Specifications Main Breaker: 400A Maximum Main Lugs only: 400A Maximum Voltages: 480Y/277V AC Maximum 250V DC Maximum 3Ø3W, 3Ø4W, 1Ø3W, 1Ø2W General — P1 panelboards comply the with following standards: NEMA Standards PB-1, 250 UL Standards - Enclosure — UL 50 - Panelboards — UL 67 National Electric Code (NFPA 70) Federal Specification W-P 115c Main Breakers — BL, BLH, BQD, NGB, FD6, FXD6, HBL, HFD6, HFXD6,HJD6, JD6, JXD6, HJXD6, ED2, ED4, ED6, HED4, HED6, HFXD6, QJ2, QJ2H and QJH2 main breakers are bolted to the busbars. Box — Fabricated from galvanized steel. Removable end walls. Bussing — Main bus is tin plated aluminum temperature rated per UL 67 as a standard. See panel submittals for optional call outs. Branch bus is copper as a standard. Copper bus is available as option. Front — Fabricated from cold rolled steel and equipped with the concealed hinges, flush lock and a holder for directory card. Trim screws are concealed behind a lockable door. type P1 Overview — P1 Panelboards Lighting and Power Distribution Panelboards Main Lug or Main Breakers Maximum Ampere Rating Main Breaker Types Maximum Number of Poles BL, BLH HBL BQD NGB 100 125 ED2, ED4 ED6, HED4 HED6 QJ2 QJH2 QJ2-H FXD6 FD6 HFD6, HFXD6 MLO 225 250 18 30 42 ≤250 JD6, JXD6, HJD6, HJXD6 MLO 400 18 30 42 Side Gutter Wiring Space Inches (mm) (Fig. P1-1) Box Height Inches (mm) Connectors Suitable for Cu or Al 32 (813) 38 (965) 44 (1118) 32 (813) 38 (965) 44 (1118) 32 (813) 38 (965) #8-#6 AWG Cu or Al #8-6 AWG Cu or #8-4 AWG Al #8-#1 AWG Cu or #6-#1/0 AWG Al 15-30 amp #14-#6 Cu or #12-#6 Al 35-125 amp #6-1/0 Cu. #4-2/0 Al #14-#10 AWG Cu or #12-10 AWG Al #3-3/0 Cu or 44 (1118)#1-2/0 Al #6 AWG-300 Kcmil (Cu) or #4 AWG-300 Kcmil (Al) #6 AWG-350 Kcmil (Cu) or #4 AWG-350 Kcmil (Al) 32 (813) 38 (365) 44 (1118) 32 (813) 38 (365) 44 (1118) 32 (813) 38 (365) 44 (1118) 56 (1422) 62 (1575) 68 (1727) 56 (1422) 62 (1575) 68 (1727) (1) #4 - 350 Kcmil 3/0-500 Kcmil (Cu) or 4/0-500 Kcmil (Al) (1) 250-600 Kcmil or (2) #3/0 - 500 Kcmil Fig. P1-1 Reference Letter Panel Width 20” Panel Width 24” Optional A B C D E F 6.375 (162) 5.500 (140) 5.000 (127) 6.125 (156) 6.500 (165) 5.250 (133) 8.375 (213) 7.500 (191) 7.000 (178) 8.125 (206) 8.500 (216) 7.250 (184) A Main Device Gutter BL, BLH, HBL BL, BLH, HBL ≤ 250A - MB A BLF, BLHF BLF, BLHF B BQD BQD B C NGB NGB C D 400A-MB All MLO ED2, ED4, ED6, HED4, HED6 E QJ2, QJH2, QJ2-H F FXD6, FD6, HFD6 Panel Width 20 in. (508 mm) Subfeed mounting limit 1 per panel. Main Breaker Gutter Dimensions Inches (mm) Main Breaker BL, BLH, HBL, BQD ED2, ED4, ED6, HED4 QJ2, QJH2, QJ2-H FD6, FXD6, HFD6 JD6, JXD6 Gutter 20” wide box 8.500 (216) 6.125 (156) 6.500 (165) 5.250 (133) 15.000 (381) 24” wide box 10.500 (267) 8.125 (206) 8.500 (216) 7.250 (184) 15.000 (381) Neutral Location 20” wide box 11.500 (292) 11.500 (292) 11.500 (292) 11.500 (292) 26.750 (680) JD frame mounted vertically. Typical Panelboard Wiring Diagrams Main Breaker 1 Phase, 3 Wire Main Breaker 3 Phase, 4 Wire, 3 Phase, 3 Wire (No SN) Main Lugs 1 Phase, 3 Wire Main Lugs 3 Phase, 4 Wire, 3 Phase, 3 Wire (No SN) Breaker Mounting Kit – Main or Subfeed w/o Breaker 200% Neutral Lug Kits – 250A Amp Rating No. of Circuits Breaker Frames BL, BLH, HBL 100 BQD NGB 125 ED2, ED4, ED6, HED4, HED6 QJ2, QJH2, QJ2-H 225 FXD6, FD6, HFD 250 JD2, JD6, JXD6, HJD6, HJXD6 400 Service 1 Phase 3 Phase 3 Phase 1 Phase 3 Phase 1 Phase 3 Phase 1 Phase 3 Phase 1 Phase 3 Phase 1 Phase 3 Phase Catalog