Sentron™ Lighting and Power Distribution Panelboards TYPES S1/ S2

advertisement
Sentron™ Lighting and Power Distribution Panelboards
TYPES S1/ S2
Main Breakers
Main Breaker: 600A Maximum,
Main Lugs Only: 600A Maximum
S1: 240V Maximum, 3:4W, 1:3W
S2: 480Y/277V Maximum 3:4W
Max.
Amps.
Specifications
100
A) General:
S1/ S2 panelboards comply with the
following standards:
a) NEMA Standards PB-1, 250
b) UL Standards
1) Enclosure — UL 50
2) Panelboards — UL 67
c) National Electric Code (NFPA 70)
d) Federal Specification W-P-115b
125
225
Trim
Overlap
B) Main Breakers:
BL, BLH, BQD, ED4, ED6, FD6,
FXD6, HBL, HFD6, HED4, HHED6,
HJD6, HHJD6, HLD6, HHLD6 JXD6,
LXD6, QJ2, QJ2H, QJH2 Main
breakers are bolted to the bus bars.
Flush Mounting
Box Depth( D )= 5.75”for
125A, 250A
7.75” for
400A, 600A
Box Width( W )= 20” for
100A - 250A
24” for
400A, 600A
C) Box:
Fabricated from galvanized or
galvanealed steel. Removable
end walls.
E) Front:
Fabricated from cold rolled steel
and equipped with concealed
hinges, flush lock and a holder for
directory card. Trim screws are
concealed behind a lockable door.
Patented Feature! The trim screws
do not enter the wire way to
prevent conductor damage.
Panel
Width 20”
Panel
Width 24”
A
6.375
7.750
B
5.500
7.125
C
6.125
6.000
Da
6.500
8.500
E
5.250
7.250
F
—
8.000
G
—
8.000
a Panel limited to (1) Subfeed at 250
amperes and (2) Subfeeds at 400
and 600 amperes.
PBIS-4106C (Supersedes 4.1-6B)
BL, BLH, HBL
BQD, ED4
ED4, ED6,
HED4, HHED6
QJ2
QJH2
QJ2-H
Connectors
Suitable for
Cu or Al
18
30
42
32
38
44
(1) #12-1/0 AWG
18
30
42
32
38
44
(1) #1 AWG-300 kcmil
250
FXD6
FD6
HFD6
18
30
42
32
38
44
(1) #6 AWG-350 kcmil
400
JXD6
HJD6
42
68
(2) #3/0-500 kcmil
(2) #4/0-500 kcmil Al
600
LXD6
HLD6
42
68
(2) #3/0-500 kcmil Cu
or
(2) #4/0-500 kcmil Al
Max.
Amps.
Max.
No. of
Poless
Unit
Space
(H)
Ht.
(In.)
Connectors
Suitable for
Cu or Al
125
18
30
42
9
15
21
32
38
44
(1) #H6 AWG-350 kcmil
250
18
30
42
9
15
21
32
38
44
(1) #6 AWG-350 kcmil
400
42
21
68
(2) #3/0-500 kcmil
600
42
21
68
(2) #3/0-500 kcmil
s 1” per pole breakers double branch mounted.
Main Lug and
Main Breaker Gutters
Typical Panelboard Wiring Diagrams
Max. Main Lug Main Breaker
Amps
(ML)
(MB)
Side Gutter Wiring Space
(Inches)
Reference
Letter
Max.
(H)
No. of
Ht.
Poless (In.)
Main Lug Panels
Main Lug and
Main Breaker
Gutter
D) Bussing:
Bus bars are tin plated aluminum
per UL 67 unless otherwise stated.
Breaker branch bus is tin finished
copper.
