CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SYSTEM DESIGN SECTION SPECIFICATION EO – 4019 REVISION 34 DECEMBER 2015 EFFECTIVE DATE DECEMBER 28, 2015 TESTING OF AC FEEDERS OPERATING AT 4kV TO 33kV FILE: SYSTEM OPERATION MANUAL No. 5 FIELD MANUAL No. 6, Section No. 8 TARGET AUDIENCE REGIONAL ENGINEERING, SUBSTATION OPERATIONS, SYSTEM OPERATION, FIELD OPERATION AND DISTRIBUTION ENGINEERING NESC REFERENCE Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Page 1/13 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution for the current version prior to use. TABLE OF CONTENTS PARAGRAPH DESCRIPTION 1.0 SCOPE 2.0 APPLICATION 3.0 GENERAL 4.0 DEFINITIONS 5.0 HIPOT TESTING 13kV, 27kV OR 33kV DISTRIBUTION FEEDERS TABLE I VOLTAGE AND LEAKAGE CURRENT LIMITS FOR HIPOT TESTS TABLE II VOLTAGE AND LEAKAGE CURRENT LIMITS FOR REDUCED VOLTAGE HIPOT TESTS TABLE III VOLTAGE AND LEAKAGE CURRENT LIMITS FOR RAISED VOLTAGE HIPOT TESTS 6.0 AMMETER CLEAR TEST 7.0 EQUIPMENT TO BE DISCONNECTED PRIOR TO TESTS 8.0 VALIDATION OF TESTING MEASUREMENTS 9.0 REFERENCES ATTACHMENTS TABLE IV AMMETER CLEAR TEST LIMITS APPENDIX A FEEDER LIST APPENDIX B NOTES TO TABLE I, TABLE II, AND TABLE III Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 2/13 TESTING OF AC FEEDERS OPERATING AT 4 kV TO 33 kV 1.0 SCOPE This document specifies the electrical tests performed on 4, 13, 27, and 33 kV AC feeders to verify the restoration of adequate electrical insulation levels and the absence of short-circuit conditions following an outage. These tests are described as a High Potential Test (Hipot) and an Ammeter Clear Test. 2.0 APPLICATION This specification applies to all Regions. 3.0 GENERAL The application of this specification shall be in accordance with the “General Instructions Governing Work on System Electric Equipment,” and under the jurisdiction of the District Operator. 3.1 The Regional Engineering Manager, Control Center Shift Manager, District Operator, or the System Design Department Manager of Distribution Engineering may waive Hipot Test requirements based on system conditions. These conditions include: network feeder contingencies, local second or third conflicts, next contingency resulting in overloads or customer outages, customers out of service, extreme weather, or there is no indication of an additional fault on the feeder. The criteria used to waive the Hipot Test must be entered in the Electric Control Center Shift Manager’s log book and communicated (e.g. emailed) to the System Design Department Manager of Distribution Engineering in a timely manner. 3.2 A VLF Hipot Test is the preferred High Potential Test and should be used whenever a test set is available. 3.3 Hipot Tests on 4kV feeders are not required by Distribution Engineering. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 3/13 4.0 5.0 DEFINITIONS 4.1 VLF Hipot Test – A High-Potential withstand test using a very low frequency (VLF) power source. The typical VLF frequency is 0.1 hertz. A VLF Hipot test is the preferred method of High-Potential testing and should be used whenever a VLF test set is available. 4.2 DC Hipot Test – A High-Potential withstand test using a DC power source. A DC Hipot test should be used only when a VLF test set is not available. 4.3 Ammeter Clear Test – A low-voltage test using a 60 Hz 125V AC power source to verify the absence of short circuits on or between the primary feeder conductors or grounds on transformer secondaries. 4.4 Feeder Crossing – The portion of a feeder that runs along a bridge or under a waterway. 4.5 Network Reliability Index (NRI) – A statistical value indicating a networks susceptibility to a shutdown. Refer to EO-2152 and EOP-5022 for more information. 4.6 Forced Outage – Any outage where the feeder was automatically removed from service or unable to be restored to service due to a fault. This includes Open-Auto (AUTO), Fail-on-Test (FOT), and Cut-In-OpenAuto (CIOA) due to a fault. 4.7 Planned Outage – Any outage where the feeder was deliberately taken out of service. This includes Scheduled (SCHD), When Ready (WR), Isolated (ISO), Rapid Availability (RAP), or Off-On-Emergency (OOE1 or OOE2) outages. HIPOT TESTING 13kV, 27kV OR 33kV DISTRIBUTION FEEDERS 5.1 Subject feeders to a Table I Hipot Test for five (5) minutes following: 5.1.1 Any forced outage. 5.1.2 Any outage where station work was performed that disturbed feeder clearances. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 4/13 5.1.3 Any outage where a portion of the feeder has been out of service longer than six (6) months. (The Hipot Test is only required on the portion of the feeder being picked-up). 5.1.4 Any outage where a total of four (4) or more sections of feeder cable are installed or replaced. 5.1.5 A high tension customer installation or repair on new or existing equipment or cable. NOTE: High tension equipment or cable which is directly connected to the Company’s supply feeder or is energized by closing the line circuit breaker or circuit closing device must have been subjected to a Hipot Test within the six (6) months prior to energization. 