Number MBKBL1 MBKBL3 MBKBC3 MBKNB1 MBKNB3 MBKED1 MBKED3 MBKQJ1 MBKQJ3 MBKFD1 MBKFD3 MBKJD1 MBKJD3 18 30 42 Amp Rating Material No. of Circuits Al 250 Cu Al 400 Cu Catalog Service Number (1) #6 AWG-350 Kcmil (Cu or Al) (1) #6 AWG-350 Kcmil (Cu or Al) (1) #6 AWG-350 Kcmil (Cu or Al) (1) #6 AWG-350 Kcmil (Cu or Al) (2) 3/0 - (1) 600 Kcmil (2) 3/0 - (1) 600 Kcmil (2) 3/0 - (1) 600 Kcmil (2) 3/0 - (1) 600 Kcmil 1 Phase 3 Phase 1 Phase 3 Phase 1 Phase 3 Phase 1 Phase 1 Phase MLKA1 MLKA3 MLKC1 MLKC3 4MLKA1 4MLKA3 4MLKC1 4MLKC3 2NLK30 2NLK42 Catalog Number Description 2 Branch Neutral Strips, 4 Main Neutral Lug, Hardware 2 Branch Neutral Strips, 4 Main Neutral Lug, Hardware 2 Branch Neutral Strips, 4 Main Neutral Lug, Hardware 18 42 Wire Range 2NLK18 200% Neutral Lug Kits – 400A 30 Lug Kits – Main or Feed-thru Catalog Number Description 2 Branch Neutral Strips, 2 Main Neutral Lug, Hardware 2 Branch Neutral Strips, 2 Main Neutral Lug, Hardware 2 Branch Neutral Strips, 2 Main Neutral Lug, Hardware 42NLK18 42NLK30 42NLK42 Copper Neutral Lug Kits – 250A and 400A No. of Circuits Catalog Number Description 2 Branch Neutral Strips, 1 Main Neutral Lug, Hardware 2 Branch Neutral Strips, 1 Main Neutral Lug, Hardware 2 Branch Neutral Strips, 1 Main Neutral Lug, Hardware 18 30 42 CNLK18 CNLK30 CNLK42 Branch Circuit Breakers Max. Amp Rating Breaker Type BL BL HID BLR BLE BLEH BLF 100 BLHF BGL BAF BAFH BLH HBL BQD 125 NGB No. of Poles 1 2 3 1 2 2 1 2 1 2 1 2 1 3 2 3 1 1 1 2 3 1 2 3 1 2 3 1 2 3 Amp Rating 15 - 70 15 - 100 15 - 100 15 - 30 15 - 30 15 - 100 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 30 15, 20 15, 20 15 - 70 15 - 100 15 - 100 15 - 70 15 - 100 15 - 100 15 - 100 15 - 125 Maximum Interrupting Rating (kA) Volts – AC 120 120/240 240 277 480 10 — — — — — 10 — — — — — 10 — — 10 — — — — — 10 — — — — — 10 — — 10 — — — — — 10 — — — 22 — — — — — 22 — — — 10 — — — — — 10 — — — 22 — — — — — 22 — — — 10 — — — — — 10 — — — 10 — — — — 22 — — — — — 22 — — — — 22 — — — — — 22 — — — 65 — — — — 65 — — — — — 65 — — — 65 — 14 — — 65 — — 14 — — 65 — 14 600 — — — — — — — — — — — — — — — — — — — — — — — — — — — DC 250 — — — — — — — — — — — — — — — — — — — — — — — — 14 14 14 100 — — — — — 14 — — — 100 100 — 100 100 25 — — — 25 25 Main Only Two pole breaker is one phase and neutral. Three pole is two phase and neutral. P1 panel with NGB branch devices will not accept BL or BQD frames in the same panel as branch devices. NOTE: BL, HBL, BLH and BQD breakers are mounted in common mountings in 3” or (6) pole increments. Load Connectors 15-20A 25-35A 40-50A 55-70A 80-100A 15-40A 45-100A 15-30A 35-125 #14-#10 AWG Cu #12-#10 AWG Al #8-#6 AWG Cu #8-#6 AWG Al #8-#6 AWG Cu #8-#4 AWG Al #8-#4 AWG Cu #8-#2 AWG Al #4-#1/0 AWG Cu #2-#1/0 AWG Al #14-#6 AWG Cu #12-#6 AWG Al #8-#1 AWG Cu #6-#1/0 AWG Al #14-#6 Cu #12 - #6 Al #6-1/0 Cu #4-2/0 Al Modifications and Dimensions Panel Options, Enclosures • Extra gutter to sides or ends of the can • 24" wide boxes • Hinged trims • Door-in-door trims • Screw to the box trims • Trim mounted devices (Devices mountedand wired to the trim should also have hinged trim specified.) - Pilot lights - Toggle switches - Push buttons • Painted boxes • Custom colors • Increase gauge trims and boxes • Stainless steel trims and boxes, Type 1 • Aluminum trims and boxes, Type 1 • NEMA 3R enclosures • NEMA 3R/12 enclosures • NEMA 4 enclosures • NEMA 4X enclosures • Special keyed locks - TEY - TEU1 - Cat 60 - LL803 - LL806 - Yale • Meters (Contact application engineering for space requirements.) • Panel skirts • Gaskets between trim and box Type P1Dimensions Type 3R and 3R/12 Box Type 1 Box (Box is Symmetrical) Box To Wall Mounting Holes 2 in. [ 51 ] .31 in. [8] 7.5 in. [ 191 ] .50 in. [ 13 ] 2 in. [ 51 ] 4.63 in. [ 118 ] Mounting Dimple Interior To Box Mounting Stubs Mounting Bracket 32 in. 38 in. 44 in. [ 816 ] [ 969 ] [ 1222 ] 햲앱 56 in. 62 in. 68 in. [ 1428 ] [ 1581 ] [ 1734 ] 32 in. 38 in. 44 in. [ 813 ] [ 965 ] [ 1118 ] 햲 56 in. 62 in. 68 in. [ 1422 ] [ 1574 ] [ 1727 ] 2 in. [ 51 ] 4.63 in. [ 118 ] 12.63 in. [ 321 ] 15 in. [ 381 ] 2 in. [ 51 ] 2 in. [ 51 ] 5.75 in. [ 146 ] 햲 20 in. 햲 [ 510 ] 21.5 in. [ 546 ] 20 in. [ 508 ] 1 in. [25] 5.75 in. [ 146 ] 햲 23.5 in. [ 597 ] 햲 Flush Mounting ³⁄₄ in. [19 ] 20 in. [ 508 ] ³⁄₄ in. [19 ] 5.75 in. [ 146 ] Dimensions are interior of the box. Add 5/8” to width for absolute dimension. Add 1/8” to height for absolute dimension. Dimensions shown in inches and millimeters [ ]. Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 info.sea@siemens.com www.sea.siemens.com/power ©2007 Siemens Energy & Automation, Inc. All Rights Reserved Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. PBSS-20301-0407 1M0407PP Printed in USA Specifications Main Breaker: 600A Maximum Main Lugs only: 600A Maximum Voltages: 600V AC Maximum 250V DC Maximum 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W General — P2 panelboards comply the with following standards: NEMA Standards PB-1 UL Standards - Enclosure — UL 50 - Panelboards — UL 67 National Electric Code (NFPA 70) Federal Specification W-P 115c Main Breakers — BL, BLH, HBL, BQD, NGB, ED4, ED6, HED4, HHED6, CED6, QJ2, QJH2, QJ2-H, FXD6, FD6, HFD6 and HFXD6 main breakers are mounted horizontally. CFD6, JXD6, JD6, HJD6, CJD6, SJD6, SHJD6, LXD6, LD6, HJXD, HLD6, HLXD, CLD6, SLD6, SHLD6 and SCLD6 are mounted vertically. JD6, HJD6, CJD6, SJD6, SHJD6, LD6, HLD6, CLD6, SLD6, SHLD6 and SCLD6 must be mounted at top only. Box — Fabricated from galvanized steel. Removable end walls. Bussing — Busbars and breaker branch bus is tin-finished aluminum per UL 67 unless otherwise stated. See panel submittals for optional call outs. Copper bus is available as an option. Front — Fabricated from cold rolled steel and equipped with the concealed hinges, flush lock and a holder for directory card. Trim screws are concealed behind a lockable door. type P2 All main and branch devices are bolted to the bars Overview — P2 Panelboards Lighting and Power Distribution Panelboards Panel Unit Space To Box Height Requirements P2 Panels With Standard Line Lugs. Unit Space (starting with 9" and adding 6" increments) “A” Dimension “B” Main Breakers Dimen- Main Lugs sion 125A 250A 400A 600A 125A 125A 125A 225A 250A 250A 400A 400A Box Horiz. Horiz. Vert. Horiz. Horiz. Vert. JD CJD Height BL, BQD, CED ED QJ FD CFD NGB, ED 26 9 — — — 9 — — — — — — — 32 15 9 — — 15 9 9 9 — — — — 38 21 15 9 9 21 15 15 15 9 — — — 44 27 21 15 15 27 21 21 21 15 — — — 50 33 27 21 21 33 27 27 27 21 9 9 — 56 39 33 27 27 39 33 33 33 27 15 15 — 62 45 39 33 33 45 39 39 39 33 21 21 9 68 51 45 39 39 51 45 45 45 39 27 27 15 74 57 51 45 45 57 51 51 51 45 33 33 21 Main Breaker Selection Ampere Rating 100 Breaker Type BL (STD) BLH HBL BQD ED4 ED6 HED4 HHED6 CED6 ED4 (STD) ED6 NGB 125 225 250 400 600 HED4 HHED6 CED6 QJ2 (STD) QJH2 QJ2H FD6, FXD6 HFD6, HFXD6 CFD6 FD6, FXD6 (STD) HFD6, HFXD6 CFD6 JXD6 (STD), JD6 HJD6, HJXD6 