Connecting leads Radox 125

advertisement
Radox 125
Connecting leads
GENERAL PROPERTIES :
Excellent high temperature, low temperature, ozone and weathering resistance, halogen free,
soldering iron resistant, easy to strip and process, flexible.
APPLICATION :
For protected and fixed installation inside electrical equipment, especially suitable for the connection of motor windings,
switchboards, magnets and transformers.
2
1
1.
Conductor : Stranded tin plated copper, according to IEC 228 cl.5
2.
Insulation : RADOX 125 ,
extruded irradiation crosslinked polyolefin
Colours : diverse
Printing: HUBER + SUHNER SWITZERLAND RADOX 125 ...mm2
TECHNICAL DATA :
Temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -- 40 ... + 125 . . . . . °C
TABLE 1 : Dimensions, conductor resistance, weight
Cross
section
nom.
Conductor
construction
nom.
Conductor
diameter
max.
Core
diameter
D
R20
IEC 228
max.
Weight
nom.
Nominal
voltage
Test
voltage
Min.
bending
radius
mm2
n x mmØ
mm
mm
Ω / km
kg / 100m
V
V
mm
0.25
19 x 0.13
0.6
1.45 ± 0.05
85.9
0.4
450/750
2500
3xD
0.34
19 x 0.16
0.8
1.60 ± 0.10
52.1
0.5
450/750
2500
3xD
0.50
19 x 0.18
0.9
1.70 ± 0.10
40.1
0.7
450/750
2500
3xD
0.75
24 x 0.20
1.15
2.20 ± 0.10
26.7
1.1
600/1000
3500
3xD
1.0
32 x 0.20
1.3
2.60 ± 0.10
20.0
1.5
600/1000
3500
3xD
1.5
30 x 0.25
1.55
2.73 ± 0.10
13.7
1.9
600/1000
3500
3xD
2.5
48 x 0.25
2.05
3.50 ± 0.10
8.21
3.0
600/1000
3500
3xD
4.0
56 x 0.30
2.6
4.15 ± 0.15
5.09
4.6
600/1000
3500
3xD
6.0
82 x 0.30
3.4
4.95 ± 0.15
3.39
6.7
600/1000
3500
3xD
10
78 x 0.40
4.4
6.15 ± 0.15
1.95
11
600/1000
3500
3xD
16
119 x 0.40
5.4
7.35 ± 0.15
1.24
16.5
600/1000
3500
3xD
25
182 x 0.40
6.7
8.9 ± 0.2
0.795
25
600/1000
3500
3xD
35
266 x 0.40
7.9
10.3 ± 0.2
0.565
34.9
600/1000
3500
3xD
50
378 x 0.40
9.4
12.1 ± 0.25
0.393
50
600/1000
3500
4xD
70
348 x 0.50
11.5
14.4 ± 0.25
0.277
70.8
600/1000
3500
4xD
95
444 x 0.50
12.9
16.0 ± 0.3
0.210
89
600/1000
3500
4xD
120
570 x 0.50
15.1
18.6 ± 0.3
0.164
116
600/1000
3500
4xD
150
722 x 0.50
17.0
20.5 ± 0.3
0.132
145
600/1000
3500
4xD
185
874 x 0.50
18.5
22.2 ± 0.3
0.108
173
600/1000
3500
4xD
240
1147 x 0.50
21.3
25.4 ± 0.3
0.0817
225
600/1000
3500
4xD
Copyright 2010 Huber + Suhner AG. This document may not be copied nor be passed on to third
parties without our written permission.
Uncontrolled copy when printed (will not be updated].
Wire+Cable Division
CH--8330 Pfäffikon
+41 (0)44 952 22 11
+41 (0)44 952 26 40
FAX
www.hubersuhner.com
The product fulfils the test and specification requirements described in this document for the stated
areas of application and operating conditions. HUBER+SUHNER AG does not expressly or implicitly
guarantee performance under additional or changed conditions. Deviations are to be agreed upon in
writing.
Issue
06.07.2010 / 2447
Release
2453
Supersedes issue H
08.01.2009
TechnicalDatasheet
Page 1/2
559 926 I (e)
Radox 125
Connecting leads
The cables are in conformity with :
Halogen--free compound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . fulfilled . . . . . . . . . . . . . . . EN 50363
Corrosivity of combustion gases . . . . . . . . . . . . . . . . . . . . . . . . . pH ≥ 4.3, σ ≤ 10 μS/mm EN 50267--2--2
Amount of halogen acid gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . HCI+HBr ≤ 0.5% . . . . . . EN 50267--2--1
Content of fluorine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HF ≤ 0.1% . . . . . . . . . . . EN 60684--2, # 45.2
Issue
06.07.2010 / 2447
Release
2453
Supersedes issue H
08.01.2009
TechnicalDatasheet
Page 2/2
559 926 I (e)