.5) 15.0 – 15.0 – 8.0 – 8.0 – 8.0 – 7.0 – 6.0 – 4.5 – 4.0 – 3.5 – 3.5 – 20.0 – 15.0 – 12.0 – 12.0 – 10.0 – 10.0 – 9.0 – 6.25 – 6.0 – 6.0 – 5.0 – 25.0 – 20.0 – 15.0 – 15.0 – 15.0 – 15.0 – 12.0 – 9.0 – 8.0 – 8.0 – 7.0 – – – – – 20.0 – 20.0 – 20.0 – 15.0 – 15.0 – 15.0 – 12.0 – 12.0 – 10.0 – Transformers and Filters – – – – 30.0 – 30.0 – 30.0 – 30.0 – 25.0 – 20.0 – 15.0 – 15.0 – 15.0 – Circuit Protection Tools Test Equipment Enclosures Enclosure Climate Control Safety: Electrical Components Safety: Protective Wear Terms and Conditions Book 3 (14.3) www.automationdirect.com/power-transformers Transformers eTX-15 Prices as of April 27, 2016. Check Web site for most current prices. Recommendations for Overcurrent Protection UL and CSA (North American) Standards, continued MEN General Purpose Midget Class Fuses SECONDARY Part Number MEN-5 MEN-6 MEN1 MEN1-4 MEN1-5 MEN2 MEN2-5 MEN3 MEN3-5 MEN4 MEN5 MEN6 MEN7 MEN8 MEN10 MEN12 MEN15 MEN20 MEN25 MEN30 The overcurrent protection listed below, in amperes, is 125% of the rated current of the transformer. Choose the next higher fuse rating if these numbers do not correspond with standard fuse selections. Recommended Maximum Secondary Fuse Ratings in Amps. AMP Rating Pcs/Pkg Weight Price 0.5 0.6 1 1.4 1.5 2 2.5 3 3.5 4 5 6 7 8 10 12 15 20 25 30 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 10/1 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb 0.2 lb $34.00 $33.50 $31.50 $40.00 $33.50 $29.00 $31.50 $29.50 $29.00 $29.50 $29.00 $31.50 $29.00 $29.50 $29.00 $34.00 $30.00 $32.00 $34.50 $32.00 Note: See MEN fuse catalog page for characteristic curves. Hammond Transformers VA RATING Secondary Overload Voltage Protection 50 75 100 150 250 350 500 750 1000 1500 2000 3000 5000 12 24 110 115 120 220 230 125% 5.3 7.9 11.0 16.0 27.0 – – – – – – – – 125% 2.7 4.0 5.3 7.9 14.0 19.0 27.0 – – – – – – 125% 0.6 0.9 1.2 1.8 2.9 4.0 5.7 8.6 12.0 18.0 23.0 – – 125% 0.6 0.9 1.1 1.7 2.8 3.9 5.5 8.2 11.0 17.0 22.0 – – 125% 0.6 0.8 1.1 1.6 2.7 3.7 5.3 7.9 11.0 16.0 21.0 – – 125% 0.3 0.5 0.6 0.9 1.5 2.0 2.9 4.3 5.7 8.6 12.0 18.0 29.0 125% 0.3 0.5 0.6 0.9 1.4 2.0 2.8 4.1 5.5 8.2 11.0 17.0 28.0 Book 3 (14.3) eTX-16 Transformers 1-800-633-0405