Eaton WMZT Miniature Circuit Breakers

advertisement
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Miniature Circuit Breakers
Overview
Eaton WMZT miniature circuit breakers
offer optimum and efficient protection
for branch and control circuits up to 40
amps. The WMZT series is available with
C or D trip characteristics in accordance
with UL489. These circuit breakers are
current limiting, which means they interrupt fault currents within one half cycle
of the fault. The WMZT series is DIN-rail
mountable and can be used in branch
circuit applications.
Listings
• UL Listed and Recognized under UL 489
Category DIVQ File E7819
Category DKSY2 File E7819
Category DIHS E64983
• CSA 22.2, No. 5 File 245545
• CE LVD 2006/95/EC
• IEC/EN 60947-2
Features and Benefits
• Complete range of UL489 listed DIN rail
mounted miniature circuit breakers up
to 40 ampere current rating
• Single pole, two-pole and three pole
models
• Current limiting design provides fast
short circuit interruption that reduces
the
let-through energy, which can damage
the circuit
• Suitable for branch circuit device
protection
• Thermal-magnetic overcurrent protection
— two levels of short circuit protection,
categorized by C and D curves
C curve magnetic trip point:
5 to 10 times the rated current,
typically used for small
transformers, pilot devices, etc.
D curve magnetic trip point:
10 to 20 times the rated current,
typically used for transformers or loads
with very high inductive loads.
• Trip-free design — breaker cannot be
defeated by holding the handle in the
“ON” position
• Captive screws cannot be lost
• SWD (switching duty) rated circuit
breaker — suitable for switching
fluorescent
lighting loads (In m 20A)
• Fulfills UL 489, CSA C22.2 No.5 and also
IEC 60947-2 Standard
• Can also be used in applications for
which UL 1077 or CSA C22.2 No.235 are
also allowed
• Field installable shunt trip and auxiliary
switch subsequent mounting (See Allowable Combinations page)
• Module width of only 17.7 mm (per pole)
• Contact position indicator (red / green)
• 35mm DIN-rail mountable, utilizing
spring clip
• Suitable for reverse feed applications
Applications
Feeder and Branch Circuit Protection
• Convenience receptacle circuits
(internal / external)
• Motor control circuits
• Load circuits leaving the equipment
(external)
• HACR Equipment (Heating Air Conditioning, Refrigeration)
• PLC I/O points
• Computers
• Power supplies
• Control instrumentation
• Relays
• UPS
• Power conditioners
Book 3 (14.1)
eCP-66
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Miniature Circuit Breakers
Company
Information
Terminal Blocks
Tripping Characteristics
Labeling
Power
Distribution
Blocks
Eaton WMZT miniature circuit breakers are available with “C”
and “D” tripping characteristics.
The front of each Eaton WMZT miniature circuit breaker is
labeled for positive identification.
Wiring
Accessories
Type C trip curve: 5 to10 In
ZIPLink
Connection
System
C-curve devices are suitable for applications where medium
levels of inrush current are expected. Applications include small
transformers, lighting, pilot devices, control circuits and coils.
C-curve devices provide a medium magnetic trip point.
Multi-wire
Connectors
Sensor Cables
and Connectors
Type D trip curve: 10 to 20 In
D-curve devices are suitable for applications where high levels
of inrush current are expected. The high magnetic trip point
prevents nuisance tripping in high inductive applications such
as motors, transformers and power supplies.
M12 Junction
Blocks
Eaton WMZT devices are current limiting, which means they
interrupt fault currents within one half cycle of the fault. Current limiting devices offer superior protection by reducing peak
let-through current and energy.