Main
Breaker
Types
125
250
400
600
5.5”
7.0”
11.0”
14.0”
B
C
D
E
F
G
BL, BLH, HBL
BL, BLH, HBL
BLF, BLHF
BLF, BLHF
BQD
Main Breaker
1 Phase 3 Wire
3 Phase 4 Wire,
3 Phase 3 Wire (No SN)
Main Lugs
Main Lugs
1 Phase 3 Wire
3 Phase 4 Wire,
3 Phase 3 Wire (No SN)
5.75”
5.0”
14.0”
15.5”
Branch Breaker Side Gutters
A
Main Breaker
BQD
ED, ED4, ED6, HED4,HHED6
QJ2, QJH2, QJ2-Ha
FXD6, FD6, HFD6
JXD6, HJD6
LXD6, HLD6
A
B
C
D
E
F
G
Branch Circuit Breakers
ad
Ampere Breaker No. of Ampere Height 120V
Frame Frame Poles Rating (Inches) AC
100
BL
1
2
2
3
15- 60
15 -100
15-100
15- 100
1
2
2
3
—
—
—
—
10,000
10,000
10,000
10,000
BLH
1
2
3
15-600
15- 100
15-100
1
2
3
—
—
—
22,000
22,000
—
HBL
1
2
3
15-600
15-100
15-100
1
2
3
—
—
—
65,000
65,000
—
BQD
1
2
3
15-60
15-100
15-100
1
2
3
1
2
3
15-70
15-90
15-100
1
2
3
ED2
1
2
3
15- 100
15-100
15-100
s
s
s
10,000
—
—
—
—
—
—
10,000
10,000
ED4
1
2
3
15- 100
15- 125
15- 125
s
s
s
65,000
—
—
—
—
—
2
3
15- 125
15- 125
s
s
—
—
—
—
1
15-30
35-100
15-100
110- 125
15-100
110- 125
s
100,000
100,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
BQD6
f
ED6
125
HED4
2
3
250
s
s
65,000
—
—
—
—
—
277V AC 480Y/ 277V AC 480V AC 600Y/347V AC 125V DC 250V DC
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
22,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
65,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
14,000
14,000
—
—
—
—
—
—
14,000
—
—
—
14,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
22,000
65,000
—
65,000
—
—
—
—
—
18,000
18,000
—
—
—
65,000
65,000
—
—
25,000
25,000
18,000
18,000
—
—
30,000
—
—
65,000
—
25,000
100,000
—
100,000
—
100,000
—
100,000
—
—
—
—
—
—
—
—
—
42,000
25,000
42,000
25,000
—
—
—
—
—
—
30,000
30,000
—
—
—
—
—
—
30,000
30,000
—
—
—
—
—
—
100,000
100,000
100,000
100,000
—
—
—
—
—
—
—
—
42,000
42,000
42,000
42,000
25,000
25,000
25,000
25,000
—
—
—
—
30,000
30,000
—
—
—
—
—
—
—
—
—
—
—
—
Max. Interrupting Rating Symmetrical RMS Amperes
—
14,000
65,000
—
65,000
—
—
—
—
—
—
10,000
10,000
10,000
—
—
—
5,000
—
—
5,000
5,000
—
—
30,000
—
15- 100
110- 125
15-100
110- 125
s
2
3
60-225
60-225
s
s
—
—
—
—
10,000
10,000
—
—
—
—
—
—
—
—
—
—
—
—
QJH2
2
3
60-225
60-225
s
s
—
—
—
—
22,000
22,000
—
—
—
—
—
—
—
—
—
—
—
—
QJ2-H
2
3
60-225
60-225
s
s
—
—
—
—
42,000
42,000
—
—
—
—
—
—
—
—
—
—
—
—
FXD6
2,3
70-250
s
—
—
65,000
—
—
35,000
18,000
—
30,000
FD6
2,3
70-250
s
—
—
65,000
—
—
35,000
18,000
—
30,000
HFD6
2,3
70-250
s
—
—
100,000
—
—
65,000
25,000
—
30,000
JXD6
2,3
200-400
s
—
—
65,000
—
—
35,000
25,000
—
30,000
HJD6
2,3
200-400
s
—
—
100,000
—
—
65,000
35,000
—
35,000
LXD6
2,3
250-600
s
—
—
65,000
—
—
35,000
25,000
—
30,000
HLD6
2,3
250-600
s
—
—
100,000
—
—
65,000
35,000
—
35,000
2
225
120 / 240V 240V
AC
AC
HHED6
3
QJ2
s
400
600
a Branch breakers have non-interchangeable trip units.
s Mounted as subfeed at opposite end of incoming feed. Limit one per
panel. Limit two QJ subfeeds on 400 and 600 amps. Cannot be
combined with feed thru lugs.
d Branch breakers are bolted to the bus bars.
f CSA Listed only at 600Y/347V AC.
PBIS-4106C (Supersedes 4.1-6B)
Sentron™ Lighting and Power Distribution Panelboards
TYPES S3
Main Breakers
600A Maximum Main Breaker / Main Lugs
600V AC, 250 DC Maximum,
1:3W, 3:3W, 3:4W
Max.
Amps.
Specifications
A) General:
S3 panelboards comply with the
following standards:
a) NEMA Standards PB-1
b) UL Standards
1) Enclosure — UL 50
2) Panelboards — UL 67
c) National Electric Code (NFPA 70)
d) Federal Specification W-P-115b
100
125
Trim
Overlap
Flush Mounting
C) Main Breakers: ;
D) Box:
Fabricated from galvanized or
galvanealed steel. Removable
end walls.
