CS, SWA - General Cable New Zealand

advertisement
INSTRUMENTATION
PROCON
B55 CS SWA
Overall Screened
APPLICATION
Suitable for the interconnection of:
Electrical measuring devices to instrument panel.
Instrument to instrument.
Electrical sensing devices to control cabinets.
Control cabinets to supervisory consoles and panels.
Telemeters to recorders and annunciators
Suitable for glanding.
Armoured version offers additional mechanical protection
COLOUR CODE
Wire 1 – White with number mark
Wire 2 – Black with number mark
STANDARD
AS/NZS 1125
AS/CA S008
IEC 60332-3 Cat.A, IEC 60332-1
IS Circuits to AS/NZS 60079.14
AS/NZS 3808
CONDUCTOR
Annealed Copper (16 AWG)
INSULATION
PVC V-90HT
SCREEN
Aluminium/Polyester tape with 7/0.25mm
Tinned Copper Drain Wire
BEDDING
Flame Retardant PVC Black
ARMOUR
Galvanised Steel Wire
SHEATH
Flame Retardant Black
(Intrinsically Safe blue PVC Sheath
available on request)
TECHNICAL SPECIFICATIONS
ITEM
NUMBER
TYPE
28200016
28210016
28220016
25550016
29650016
29680016
29690016
29698016
29700016
29736016
29740016
B5502 CS SWA
B5504 CS SWA
B5506 CS SWA
B5508 CS SWA
B5510 CS SWA
B5512 CS SWA
B5516 CS SWA
B5520 CS SWA
B5524 CS SWA
B5536 CS SWA
B5550 CS SWA
CONDUCTOR
mm2
(No./mm)
APPROX.
MASS
(kg/km)
NOMINAL DIAMETER
NUMBER
OF PAIRS
OVER
BEDDING
mm
OVER
ARMOUR
mm
OVERALL
mm
MINIMUM INSTALLED
BENDING RADIUS
mm
MAXIMUM PULLING
TENSION (a)
kN
2
4
6
8
10
12
16
20
24
36
50
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
7/0.50
7/0.50
7/0.50
7/0.50
7/0.50
7/0.50
7/0.50
7/0.50
7/0.50
7/0.50
7/0.50
360
590
760
1070
1240
1390
1710
1950
2560
3850
4800
11.7
13.5
16.3
17.3
19.4
20.6
23.5
25.9
28.1
34.2
40.2
13.5
16.0
18.8
20.5
22.6
23.8
26.7
29.1
32.0
39.2
45.2
15.7
18.3
21.1
23.7
25.5
26.9
29.8
32.7
35.4
43.2
49.5
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
2.2
3.8
4.5
6.8
7.4
8.0
9.3
9.9
14.1
20.0
20.0
(a) Based on a steel strength of 100 N/mm2.
New Zealand/Instrumentation/Procon (B50, B51, B53, B55, B56)/B55/B55 CS SWA │ VERSION:
ELECTRICAL CHARACTERISTICS
PROPERTY
VALUE
UNITS
DC Conductor Resistance @ 20°C
Maximum Continuous Current Rating
Maximum recommended Voltage
Capacitance of Pairs
B5502 CS
B5504 CS onwards
Inductance @ 1kHz
L/R Ratio
13.6
13
110/150
Ω/km
Amps
VRMS/ VDC
120
200
0.8
31
pF/m
pF/m
mH/km
µH/Ω
NOTE
All cables are subject during manufacture to in-process spark testing at 4kV AC.
All cables are tested between each conductor and screens earthed at 3kV DC.
These cables are not to be regarded as power cables or for the direct connection of equipment to mains power supplies.
Values are nominal unless otherwise specified.
GENERAL CABLE NEW ZEALAND LIMITED
75 – 89 Main South Road
Riccarton, Christchurch
PO Box 8044, Riccarton, Christchurch, New Zealand
Phone:
0800 CABLES (0800 222 537)
FAX:
EMAIL:
0800 242 267
sales@generalcable.co.nz
New Zealand/Instrumentation/Procon (B50, B51, B53, B55, B56)/B55/B55 CS SWA │ VERSION: B55 CS SWA v180615