SJD6 CJD6,SCJD6 LXD6 (STD), LD6 HLD6, HLXD6 SLD6 SHLD6 CLD6, SCLD6 600A CLD — — — — — 9 15 21 27 — — — — — — 9 15 21 Main Lug Connectors Maximum Interrupting Rating (kA) 240V 480V 600V Lug Wire Range 10 N/A N/A #8-#6 AWG Cu or Al 22 N/A N/A 65 N/A N/A 65 14 N/A #8-#1 AWG Cu or #6-#1/0 AWG Al 65 25 N/A #14-#10 AWG Cu or Al 100 42 18 #12-10 AWG 100 65 N/A #3-3/0 Cu or 100 65 25 #1-2/0 Al 200 200 100 #10-4 Cu or Al 65 18 N/A #14-#10 AWG Cu or 65 25 18 #12-10 AWG Al 100 25 — 15-30A #14-#6 Cu or #12-#6 Al 35-125A #6-1/0 Cu or #4-2/0 Al 100 42 N/A #3-3/0 Cu or 100 65 25 or #1-2/0 Al 200 200 100 #10-4 Cu or Al 10 N/A N/A #6 AWG-300 Kcmil (Cu) 22 N/A N/A or 42 N/A N/A #4 AWG-300 Kcmil Al 65 35 18 #6 AWG-350 Kcmil Cu 100 65 25 or 200 150 100 #4 AWG-350 Kcmil Al 65 35 18 #6 AWG-350 Kcmil Cu 100 65 25 or 200 150 100 #4 AWG-350 Kcmil Al 65 35 25 3/0-500 Kcmil Cu 100 65 35 or 65 35 25 4/0-500 Kcmil Al 200 200 100 65 35 25 100 65 35 3/0-500 Kcmil Cu 65 35 25 or 100 65 35 4/0-500 Kcmil Al 200 150 100 Branch Breaker Side Gutters Inches (mm) (Fig. P2-1) Reference Letter A B C D E 600A LD Panel Width 20” (508) 5.750 (146) 5.125 (130) 4.600 (117) 4.000 (102) 5.000 (127) Single branch mounting construction. Panel Amps Standard Connectors 125 250 400 (1) #14 - 2/0 (1) #6 AWG - 350 Kcmil (1) #4 AWG - 600 Kcmil or #6 250 Kcmil (2) #4 AWG - 500 Kcmil 600 Typical Panelboard Wiring Diagrams Main Breaker, Main Lugs 1 Phase 3 Wire 3 Phase 4 Wire, 3 Phase 3 Wire (No SN) Table P2-2 – Main Breaker (Fig. P2-2) Panel Amps 100 125 225 250 400 600 Breaker Frames BL BQD NGB ED QJ FD JD LD C 5.75 5.125 4.63 4.00 5.00 5.00 14.00 15.50 Fig. P2-2 Fig. P2-1 BL, BLH, HBL BL, BLH, HBL BLF, BLFH BLF, BLFH B BQD, BQD6 BQD, BQD6 B C NGB NGB C A D E ED, ED4, ED6 ED, ED4, ED6 HED4, HHED6 HED4, HHED6 QJ2, QJH2, QJ2-H, HQJ2H Panel Width 20 in. (508 mm) Interchangeable trip main breakers are mounted at top of panel only. For use on 480Y/277 volt systems not suitable for 480 delta 3 phase 3 wire systems. A D E Box depth = 5.75 in. (146 mm) Box width – 20 in. (508 mm) for 100-600A D 8.00 8.00 8.00 8.00 7.00 7.00 25.00 23.00 Standard Enclosures Box Height (in.) 26 32 38 44 50 56 62 68 74 Options For Type 1 Trims Catalog Number Type 1 - Standard Trim Box Surface B26 S26B B32 S32B B38 S38B B44 S44B B50 S50B B56 S56B B62 S62B B68 S68B B74 S74B Flush F26B F32B F38B F44B F50B F56B F62B F68B F74B Type 3R Type 3R/12 NR26 NR32 NR38 NR44 NR50 NR56 NR62 NR68 NR74 WP26 WP32 WP38 WP44 WP50 WP56 WP62 WP68 WP74 Items must be ordered as manual line item on Spartanburg Hinged trim – Replace “B” suffix with “H” Door-in-door – Replace “B” suffix with “D” Metal card holder – Replace “B” suffix with “M” on standard trim, add “M” suffix on optional trims Option For 24” Wide Enclosures with Equal Gutter on Both Sides 24” wide with equal gutter on both sides, add “24” as prefix Breaker Kits and Accessories Kit No. BBKB32 BBKNB32 BBKED32 BBKQ1 DFK1 DFFP3 DFFP6 BNK2 P2BK1 P2BK2 P2BK3 Description BL/BQD 6-pole 3” branch breaker kit NGB 6-pole 3” branch mounting kit ED 6-pole 3” branch breaker kit QJ branch breaker kit for 2 and 3-pole single mount BL, BQD, ED Dead front kit for 1” pole breakers Dead front filler 3” Dead front filler 6” Branch neutral (P2) P2 250A max. bonding kit P2 400A max. Bonding Kit P2 600A max. Bonding Kit Contents Kit contains top barrier, (3) A/C connectors, (1) B connector, hardware Kit contains breaker support, interphase barriers (3) A/C connectors, (1) B