225
Box Depth( D )= 5.75”for
100A, 225A, 400A
Box Width( D)= 7.75” for
400Aa, 600As
BL, BLH, HBL, BQD, ED4, ED6,
HED4, HHED6, CED6, QJ2, QJH2,
QJ2-H, FXD6, FD6 and HFD6 main
breakers are mounted horizontally.
CFD6, JXD2, JXD6, JD6, HJD6, CJD6,
SJD6, SHJD6, SCJD6, LXD6, LD6,
HLD6, CLD6, SLD6, SHLD6 and
SCLD6 are mounted vertically. JD6,
HJD6, HHJD6, CJD6, SJD6, SHJD6,
SCJD6, LD6, HHLD6, HLD6, CLD6,
SLD6, SHLD6 and SCLD6 must be
mounted at top only.
400a
F) Front:
Fabricated from cold rolled steel
and equipped with concealed
hinges, flush lock and a holder for
directory card. Trim screws are
concealed behind a lockable door.
Patented Feature! The trim screws
do not enter the wire way to prevent
conductor damage.
18
30
32
29
42
35
QJ2
QJH2
QJ2-H
18
30
42
18
30
42
29
35
41
29
35
41
FXD6
FD6
HFD6
18
30
42
32
38
44
(1) #6 AWG-300 kcmil
CFD6
18
30
42
44
50
56
(1) #6 AWG-300 kcmil
18
30
42
54
47
53
59
65
(1) #3/0 AWG500 kcmil Cu or
(2) #4/0 AWG500 kcmil Al
Main Breaker
Main Lugs
3 Phase 4 Wire,
3 Phase 3 Wire (No SN)
JXD6, JD6,
HJD6, SJD6
SHJD6
(1) #12-1/0 AWG
(1) #12-1/0 AWG
(1) #1 AWG-300 kcmil
CJD6
SCLD6
18
30
42
54
56
62
68
74
(1) #3/0 AWG500 kcmil Cu or
(2) #4/0 AWG500 kcmil Al
600s
LXD6,LD6
HLD6, SLD6
SHLD6
SCLD6
18
30
42
54
50
56
62
68
(2) #3/0 AWG500 kcmil Cu or
(2) #4/0 AWG500 kcmil Al
600s
CLD6
SCLD6
18
30
42
54
59
65
71
77
(2) #3/0 AWG500 kcmil Cu or
(2) #4/0 AWG500 kcmil Al
Main Lug Panels
Max.
Amps.
Max.
No. of
Polesf
Unit
Space
(H)
Ht.
(In.)
100
18
30
42
9
15
21
23
29
35
(1) #12-1/0 AWG
225
18
30
42
9
15
21
26
32
38
(1) #6 AWG-300 kcmil
400a
18
30
42
54
9
15
21
27
32
38
44
50
(1) 250-500 kcmil
or
(2) #3/0 AWG250 kcmil
600s
18
30
42
54
9
15
21
27
38
44
50
56
(2) #3/0 AWG500 AWG
Typical Panelboard Wiring Diagrams
PBIS-4107F (Supersedes 4.1-7E)
BL, BLH, HBQ
BQ, BQDl
ED4, ED6,
HED4, HHED6
Connectors
Suitable for
Cu or Al
400a
Notes:
E) Bussing:
Bus bars and breaker branch bus is
tin finished aluminum per UL 67
unless otherwise stated.
1 Phase 3 Wire
Max.
(H)
No. of
Ht.
Poles f (In.)
CED6
B) Main Lugs:
Suitable for copper or aluminum wire.
Main Breaker
Main Lugs
Main
Breaker
Types
Connectors
Suitable for
Cu or Al
Side Gutter Wiring
Space (Inches)
Branch Breaker Side
BL, BLH, HBL BL, BLH, HBL
A
BLF, BLHF
B
C
A
BLF, BLHF
BQD
BQD
BQD6
BQD6
Panel Width
20”
A
5.75”
B
5.125”
C
4.0”
Dd
5.0”
B
ED2, ED4, ED6
ED2, ED4, ED6
HED4, HHED6
HED4, HHED6
C
QJ2, QJH2, QJ2-H
D
Reference
Point
D
a A 7.75” deep box is required for 400 ampere
panels when main bus is 750 amps/square
inch aluminum or 1000 amps/square inch
copper, or when JXD2, JXD6, JD6 or HJD6
breakers are used as subfeed breakers.