5.1.6 A planned outage to break down a self-clearing (e.g. sub-cycle) fault. NOTE: The duration of the Hipot Test will be increased to thirty (30) minutes if any condition in the following section (5.2) is met. This increase in duration does not apply during the summer period, June 1 through August 31, or when dictated by system conditions. 5.2 Subject a feeder to a Table I Hipot Test for thirty (30) minutes following a non-summer outage if the feeder meets the criteria in Appendix A. These feeders have not received a 30 minute Hipot test during the previous three (3) years and operate in networks with a NRI greater than 0.2. Refer to Appendix B for notes. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 5/13 5.3 Exceptions to the Hipot Test: 5.3.1 Feeders that contain a grounding transformer or have no source of backfeed (from network transformers or unit substations) will only be subjected to a Table II Reduced Voltage Hipot Test for five (5) minutes. Refer to Appendix B for notes. 5.3.2 Subject feeders to a Table III Raised Voltage Hipot Test for thirty (30) minutes when a “condition” is not able to be established after: 5.3.2.1 A forced outage. This only applies when there is a confirmed fault on the feeder. 5.3.2.2 The feeder was proactively taken out of service to locate a self-clearing fault (as in section 5.1.6). Refer to Appendix B for notes. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 6/13 5.3.3 Any forced outages due to a non-fault condition, such as an overtrip due to mis-co-ordination with a downstream device (e.g. Loop FVRS) or a CIOA due to a breaker problem or inrush, are not required to be Hipot Tested. (Refer to the Power Quality SharePoint site for more information on inrush versus fault characteristics). 5.3.4 Feeders that contain crossings only require a Table II Reduced Voltage Hipot Test for five (5) minutes following a forced outage. Hipot Testing that follows a Planned Outage may be waived for feeders with crossings even if that feeder appears in Appendix A. 5.3.5 The testing of feeders with Metro North open-wire portions is covered by SO 18-07. NOTE: When a Hipot Test is required after a forced outage it will be applied to all portions of the feeder; including those partially restored by the use of sectionalizing switches. 6.0 AMMETER CLEAR TEST All AC distribution feeders should be subjected to an Ammeter Clear Test before they are restored to service. Where the feeder is also subjected to a Hipot Test, the Ammeter Clear Test should be performed prior to the Hipot Test. The results of the Ammeter Clear Test shall conform to the requirements stated in Table IV. Refer to SO 11-06 for information on waiving the Ammeter Clear Test. 7.0 EQUIPMENT TO BE DISCONNECTED PRIOR TO TESTS The following apparatus shall be disconnected prior to performing a Phase-toGround DC or VLF Hipot Test on any distribution feeder: • Phase to neutral connected potential transformers • Lightning arrestors • Grounding transformers • Shunt reactors • Any transformer with a neutral/ground connected HV winding • High tension customer equipment NOTE: Lightning arrestors are not required to be disconnected during Reduced Voltage Hipot Test. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 7/13 8.0 VALIDATION OF TESTING MEASUREMENTS 8.1 Prior to the application of any Hipot Test, test facilities leakage measurements shall be made at Hipot Test voltage for five minutes. 8.2 Upon the completion of any Hipot Test, test facilities leakage measurements shall be made at Hipot Test voltage for five minutes. 8.3 At stations with ammeter test sets, the condition of the test set shall be checked for ground continuity before and after each test. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 8/13 9.0 REFERENCES SPEC. NO. TITLE FILED IN ES-1002 Specification of Proof Testing of Station Electric Equipment and Circuits Station Electric Section Manual EO-2022 General Specification for High Tension Service Application & Design Manual No. 4 EO-2152 Distributed Network Reliability Improvements Application & Design Manual No. 4 EO-4035 Operating and Maintenance of Equipment on High Tension Customer’s Premises System Operation Manual No. 5 EOP-5022 Automated Voltage Reduction Program and Demand Response Programs Electric Operations Guidelines: Manual No. 4 SO11-06-11 Guide for Waiving Ammeter Clear Test Public Folders\Con Ed Co of NY\Central Operations\STO System & Transmission Operations\System Operation Procedures SO18-07-15 Operating Requirements Associated with Distribution Feeders Supplying Metro North Public Folders\Con Ed Co of NY\Central Operations\STO System & Transmission Operations\System Operation Procedures CIOA Guideline http://pq/CIOA/VisioCIOA%20guideline.pdf Christopher G. Jones (Signature on File) Department Manager, System Design Distribution Engineering Department George Murray (Signature on File) Section Manager, Dist. Cable Systems Distribution Engineering Department John Foglio REVISION 34: Changed requirements for Hipot Testing. Changes made to add clarity. Specification Revision EO-4019 34 Filing Information Rev Date FILE: SYSTEM OPERATION MANUAL No. 5 FIELD MANUAL No. 6, Section No. 8 Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 9/13 TABLE IV AMMETER CLEAR TEST LIMITS Maximum Limits 1. If the ammeter