phase connector, hardware Kit contains breaker support, inter-phase barriers, (3) A/C connectors, (1) B connector, hardware Kit to contain all connectors and cover plates necessary to mount both 2 or 3-pole breakers Center strips 3”, 6”, 9,” 15,” 21” plus mounting hardware 3” empty space filler and hardware 6” empty space filler and hardware Three tier lug with mounting hardware to increase neutral capacity Bonding strap and hardware Bonding strap and hardware Bonding strap and hardware Branch Circuit Breakers Max. Amp Rating Bolt-On Breaker Type BL BL HID BLR BLE BLEH BLF BLHF 100 BGL BAF BAFH BLH HBL BQD NGB ED2 ED4 125 225 ED6 HED4 HHED6 QJ2 QJH2 QJ2-H HQJ2H No. of Poles 1 2 3 1 2 2 1 2 1 2 1 2 1 3 2 3 1 1 1 2 3 1 2 3 1 2 3 1 2,3 1 2,3 1 2 3 2 3 1 2 3 2&3 2&3 2&3 2&3 Amp Rating 15 - 70 15 - 100 15 - 100 15 - 30 15 - 30 15 - 100 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 30 15, 20 15, 20 15 - 70 15 - 100 15 - 100 15 - 70 15 - 100 15 - 100 15 - 100 15 - 125 15 - 125 15 - 125 15 - 125 15 - 125 60 - 225 60 - 225 60 - 225 100 - 225 Maximum Interrupting Rating (kA) Volts – AC 120 120/240 240 277 480 10 — — — — — 10 — — — — — 10 — — 10 — — — — — 10 — — — — — 10 — — 10 — — — — — 10 — — — 22 — — — — — 22 — — — 10 — — — — — 10 — — — 22 — — — — — 22 — — — 10 — — — — — 10 — — — 10 — — — — 22 — — — — — 22 — — — — 22 — — — — — 22 — — — 65 — — — — 65 — — — — — 65 — — — 65 — 14 — — 65 — — 14 — — 65 — 14 600 — — — — — — — — — — — — — — — — — — — — — — — — — — — DC 250 — — — — — — — — — — — — — — — — — — — — — — — — 14 14 14 Load Connectors 15-20A 25-35A 40-50A 55-70A 80-100A 15-40A 45-100A 100 — 10 — 100 — — 100 — 25 — — — — 25 — — — 14 — — 15-30A 35-125A 65 — — — — 100 — — — — — — — — — — — — — — — — — — — 65 65 65 65 — — 100 10 22 42 100 22 — — — — — 65 42 — — — — — 18 18 25 25 — — 42 — — — — — 30 — 30 — — — 30 — — — — 15-25A — — — 18 18 — — — — — — — 30-100A 100-125A 60-225A #14-#10 AWG Cu #12-#10 AWG Al #8-#6 AWG Cu #8-#6 AWG Al #8-#6 AWG Cu #8-#4 AWG Al #8-#4 AWG Cu #8-#2 AWG Al #4-#1/0 AWG Cu #2-#1/0 AWG Al #14-#6 AWG Cu #12-#6 AWG Al #8-#1 AWG Cu #6-#1/0 AWG Al #14-#6 Cu or #12 - #6 Al #6-1/0 Cu. #4-2/0 Al #14-#10 AWG Cu #12-#10 AWG Al #10-#1/0 Cu or Al #3-3/0 Cu #1-2/0 Al #6 AWG-300 Kcmil Cu #4 AWG-300 Kcmil Al NOTE: QJ Breakers are single mounted in nit space and take 6” of unit space. Limited to (3) per panel max. BL, HBL, HBL and BQD breakers are mounted in common mountings in 3” or (6) pole increments. ED2, ED4, ED6, HED4 and HHED6 breakers are mounted in common mountings in 3” or (6) pole increments. NGB breakers are mounted in common mounting in 3" or (6) pole increments. Two pole breaker is one phase and neutral. Three pole is two phase and neutral. For use on 480Y/277 volt systems not suitable for 480 delta 3 phase 3 wire systems. Modifications and Dimensions Panel Options, Enclosures • Extra gutter to sides or ends of the can • 24" wide boxes • Hinged trims • Door-in-door trims • Screw to the box trims • Trim mounted devices (Devices mounted and wired to the trim should also have hinged trim specified.) - Pilot lights - Toggle switches - Push buttons • Painted boxes • Custom colors • Increase gauge trims and boxes • Stainless steel trims and boxes, Type 1 • Aluminum trims and boxes, Type 1 • NEMA 3R enclosures • NEMA 3R/12 enclosures • NEMA 4 enclosures • NEMA 4X enclosures • Special keyed locks - TEY - TEU1 - Cat 60 - LL803 - LL806 - Yale • Meters (Contact application engineering for space requirements.) • Panel skirts • Gaskets between trim and box Type P2 Dimensions Type 3R and 3R/12 Box Type 1 Box (Box is Symmetrical) Box To Wall Mounting Holes 2 in. [ 51 ] 7.5 in. [ 191 ] .31 in. [8] .50 in. [ 13 ] 2 in. [ 51 ] 4.63 in. [ 118 ] Mounting Dimple Interior To Box Mounting Stubs Mounting Bracket 26 in. 32 in. 38 in. 26 in. 32 in. 38 in. 