s A 7.75” deep box is required
d Single branch mounting construction
QJ2, QJH2, QJ2-H
Panel Width 20”
Branch Circuit Breakers g ;
Ampere Breaker No. of Ampere Height 120V 120 /240V
Frame Frame Poles Rating (Inches) AC
AC
Max. Interrupting Rating Symmetrical RMS Amperes
240V
AC
277V AC 480Y/ 277V AC 480V AC 600Y/347V AC 125V DC 250V DC
BL
1
2
2
3
15-60
15-100
15-100
15-100
1
2
2
3
—
—
—
—
10,000
10,000
—
—
—
—
10,000
10,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
BLH
1
2
3
15-60
15-100
15-100
1
2
3
—
—
—
22,000
22,000
—
—
—
22,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
HBL
1
2
3
15-60
15-100
15-100
1
2
3
—
—
—
65,000
65,000
—
—
—
65,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
BQD
1
2
3
15-100
15-100
15-100
1
2
3
—
14,000
14,000
—
—
—
—
—
—
—
—
—
—
—
—
A
1
2
3
15-70
15-70
15-70
1
2
3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
10,000
10,000
10,000
—
—
—
—
—
—
ED2
1
2
3
15-100
15-100
15-100
1
2
3
10,000
—
—
—
—
—
—
10,000
10,000
—
—
—
—
—
—
—
—
—
—
—
—
5,000
—
—
5,000
—
ED4
1
2
3
15-100
15-125
15-125
1
2
3
65,000
—
—
—
—
—
—
65,000
65,000
22,000
—
—
—
—
—
—
18,000
18,000
—
—
—
5,000
—
—
—
30,000
—
ED6
2
3
15-125
15-125
2
3
—
—
—
—
65,000
65,000
—
—
—
—
25,000
25,000
18,000
18,000
—
—
30,000
—
1
15-30
35-100
15-100
110-125
15-100
110-125
1
100,000
100,000
—
—
—
—
—
—
—
—
—
—
—
—
100,000
100,000
100,000
100,000
65,000
25,000
—
—
—
—
—
—
—
—
—
—
—
—
42,000
25,000
42,000
25,000
—
—
—
—
—
—
30,000
30,000
—
—
—
—
—
—
30,000
30,000
—
—
—
—
—
—
100,000
100,000
100,000
100,000
—
—
—
—
—
—
—
—
42,000
42,000
42,000
42,000
25,000
25,000
25,000
25,000
—
—
—
—
30,000
30,000
—
—
100
l
BQD6
65,000
—
—
—
—
—
—
14,000
65,000
—
65,000
—
125
HED4
2
3
2
225
2
3
HHED6
3
15-100
110-125
15-100
110-125
2
3
—
—
—
—
QJ2
2
3
60-225
60-225
6 hj
6jk
—
—
—
—
10,000
10, 000
—
—
—
—
—
—
—
—
—
—
—
—
QJH2
2
3
60-225
60-225
6hj
6jk
—
—
—
—
22,000
22,000
—
—
—
—
—
—
—
—
—
—
—
—
QJ2-H
2
60-225
6hj
—
—
42,000
—
—
—
—
—
—
f 1” per pole breakers double branch mounted
g Branch breakers have non-interchangeable trip units
h For additional 2-pole QJ breakers add 3” each
j Combinations of 2-pole & 3-pole QJ breakers may require less space
k For additional 3-pole QJ breakers add 6” each
l Not for use on 480V delta systems
; All main and branch devices are bolted to the bus bars
A CSA listed only at 600Y/347V AC
PBIS-4107F (Supersedes 4.1-7E)
Sentron™ Distribution and Power Panelboards
TYPES S4 / S5
Main Breaker
1200A Maximum Main Breaker / Main Lugs
600V AC, 250V DC Maximum,
1:3W, 3:3W, 3:4W
Panel
Type
Ampere
Rating
Specifications
A) General:
S4/ S5 panels comply with the following
standards:
a) NEMA Standards PB-1, 250
b) UL Standards
1) Enclosure — UL 50
2) Panelboards — UL 67
c) National Electric Code (NFPA 70)
d) Federal Specification W-P-115b
Horizontal Mounted
Main Breaker
Connectors
400
JXD6, JD6
HJD6, CJD6, SJD6
SHJD6, SCJD6, HHJD6
(2) - #3/0 AWG-500 kcmil (Cu)
(2) - #4/0 AWG-500 kcmil (Al)
600
LXD6, LD6, HLD6
CLD6, SLD6, SHLD6
SCLD6, HHLD6
(2) - #4/0 AWG-500 kcmil (Cu)
(2) - #3/0 AWG 500 kcmil (Al)
800
MD6, HMD6, CMD6, LMD6
SMD6, SHMD6, SCMD6, LMXD6
(2) - #1/0 AWG-500 kcmil (Cu/Al)
ND6, HND6, CND6
SND6, SHND6, SCND6
(4) - 250 kcmil-500 kcmil (Cu/Al)
S4
S5
1200
B) Main Devices:
Suitable for copper or aluminum wire.
Main devices are bolted to the bus bars.
C) Bussing:
Bus Bars are tin-plated aluminum per UL 67
unless otherwise stated.
