Design, Function and Operation of On-Load Tap-Changers Uwe Seltsam Maschinenfabrik Reinhausen GmbH TRANSFORM Partner About the Author Uwe Seltsam Maschinenfabrik Reinhausen GmbH, Regensburg / Germany – Manager Technical Specialists – Scientific Background Dipl.-Ing. (FH) Electrical Engineering Professional Background 10 years at Maschinenfabrik Reinhausen GmbH Technical Service / Troubleshooting Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 2 Agenda 1. On-load tap-changer in regulating transformer 2. On-load tap-changer – Design types 3. Switching sequence of tap selector and diverter switch insert 4. Maintenance Intervals for OILTAP® and VACUTAP® Parameter contact wear Parameter replacement of parts Parameter oil carbonization Checks after maintenance Checks between maintenances 5. Oil change criteria 6. Influence of humidity on dielectric strength 7. Avoiding carbon deposits or their effects 8. On-load tap-changer – Protective devices 9. Diagnostics Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 3 1. On-load tap-changer in regulating transformer On-load tap-changers (OLTCs) are used for changing the transmission ratio under load 110 kV U1 Mwg = Main winding Cwg = Coarse winding Rwg = Regulating winding LU = Diverter switch insert Mwg 555 wdgs Cwg 120 wdgs Transformer: OLTC: Step voltage: % 40 MVA, 110 kV 16 / 21 kV 17.6 kV M III 350 Y – 123/C – 10 19 1G 17.6 kV : 9 steps ≙ 1.955 kV/step ≙ 1.78 % U2 21 kV 129 wdgs + k Rwg 108 wdgs 12 wdgs/step Nominal: Example 1: Example 2: 9 LU 2 1 U1 = N1 U2 N2 U2 = 21 kV = constant U1 = 110 kV N1 = 110 kV • 129 wdgs / 21 kV = 675 wdgs U2 = 110 kV • 129 wdgs / 675 wdgs = 21.02 kV U1 = 116 kV N1 = 116 kV • 129 wdgs / 21 kV = 711 wdgs U2 = 116 kV • 129 wdgs / 711 wdgs = 21.05 kV Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 4 2. On-load tap-changer – Design types Tap-change operation Vectorial diagram Contact movement A,B Main contacts (only for V III 350 Y/Δ, V III 500 Y / Δ, V I 350, V I 700) OILTAP® Type M since 1972 a,b Main switching contacts e. g. M III 600 9 steps 3-pole Star connection Insulation to ground Um = 123 kV a1, b1 Transition contacts Ra, Rb Transition resistors Ua, Ub Voltages of tappings Ust Step voltage U, I Voltage, current of tapchanger terminals Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 5 2. On-load tap-changer – Design types Operation Vectorial diagram Contact movement A,B Main contacts (only V III 350 Y/Δ, V III 500 Y/ Δ, V I 350, V I 700) OILTAP® Type V since 1979 a,b Main switching conttacts e. g. V III 200 10 steps 3-pole Star connection Insulation to ground Um = 76 kV a1, b1 Transition contacts R Transition resistor Ua, Ub Voltages of tappings Ust Step voltage U, I Voltage, current of tap-changer terminals Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 6 2. On-load tap-changer – Design types VACUTAP® Type VR® since 2004 e. g. VRF III 1300 10 steps 3-pole Star connection Insulation to ground Um = 76 kV Switching sequence Switching direction n n+1 MSV Main switching contact (vacuum interrupter), main path MTF Transfer contact, main path TTV Main switching contact (vacuum interrupter), transition path TTF Transfer contact, transition path MCA Main contact side A MCB Main contact side B ZnO ZNO varistor R Uwe Seltsam, Maschinenfabrik Reinhausen GmbH Transition resistor 07.06.2013 Page 7 2. On-load tap-changer – Design types VACUTAP® Type VV since 2000 e. g. VV III 400 10 steps MTS MSV TTS TTV STC R IC Uwe Seltsam, Maschinenfabrik Reinhausen GmbH Tap-selector contact, main path Main switching contact (vacuum interrupter), main path Tap-selector contact, transition path Transition contact (vacuum interrupter), transition path Sliding take-off contact Transition resistor Circulating current 07.06.2013 Page 8 3. Switching sequence of tap selector and diverter switch IB Tap pre-selection without current Diverter switch insert operation type M Switching principle of diverter switch insert: Flag switching cycle Operation switching time approx. 40 – 50 ms Load period of transition resistors approx. 30 ms Link to movie Uwe Seltsam, Maschinenfabrik Reinhausen GmbH IB = Operating through-current IK = Circulating current R = Transition resistor 07.06.2013 Page 9 4.1 Maintenance – Intervals for OILTAP® and VACUTAP® OILTAP® - Regular maintenance, depending on time of service or no. of operations (whichever comes first) Neutral-point application after every 5 – 7 years after every 50,000 – 150,000 operations Delta application after every 2 – 4 years after every 20,000 – 100,000 operations Maintenance of tap selector after every 1 to 1.2 million operations Diverter switch insert type M Service life 800,000 operations For OLTC-specific maintenance intervals, refer to the respective operating instructions or the label on the motor-drive unit. Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 10 4.1 Maintenance – Intervals for OILTAP® and VACUTAP® VACUTAP® - Regular maintenance, only depending on the number of operations Neutral-point or phase application after every 300,000 operations Tap selector maintenance after every 1.2 million operations Reason for time-independent maintenance: No oil carbonization since arcs do not occur in insulating oil For network applications, the VACUTAP® is more or less maintenance-free. Example: Switching frequency 5,000 operations per year maintenance after 60 years. Uwe Seltsam, Maschinenfabrik Reinhausen GmbH Diverter switch insert type VR® Service life 1.2 million operations 07.06.2013 Page 11 4.1 Maintenance – Intervals for OILTAP® and VACUTAP® Monitoring – TM100, Tapguard® 260 Maintenance depending on condition Maintenance criterion Parts subject to wear Oil change and cleaning Contact wear Calculation No. of ops. specification for parts change Calculation algorithm for oil carbonization Calculation algorithm for single and difference wear Maintenance time Visual presentation Present condition 0 ... 100 % Prediction for 100 % moment Semaphore function green/yellow/red Red signal prevents additional operations by the motor-drive unit, but it is not integrated into the tripping circuit for the circuit breaker. Front panel Tapguard® 260 Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 12 4.2 Maintenance – Parameter contact wear MSCB TCB TCA MCA Criteria for OILTAP®: Single wear and Difference in wear between switching and transition contact Parameters for contact wear: Number of operations: Arcing current: Medium arc duration: Arc voltage: Contact material: MCA MCB MSCA MSCB TCA TCB variable value Contact system of diverter switch type M variable value approx. 6 ms 25 – 30 V Step voltage Ust Cu or CuW sintered material Wear on main switching contact: SG proportional to operating through-current Wear on resistor contact: independent of operating current, but proportional to circulating current Ic (Ic = Ust / Rres) Exceeding the wear differences influences the switching sequence – a short circuit between taps may occur. Uwe Seltsam, Maschinenfabrik Reinhausen GmbH MCA MSCA TCA TCB SCB MCB MC = Main contact MSC = Main switching contact TC = Transition contact R = Transition resistor SG = Spark gap Max. permissible single wear = 4 mm Max. permissible difference in wear = 2.5 mm 07.06.2013 Page 13 4.3 Maintenance – Parameter replacement of parts Depending on no. of ops. Springs, leads, etc. Depending on wear Arc contacts, etc. Preventively Cover gasket, etc. Up-dating E.g. Energy accumulator spring for type M: 400,000 – 500,000 ops. Measure for increasing operating reliability Adjustment to current state of manufacture Diverter switch insert: Replacement after 800,000 operations (OILTAP®) Replacement after 1.2 million ops. (VACUTAP®) Tap selector: Maintenance after every 1.0 to 1.2 million operations, depending on OLTC type E.g. Braided lead for type M: 250,000 operations MR original parts are the basis for safe operation. Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 14 4.4 Maintenance – Parameters oil carbonization Criterion: Heat removal from the transition resistors must not be restricted by oil carbonization. Determining factors for degree of carbonization: Number of operations Arc energy Type of oil: Little difference between naphthenic-base or paraffin-base oil Drying of a sooted tap-changer leads to baking of carbon deposits on the surfaces and to a reduction of the dielectric strength. Use only transformer oil for cleaning. Electrical cleaners evaporate on the surface of the insulating material and lead to humidity. Diverter switch type insert T before cleaning Uwe Seltsam, Maschinenfabrik Reinhausen GmbH Diverter switch type insert T after cleaning 07.06.2013 Page 15 4.5 Maintenance – Checks after maintenance The following checks have to be performed: Identical indication of positions between on-load tap-changer and motor-drive unit Functional check of final positions If protective relay is in position “OFF“, it must not be possible to put the circuit breaker in the circuit Transformer ratio test during major modification work on the on-load tap-changer (e. g., replacement of motor-drive unit, or after connecting or disconnecting tap-selector leads) 1) 2) 3) 4) Diverter switch with oil compartment Motor-drive unit Protective relay Drive shafts Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 16 4.6 Maintenance – Checks between maintenances Motor-drive unit Visual check Heater in operation Door closed Protective relay Functional check together with transformer protection test Drying agent OLTC oil conservator Reliability (effectiveness) Oil monitoring Oil exchange criteria, see section 5 Disconnected transformer OLTC maintenance before re-commissioning of transformer if operating time and downtime exceed maintenance interval of on-load tap-changer (OILTAP®) together with transformer test Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 17 5. Oil change criteria OLTC application of OILTAP® Dielectric strength* Water content Neutral-point application Minimum 30 kV / 2.5 mm Maximum 40 ppm Use in auto-transformer or regulation in delta winding Minimum 40 kV / 2.5 mm Maximum 30 ppm Minimum 30 kV / 2.5 mm Maximum 30 ppm OLTC application of VACUTAP® All *Dielectric strength, measured in accordance with IEC 60156 The temperature of the oil sample must be measured at the time when the oil was taken. The values specified for dielectric strength apply to oil temperatures of 20 ± 5 °C at the time of evaluating the oil sample. Recommendation: Dielectric strength of > 50 kV / 2.5 mm for new insulating oil that must be filled in after maintenance. Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 18 5. Oil change criteria Time of oil sample test: It is up to the user of the transformer to check the insulating oil, and the test should be done at the same time when an oil sample of the transformer is taken Class 1 in accordance with IEC 60214-1: after every 5 years (use in neutral-point) Class 2 in accordance with IEC 60214-1: after every 2 years (use in auto-transformer,…) Whenever it is suspected that humidity is absorbed (drying agent ineffective etc.) Ask the OLTC manufacturer if other insulating liquids (ester liquids, etc.) are used. Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 19 6. Influence of humidity on dielectric strength Facts: Diverter switch oil of OILTAP® is a mixture of oil, carbon deposits and humidity Water absorption of carbon deposits is several times as high as water absorption of oil Carbonized oil with inadmissibly high water content puts insulation distances at risk which are exposed to voltage stress Effects: Electrical-field distortion with local discharges Thermal decomposition of surface of insulating material Creepage paths Breakdown of insulating distance with flashover Switching shaft Example of creepage paths Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 20 7. Avoiding carbon deposits or their effects Vacuum technology in the VACUTAP® No carbon deposits since arcs do not occur in insulating oil Vacuum interrupter Oil filter unit, filter cartridge with paper filter: absorbs carbon particles (6 – 9 microns); in use for annual number of > 15,000 operations / year with paper filter and drying agent (4 kg granulate): absorbs carbon particles and water (approx. 420 g) The effectiveness of the drying agent of the filter cartridge must be determined by oil sample and water content analysis. Oil filter unit – OF100 Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 21 8. On-load tap-changer – Protective devices Protective relay = flow-controlled relay type RS2001 (standard equipment) Response value, e. g. for M III 600: 1.2 m/sec ± 20% bei 20°C Pressure relief (burst membrane) in OLTC cover Static response pressure about 4 – 5 bar Pressure relief valve type MPreC® (instead of burst membrane) RS2001 Response value about 1.3 – 1.8 bar, depending on OLTC type Monitoring of drive shafts, e. g., for multiple-column OLTC design The above-mentioned protective devices must be integrated in the tripping circuit of the circuit breaker of the transformer. End position limiting device in OLTC and/or motor-drive unit Burst membrane Find out the cause after a protective device has responded! MPreC® Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 22 9. Diagnostics Increased tap selector contact resistance if contacts are not silver-plated: Signs of impurity layer Resistance measurement in accordance with CIGRE report 12-205/1994 rounds off gas-in-oil analysis; Extract from CIGRE report Tap-selector contacts colored to “black-grey“: Signs of silver-sulfide (impurity layer) Check for corrosive sulfur (oil, etc.) Separated silver-sulfide layer may lead to flashovers. Tap selector contact with silver-sulfide Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 23 9. Diagnostics Gas-in-oil analysis for diverter switch insert oil in OILTAP®: No informative value with respect to arcing on main switching contacts and transition contacts. No. of ops. Oil temp. [°C] H2 CH4 C2H6 C2H4 C2H2 CO CO2 0 16 127 31 3 70 359 10 344 17500 39400 29000 50 17796 12205 3642 36170 102172 330 3032 10800 48100 50000 22 13553 13000 4200 50000 103000 317 7733 4900 O2 N2 25300 Example for OLTC type M Gas-in-oil analysis for diverter switch insert oil in VACUTAP®: An evaluation pattern is currently being developed. Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 24 9. Diagnostics Torque measurement: Integral part of monitoring TM100 and TG260®, including assessment (semaphore function). Online procedure. Torque measurement directly on OLTC head with mobile measuring device. Example of torque progress Tap-change operation sequence assessment: Indirect assessment of tap-change operation sequence of diverter switch by measuring the contact wear (OILTAP®). Measurement of tap changes of diverter switch insert operation using direct current. Diverter switch insert type G Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 25 Summary • On-load tap-changers are available in/with different switching principles: types: high-speed resistor and reactor principle non-vacuum and vacuum • On-load tap-changers are available for different applications power transformers for transmission and distribution transformer for industrial use (e.g. arc-furnace or ladle furnace transformers) HVDC transformers phase-shifting-transformers transformers for operation at explosion-prone sites (e.g. offshore platform) • Maintenance maintenance intervals of the respective on-load tap-changer shall be observed at any time to ensure trouble-free operation of the transformer. Original spare parts and trained service staff have also be seen as mandatory. Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 26 About MR Maschinenfabrik Reinhausen GmbH Founded in 1868 Family ownership since 1891 Brand name since1901 World market leader in transformer switching 2,850 employees in 7 business areas 30 locations – world-wide Doing business in 190 countries Company sales: 630 million EUR www.reinhausen.com Uwe Seltsam, Maschinenfabrik Reinhausen GmbH 07.06.2013 Page 27