Sentron™ Lighting and Power Distribution Panelboards TYPES S1/ S2 Main Breakers Main Breaker: 600A Maximum, Main Lugs Only: 600A Maximum S1: 240V Maximum, 3:4W, 1:3W S2: 480Y/277V Maximum 3:4W Max. Amps. Specifications 100 A) General: S1/ S2 panelboards comply with the following standards: a) NEMA Standards PB-1, 250 b) UL Standards 1) Enclosure — UL 50 2) Panelboards — UL 67 c) National Electric Code (NFPA 70) d) Federal Specification W-P-115b 125 225 Trim Overlap B) Main Breakers: BL, BLH, BQD, ED4, ED6, FD6, FXD6, HBL, HFD6, HED4, HHED6, HJD6, HHJD6, HLD6, HHLD6 JXD6, LXD6, QJ2, QJ2H, QJH2 Main breakers are bolted to the bus bars. Flush Mounting Box Depth( D )= 5.75”for 125A, 250A 7.75” for 400A, 600A Box Width( W )= 20” for 100A - 250A 24” for 400A, 600A C) Box: Fabricated from galvanized or galvanealed steel. Removable end walls. E) Front: Fabricated from cold rolled steel and equipped with concealed hinges, flush lock and a holder for directory card. Trim screws are concealed behind a lockable door. Patented Feature! The trim screws do not enter the wire way to prevent conductor damage. Panel Width 20” Panel Width 24” A 6.375 7.750 B 5.500 7.125 C 6.125 6.000 Da 6.500 8.500 E 5.250 7.250 F — 8.000 G — 8.000 a Panel limited to (1) Subfeed at 250 amperes and (2) Subfeeds at 400 and 600 amperes. PBIS-4106C (Supersedes 4.1-6B) BL, BLH, HBL BQD, ED4 ED4, ED6, HED4, HHED6 QJ2 QJH2 QJ2-H Connectors Suitable for Cu or Al 18 30 42 32 38 44 (1) #12-1/0 AWG 18 30 42 32 38 44 (1) #1 AWG-300 kcmil 250 FXD6 FD6 HFD6 18 30 42 32 38 44 (1) #6 AWG-350 kcmil 400 JXD6 HJD6 42 68 (2) #3/0-500 kcmil (2) #4/0-500 kcmil Al 600 LXD6 HLD6 42 68 (2) #3/0-500 kcmil Cu or (2) #4/0-500 kcmil Al Max. Amps. Max. No. of Poless Unit Space (H) Ht. (In.) Connectors Suitable for Cu or Al 125 18 30 42 9 15 21 32 38 44 (1) #H6 AWG-350 kcmil 250 18 30 42 9 15 21 32 38 44 (1) #6 AWG-350 kcmil 400 42 21 68 (2) #3/0-500 kcmil 600 42 21 68 (2) #3/0-500 kcmil s 1” per pole breakers double branch mounted. Main Lug and Main Breaker Gutters Typical Panelboard Wiring Diagrams Max. Main Lug Main Breaker Amps (ML) (MB) Side Gutter Wiring Space (Inches) Reference Letter Max. (H) No. of Ht. Poless (In.) Main Lug Panels Main Lug and Main Breaker Gutter D) Bussing: Bus bars are tin plated aluminum per UL 67 unless otherwise stated. Breaker branch bus is tin finished copper. Main Breaker Types 125 250 400 600 5.5” 7.0” 11.0” 14.0” B C D E F G BL, BLH, HBL BL, BLH, HBL BLF, BLHF BLF, BLHF BQD Main Breaker 1 Phase 3 Wire 3 Phase 4 Wire, 3 Phase 3 Wire (No SN) Main Lugs Main Lugs 1 Phase 3 Wire 3 Phase 4 Wire, 3 Phase 3 Wire (No SN) 5.75” 5.0” 14.0” 15.5” Branch Breaker Side Gutters A Main Breaker BQD ED, ED4, ED6, HED4,HHED6 QJ2, QJH2, QJ2-Ha FXD6, FD6, HFD6 JXD6, HJD6 LXD6, HLD6 A B C D E F G Branch Circuit Breakers ad Ampere Breaker No. of Ampere Height 120V Frame Frame Poles Rating (Inches) AC 100 BL 1 2 2 3 15- 60 15 -100 15-100 15- 100 1 2 2 3 — — — — 10,000 10,000 10,000 10,000 BLH 1 2 3 15-600 15- 