Main Lug Panels
Panel
Type
D) Construction:
Box is constructed of code gauge steel.
Knockouts are not provided.
Includes non-insulated ground bus as standard. Suitable for use as service entrance
equipment when specified on order.
Ampere
Rating
Connectors
Suitable for Cu or Al
400
(1) - #3/0 AWG-500 kcmil or
(2) - #3/0 AWG-250 kcmil
600
(2) - #3/0 AWG-500 kcmil
S4/S5
800
(3) - #3/0 AWG-500 kcmil
S4/S5
1200
(4) - #3/0 AWG-500 kcmil
S4
Notes:
Type 3R/12 Enclosure
Type
S4
S5
NEMA Type
W
D
Type 1
32
10
Type 3R/12
32
10
Type 1
38
12.75
Type 3R/12
38
14.25
a See reverse for enclosure selection
PBIS-4109D (Supersedes 4.1-9C)
a
Branch Circuit Breakers
Ampere
Frame
af
Mounting Height
(Inches)
Breaker
Ampere
Rating
Breaker Type
Twin
Mounted
Single
Mounted
Minimum
Width
Box
(Inches)
Max. Interrupting Rating
Symmetrical RMS Amperes
240V
480V
600V
BL
BLH
HBL
BQD
BQD6g
15-100
15-100
15-100
15-100
15-100
3.75
3.75
3.75
3.75
3.75
—
—
—
—
—
32
32
32
32
32
10,000
22,000
65,000
65,000
—
—
—
—
14,000
—
—
—
—
—
10,000
ED2
15-100
3.75
—
32
10,000
—
—
ED4
3.75
—
32
65,000
18,000
—
3.75
—
32
65,000
25,000
18,000
3.75
—
32
100,000
42,000
—
3.75
—
32
100,000
42,000
25,000
CED6
15-100
110-125
15-100
110-125
15-100
110-125
15-100
110-125
15-100
3.75
—
32
200,000
200,000
100,000
225
QJ2
QJH2
QJ2-H
125-225
125-225
125-225
5
5
5
—
—
—
32
32
32
10,000
22,000
42,000
—
—
—
—
—
—
250
FXD6, FD6
HFD6
CFD6
70-250
70-250
70-250
5
5
—
—
—
5
32
32
32
65,000
100,000
200,000
35,000
65,000
200,000
18,000
25,000
100,000
400
JXD2
JXD6, JD6, SJD6
HJD6, SHJD6
CJD6, SCJD6, HHJD6
200-400
200-400
200-400
200-400
s
s
s
—
8.75
8.75
8.75
8.75
32
32
32
32
65,000
65,000
100,000
200,000
—
35,000
65,000
150,000
—
25,000
35,000
100,000
600
LXD6, LD6, SLD6
HLD6, SHLD6
CLD6, SCLD6, HHLD6
250-600
250-600
250-600
—
—
—
8.75
8.75
8.75
32
32
32
65,000
100,000
200,000
35,000
65,000
150,000
25,000
35,000
100,000
LMD6, LMXD6
500-800
—
8.75
38
65,000
50,000
25,000
800
MD6, SMD6
HMD6, SHMD6
CMD6, SCMD6
500-800
500-800
500-800
—
—
—
10
10
10
38
38
38
65,000
100,000
200,000
50,000
65,000
100,000
25,000
50,000
50,000
1200
ND6, SND6
HND6, SHND6
CND6, SCND6
800-1200
800-1200
800-1200
—
—
—
10
10
10
38
38
38
65,000
100,000
200,000
50,000
65,000
100,000
25,000
50,000
50,000
100
ED6
125
HED4
HHED6
d
d
a Branch breakers are bolted to the bus bars.
s May be Twin Mounted. Requires 38” wide x 12.75” deep Enclosure.
TYPE S4
d S5 Only
f Will accept fusible switches, see F1/F2 for application.
g CSA Listed only at 600VAC.