햲 [ 660 ] [ 816 ] [ 965 ] 44 in. 50 in. 56 in. [ 1118 ] [ 1270 ] [ 1422 ] 62 in. 68 in. 74 in. [ 1575 ] [ 1727 ] [ 1880 ] 햲 [ 660 ] [ 816 ] [ 965 ] 44 in. 50 in. 56 in. [ 1118 ] [ 1270 ] [ 1422 ] 62 in. 68 in. 74 in. [ 1575 ] [ 1727 ] [ 1880 ] 2 in. [ 51 ] 4.63 in. [ 118 ] 12.63 in. [ 322 ] 15 in. [ 381 ] 2 in. [ 51 ] 2 in. [ 51 ] 5.75 in. [ 146 ] 햲 20 in. [ 508 ] 20 in. 햲 [ 510 ] 21.5 in. [ 546 ] 1 in. [25] 5.75 in. [ 146 ] 햲 23.5 in. [ 597 ] 햲 Flush Mounting ³⁄₄ in. [19 ] 20 in. [ 508 ] ³⁄₄ in. [19 ] 5.75 in. [ 146 ] Dimensions are interior of the box. Add 5/8” to width for absolute dimension. Add 1/8” to height for absolute dimension. Dimensions shown in inches and millimeters [ ]. Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 info.sea@siemens.com www.sea.siemens.com/power ©2007 Siemens Energy & Automation, Inc. All Rights Reserved Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. PBSS-20302-0407 1M0407PP Printed in USA Specifications Main Breaker: 600A Maximum Main Lugs only: 800A Maximum Voltages: 600V AC Maximum 250V DC Maximum 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W General — P3 panelboards comply the with following standards: NEMA Standards PB-1 UL Standards - Enclosure — UL 50 - Panelboards — UL 67 National Electric Code (NFPA 70) Federal Specification W-P 115c Main Lugs – Suitable for copper or aluminum wire. Main Breakers — FXD6, FD6, HFD6 and HFXD6 main breakers are mounted horizontally. CFD6, JXD6, JD6, HJD6, HJXD6, SJD6, LXD6, LD6, HLD6 and HLXD6 are mounted vertically. CJD6, SCJD6, CLD6, SLD6, SHLD6 and SCLD6 must be mounted at top only. Box — Fabricated from galvanized steel. Removable end walls. Bussing — Busbars and breaker branch bus is tin-finished aluminum per UL 67 unless otherwise stated. See panel submittals for optional call outs. Copper bus is available as an option. Front — Fabricated from cold rolled steel and equipped with the concealed hinges, flush lock and a holder for directory card. Trim screws are concealed behind a lockable door. type P3 All main and branch devices are bolted to the bars Overview — P3 Panelboards Lighting and Power Distribution Panelboards Panel Unit Space To Box Height Requirements “B” Dimension Box Height 56 62 68 74 80 P3 Panels With Standard Line Lugs. Unit Space (starting with 9" and adding 6" increments) “A” Dimension Main Lugs Main Breakers 250A 400A 600A 800A 250A 250A 250A 400A 400A 600A Horiz. Vert. FD FD CFD JD CJD LD 27 21 21 21 21 15 9 9 — 9 33 27 27 27 27 21 15 15 9 15 39 33 33 33 33 27 21 21 15 21 45 39 39 39 39 33 27 27 21 27 51 45 45 45 45 39 33 33 27 33 600A CLD — 9 15 21 27 Main Breaker Selection Ampere Rating Maximum Interrupting Rating (kA) 240V 480V 600V 65 35 18 100 65 25 200 150 100 65 35 25 100 65 35 65 35 25 200 200 100 65 35 25 65 35 25 100 65 35 65 35 25 100 65 35 200 150 100 Breaker Type FD6, FXD6 (STD) HFD6, HFXD6 CFD6 JXD6 (STD), JD6 HJD6, HJXD6 SJD6 CJD6,SCJD6 LXD6 (STD) LD6 HLD6, HLXD6 SLD6, SHLD6 CLD6, SCLD6 250 400 600 Fig. P3-1 Lug Wire Range #6 AWG-350 Kcmil Cu or #4 AWG-30 Kcmil Al 3/0-500 Kcmil Cu or 4/0-500 Kcmil Al 3/0-500 Kcmil Cu or 4/0-500 Kcmil