100 15-100 1 2 3 — — — 22,000 22,000 — HBL 1 2 3 15-600 15-100 15-100 1 2 3 — — — 65,000 65,000 — BQD 1 2 3 15-60 15-100 15-100 1 2 3 1 2 3 15-70 15-90 15-100 1 2 3 ED2 1 2 3 15- 100 15-100 15-100 s s s 10,000 — — — — — — 10,000 10,000 ED4 1 2 3 15- 100 15- 125 15- 125 s s s 65,000 — — — — — 2 3 15- 125 15- 125 s s — — — — 1 15-30 35-100 15-100 110- 125 15-100 110- 125 s 100,000 100,000 — — — — — — — — — — — — — — BQD6 f ED6 125 HED4 2 3 250 s s 65,000 — — — — — 277V AC 480Y/ 277V AC 480V AC 600Y/347V AC 125V DC 250V DC — — — — — — — — — — — — — — — — — — — — — — — — — — 22,000 — — — — — — — — — — — — — — — — — — — — 65,000 — — — — — — — — — — — — — — — — — — — 14,000 14,000 — — — — — — 14,000 — — — 14,000 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 22,000 65,000 — 65,000 — — — — — 18,000 18,000 — — — 65,000 65,000 — — 25,000 25,000 18,000 18,000 — — 30,000 — — 65,000 — 25,000 100,000 — 100,000 — 100,000 — 100,000 — — — — — — — — — 42,000 25,000 42,000 25,000 — — — — — — 30,000 30,000 — — — — — — 30,000 30,000 — — — — — — 100,000 100,000 100,000 100,000 — — — — — — — — 42,000 42,000 42,000 42,000 25,000 25,000 25,000 25,000 — — — — 30,000 30,000 — — — — — — — — — — — — Max. Interrupting Rating Symmetrical RMS Amperes — 14,000 65,000 — 65,000 — — — — — — 10,000 10,000 10,000 — — — 5,000 — — 5,000 5,000 — — 30,000 — 15- 100 110- 125 15-100 110- 125 s 2 3 60-225 60-225 s s — — — — 10,000 10,000 — — — — — — — — — — — — QJH2 2 3 60-225 60-225 s s — — — — 22,000 22,000 — — — — — — — — — — — — QJ2-H 2 3 60-225 60-225 s s — — — — 42,000 42,000 — — — — — — — — — — — — FXD6 2,3 70-250 s — — 65,000 — — 35,000 18,000 — 30,000 FD6 2,3 70-250 s — — 65,000 — — 35,000 18,000 — 30,000 HFD6 2,3 70-250 s — — 100,000 — — 65,000 25,000 — 30,000 JXD6 2,3 200-400 s — — 65,000 — — 35,000 25,000 — 30,000 HJD6 2,3 200-400 s — — 100,000 — — 65,000 35,000 — 35,000 LXD6 2,3 250-600 s — — 65,000 — — 35,000 25,000 — 30,000 HLD6 2,3 250-600 s — — 100,000 — — 65,000 35,000 — 35,000 2 225 120 / 240V 240V AC AC HHED6 3 QJ2 s 400 600 a Branch breakers have non-interchangeable trip units. s Mounted as subfeed at opposite end of incoming feed. Limit one per panel. Limit two QJ subfeeds on 400 and 600 amps. Cannot be combined with feed thru lugs. d Branch breakers are bolted to the bus bars. f CSA Listed only at 600Y/347V AC. PBIS-4106C (Supersedes 4.1-6B) Sentron™ Lighting and Power Distribution Panelboards TYPES S3 Main Breakers 600A Maximum Main Breaker / Main Lugs 600V AC, 250 DC Maximum, 1:3W, 3:3W, 3:4W Max. Amps. Specifications A) General: S3 panelboards comply with the following standards: a) NEMA Standards PB-1 b) UL Standards 1) Enclosure — UL 50 2) Panelboards — UL 67 c) National Electric Code (NFPA 70) d) Federal Specification W-P-115b 100 125 Trim Overlap Flush Mounting C) Main Breakers: ; D) Box: Fabricated from galvanized or galvanealed steel. Removable end walls. 