Wiring Duct
Panel Interface
Connectors
Cable Ties
Wire
Flexible Cord
Multi-conductor
Flex Cable
7200
3600
2
tripping characteristic
acc. to UL 489 / CSA 22.2 No. 235
1
1200
1
conventional non-tripping current
Int= 1.0 I N (T=40 °C )
2
conventional tripping current
I t = 1.35 I N: t < 1 h (T=25 °C )
3
2.0 I N : t = 12- 120 s (T=25 °C )
600
300
3
120
Data Cables
Wire
Management
Products
Power Supplies
60
instantaneous tripping
acc. to IEC 60898-1
Tr ipping time t [sec]
30
3
10
5
4
type C: 5 I N : t > 0.1 s
10 I N: t < 0.1 s
6
type D: 10 I N: t > 0.1 s
20 I N: t < 0.1 s
DC Converters
Transformers
and Filters
2
Circuit Protection
1
Tools
0.5
Test
Equipment
0.2
5
4
0.1
4
C
0.05
5
D
Enclosures
0.02
Enclosure
Climate Control
0.01
0.005
Safety: Electrical
Components
0.002
0.001
Safety: Protective
Wear
0.0005
1
2
3
4
5
6
7 8 9 10
15
20
30
40
50
Terms and
Conditions
Multiples of In
Book 3 (14.1)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
eCP-67
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Selection Guide
WMZT - Single-Pole Selection Guide
Ampere
Rating
0.5
1
1.5
2
3
4
5
6
7
8
10
13
Single-Pole
15
16
20
25
30
32
*40
C Curve
Part Number
WMZT1CX0
WMZT1C01
WMZT1CX1
WMZT1C02
WMZT1C03
WMZT1C04
WMZT1C05
WMZT1C06
WMZT1C07
WMZT1C08
WMZT1C10
WMZT1C13
WMZT1C15
WMZT1C16
WMZT1C20
WMZT1C25
WMZT1C30
WMZT1C32
WMZT1C40
Price
$18.00
D Curve
Part Number
WMZT1DX0
WMZT1D01
WMZT1DX1
WMZT1D02
WMZT1D03
WMZT1D04
WMZT1D05
WMZT1D06
WMZT1D07
WMZT1D08
WMZT1D10
WMZT1D13
WMZT1D15
WMZT1D16
WMZT1D20
WMZT1D25
WMZT1D30
WMZT1D32
WMZT1D40
Price
$18.00
* Rated 240VAC
WMZT - Two-Pole Selection Guide
Ampere
Rating
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
Two-Pole
20
25
30
Note: Eaton parts available for
sale to North America
locations only.
32
*40
C Curve
Part Number
WMZT2CX0
WMZT2C01
WMZT2CX1
WMZT2C02
WMZT2C03
WMZT2C04
WMZT2C05
WMZT2C06
WMZT2C07
WMZT2C08
WMZT2C10
WMZT2C13
WMZT2C15
WMZT2C16
WMZT2C20
WMZT2C25
WMZT2C30
WMZT2C32
WMZT2C40
Price
$35.00
D Curve
Part Number
WMZT2DX0
WMZT2D01
WMZT2DX1
WMZT2D02
WMZT2D03
WMZT2D04
WMZT2D05
WMZT2D06
WMZT2D07
WMZT2D08
WMZT2D10
WMZT2D13
WMZT2D15
WMZT2D16
WMZT2D20
WMZT2D25
WMZT2D30
WMZT2D32
WMZT2D40
Price
$35.00
* Rated 240VAC
Book 3 (14.1)
eCP-68
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Selection Guide
Company
Information
Terminal Blocks
Power
Distribution
Blocks
WMZT - Three-Pole Selection Guide
Ampere
Rating
C Curve
Part Number
WMZT3CX0
WMZT3C01
WMZT3CX1
WMZT3C02
WMZT3C03
WMZT3C04
WMZT3C05
WMZT3C06
WMZT3C07
WMZT3C08
WMZT3C10
WMZT3C13
WMZT3C15
WMZT3C16
WMZT3C20
WMZT3C25
WMZT3C30
WMZT3C32
WMZT3C40
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
*40
D Curve
Part Number
WMZT3DX0
WMZT3D01
WMZT3DX1
WMZT3D02
WMZT3D03
WMZT3D04
WMZT3D05
WMZT3D06
WMZT3D07
WMZT3D08
WMZT3D10
WMZT3D13
WMZT3D15
WMZT3D16
WMZT3D20
WMZT3D25
WMZT3D30
WMZT3D32
WMZT3D40
Price
$54.50
Wiring
Accessories
Price
ZIPLink
Connection
System
Multi-wire