Al Table P3-1 – Gauge Steel of Boxes Fronts, Surface & Flush Dimensions in inches (mm) Width Height 24” 56 - 80 (610) (1422, 2032) Gauge Steel Box #16 Front #14 Typical Panelboard Wiring Diagrams Main Breaker Main Lugs Main Breaker Main Lugs 1 Phase, 3 Wire 3 Phase, 4 Wire, 3 Phase 3 Wire (No SN) Box depth = 7.75 in. (197 mm) Box width = 24 in. (610 mm) Branch Breaker Side Gutters Inches (mm) (Fig. P3-2) Reference Letter A B C D E F Fig. P3-2 Panel Width 24” (609) 7.750 (197) 7.125 (181) 6.620 (168) 6.440 (164) 6.000 (152) 7.000 (178) BL, BLH, HBL BL, BLH, HBL BLF, BLFH BLF, BLFH B BQD, BQD6 BQD, BQD6 B C NGB NGB C D A D E F Catalog Number Box Height (in.) 56 62 68 74 80 NEB, HEB ED, ED4, ED6 HED4, HHED6 HED4, HHED6 QJ2, QJH2, QJ2-H, HQJ2H QJ2, QJH2, QJ2-H, HQJ2H E F Panel Width 24 in. (610 mm) Standard Enclosures Type 1 Standard Trim Box 24WD56 24WD62 24WD68 24WD74 24WD80 NEB, HEB ED, ED4, ED6 A Surface P3S56 P3S62 P3S68 P3S74 P3S80 Flush P3F56 P3F62 P3F68 P3F74 P3F80 Interchangeable trip main breakers are mounted at top of panel only. Type 3R Type 3R/12 24NRD56 24NRD62 24NRD68 24NRD74 24NRD80 24WPD56 24WPD62 24WPD68 24WPD74 24WPD80 Options For Type 1 Trims Items must be ordered as manual line item on factory. Hinged trim – Add “H” suffix Door-in-door – Add “D” suffix Metal card holder – Add “M” suffix Breaker Kits and Accessories Kit No. Description Contents BBKB32 BL/BQD 6-pole 3” branch breaker kit Kit contains top barrier, (3) A/C connectors, (1) B connector, hardware Kit contains breaker support, interphase barriers (3) A/C connectors, (1) B phase connector, hardware Kit contains breaker support, interphase barriers (3) A/C connectors, (1) B phase connector, hardware Kit contains breaker support, inter-phase barriers, (3) A/C connectors, (1) B connector, hardware BBKNB32 NGB 6-pole 3" branch mounting kit BBKEB32 NEB /HEB 6 pole 3" branch breaker kit BBKED32 ED 6-pole 3” branch breaker kit QJ branch breaker kit for 2 and BBKQ1 3-pole single mount Branch breaker kit for 2 and 3-pole BBKQ2 QJ twin mount DFFP3 Deadfront filler 3” DFFP6 Deadfront filler 6” P3BK1 P3 bonding kit Filler plate for BL, BQD, ED frame QF3 branch breaker provisions Filler plate for NEB/HEB branch EBF1 breaker provision content Kit to contain all connectors and cover plates necessary to mount both 2 and 3-pole breakers Kit to contain all connectors and cover plates necessary to mount both 2 and 3-pole breakers 3” empty space filler and hardware 6” empty space filler and hardware Bonding strap and hardware 1” filler plate 1” filler plate Branch Circuit Breakers Max. Amp Rating Bolt-On Breaker Type BL BL HID BLR BLE BLEH BLF BLHF 100 BGL BAF BAFH BLH HBL BQD NGB NEB 125 HEB ED4 ED6 HED4 HHED6 225 QJ2 QJH2 QJ2-H HQJ2H No. of Poles 1 2 3 1 2 2 1 2 1 2 1 2 1 3 2 3 1 1 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 2 3 1 2 3 2&3 2&3 2&3 2&3 Amp Rating 15 - 70 15 - 100 15 - 100 15 - 30 15 - 30 15 - 100 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 60 15 - 30 15 - 30 15, 20 15, 20 15 - 70 15 - 100 15 - 100 15 - 70 15 - 100 15 - 100 15 - 100 15 - 125 15 - 125 15 - 125 15 - 125 15 - 125 15 - 125 60 - 225 60 - 225 60 - 225 100 - 225 Maximum Interrupting Rating (kA) Volts – AC 120 120/240 240 277 480 10 — — — — — 10 — — — — — 10 — — 10 — — — — — 10 — — — — — 10 — — 10 — — — — — 10 — — — 22 — — — — — 22 — — — 10 — — — — — 10 — — — 22 — — — — — 22 — — — 10 — — — — — 10 — — — 10 — — — — 22 — — — — — 22 — — — — 22 — — — — — 22 — — — 