225 Box Depth( D )= 5.75”for 100A, 225A, 400A Box Width( D)= 7.75” for 400Aa, 600As BL, BLH, HBL, BQD, ED4, ED6, HED4, HHED6, CED6, QJ2, QJH2, QJ2-H, FXD6, FD6 and HFD6 main breakers are mounted horizontally. CFD6, JXD2, JXD6, JD6, HJD6, CJD6, SJD6, SHJD6, SCJD6, LXD6, LD6, HLD6, CLD6, SLD6, SHLD6 and SCLD6 are mounted vertically. JD6, HJD6, HHJD6, CJD6, SJD6, SHJD6, SCJD6, LD6, HHLD6, HLD6, CLD6, SLD6, SHLD6 and SCLD6 must be mounted at top only. 400a F) Front: Fabricated from cold rolled steel and equipped with concealed hinges, flush lock and a holder for directory card. Trim screws are concealed behind a lockable door. Patented Feature! The trim screws do not enter the wire way to prevent conductor damage. 18 30 32 29 42 35 QJ2 QJH2 QJ2-H 18 30 42 18 30 42 29 35 41 29 35 41 FXD6 FD6 HFD6 18 30 42 32 38 44 (1) #6 AWG-300 kcmil CFD6 18 30 42 44 50 56 (1) #6 AWG-300 kcmil 18 30 42 54 47 53 59 65 (1) #3/0 AWG500 kcmil Cu or (2) #4/0 AWG500 kcmil Al Main Breaker Main Lugs 3 Phase 4 Wire, 3 Phase 3 Wire (No SN) JXD6, JD6, HJD6, SJD6 SHJD6 (1) #12-1/0 AWG (1) #12-1/0 AWG (1) #1 AWG-300 kcmil CJD6 SCLD6 18 30 42 54 56 62 68 74 (1) #3/0 AWG500 kcmil Cu or (2) #4/0 AWG500 kcmil Al 600s LXD6,LD6 HLD6, SLD6 SHLD6 SCLD6 18 30 42 54 50 56 62 68 (2) #3/0 AWG500 kcmil Cu or (2) #4/0 AWG500 kcmil Al 600s CLD6 SCLD6 18 30 42 54 59 65 71 77 (2) #3/0 AWG500 kcmil Cu or (2) #4/0 AWG500 kcmil Al Main Lug Panels Max. Amps. Max. No. of Polesf Unit Space (H) Ht. (In.) 100 18 30 42 9 15 21 23 29 35 (1) #12-1/0 AWG 225 18 30 42 9 15 21 26 32 38 (1) #6 AWG-300 kcmil 400a 18 30 42 54 9 15 21 27 32 38 44 50 (1) 250-500 kcmil or (2) #3/0 AWG250 kcmil 600s 18 30 42 54 9 15 21 27 38 44 50 56 (2) #3/0 AWG500 AWG Typical Panelboard Wiring Diagrams PBIS-4107F (Supersedes 4.1-7E) BL, BLH, HBQ BQ, BQDl ED4, ED6, HED4, HHED6 Connectors Suitable for Cu or Al 400a Notes: E) Bussing: Bus bars and breaker branch bus is tin finished aluminum per UL 67 unless otherwise stated. 1 Phase 3 Wire Max. (H) No. of Ht. Poles f (In.) CED6 B) Main Lugs: Suitable for copper or aluminum wire. Main Breaker Main Lugs Main Breaker Types Connectors Suitable for Cu or Al Side Gutter Wiring Space (Inches) Branch Breaker Side BL, BLH, HBL BL, BLH, HBL A BLF, BLHF B C A BLF, BLHF BQD BQD BQD6 BQD6 Panel Width 20” A 5.75” B 5.125” C 4.0” Dd 5.0” B ED2, ED4, ED6 ED2, ED4, ED6 HED4, HHED6 HED4, HHED6 C QJ2, QJH2, QJ2-H D Reference Point D a A 7.75” deep box is required for 400 ampere panels when main bus is 750 amps/square inch aluminum or 1000 amps/square inch copper, or when JXD2, JXD6, JD6 or HJD6 breakers are used as subfeed breakers. s A 7.75” deep box is required d Single branch mounting construction QJ2, QJH2, QJ2-H Panel Width 20” Branch Circuit Breakers g ; Ampere Breaker No. of Ampere Height 120V 120 /240V Frame Frame Poles Rating (Inches) AC AC Max. Interrupting Rating Symmetrical RMS Amperes 240V AC 277V AC 480Y/ 277V AC 480V AC 600Y/347V AC 125V DC 250V DC BL 1 2 2 3 15-60 15-100 15-100 15-100 1 2 2 3 — — — — 10,000 10,000 — — — — 10,000 10,000 — — — — — — — — — — — — — — — — — — — — — — — — BLH 1 2 3 15-60 