Catalog Page

advertisement
PRESSURE
PSI
NEW!
Room Pressure Monitor / Transmitter
KRPC Series
Description
The Kele KRPC Series room pressure monitor is used to
measure differential pressure in the range of ±0.125" to
1"WC or ±30 to 250 Pa. It combines precision high sensitivity
silicon sensing capabilities and the latest ASIC technology
to substantially reduce offset errors due to changes in
temperature, stability to warmup, long term instability and
position sensitivity. It is ideal for monitoring pressure for air or
other clean inert gas. It features field selectable bi-directional
pressure ranges and output signal types for the most flexible
application. The device has an on-board auto-zero function,
backlit LCD and alarm function with silence switch.
Features
Low pressure monitoring to ±0.125"WC (30 Pa)
Four selectable ranges per model
Selectable analog output model
BACnet communications model
Alarm funtions with selectable trip point
Easy set up via menu on LCD display
PRESSURE
•
•
•
•
•
•
KRPC with
Display
KAC
KAA-1
KRPM
Specifications
Accuracy
18
± 1% F.S.O. (± 2% F.S.O. for 0.125"
WC and 30 Pa ranges)
Stability
± 1% FS max (1 year)
Thermal Effect
< ± 3.5% FS max, 41° to 122°F
(5° to 50°C)
Response Time
0-60 seconds, menu selectable
Operating Temperature32° to 140°F (0° to 60°C)
Operating Humidity
10-90% RH non-condensing
Media Compatibility
Dry air and inert gas
Zero Adjustment
Pushbutton auto-zero
Power Supply
24 VAC/VDC, ± 10%
Output Signal
4-20 mA (3-wire), 0-5 VDC or
0-10 VDC (3-wire), field selectable
Output Impendence
750Ω max (4-20 mA), 2 KΩ min
(voltage)
Wiring Connections
Screw terminal block (14 to 22 AWG)
Pressure Connections 1/4" OD
Enclosure
Wall mount, white ABS, IP30
(NEMA 1)
1130
888-397-5353 USA
kele.com
LCD Display Size
1.5" x 0.65" (38.1 x 16.5 mm)
Alarm Functions
Alarm Relay OutputN.O. contact, 2 Amps@120 VAC
or 30 VDC
Alarm Visual
Red flashing LED
Remote Buzzer Output 24 VDC
Remote Buzzer Current 5 mA or 9 VDC and
20 mA or 48 VDC
Alarm Audible On-board buzzer 85 db
(menu selectable)
BACnet Communications Model
Communications2-Wire RS-485, BACnet MS/TP
protocol
Baud RateLocally set to 9600, 19200,
38400 or 76800
MAC Address RangeLocally set to 0-127
(factory default is 3)
Weight
0.25 lb (0.11 kg)
When you need it right, right now, call Kele.
March 2014
NEW!
Installation for BACnet
PRESSURE
Room Pressure Monitor / Transmitter
KRPC Series
PSI
installation for analog
MODEL
DESCRIPTION
KRPC1
KRPC1-AC
KRPC1-BAC
KRPC1-BAC-AC
KRPC1-BAC-SP
KRPC1-SP
KRPC2
KRPC2-AC
KRPC2-BAC
KRPC2-BAC-AC
KRPC2-BAC-SP
KRPC2-SP
KRPM
KAA-1
Room pressure monitor, +/- 1.0"wc, +/-0.5"wc, +/-125 Pa, +/-250 Pa ranges (selectable)
Room pressure monitor, +/- 1.0"wc, +/-0.5"wc, +/-125 Pa, +/-250 Pa ranges (selectable) with continenal pick-up port
Room pressure monitor, +/- 1.0"wc, +/-0.5"wc, +/-125 Pa, +/-250 Pa ranges (selectable) and BACnet communications
Room pressure monitor, +/- 1.0"wc, +/-0.5"wc, +/-125 Pa, +/-250 Pa ranges (selectable) with continenal pick-up port and BACnet communications
Room pressure monitor, +/- 1.0"wc, +/-0.5"wc, +/-125 Pa, +/-250 Pa ranges (selectable) with stainless plate pick-up port and BACnet communications
Room pressure monitor, +/- 1.0"wc, +/-0.5"wc, +/-125 Pa, +/-250 Pa ranges (selectable) with stainless plate pick-up port
Room pressure monitor, +/- 0.25"wc, +/-0.125"wc Pa, +/-30 Pa, +/-60 Pa ranges (selectable)
Room pressure monitor, +/- 0.25"wc, +/-0.125"wc Pa, +/-30 Pa, +/-60 Pa ranges (selectable) with contential pick-up port
Room pressure monitor, +/- 0.25"wc, +/-0.125"wc Pa, +/-30 Pa, +/-60 Pa ranges (selectable) and BACnet communications
Room pressure monitor, +/- 0.25"wc, +/-0.125"wc Pa, +/-30 Pa, +/-60 Pa ranges (selectable) with contential pick-up port and BACnet communications
Room pressure monitor, +/- 0.25"wc, +/-0.125"wc Pa, +/-30 Pa, +/-60 Pa ranges (selectable) with stainless plate pick-up port and BACnet communications
Room pressure monitor, +/- 0.25"wc, +/-0.125"wc Pa, +/-30 Pa, +/-60 Pa ranges (selectable) with stainless plate pick-up port
Stainless plate pick-up port
Remote audible alarm
PRESSURE
ORDERING INFORMATION
18
KAA-1
KAC
KRPM
T-101
T-141
March 2014
ACCESSORIES
Remote audible alarm
Pressure pick up port (continental)
Stainless steel plate pick-up port
1/4" OD Poly Tubing 250' spool
1/4" OD Poly Tubing 250' spool - anti kink
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1131
Download