65 — — — — 65 — — — — — 65 — — — 65 — 14 — — 65 — — 14 — — 65 — 14 600 — — — — — — — — — — — — — — — — — — — — — — — — — — — DC 250 — — — — — — — — — — — — — — — — — — — — — — — — 14 14 14 100 — — — 100 100 — 100 100 25 — — — 25 25 — — — 14 — — 15-30A 85 — — 100 — — 65 — — — — 100 — — — — — — — 85 85 — 100 100 — — — — — — — — — — — — — 85 85 — 100 100 — 65 65 65 65 — — 100 10 22 42 100 35 — — 65 — — 22 — — — — — 65 42 — — — — — 35 35 — 65 65 — 18 18 25 25 — — 42 — — — — — — — — — — — — — 18 18 — — — — — — — — — — — — — — 30 — 30 — — — 30 — — — — 15-100 A 110-125A #14-#6 AWG Cu #12-#6 AWG Al #8-#1 AWG Cu #6-#1/0 AWG Al #14-#6 Cu #12 - #6 Al #6-1/0 Cu #4-2/0 Al #14-1/0 Al/Cu #6 - 3/0 Al/Cu 15-100A 110-125A #14-1/0 Al/Cu #6 - 3/0 Al/Cu 15-25A #14-#10 AWG Cu #12-#10 AWG Al #10-#1/0 Cu or Al #3-3/0 Cu #1-2/0 Al BL, HBL, BLH and BQD breakers are mounted in common mountings in 3” or 6 pole increments. NGB breakers are counted in common mountings of 3” or 6 pole increments. For use on 480Y/277 volt systems. Not suitable for 480 Delta 3 phase 3 wire systems. Load Connectors 15-20A 25-35A 40-50A 55-70A 80-100A 15-40A 45-100A 35-125A 30-100A 100-125A 60-225A #14-#10 AWG Cu #12-#10 AWG Al #8-#6 AWG Cu #8-#6 AWG Al #8-#6 AWG Cu #8-#4 AWG Al #8-#4 AWG Cu #8-#2 AWG Al #4-#1/0 AWG Cu #2-#1/0 AWG Al #6 AWG-300 Kcmil Cu #4 AWG-300 Kcmil Al NEB/HE breakers are counted in common mountings of 3” or 6 pole increments. ED4, ED6, HED4 and HHED6 breakers are mounted in common mountings in 3” or (6) pole increments. QJ Breakers are single mounted in unit space and take 6” of unit space. Limited to (3) per panel max. Modifications and Dimensions Panel Options, Enclosures • Extra gutter to sides or ends of the can • 24" wide boxes • Hinged trims • Door-in-door trims • Screw to the box trims • Trim mounted devices (Devices mounted and wired to the trim should also have hinged trim specified.) - Pilot lights - Toggle switches - Push buttons • Painted boxes • Custom colors • Increase gauge trims and boxes • Stainless steel trims and boxes, Type 1 • Aluminum trims and boxes, Type 1 • NEMA 3R enclosures • NEMA 3R/12 enclosures • NEMA 4 enclosures • NEMA 4X enclosures • Special keyed locks - TEY - TEU1 - Cat 60 - LL803 - LL806 - Yale • Gaskets between trim and box • Meters (Contact application engineering for space requirements.) • Panel skirts Type P1Dimensions Type 3R and 3R/12 Box Type 1 Box (Box is Symmetrical) Box To Wall Mounting Holes 2 in. [ 51 ] 9.5 in. [ 241 ] .31 in. [8] .50 in. [ 13 ] 2 in. [ 51 ] 7.625 in. [ 199 ] Mounting Dimple Interior To Box Mounting Stubs Mounting Bracket 햲 56 in. 62 in. 68 in. 햲 [ 1422 ] [ 1575 ] [ 1727 ] 74 in. 80 in. [ 1880 ] [ 2032 ] 56 in. 62 in. 68 in. [ 1422 ] [ 1575 ] [ 1727 ] 74 in. 80 in. [ 1880 ] [ 2032 ] 2 in. [ 51 ] 2 in. [ 51 ] 7.625 in. [ 199 ] 12.63 in. [ 322 ] 15 in. [ 381 ] 2 in. [ 51 ] 7.75 in. [ 197 ] 햲 24 in. 햲 [ 610 ] 25.5 in. [ 648 ] 24 in. [ 610 ] 1 in. [25] 7.75 in. [ 197 ] 햲 27.5 in. [ 699 ] 햲 Flush Mounting ³⁄₄ in. [19 ] 24 in. [ 610 ] ³⁄₄ in. [19 ] 7.75 in. [ 197 ] Dimensions are interior of the box. Add 5/8” to width for absolute dimension. Add 1/8” to height for absolute dimension. Dimensions shown in inches and millimeters [ ]. Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 info.sea@siemens.com www.sea.siemens.com/power ©2007 Siemens Energy & Automation, Inc. All Rights Reserved Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. PBSS-20303-0407 1M0407PP Printed in USA