15-100 15-100 1 2 3 — — — 22,000 22,000 — — — 22,000 — — — — — — — — — — — — — — — — — — HBL 1 2 3 15-60 15-100 15-100 1 2 3 — — — 65,000 65,000 — — — 65,000 — — — — — — — — — — — — — — — — — — BQD 1 2 3 15-100 15-100 15-100 1 2 3 — 14,000 14,000 — — — — — — — — — — — — A 1 2 3 15-70 15-70 15-70 1 2 3 — — — — — — — — — — — — — — — — — — 10,000 10,000 10,000 — — — — — — ED2 1 2 3 15-100 15-100 15-100 1 2 3 10,000 — — — — — — 10,000 10,000 — — — — — — — — — — — — 5,000 — — 5,000 — ED4 1 2 3 15-100 15-125 15-125 1 2 3 65,000 — — — — — — 65,000 65,000 22,000 — — — — — — 18,000 18,000 — — — 5,000 — — — 30,000 — ED6 2 3 15-125 15-125 2 3 — — — — 65,000 65,000 — — — — 25,000 25,000 18,000 18,000 — — 30,000 — 1 15-30 35-100 15-100 110-125 15-100 110-125 1 100,000 100,000 — — — — — — — — — — — — 100,000 100,000 100,000 100,000 65,000 25,000 — — — — — — — — — — — — 42,000 25,000 42,000 25,000 — — — — — — 30,000 30,000 — — — — — — 30,000 30,000 — — — — — — 100,000 100,000 100,000 100,000 — — — — — — — — 42,000 42,000 42,000 42,000 25,000 25,000 25,000 25,000 — — — — 30,000 30,000 — — 100 l BQD6 65,000 — — — — — — 14,000 65,000 — 65,000 — 125 HED4 2 3 2 225 2 3 HHED6 3 15-100 110-125 15-100 110-125 2 3 — — — — QJ2 2 3 60-225 60-225 6 hj 6jk — — — — 10,000 10, 000 — — — — — — — — — — — — QJH2 2 3 60-225 60-225 6hj 6jk — — — — 22,000 22,000 — — — — — — — — — — — — QJ2-H 2 60-225 6hj — — 42,000 — — — — — — f 1” per pole breakers double branch mounted g Branch breakers have non-interchangeable trip units h For additional 2-pole QJ breakers add 3” each j Combinations of 2-pole & 3-pole QJ breakers may require less space k For additional 3-pole QJ breakers add 6” each l Not for use on 480V delta systems ; All main and branch devices are bolted to the bus bars A CSA listed only at 600Y/347V AC PBIS-4107F (Supersedes 4.1-7E) Sentron™ Distribution and Power Panelboards TYPES S4 / S5 Main Breaker 1200A Maximum Main Breaker / Main Lugs 600V AC, 250V DC Maximum, 1:3W, 3:3W, 3:4W Panel Type Ampere Rating Specifications A) General: S4/ S5 panels comply with the following standards: a) NEMA Standards PB-1, 250 b) UL Standards 1) Enclosure — UL 50 2) Panelboards — UL 67 c) National Electric Code (NFPA 70) d) Federal Specification W-P-115b Horizontal Mounted Main Breaker Connectors 400 JXD6, JD6 HJD6, CJD6, SJD6 SHJD6, SCJD6, HHJD6 (2) - #3/0 AWG-500 kcmil (Cu) (2) - #4/0 AWG-500 kcmil (Al) 600 LXD6, LD6, HLD6 CLD6, SLD6, SHLD6 SCLD6, HHLD6 (2) - #4/0 AWG-500 kcmil (Cu) (2) - #3/0 AWG 500 kcmil (Al) 800 MD6, HMD6, CMD6, LMD6 SMD6, SHMD6, SCMD6, LMXD6 (2) - #1/0 AWG-500 kcmil (Cu/Al) ND6, HND6, CND6 SND6, SHND6, SCND6 (4) - 250 kcmil-500 kcmil (Cu/Al) S4 S5 1200 B) Main Devices: Suitable for copper or aluminum wire. Main devices are bolted to the bus bars. C) Bussing: Bus Bars are tin-plated aluminum per UL 67 unless otherwise stated. Main Lug Panels Panel Type D) Construction: Box is constructed of code gauge steel. Knockouts are not provided. Includes non-insulated ground bus as