Connectors
Sensor Cables
and Connectors
M12 Junction
Blocks
$54.50
Panel Interface
Connectors
Wiring Duct
Cable Ties
Three-Pole
Wire
Flexible Cord
Multi-conductor
Flex Cable
* Rated 240VAC
Data Cables
Miniature Circuit Breaker - IEC
Miniature Circuit Breaker - UL / CSA
Short Circuit Trip Response
Current Range
0.5 - 32A
Maximum Voltage
32A
Ratings - UL / CSA
Per pole
Single pole
Thermal Tripping
Characteristics
Multi-pole
1 pole
Short Circuit Ratings 2 pole
(At Max. Voltage)
3 pole
Rated Frequency
C Curve
D Curve
5 - 10 x I n
10 - 20 x I n
0.5 - 40A
0.5 - 40A
277 / 480Y
240VAC
48VDC
40°C
10kA
Short Circuit Trip Response
Current Range
Maximum Voltage 1 pole
2 pole
Ratings IEC/EN 60947-2
3 pole
Single pole
Thermal Tripping
Characteristics
Multi-pole
Interrupt Ratings (At Max Voltage)
Rated Frequency
C Curve
D Curve
5 - 10 x I n
10 - 20 x I n
0.5 - 40A
0.5 - 40A
240 / 415 VAC
30°C
30°C
15kA
50 / 60Hz
M20,000 (1 operation = ON/OFF)
489, CSA C22.2 No.5 = 40°C
Operating Temperature UL
IEC 60947-2
= 30°C
10g 20-25 ms
Shock (UL 489)
Nylon
Housing Material
Vertical
Mounting Position
Weight
One-Pole
Two-Pole
Three-Pole
0.3 lb (136g)
0.6 lb (272g)
0.9 lb (408g)
Circuit Protection
Tools
Test
Equipment
Enclosure
Climate Control
Ampere Rating
0.5 - 40
Cable Size
One wire
0.75 to 13 mm2
18 to 6 AWG
Two wires
0.75 to 5 mm2
18 to 10 AWG
Note: Eaton does not recommend the use of wire ferrules or crimping terminals. The wire gauges are specified above and in the
installation instructions included with each circuit breaker.
Tightening Torque - WMZT
Cable Size
Tightening Torque
18 - 12 AWG
2.4 N·m
21 lb·in
10 - 8 AWG
2.8 N·m
25 lb·in
6 AWG
4.1 N·m
36 lb·in
Book 3 (14.1)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Transformers
and Filters
Enclosures
Wire Size - WMZT
Lifespan / Endurance
Power Supplies
DC Converters
50 / 60Hz
General Specifications - WMZT
Wire
Management
Products
Circuit Protection
eCP-69
Safety: Electrical
Components
Safety: Protective
Wear
Terms and
Conditions
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Technical Data
Let-Through Energy
Characteristic C (0.5-20A), 277V
Characteristic C (25-40A), 240V
80000
70000
60000
80000
70000
60000
50000
50000
40000
20
C
30000
C1
5,
40000
C1
C13
C10
C8 7
C6 , C
20000
15000
C5
C4
C3
10000
9000
8000
7000
6000
6
30000
C40
C35
C32
C30
20000
C25
15000
10000
9000
8000
7000
6000
5000
5000
4000
4000
3000
3000
C2
C 1,5
2000
2000
1500
1500
1000
900
800
700
600
1000
900
800
700
600
C1
500
500
400
400
6000
7000
8000
9000
10000
4000
5000
3000
1500
500
6000
7000
8000
9000
10000
4000
5000
3000
1500
2000
1000
500
2000
300
C 0.5
1000
300
Prospective short-circuit current [A]
Prospective short-circuit current [A]
Characteristic D (0.5-20A), 277V
Characteristic D (25-40A), 240V
80000
70000
60000
80000
70000
60000
50000
50000
0
D2
40000
30000
5, D
D1
D 13
0
1
D
D8
7
D6,D
20000
15000
D5
D4
10000
9000
8000
7000