reading obtained during an Ammeter Clear Test is in excess of the following values, the feeder shall not be placed in service until the cause of the high reading has been determined and, if necessary, eliminated: NOMINAL OPERATING VOLTAGE BETWEEN CONDUCTORS ________[KV]_________ NORMAL MAXIMUM ALLOWABLE AMMETER CLEAR TEST READING ______ [AMPERES]______ 33 0.3 27 0.4 13 0.1 NOTE: Current readings in excess of those specified may be accepted if equally consistent on all phases with results of previous AC tests on the feeder. Interpretation of Reading 2. The following tabulation shall be used as a guide to interpret readings of the Ammeter Clear Tests: APPROXIMATE AMMETER CONDITION OF FEEDER __ READING [AMPERES]__ Feeder grounded 3-5 Phase to phase short circuit 3-5 Short Circuit on low voltage side of substation transformer or large high tension customer transformer 2-3 Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 10/13 TABLE IV (Cont’d) APPROXIMATE AMMETER __ READING [AMPERES]__ CONDITION OF FEEDER Short circuits on low voltage side of distribution transformer: a. 33kV System 0.9* b. 27kV System 1.4* c. 13kV System 4.0* d. 4kV System 2.0** 27kV shunt reactor, neutral ground switch closed. 0.1 (per shunt reactor) 13kV grounding transformer neutral ground switch closed 2.25 (per grounding transformer) Excitation current of transformer and charging current of cable. Less than 0.1 * Per 1000 kVA of transformer capacity. ** Per 10 kVA of transformer capacity. 3. If any of the following types of transformers are connected to the feeder when the Ammeter Clear Test is made, an abnormally high reading will be obtained: a. Three-phase transformer or auto-transformer banks with a three-legged core with the feeder winding wye-connected and the neutral grounded. b. Wye-delta transformer banks with the neutral grounded, where the wye winding is connected to the portion of the feeder on which the Ammeter Clear Test is being made. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 11/13 APPENDIX A FMS Online will now provide a real time list of feeders that meet the Appendix A criteria. These are feeders that have not received a 30 minute Hipot test during the previous three (3) years and operate in networks with a NRI greater than 0.2. For a list of these feeders: • • • Open FMS Online. Select ‘Reports.’ A drop-down list will appear. Select ‘Appendix A Feeders.’ A current list of all the feeders that meet the Appendix A criteria will appear. Note 1 This list is compiled in real-time by FMS Online. Note 2 The Control Center Shift Manager may waive a Hipot Test on any feeder on this list if it can be verified that a 30 minute Hipot was carried out during the previous three (3) calendar years, this is a non-network feeder, or the feeder has a grounding transformer. Note 3 For feeders with crossings, a Hipot Test following a Planned Outage may be waived even if that feeder appears on Appendix A. • • • To request access to FMS Online: Access the Product Access System via http://sto/Information/Request.aspx. Select ‘New Access Request.’ Check ‘Feeder Management System (FMS); select Read Only in the ‘Type of Access’ field. After you acknowledge the requirements you can submit your request. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 12/13 APPENDIX B – NOTES TO TABLE I, TABLE II, AND TABLE III Note A The VLF Hipot Test is preferred and should be used whenever the test set is available. The rate of rise of the applied voltage should not exceed 1kV per second with a pause of two or three seconds (not to exceed 5 seconds) after every 5kV step. Note B Hipot Tests are satisfactory only if the leakage current is constant or decreases without fluctuations or surges after the full test potential has been applied and is below the specified values at the end of the test. Current readings in excess of those specified may be accepted if they are consistent with the results of previous tests on the feeder. For the rate of rise of applied voltage, refer to Note A. Note C Upon the completion of tests on each phase and with the test set still connected to the cable, the supply voltage to the test set shall be reduced to zero and the cable grounded. Note D High tension customer's incoming devices shall be opened prior to performing a Hipot Test. All high tension customer's equipment connected to the line side of the incoming disconnect device shall be subject to the Company Hipot values in force during the time of the test. Note E All Hipot Tests are to be made with all conductors connected together and ground. On 33kV cable, Hipot Tests on 3-conductor cable or where 3 single conductor cables are in 1 duct, test between all 3 conductors connected together and ground. On single conductor cable in separate ducts, test between phase and ground with the other phases grounded. Specification Revision EO-4019 34 Filing Information Rev Date Effective Date 12/28/2015 System Operations Copyright Information 1966-2015 Consolidated Edison Co. of New York, Inc. Manual No. 5 Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution Engineering Intranet Site Distribution Engineering or http://distribution, for the current version prior to use. Page 13/13