standard. Suitable for use as service entrance equipment when specified on order. Ampere Rating Connectors Suitable for Cu or Al 400 (1) - #3/0 AWG-500 kcmil or (2) - #3/0 AWG-250 kcmil 600 (2) - #3/0 AWG-500 kcmil S4/S5 800 (3) - #3/0 AWG-500 kcmil S4/S5 1200 (4) - #3/0 AWG-500 kcmil S4 Notes: Type 3R/12 Enclosure Type S4 S5 NEMA Type W D Type 1 32 10 Type 3R/12 32 10 Type 1 38 12.75 Type 3R/12 38 14.25 a See reverse for enclosure selection PBIS-4109D (Supersedes 4.1-9C) a Branch Circuit Breakers Ampere Frame af Mounting Height (Inches) Breaker Ampere Rating Breaker Type Twin Mounted Single Mounted Minimum Width Box (Inches) Max. Interrupting Rating Symmetrical RMS Amperes 240V 480V 600V BL BLH HBL BQD BQD6g 15-100 15-100 15-100 15-100 15-100 3.75 3.75 3.75 3.75 3.75 — — — — — 32 32 32 32 32 10,000 22,000 65,000 65,000 — — — — 14,000 — — — — — 10,000 ED2 15-100 3.75 — 32 10,000 — — ED4 3.75 — 32 65,000 18,000 — 3.75 — 32 65,000 25,000 18,000 3.75 — 32 100,000 42,000 — 3.75 — 32 100,000 42,000 25,000 CED6 15-100 110-125 15-100 110-125 15-100 110-125 15-100 110-125 15-100 3.75 — 32 200,000 200,000 100,000 225 QJ2 QJH2 QJ2-H 125-225 125-225 125-225 5 5 5 — — — 32 32 32 10,000 22,000 42,000 — — — — — — 250 FXD6, FD6 HFD6 CFD6 70-250 70-250 70-250 5 5 — — — 5 32 32 32 65,000 100,000 200,000 35,000 65,000 200,000 18,000 25,000 100,000 400 JXD2 JXD6, JD6, SJD6 HJD6, SHJD6 CJD6, SCJD6, HHJD6 200-400 200-400 200-400 200-400 s s s — 8.75 8.75 8.75 8.75 32 32 32 32 65,000 65,000 100,000 200,000 — 35,000 65,000 150,000 — 25,000 35,000 100,000 600 LXD6, LD6, SLD6 HLD6, SHLD6 CLD6, SCLD6, HHLD6 250-600 250-600 250-600 — — — 8.75 8.75 8.75 32 32 32 65,000 100,000 200,000 35,000 65,000 150,000 25,000 35,000 100,000 LMD6, LMXD6 500-800 — 8.75 38 65,000 50,000 25,000 800 MD6, SMD6 HMD6, SHMD6 CMD6, SCMD6 500-800 500-800 500-800 — — — 10 10 10 38 38 38 65,000 100,000 200,000 50,000 65,000 100,000 25,000 50,000 50,000 1200 ND6, SND6 HND6, SHND6 CND6, SCND6 800-1200 800-1200 800-1200 — — — 10 10 10 38 38 38 65,000 100,000 200,000 50,000 65,000 100,000 25,000 50,000 50,000 100 ED6 125 HED4 HHED6 d d a Branch breakers are bolted to the bus bars. s May be Twin Mounted. Requires 38” wide x 12.75” deep Enclosure. TYPE S4 d S5 Only f Will accept fusible switches, see F1/F2 for application. g CSA Listed only at 600VAC. f 32” Wide, 10” Deep 600A Maximum Breaker, 200A Fusible Switch ENCLOSURE SELECTION DATA Type 3R/12 Catalog Number Type 1 Catalog Number WP260 WP275 WP290 B60 B75 B90 Enclosure Height (Inches) 60 75 90 400 Available Circuit Space - (Inches) Main Lugs 600 800 1200 30 45 60 30 45 60 30 45 60 Main Breaker 400 600 30 45 60 — 36.25 51.25 — 36.25 51.25 TYPE S5 ENCLOSURE SELECTION DATA h 38” Wide, 12.75” Deep Type 1, 35” Wide, 14.25” Deep Type 3R/12 1200A Maximum Breaker, 600A Fusible Switch Type 3R/12 Catalog Number WP860 WP875 WP890 Type 1 Catalog Number B860 B875 B890 Enclosure Height (Inches) 60 75 90 Available Circuit Space - (Inches) Main Lugs Main Breaker 800 1200 800 1200 