Data Sheet TP/.. Twisted Pair Cable TP/.. Twisted Pair Cable Description Features Screened and unscreened twisted pair cables recommended for general purpose Trend system installations. All cables are manufactured with a violet, halogen-free outer sheath. Screened cables have twisted pairs wrapped in an aluminium polyester tape with a tinned copper drain wire ▪▪ Violet sheath for ease of identification ▪▪ Flame retardant halogen-free sheath ▪▪ 600 V rating Physical TP/1/1/22/HF/200-600V. Screened single twisted pair, 22 AWG, 200 m (*Belden equivalent 8761NH). Recommended Trend system use: Trend current loop Lan, Input/ output wiring (Analogue voltage, Analogue current, Thermistor, Digital inputs and Analogue voltage outputs) TP/2/2/22/HF/200-600V. Screened twin twisted pair, 22 AWG, 200m (*Belden equivalent 8723NH). diam 4.6 mm diam 5.7 mm Recommended Trend system use: Trend current loop Lan TP/1/0/16/HF/200-600V. Unscreened single 16 AWG, 200 m (*Belden equivalent 8471NH). twisted pair, diam 7.3 mm Recommended Trend system use: LONWORKS ® bus TP/1/1/24/HF/305-600V. Screened twin twisted pair, 24 AWG, 305 m (*enhancement of Belden equivalent 9841NH). diam 5.9 mm Recommended Trend system use: This is the cable recommended for wiring Trend networks using BACnet over MS/TP (e.g. IQeco controllers). It is important that the installation requirements detailed in the IQeco data sheet and installation instructions are followed. *The TP cables are of a similar construction and specification to the Belden equivalents given. However, the Trend TP cables are of a higher voltage rating (600 V) and have a halogen free sheath. TP/.. Twisted Pair Cable Data Sheet TA200541 Issue 6, 20-Nov-20131 TP/.. Data Sheet ORDER CODES TP/1/1/22/HF/200-600V TP/2/2/22/HF/200-600V TP/1/0/16/HF/200-600V TP/1/1/24/HF/305-600V 200 m reel of screened single twisted pair 22 AWG 200 m reel of screened twin twisted pair 22 AWG 200 m reel of unscreened single twisted pair 16 AWG 305 m reel of screened single twisted pair 24 AWG Specifications TP/1/1/22/HF/200-600V and TP/2/2/22/HF/200-600V Description Belden equivalent Trend system use TP/1/1/22/HF/200-600V Single shielded twisted pair. 22 AWG (7x30 AWG) stranded tinned copper, polyethylene insulated twisted pair - over aluminium - polyester shield with 22 AWG (7x30 AWG) stranded tinned copper drain wire, flame retardant halogen-free sheath TP/2/2/22/HF/200-600V Two twisted pairs individually shielded. 22 AWG (7x30 AWG) stranded tinned copper, polyethylene insulation, twisted aluminium-polyester shielded pair. Cabled on common axis with a common 24 AWG (7x32 AWG) stranded tinned copper drain wire, flame retardant halogen-free sheath. 8761NH 8723NH Trend current loop Lan, Trend Trend Lan input/output wiring (Analogue voltage, Analogue current, Thermistor, Digital inputs, and Analogue voltage outputs) Electrical Characteristics Maximum operating voltage Velocity of propagation Maximum continuous current per conductor at 25 °C Test voltage conductor - screen Test voltage conductor - conductors Nominal capacitance between conductors Nominal capacitance between conductor and shield (one conductor to other conductor and shield) Nominal resistance shield Nominal conductor DC resistance at 20 °C Nominal impedance Physical Characteristics Temperature range Installing Temperature range Operating (Moving installation) Temperature range Operating (Fixed installation) Temperature range Storage Insulation Material Screen type Braid Sheath Material (colour) Sheath radial thickness Overall nominal diameter Colour Code Pulling tension Minimum bending radius UV stability 2 600 V RMS 2.9 A 2.5 kV 3 s 2.5 kV 3 s 78.7 pF/m - 600 V RMS 65% nominal 2.3 A 2.5 kV 3 s 2.5 kV 3 s - 52.5 ohms/km - 49.2 ohms/km - -15 to +70 °C -15 to +70 °C -30 to +70 °C -30 to +70 °C Polyethylene Aluminium/polyester 9/12 µm Flame retardant, halogen-free (violet) 0.7 mm 4.6 mm black/clear 158 N 10x cable diameter Compliant with resistance to UVcycle test, 1000 h, according to ASTM D 2565-99 -15 to +70 °C -15 to +70 °C -30 to +70 °C -30 to +70 °C Polyethylene Aluminium/polyester 9/12 µm Flame retardant, halogen-free (violet) 0.7 mm 5.7 mm black/red, green/white 187 N 10x cable diameter Compliant with resistance to UVcycle test, 1000 h, according to ASTM D 2565-99 TP/.. Twisted Pair Cable Data Sheet TA200541 Issue 6, 20-Nov-2013 Data Sheet TP/.. TP/1/0/16/HF/200-600V and TP/1/1/24/HF/305-600V Description TP/1/0/16/HF/200-600V Single unshielded twisted pair. 16 AWG (19x29 AWG) stranded tinned copper, polyethylene insulated twisted pair, unshielded flame retardant, halogen-free sheath Belden equivalent 8471NH Trend system use Electrical Characteristics Maximum operating voltage Velocity of propagation Maximum continuous current per conductor at 25 °C Test voltage conductor - screen Test voltage conductor - conductors Nominal capacitance between conductors Nominal capacitance between conductor and shield (one conductor to other conductor and shield) Nominal resistance shield Nominal conductor DC resistance at 20 °C Nominal impedance Physical Characteristics Temperature range Installing Temperature range Operating (Moving installation) Temperature range Operating (Fixed installation) Temperature range Storage Insulation Material Screen type Braid LONWORKS network Sheath Material (colour) Sheath radial thickness Overall nominal diameter Colour Code Pulling tension Minimum bending radius UV stability 600 V RMS TP/1/1/24/HF/305-600V Single shielded twisted pair. 24 AWG (7x32 AWG) stranded tinned copper, polyethylene insulated twisted pair . Over aluminium polyester shield with 24 AWG (7x32 AWG) stranded tinned copper drain wire, 0.122 mm tinned copper braid and flame retardant halogen-free sheath Enhanced version of Belden 9841NH BACnet MS/TP network 2.5 kV, 3 s 52 pF/m - 600 V RMS 66% 2.1 A 2.5 kV, 3 s 2.5 kV, 3 s 42.0 pF/m 75.5 pF/m 14.7 ohms/km - 11.0 ohms/km 78.7 ohms/km 120 ohms -15 to +70 °C -15 to +70 °C -30 to +70 °C -30 to +70 °C Polyethylene -15 to +70 °C -15 to +70 °C -30 to +70 °C -30 to +70 °C 7.1 A Aluminium/polyester 9/23 µ 0.122 tinned copper, 90% coverage Flame retardant, Flame retardant, halogen-free (violet) halogen-free (violet) 0.9 mm 0.9 mm 7.3 mm 5.9 mm black/white white/blue, blue/white 127 N 328 N 10x cable diameter 10x cable diameter Compliant with resistance to UV- Compliant with resistance to UVcycle test, 1000 h, according to cycle test, 1000 h, according to ASTM D 2565-99 ASTM D 2565-99 TP/.. Twisted Pair Cable Data Sheet TA200541 Issue 6, 20-Nov-20133 TP/.. Data Sheet cable construction TP/1/1/22/HF/200-600V TP/2/2/22/HF/200-600V 1 1 2 2 4 4 5 5 7 7 TP/1/1/16/HF/200-600V TP/1/1/24/HF/305-600V 1 1 2 2 3 4 (polyester) 4 7 5 6 Key: 7 1Conductor 2Insulation 3Filler 4Foil 5Drainwire 6Braiding 7Sheath DISPOSAL COSHH (Control of Substances Hazardous to Health UK Government Regulations 2002) ASSESSMENT FOR DISPOSAL OF TP/.. Twisted Pair Cable. No parts affected. WEEE Directive: At the end of their useful life the packaging, and product , and battery (if fitted) should be disposed of by a suitable recycling centre. RECYCLING . All plastic and metal parts are recyclable. Do not dispose of with normal household waste. Do not burn. Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com © 2013 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes. Trend Control Systems Limited Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com Trend Control Systems USA 6670 4 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com TP/.. Twisted Pair Cable Data Sheet TA200541 Issue 6, 20-Nov-2013