f
32” Wide, 10” Deep
600A Maximum Breaker, 200A Fusible Switch
ENCLOSURE SELECTION DATA
Type 3R/12
Catalog
Number
Type 1
Catalog
Number
WP260
WP275
WP290
B60
B75
B90
Enclosure
Height
(Inches)
60
75
90
400
Available Circuit Space - (Inches)
Main Lugs
600
800
1200
30
45
60
30
45
60
30
45
60
Main Breaker
400
600
30
45
60
—
36.25
51.25
—
36.25
51.25
TYPE S5
ENCLOSURE SELECTION DATA h
38” Wide, 12.75” Deep Type 1, 35” Wide, 14.25” Deep Type 3R/12
1200A Maximum Breaker, 600A Fusible Switch
Type 3R/12
Catalog
Number
WP860
WP875
WP890
Type 1
Catalog
Number
B860
B875
B890
Enclosure
Height
(Inches)
60
75
90
Available Circuit Space - (Inches)
Main Lugs
Main Breaker
800
1200
800
1200
30
45
60
30
45
60
—
35
50
—
35
50
h Standard trim is four piece without door. Surface or flush one piece trim is available for 32” wide circuit breaker
panel at no extra charge if specified on the order. Trim with door not available on S5
PBIS-4109D (Supersedes 4.1-9C)
Sentron™ Lighting and Power Distribution Panelboards
TYPE SE
Main Breakers
Main Breaker: 600A Maximum,
Main Lugs Only: 600A Maximum
SE: 208Y/120V. 1:3W, 120/240V. 1:3W,
208Y/120V. 3:4W, 240V. 3:3W,
480Y/277V. 3:4W, 480V. 3:3W,
600Y/347V. 3:4W, 600V. 3:3W
Specifications
A) General:
SE panelboards comply with the
following standards:
a) NEMA Standards PB-1, 250
b) UL Standards
1) Enclosure — UL 50
2) Panelboards — UL 67
c) National Electric Code (NFPA 70)
d) Federal Specification W-P-115b
Trim
Overlap
Max.
Amps.
Main
Breaker
Types
Max.
(H)
No. of
Ht.
Poles s (In.)
Connectors
Suitable for
Cu or Al
125
ED4, ED6
HED4, HHED6
30
42
44
50
(1) #12-1/0 AWG
250
FXD6,
HFD6
30
42
44
50
(1) #6AWG 350 kcmil
400
JXD6
HJD6, HHJD6
42
68
(2) #3/0-500 kcmil Cu
or
(2) #4/0-500 kcmil Al
600
LXD6
HLD6, HHLD6
42
68
(2) #3/0-500 kcmil Cu
or
(2) #4/0-500 kcmil Al
Flush Mounting
Box Depth( D )= 7.75”
B) Main Breakers:
ED4, ED6, HED4, HHED6, FXD6,
HFD6, JXD6, HJD6, LXD6 and
HLD6 All main breakers are bolted
to the bus bars. Main breakers are
mounted horizontally
Main Lug Panels
Main Lug and
Main Breaker
Gutter
Max.
Amps.
C) Box:
Fabricated from galvanized or
galvanealed steel. Removable
end walls.
D) Bussing:
Bus bars are tin plated aluminum
per UL 67 unless otherwise stated.
Breaker branch bus is tin plated
aluminum.
(H)
Ht.
(In.)
Connectors
Suitable for
Cu or Al
125
30
42
15
21
44
50
(1) #6 AWG-350 kcmil
250
30
42
15
21
44
50
(1) #6 AWG-350 kcmil
400
42
21
68
(2) #3/0-500 kcmil
600
42
21
68
(2) #3/0-500 kcmil
a 1” per pole breakers double branch mounted.
Main Lug and
Main Breaker Gutters
Max. Main Lug Main Breaker
Amps
(ML)
(MB)
E) Front:
Fabricated from cold rolled steel
and equipped with concealed
hinges, flush lock and a holder for
directory card. Trim screws are
concealed behind a lockable door.
Max.
No. of
Unit
Poles a Space
125
250
400
600
5.5”
7.0”
11.0”
14.0”
Typical Panelboard Wiring Diagrams
8.125”
7.250”
8.00”
8.00”
Main Breaker
Main Breaker
1 Phase 3 Wire
3 Phase 4 Wire,
3 Phase 3 Wire (No SN)
Main Lugs
Main Lugs
1 Phase 3 Wire
3 Phase 4 Wire,
3 Phase 3 Wire (No SN)
Notes:
Side Gutter
Wiring Space (Inches)
Reference
Letter
A
Panel
Width 24”
6.00
Branch Breaker Side Gutters
A
ED4, ED6
ED4, ED6
Panel Width 24”
PBIS-4112A (New)
A
HED4, HHED6 HED4, HHED6
Branch Circuit Breakers a (All Breakers Are Bolt-On)
Ampere Breaker No. of Ampere Height