30 45 60 30 45 60 — 35 50 — 35 50 h Standard trim is four piece without door. Surface or flush one piece trim is available for 32” wide circuit breaker panel at no extra charge if specified on the order. Trim with door not available on S5 PBIS-4109D (Supersedes 4.1-9C) Sentron™ Lighting and Power Distribution Panelboards TYPE SE Main Breakers Main Breaker: 600A Maximum, Main Lugs Only: 600A Maximum SE: 208Y/120V. 1:3W, 120/240V. 1:3W, 208Y/120V. 3:4W, 240V. 3:3W, 480Y/277V. 3:4W, 480V. 3:3W, 600Y/347V. 3:4W, 600V. 3:3W Specifications A) General: SE panelboards comply with the following standards: a) NEMA Standards PB-1, 250 b) UL Standards 1) Enclosure — UL 50 2) Panelboards — UL 67 c) National Electric Code (NFPA 70) d) Federal Specification W-P-115b Trim Overlap Max. Amps. Main Breaker Types Max. (H) No. of Ht. Poles s (In.) Connectors Suitable for Cu or Al 125 ED4, ED6 HED4, HHED6 30 42 44 50 (1) #12-1/0 AWG 250 FXD6, HFD6 30 42 44 50 (1) #6AWG 350 kcmil 400 JXD6 HJD6, HHJD6 42 68 (2) #3/0-500 kcmil Cu or (2) #4/0-500 kcmil Al 600 LXD6 HLD6, HHLD6 42 68 (2) #3/0-500 kcmil Cu or (2) #4/0-500 kcmil Al Flush Mounting Box Depth( D )= 7.75” B) Main Breakers: ED4, ED6, HED4, HHED6, FXD6, HFD6, JXD6, HJD6, LXD6 and HLD6 All main breakers are bolted to the bus bars. Main breakers are mounted horizontally Main Lug Panels Main Lug and Main Breaker Gutter Max. Amps. C) Box: Fabricated from galvanized or galvanealed steel. Removable end walls. D) Bussing: Bus bars are tin plated aluminum per UL 67 unless otherwise stated. Breaker branch bus is tin plated aluminum. (H) Ht. (In.) Connectors Suitable for Cu or Al 125 30 42 15 21 44 50 (1) #6 AWG-350 kcmil 250 30 42 15 21 44 50 (1) #6 AWG-350 kcmil 400 42 21 68 (2) #3/0-500 kcmil 600 42 21 68 (2) #3/0-500 kcmil a 1” per pole breakers double branch mounted. Main Lug and Main Breaker Gutters Max. Main Lug Main Breaker Amps (ML) (MB) E) Front: Fabricated from cold rolled steel and equipped with concealed hinges, flush lock and a holder for directory card. Trim screws are concealed behind a lockable door. Max. No. of Unit Poles a Space 125 250 400 600 5.5” 7.0” 11.0” 14.0” Typical Panelboard Wiring Diagrams 8.125” 7.250” 8.00” 8.00” Main Breaker Main Breaker 1 Phase 3 Wire 3 Phase 4 Wire, 3 Phase 3 Wire (No SN) Main Lugs Main Lugs 1 Phase 3 Wire 3 Phase 4 Wire, 3 Phase 3 Wire (No SN) Notes: Side Gutter Wiring Space (Inches) Reference Letter A Panel Width 24” 6.00 Branch Breaker Side Gutters A ED4, ED6 ED4, ED6 Panel Width 24” PBIS-4112A (New) A HED4, HHED6 HED4, HHED6 Branch Circuit Breakers a (All Breakers Are Bolt-On) Ampere Breaker No. of Ampere Height Frame Frame Poles Rating (Inches) 120 / 240V AC 240V AC ED2 1 2 3 15- 100 15-100 15-100 1 2 3 10,000 — — — — — — 10,000 10,000 ED4 1 2 3 15- 100 15- 125 15- 125 1 2 3 65,000 — — — — — ED6 2 3 15-125 15-125 2 3 — — — — 1 15-30 35-100 15- 100 110-125 15- 100 110-125 1 100,000 100,000 — — — — — — — — — — 15- 100 110-125 15-100 110-125 2 — — — — 125 HED4 2 3 2 250 120V AC 