6000
D3
D2
D 1.5
5000
40000
16
D40
30000
D35
D32
D30
20000
D25
15000
10000
9000
8000
7000
6000
5000
4000
4000
3000
3000
2000
1500
1500
1000
900
800
700
600
1000
900
800
700
600
500
500
400
400
Prospective short-circuit current [A]
6000
7000
8000
9000
10000
5000
3000
4000
1500
300
2000
6000
7000
8000
9000
10000
5000
3000
4000
2000
1500
1000
500
D0.5
1000
300
500
D1
2000
Prospective short-circuit current [A]
Book 3 (14.1)
eCP-70
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Technical Data
Company
Information
Terminal Blocks
Tripping Curves
Power Loss at In
Power
Distribution
Blocks
Characteristic C
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
40
1p
P[W]
1.6
1.1
1.3
1.4
1.2
1.4
1.9
1.2
1.4
1.4
1.8
2.4
1.9
2.1
2.9
3.1
3.0
3.4
4.0
2p
P[W]
3.2
2.2
2.6
2.8
2.4
2.9
3.7
2.3
2.8
2.8
3.6
4.7
3.8
4.3
5.8
6.2
6.0
6.8
8.1
3p
P[W]
4.7
3.4
3.9
4.3
3.6
4.3
5.6
3.5
4.3
4.2
5.3
7.1
5.6
6.4
8.7
9.3
9.0
10.2
12.1
Power Loss at In
Characteristic D
In [A]
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
40
1p
P[W]
1.6
0.8
1.0
1.0
1.2
1.4
1.5
1.2
1.4
1.2
1.5
2.0
1.5
1.7
1.8
2.6
2.7
3.1
3.9
2p
P[W]
3.2
1.5
2.1
2.1
2.4
2.9
2.9
2.3
2.8
2.4
3.0
4.1
3.1
3.5
3.7
5.1
5.4
6.2
7.8
7200
3600
Wiring
Accessories
2
tripping characteristic
acc. to UL 489 / CSA 22.2 No. 235
1
1200
conventional non-tripping current
Int= 1.0 I N (T=40 °C )
2
conventional tripping current
I t = 1.35 I N: t < 1 h (T=25 °C )
Multi-wire
Connectors
3
2.0 I N : t = 12- 120 s (T=25 °C )
Sensor Cables
and Connectors
300
3
120
ZIPLink
Connection
System
1
600
60
M12 Junction
Blocks
instantaneous tripping
acc. to IEC 60898-1
30
Tr ipping time t [sec]
In [A]
3
10
5
4
type C: 5 I N : t > 0.1 s
10 I N: t < 0.1 s
6
type D: 10 I N: t > 0.1 s
20 I N: t < 0.1 s
Panel Interface
Connectors
Wiring Duct
Cable Ties
2
Wire
1
0.5
3p
P[W]
4.8
2.3
3.1
3.1
3.6
4.3
4.4
3.5
4.3
3.7
4.5
6.1
4.6
5.2
5.5
7.7
8.1
9.3
11.6
Flexible Cord
Multi-conductor
Flex Cable
0.2
5
4
0.1
4
C
0.05
5
Data Cables
D
Wire
Management
Products
0.02
0.01
Power Supplies
0.005
DC Converters
0.002
Transformers
and Filters
0.001
0.0005
Circuit Protection
1
2
3
4
5
6
15
7 8 9 10
20
30
40
50
Multiples of In
WMZT Miniature Circuit Breakers Dimensions
Tools
Test
Equipment
Enclosures
0.22
(5.5)
Enclosure
Climate Control
Safety: Electrical
Components
35 mm
DIN rail
mounting
4.13
(105.0)
1.77
(45.0)
0.39
(10.0)
.70
(17.7)
1.39
(35.4)
2.09
(53.1)
Dimensions are approximate, inches (mm) - Not for construction purposes
1.73
(44.0)
2.36
(60.0)
Book 3 (14.1)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
eCP-71
Safety: Protective
Wear
Terms and
Conditions
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Technical Data
Influence of Ambient Temperature T on Load Carrying Capacity
Device Market
Current Rating
In (A) at 40°C
0.5
1.0
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
10.0
13.0
15.0
16.0
20.0
25.0
30.0
32.0
40.0