Frame Frame Poles Rating (Inches)
120 / 240V
AC
240V
AC
ED2
1
2
3
15- 100
15-100
15-100
1
2
3
10,000
—
—
—
—
—
—
10,000
10,000
ED4
1
2
3
15- 100
15- 125
15- 125
1
2
3
65,000
—
—
—
—
—
ED6
2
3
15-125
15-125
2
3
—
—
—
—
1
15-30
35-100
15- 100
110-125
15- 100
110-125
1
100,000
100,000
—
—
—
—
—
—
—
—
—
—
15- 100
110-125
15-100
110-125
2
—
—
—
—
125
HED4
2
3
2
250
120V
AC
2
3
Max. Interrupting Rating Symmetrical RMS Amperes
277V AC 480Y/ 277V AC 480V AC 600V AC 125V DC 250V DC
—
—
—
—
—
—
—
—
—
—
—
—
—
22,000
65,000
—
65,000
—
—
—
—
—
18,000
18,000
—
—
—
65,000
65,000
—
—
25,000
25,000
18,000
18,000
—
—
30,000
—
—
65,000
—
25,000
100,000
—
100,000
—
100,000
—
100,000
—
—
—
—
—
—
—
—
—
42, 000
25, 000
42 ,000
25,000
—
—
—
—
—
—
30,000
30,000
—
—
—
—
—
—
30,000
30,000
—
—
—
—
—
—
100,000
100,000
100,000
100,000
—
—
—
—
—
—
—
—
42 ,000
42, 000
42, 000
42, 000
25,000
25,000
25,000
25,000
—
—
—
—
30,000
30,000
—
—
—
—
—
—
—
5,000
—
—
5,000
5,000
—
—
30,000
—
HHED6
3
FXD6
2
3
70- 250
s
—
—
65,000
—
—
35,000
18,000
—
30,000
FD6
2
3
70- 250
s
—
—
65,000
—
—
35, 000
18,000
—
30,000
HFD6
2
3
70-250
s
—
—
100,000
—
—
65, 000
25,000
—
30,000
JXD6
2
3
200-400
s
—
—
65,000
—
—
35, 000
25,000
—
30,000
HJD6
2
3
200-400
s
—
—
100,000
—
—
65,000
35,000
—
35,000
LXD6
2
3
250-600
s
—
—
65,000
—
—
35,000
25,000
—
30,000
HLD6
2
3
250-600
s
—
—
100,000
—
—
65,000
35,000
—
35,000
3
400
600
a Branch breakers have non-interchangeable trip units.
s Mounted as subfeed at opposite end of incoming feed. Limit one per panel. Cannot be combined with feed thru lugs.
PBIS-4112A(New)
Sentron™ Distribution and Power Panelboards
TYPES F1/ F2
Main Lug Panels
1200A Maximum Main Switch
1200A Maximum Main Lugs
600V AC, 250V DC Maximum, 1:3W,
3:3W, 3:4W
Panel Type
Ampere Rating
F1
400
(1) - #3/0 AWG-500 kcmil
(2) - #3/0 AWG-250 kcmil
600
(2) - #3/0 AWG-500 kcmil
800
(3) - #3/0 AWG-500 kcmil
1200
(4) - #3/0 AWG-500 kcmil
Specifications
A) General:
F1/ F2 panels comply with the following
standards:
a) NEMA Standards PB-1, 250
b) UL Standards
1) Enclosure — UL 50
2) Panelboard — UL 67
c) National Electric Code (NFPA 70)
d) Federal Specification W-P-115b
a
F1/F2
Connectors Suitable for Cu or Al
a Alternate lugs for 750 kcmil cable are available, but result in significant loss of
branch unit mounting space. Consult local sales office.
Main Switch Panels
Panel Type
B) Main Devices:
Suitable for copper or aluminum wire.
100-600A switches supplied with NEC fuse clips.
Class R, J or T clips are optional.
800 / 1200A switches have class L fuse clips.
All main devices are bolted to the bus bars.
Ampere Rating
Connectors Suitable for Cu or Al
100
(1) - #10-#1/0 AWG (Cu or Al)
200
(1) - #6 AWG-300 kcmil
400 s
(2) - #3/0 AWG-500 kcmil or
(2) - #3/0 AWG 250 kcmil
600
(2) - #3/0 AWG-500 kcmil
800
(3) - #3/0 AWG-500 kcmil
1200
(4) - #3/0 AWG-500 kcmil
F1
F2
C) Bussing:
Bus Bars are tin-plated aluminum per UL 67
unless otherwise stated.
s Alternate lugs for 750 kcmil cable are available, but result in significant loss
of branch unit mounting space. Consult local sales office.
D) Construction:
Enclosure is constructed of code gauge
coated steel.
Knockouts are not provided.
Includes non-insulated ground bus as standard.
Suitable for use as service entrance equipment
when specified on order.