2 3 Max. Interrupting Rating Symmetrical RMS Amperes 277V AC 480Y/ 277V AC 480V AC 600V AC 125V DC 250V DC — — — — — — — — — — — — — 22,000 65,000 — 65,000 — — — — — 18,000 18,000 — — — 65,000 65,000 — — 25,000 25,000 18,000 18,000 — — 30,000 — — 65,000 — 25,000 100,000 — 100,000 — 100,000 — 100,000 — — — — — — — — — 42, 000 25, 000 42 ,000 25,000 — — — — — — 30,000 30,000 — — — — — — 30,000 30,000 — — — — — — 100,000 100,000 100,000 100,000 — — — — — — — — 42 ,000 42, 000 42, 000 42, 000 25,000 25,000 25,000 25,000 — — — — 30,000 30,000 — — — — — — — 5,000 — — 5,000 5,000 — — 30,000 — HHED6 3 FXD6 2 3 70- 250 s — — 65,000 — — 35,000 18,000 — 30,000 FD6 2 3 70- 250 s — — 65,000 — — 35, 000 18,000 — 30,000 HFD6 2 3 70-250 s — — 100,000 — — 65, 000 25,000 — 30,000 JXD6 2 3 200-400 s — — 65,000 — — 35, 000 25,000 — 30,000 HJD6 2 3 200-400 s — — 100,000 — — 65,000 35,000 — 35,000 LXD6 2 3 250-600 s — — 65,000 — — 35,000 25,000 — 30,000 HLD6 2 3 250-600 s — — 100,000 — — 65,000 35,000 — 35,000 3 400 600 a Branch breakers have non-interchangeable trip units. s Mounted as subfeed at opposite end of incoming feed. Limit one per panel. Cannot be combined with feed thru lugs. PBIS-4112A(New) Sentron™ Distribution and Power Panelboards TYPES F1/ F2 Main Lug Panels 1200A Maximum Main Switch 1200A Maximum Main Lugs 600V AC, 250V DC Maximum, 1:3W, 3:3W, 3:4W Panel Type Ampere Rating F1 400 (1) - #3/0 AWG-500 kcmil (2) - #3/0 AWG-250 kcmil 600 (2) - #3/0 AWG-500 kcmil 800 (3) - #3/0 AWG-500 kcmil 1200 (4) - #3/0 AWG-500 kcmil Specifications A) General: F1/ F2 panels comply with the following standards: a) NEMA Standards PB-1, 250 b) UL Standards 1) Enclosure — UL 50 2) Panelboard — UL 67 c) National Electric Code (NFPA 70) d) Federal Specification W-P-115b a F1/F2 Connectors Suitable for Cu or Al a Alternate lugs for 750 kcmil cable are available, but result in significant loss of branch unit mounting space. Consult local sales office. Main Switch Panels Panel Type B) Main Devices: Suitable for copper or aluminum wire. 100-600A switches supplied with NEC fuse clips. Class R, J or T clips are optional. 800 / 1200A switches have class L fuse clips. All main devices are bolted to the bus bars. Ampere Rating Connectors Suitable for Cu or Al 100 (1) - #10-#1/0 AWG (Cu or Al) 200 (1) - #6 AWG-300 kcmil 400 s (2) - #3/0 AWG-500 kcmil or (2) - #3/0 AWG 250 kcmil 600 (2) - #3/0 AWG-500 kcmil 800 (3) - #3/0 AWG-500 kcmil 1200 (4) - #3/0 AWG-500 kcmil F1 F2 C) Bussing: Bus Bars are tin-plated aluminum per UL 67 unless otherwise stated. s Alternate lugs for 750 kcmil cable are available, but result in significant loss of branch unit mounting space. Consult local sales office. D) Construction: Enclosure is constructed of code gauge coated steel. Knockouts are not provided. Includes non-insulated ground bus as standard. Suitable for use as service entrance equipment when specified on order. Notes: E) UL Short Circuit Rating: NEC fuses — 10,000, Class “R” , “J” and “T” — 200,000 Class “L” — 200,000 Type 1 Enclosure Type 3R/12 Enclosure d Type F1 F2 NEMA Type W D 10 Type 1 32 Type 3R/12 32 10 Type 1 38 12.75 Type 3R/12 38 14.25 d See reverse for enclosure selection PBIS-4111C (Supersedes 4.1-11B) d TYPE F1 ENCLOSURE SELECTION DATA a 32” Wide, 10” Deep 200A Fusible Switch Type 3R/12 Catalog Number Type 1 Catalog Number WP260 WP275 WP290 Enclosure Height (Inches) B60 B75 B90 Available Circuit Space - (Inches) Main Lugs 60 75 90 TYPE F2 ENCLOSURE SELECTION DATA Main Switch 400 600 800 1200 100 200 30 45 60 30 45 60 30 45 60 30 45 60 20 35 — 20 35 — a 38” Wide, 12.75” Deep Type 1 38” Wide, 14.25” Deep Type 3R / 12 1200A Maximum Fusible Switch Type 3R/12 Catalog Number WP860 WP875 WP890 Type 1 Catalog Number Enclosure Height (Inches) B860 B875 B890 Main Lugs 60 75 90 Available Circuit Space - (Inches) Main Switch 400 600 800 1200 400 600 800 1200 30 45 60 30 45 60 30 45 60 30 45 60 — 25.0 40.0 — 25.0 40.0 — — 36.25 — — 36.25 a Standard trim is four piece without door. Door on type 1 not available. Switch Amperes Panel Width (in Inches) 32 (F1) 38 (F2) A 1200 800 — — 12.0 12.0 H 1200 800 — — 12.0 12.0 B 600 400 — — 9.3 9.3 I 600 400 — — 8.5 8.5 10.0 13.0 5.0 7.0 8.0 10.0 Reference Letter Reference Letter 600V AC Panel Width (in Inches) 32 (F1) 38 (F2) Switch Amperes 250V AC C 200 7.5 10.5 J 200 D E 100 200 /200 7.5 5.0 10.5 8.0 K L 200 /200 100 /100 F 100 /100 5.0 8.0 M 60 /60 10.0 13.0 G 30 /30 60 /60 7.0 7.0 10.0 10.0 N 30 /30 10.0 13.0 Cables Per Connector Connectors Suitable for Copper or Aluminum 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 3 2 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 3 2, 3 3 2, 3 2, 3 2, 3 2, 3 240 240 240 240 240 240 240 240 240 240 240 600 600 600 600 600 600 600 600 600 600 600 600 600 600 1 1 1 1 1 1 1 1 1 2 2 3 3 1 1 1 1 1 1 1 1 2 2 3 3 #14-#8 AWG (Cu Only) #14-#4 AWG #14-#4 AWG #14-#4 AWG #10-#1/0 AWG #10-#1/0 AWG #6 AWG-350 kcmil #6 AWG-350 kcmil #6 AWG-350 kcmil #4/0 AWG-500 kcmil #4/0 AWG-500 kcmil #3/0 AWG-500 kcmil #3/0 AWG-500 kcmil #14-#4 AWG #14-#4 AWG #14-#4 AWG #10-#1/0 AWG #10-#1/0 AWG #6 AWG-350 kcmil #10-#1/0 AWG #6 AWG-350 kcmil #4/0 AWG-500 kcmil #4/0 AWG-500 kcmil #3/0 AWG-500 kcmil #3/0 AWG-500 kcmil 2.5 5 5 5 7.5 7.5 10 — — — — — — 7.5 7.5 7.5 7.5 7.5 10 — — — — — — — — — — — — — 7.5 10 15 15 16.25 16.25 — — — — — — 7.5 10 15 15 16.25 16.25 600V AC AQ : : : : BQ CQ DQ EQ FQ GQ : : : : : : EQ Q Q Q Q 30 /30 30 /30 30/60 60 /60 F1/F2 60 /100 100 /100 200/200 200 200 400 600 F2 800 1200 30 /30 30/60 60 /60 60 /100 F1/F2 100 /100 200/200 100 200 400 600 F2 800 1200 AC Voltage KQ FQ GQ 250V AC Q Q Q Q Q Q Q Ampere Rating Mounting Height (in Inches) Number Twin Single of Poles Mounted Mounted Q Q Q Panel Type Vacu-Break Switch Side Gutter Wiring Space sd Q Q Q Q Q Q Q Branch Switches HQ Q JQ KQ LQ MQ NQ : : : I : : : : : : : : LQ MQ NQ s Note: Will accept circuit breakers. See S4/S5 panels for application. d All Branch Devices are bolted to the bus. PBIS-4111C (Supersedes 4.11B)