In (A) at Higher Ambient Temperature
15°C
20°C
25°C
30°C
40°C
50°C
55°C
60°C
0.6
1.1
1.7
2.2
3.3
4.4
5.5
6.6
7.7
8.8
11.0
14.3
16.5
17.6
22.0
27.5
33.0
35.2
44.0
0.5
1.1
1.6
2.2
3.2
4.3
5.4
6.5
7.6
8.6
10.8
14.0
16.2
17.3
21.6
27.0
32.4
34.6
43.2
0.5
1.1
1.6
2.1
3.2
4.2
5.3
6.4
7.4
8.5
10.6
13.8
15.9
17.0
21.2
26.5
31.8
33.9
42.4
0.5
1.0
1.6
2.1
3.1
4.2
5.2
6.2
7.3
8.3
10.4
13.5
15.6
16.6
20.8
26.0
31.2
33.3
41.6
0.5
1.0
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
10.0
13.0
15.0
16.0
20.0
25.0
30.0
32.0
40.0
0.5
1.0
1.4
1.9
2.9
3.8
4.8
5.8
6.7
7.7
9.6
12.5
14.4
15.4
19.2
24.0
28.8
30.7
38.4
0.5
0.9
1.4
1.9
2.9
3.8
4.7
5.6
6.6
7.5
9.4
12.5
14.1
15.0
18.8
23.3
28.2
30.1
37.6
0.5
0.9
1.4
1.8
2.8
3.7
4.6
5.5
6.4
7.4
9.2
12.0
13.8
14.7
18.4
23.0
27.6
29.4
36.8
1.40
Load factor KT [I/In]
1.30
1.20
1.10
1.00
0.90
-20
-10
0
10
20
30
40
50
Ambient temperature T [°C ]
Maximum load IL at ambient temperature T:
IL (T) = In KT (T)
IL = Maximum Load
T = Ambient Temperature
IN = Rated Current in Amps
KT = Load Factor
Book 3 (14.1)
eCP-72
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Accessories
Company
Information
Terminal Blocks
Field Mountable
Accessories
Power
Distribution
Blocks
Wiring
Accessories
• Auxiliary switch
• Alarm switch
• Shunt trip
- No tools required for mounting
ZIPLink
Connection
System
Multi-wire
Connectors
Sensor Cables
and Connectors
WMZTAUX
Auxiliary Contact
WMZSAUXTRIP
Alarm/Aux Contact
M12 Junction
Blocks
WMZTSTxxx
Shunt Trip
Panel Interface
Connectors
WMZT Accessories Selection Guide
Part Number
Description
Contacts
WMZTAUX
• 1 NO / 1 NC Contact
• Installs on left side of WMZT or Shunt Trip
• Maximum one per WMZT (489) Device
• Switches when WMZT is tripped electrically or manually
WMZSAUXTRIP
• Two Form C (One set Changeover) contacts, 1 SPDT aux / 1 SPDT alarm
• Small selector screw changes mode
• Installs on left side of WMZS, WMZT or shunt trip
• Auxilary contacts switch when WMZS or WMZT is tripped electrically or manually.
• Trip indicating contact switches only when WMZS or WMZT is tripped electrically.
(2) Form C
Description
Trip Voltage
Part Number
WMZTST415
WMZTST110
Module
Width
Module
Weight
Price
Cable Ties
1 NO / 1 NC
110 - 415 VAC
110 - 230 VDC
12 - 110 VAC
12 - 60 VDC
• Allows remote trip of WMZT
• Installs on left side of WMZT
$16.00
0.35” (8.9 mm)
$20.00
Price
0.28 lb (127g)
$28.50
Wire
Management
Products
$28.50
Power Supplies
DC Converters
WMZT Accessory Data
Part Number
Circuit Diagram
WireSize
(Solid and Stranded)
mm²
AWG
Electrical Characteristics
21
13
Rated for general use, 2A at 230 VAC / 0.5 A
at 24/110 VDC 50 / 60 Hz
WMZTAUX
22
WMZSAUXTRIP
Terminal
Tightening Torque
N·m
lb·in
(1) 0.5 to 2.5 (1) 20 to 14
(2) 0.5 to
(2) 18 to
(2) 2.5
(2) 14
1.2
(1) 0.5 to 2.5 (1) 18 to 14
(2) 0.5 to
(2) 18 to
(2) 1.5
(2) 16
0.8
10.6
WMZTST415
C1
WMZTST110
C2
1 SPDT auxiliary contact and 1 SPDT alarm contact