Notes:
E) UL Short Circuit Rating:
NEC fuses — 10,000,
Class “R”
, “J” and “T” — 200,000
Class “L” — 200,000
Type 1 Enclosure
Type 3R/12 Enclosure
d
Type
F1
F2
NEMA Type
W
D
10
Type 1
32
Type 3R/12
32
10
Type 1
38
12.75
Type 3R/12
38
14.25
d See reverse for enclosure selection
PBIS-4111C (Supersedes 4.1-11B)
d
TYPE F1
ENCLOSURE SELECTION DATA
a
32” Wide, 10” Deep
200A Fusible Switch
Type 3R/12
Catalog
Number
Type 1
Catalog
Number
WP260
WP275
WP290
Enclosure
Height
(Inches)
B60
B75
B90
Available Circuit Space - (Inches)
Main Lugs
60
75
90
TYPE F2
ENCLOSURE SELECTION DATA
Main Switch
400
600
800
1200
100
200
30
45
60
30
45
60
30
45
60
30
45
60
20
35
—
20
35
—
a
38” Wide, 12.75” Deep Type 1
38” Wide, 14.25” Deep Type 3R / 12
1200A Maximum Fusible Switch
Type 3R/12
Catalog
Number
WP860
WP875
WP890
Type 1
Catalog
Number
Enclosure
Height
(Inches)
B860
B875
B890
Main Lugs
60
75
90
Available Circuit Space - (Inches)
Main Switch
400
600
800
1200
400
600
800
1200
30
45
60
30
45
60
30
45
60
30
45
60
—
25.0
40.0
—
25.0
40.0
—
—
36.25
—
—
36.25
a Standard trim is four piece without door. Door on type 1 not available.
Switch
Amperes
Panel Width (in Inches)
32 (F1)
38 (F2)
A
1200
800
—
—
12.0
12.0
H
1200
800
—
—
12.0
12.0
B
600
400
—
—
9.3
9.3
I
600
400
—
—
8.5
8.5
10.0
13.0
5.0
7.0
8.0
10.0
Reference
Letter
Reference
Letter
600V AC
Panel Width (in Inches)
32 (F1)
38 (F2)
Switch
Amperes
250V AC
C
200
7.5
10.5
J
200
D
E
100
200 /200
7.5
5.0
10.5
8.0
K
L
200 /200
100 /100
F
100 /100
5.0
8.0
M
60 /60
10.0
13.0
G
30 /30
60 /60
7.0
7.0
10.0
10.0
N
30 /30
10.0
13.0
Cables Per
Connector
Connectors Suitable
for Copper
or Aluminum
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
3
2
3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
3
2, 3
3
2, 3
2, 3
2, 3
2, 3
240
240
240
240
240
240
240
240
240
240
240
600
600
600
600
600
600
600
600
600
600
600
600
600
600
1
1
1
1
1
1
1
1
1
2
2
3
3
1
1
1
1
1
1
1
1
2
2
3
3
#14-#8 AWG (Cu Only)
#14-#4 AWG
#14-#4 AWG
#14-#4 AWG
#10-#1/0 AWG
#10-#1/0 AWG
#6 AWG-350 kcmil
#6 AWG-350 kcmil
#6 AWG-350 kcmil
#4/0 AWG-500 kcmil
#4/0 AWG-500 kcmil
#3/0 AWG-500 kcmil
#3/0 AWG-500 kcmil
#14-#4 AWG
#14-#4 AWG
#14-#4 AWG
#10-#1/0 AWG
#10-#1/0 AWG
#6 AWG-350 kcmil
#10-#1/0 AWG
#6 AWG-350 kcmil
#4/0 AWG-500 kcmil
#4/0 AWG-500 kcmil
#3/0 AWG-500 kcmil
#3/0 AWG-500 kcmil
2.5
5
5
5
7.5
7.5
10
—
—
—
—
—
—
7.5
7.5
7.5
7.5
7.5
10
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5
10
15
15
16.25
16.25
—
—
—
—
—
—
7.5
10
15
15
16.25
16.25
600V AC
AQ
:
:
:
:
BQ
CQ
DQ
EQ
FQ
GQ
:
:
:
:
:
:
EQ
Q
Q
Q
Q
30 /30
30 /30
30/60
60 /60
F1/F2
60 /100
100 /100
200/200
200
200
400
600
F2
800
1200
30 /30
30/60
60 /60
60 /100
F1/F2
100 /100
200/200
100
200
400
600
F2
800
1200
AC
Voltage
KQ
FQ
GQ
250V AC
Q
Q
Q
Q
Q
Q
Q
Ampere
Rating
Mounting Height
(in Inches)
Number Twin
Single
of Poles Mounted Mounted
Q
Q
Q
Panel
Type
Vacu-Break Switch
Side Gutter Wiring Space
sd
Q
Q
Q
Q
Q
Q
Q
Branch Switches
HQ
Q
JQ
KQ
LQ
MQ
NQ
:
:
:
I
:
:
:
:
:
:
:
:
LQ
MQ
NQ
s Note: Will accept circuit breakers.
See S4/S5 panels for application.
d All Branch Devices are bolted
to the bus.
PBIS-4111C (Supersedes 4.11B)