that can be configured and used as an auxiliary
contact, rated for general use, 2A at 200 VAC /
0.5 A at 24/110 VDC 50 / 60 Hz
110 - 415 VAC, 110 - 230 VDC operating range
0.5 A at 110 VAC, 2A at 415 VAC
0.5 A at 110 VDC, 1.1 A at 230 VAC
12 - 110 VAC, 12 - 60 VDC operating range
0.5 A at 12 VAC, 4.4 A at 110 VAC
0.5 A at 12 VDC, 2.4 A at 60 VDC
(1) 1 to 6
(2) 1 to
(2) 6
(1) 18 to 10
(2) 18 to
(2) 10
Transformers
and Filters
Circuit Protection
Tools
Test
Equipment
14
See WMZSAUXTRIP
diagrams on next page
Multi-conductor
Flex Cable
Data Cables
Module
Weight
0.69“
(17.5 mm)
Wire
Flexible Cord
0.15 lb (68g)
Module
Width
Wiring Duct
7.0
Enclosures
Enclosure
Climate Control
2.8
25.0
Safety: Electrical
Components
Safety: Protective
Wear
Allowable Combinations of Accessories
Terms and
Conditions
or
or
WMZTAUX
Standard
Auxilary
WMZSAUXTRIP
Auxilary /
Alarm
Switch
WMZT
Miniature
Circuit
Breaker
WMZTAUX
Standard
Auxilary
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
WMZSAUXTRIP WMZTSTxxx
Auxilary /
Shunt
Alarm
Trip
Switch
WMZT
Miniature
Circuit
Breaker
Book 3 (14.1)
Circuit Protection
eCP-73
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Accessories
Accessories Dimensions
.35
(8.9)
contact 4.xx in Auxilary mode
contact 1.xx in Auxilary mode
1.94
(49.3)
.20
(5.1)
.16
(4.1)
.63
(16.0)
.21
(5.3)
.23
(5.8)
1
N
2
N
1.11
4.11
1.14
4.12
1.12
4.14
1
N
2
N
1.95
(49.5)
1
N
2
N
1.11
1.14
4.12
1.12
4.14
SEL
4.11
1.14
4.14
4.12
N
2
N
4.11
1.11
1
N
2
N
1.11
1.14
4.12
1.12
4.14
4.11
4.14
OFF
4.11
1.14
4.14
1.12
4.12
1
N
2
N
1.11
4.12
1.14
4.11
1.12
WMZSAUXTRIP
Diagrams
WMZSAUXTRIP
Electrical Trip
4.14
4.12
0.22
(5.5)
0.22
(5.5)
3.15
(80.0)
1
TRIP
ON
1.12
.16
(4.1)
3.15
(80.0)
OFF
4.11
Manual Trip
contact 4.xx in Alarm mode
contact 1.xx in Auxilary mode
OFF
2.82
(71.6)
1.11
Manual or
Electrical Trip
TRIP
ON
OFF
2.39
(60.7)
2.75
(69.9)
1.77
(45.0)
SEL
35 mm
DIN rail
mounting
1.77
(45.0)
35 mm
DIN rail
mounting
1.77
(45.0)
1.77
(45.0)
0.39
(10.0)
0.35
(8.8)
1.73
(44.0)
2.36
(60.0)
WMZTAUX
.70
(17.7)
1.73
(44.0)
2.36
(60.0)
Dimensions are approximate, inches (mm) Not for construction purposes
WMZTSTxxx
Lockout Attachment
.19” - .28”
(5.0 - 7.1mm)
WMZPLK
Lockout Attachment
WMZPLK Installation
Additional WMZT Accessories
Part Number Description
WMZPLK
Weight
Lockout attachment for Eaton WMZS series supplementary protectors and
WMZT mini circuit breakers, suitable to prevent unauthorized activation of a
de-energized circuit, accepts lock shackles up to 9/32 in. (7.1 mm) in diameter 0.10 lb (45g)
Qty: 5 pieces
Price
$30.50
Book 3 (14.1)
eCP-74
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Accessories
Company
Information
Bus Bar System
Terminal Blocks
Power
Distribution
Blocks
Wiring
Accessories
ZIPLink
Connection
System
WMZTxP6TSP
WMZT Bus Bar
WMZTxP12TSP
WMZT Bus Bar
WMZTxP18TSP
WMZT Bus Bar
Multi-wire
Connectors
Sensor Cables
and Connectors
WMZT Bus Bar
Part Number
WMZT1P6TSP
WMZT1P12TSP
WMZT1P18TSP
WMZT2P6TSP
WMZT2P12TSP
WMZT2P18TSP
WMZT3P6TSP
WMZT3P12TSP
WMZT3P18TSP
Description
Price
Bus Bar for connecting up to six (6) 1-pole WMZT series circuit breakers
$8.50
Bus Bar for connecting up to twelve (12) 1-pole WMZT series circuit breakers
$15.50
Bus Bar for connecting up to Eighteen (18) 1-pole WMZT series circuit breakers
$23.00
Bus Bar for connecting up to three (3) 2-pole WMZT series circuit breakers
$9.50
Bus Bar for connecting up to six (6) 2-pole WMZT series circuit breakers
$19.00
Bus Bar for connecting up to nine (9) 2-pole WMZT series circuit breakers
$28.00
Bus Bar for connecting up to two (2) 3-pole WMZT series circuit breakers
$10.00
Bus Bar for connecting up to four (4) 3-pole WMZT series circuit breakers
$20.00
Bus Bar for connecting up to six (6) 3-pole WMZT series circuit breakers
$29.50
M12 Junction
Blocks
Panel Interface
Connectors
Wiring Duct
Cable Ties
Wire
Flexible Cord
Note: WMZT Bus Bar is not for use with WMZS supplementary protectors.
Multi-conductor
Flex Cable
Bus Bar Specifications
Description
Operating Voltage
Frequency
Rated impulse withstand - Uimp
Max Current - Ie
Cross Section
Dimensions
UL489
Data Cables
IEC/EN60947-2
480VAC
96VDC
240 / 415 VAC
50 / 60Hz
n/a
50 / 60Hz
n/a
9.5 kV
80A @ 40°C
80A @ 30°C
n/a
16 mm2
Wire
Management
Products
Power Supplies
DC Converters
Dimensions are approximate, inches (mm) - Not for construction purposes
Transformers
and Filters
Circuit Protection
Tools
Test
Equipment
Enclosures
Enclosure
Climate Control
Safety: Electrical
Components
Safety: Protective
Wear
Terms and
Conditions
Book 3 (14.1)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
eCP-75
Prices as of April 16, 2014. Check Web site for most current prices.
WMZT Series Accessories
Bus Bar Accessories
WMZT Bus Bar Accessories
Part Number
Description
WMZT3PSHROUD Bus Bar Shroud - covers for unused bus bar terminals, (10) 3-terminal covers per package
Wiring Lug, 35mm (2 - 14 AWG), 3 lugs per package
WMZT35EXT
WMZT35EXT - Specifications
WMZT3PSHROUD
Bus Bar Shroud
Description
Operating Voltage
Frequency
Rated impulse withstand Uimp
Max Current - Ie
WMZT35EXT
Wiring Lug
UL489
Price
$22.00
$26.00
IEC/EN60947-2
480VAC
96VDC
240 / 415 VAC
50 / 60Hz
n/a
50 / 60Hz
n/a
9.5 kV
80A @ 40°C
80A @ 30°C
#2 - 14 AWG
2.5 - 35 mm2
0.56 in
14mm
WMZT35EXT - Tightening Torque
Tested Acc. To
UL 486A
UL 486B
UL 486E
Dimensions
#14 AWG
#8 - 12 AWG
#6 - 1 AWG
M 2.3 N·m (20 lb·in)
M 2.8 N·m (25 lb·in)
4 N·m (35 lb·in)
0.64
(16.2)
1.90
(48.2)
0.69
(17.6)
Cable Size Tightening Torque
1.22
(31.1)
0.51
(13.0)
0.94
(24.0)
0.14
(3.6)
0.69
(17.6)
2.82
(71.6)
0.28
(7.0)
WMZT3PSHROUD
0.53
(13.5)
Dimensions are approximate, inches
(mm) - Not for construction purposes
WMZT35EXT
WMZT35EXT
0.24
(6.1)
WMZT35EXT
0.12
(3.0)
WMZT35EXT
WMZT3P12T
5.98
(152.0)
5.00
(127.0)
WMZT3PSHROUD
Book 3 (14.1)
eCP-76
Circuit Protection