Product Description Low Suction Pressure Shutdown Alarm Panels

advertisement
Product Description
Low Suction Pressure Shutdown Alarm Panels
Fire Pump Controllers
• FTA200-D
FTA200-E
Mounted on the enclosure door are the pilot lights
for visible alarm indication, the audible device for
audible alarm indication and the SILENCE ALARM
push-button.
Each pilot light will illuminate to indicate its alarm
condition and will remain lighted until the abnormal
condition has been corrected. The audible alarm
will sound when the alarm conditions occur and will
continue to sound until the abnormal condition has
been corrected or the SILENCE ALARM push-button has been pressed. Pressing the SILENCE
ALARM push-button will silence the audible alarm
but will not extinguish the pilot light. If another alarm
condition occurs the audible alarm will again sound
until silenced by the SILENCE ALARM push-button
or until the abnormal condition has been corrected.
A pressure switch for monitoring the suction pressure is mounted on the side of the enclosure.
Description—Firetrol® FTA200 low suction pressure
alarm and shutdown panels are designed to be used
with electric and diesel engine driven fire pump controllers. They are intended for use where a local
authority mandates pump shutdown in the event of
low suction pressure.
Approvals—These alarm panels have been approved by Factory Mutual.
Standard Features—The following are included as
standard with each controller:
Type D - Type D panels provide audible and visible
alarm indication for the following conditions:
„ Supervisory Voltage Normal
„ Pump Controller Voltage Failure
„ Low Suction Pressure (Automatic Reset)
Type E - Type E panels provide the same alarm indication as the Type D except that LOW SUCTION
PRESSURE shutdown and alarm must be manually
RESET when suction pressure is restored.
Construction - FTA200 alarm panels make use of
printed circuit boards which provide reliable and
trouble free service. The enclosures are NEMA Type
2 (IEC IP11) drip-proof for indoor wall mounting. The
standard enclosure color is red.
APPROVED
Modifications—The following are available as modifications to the controllers:
Special Enclosures
-F
NEMA Type 4X, 304 stainless (IEC IP56)
Consult Factory for other style enclosures.
Substitute Amber for Red Pilot Lights
-LA To meet local code requirements.
Operation on 220-240 Volts
-BA Panel is supplied as standard for operation
on 110-120 volts.
50 HZ Operation
-GZ Controller is supplied to operate on 50 HZ
incoming power.
Dimensions and Shipping Weight
Explanation of Catalog Number
FTA200-D-GZ
Alarm Panel Type
Modification Code(s)
Example - FTA200-D-GZ
Type D Alarm Panel with modification to operate
on 50 HZ incoming power.
Information Required With Orders
„ Catalog number of shutdown panel
„ Catalog number of controller to be used with
shutdown panel
„ Modifications if any (give complete description)
WARNING- Because NFPA 20 specifically prohibits the installation of any device in the suction
piping which will restrict starting or stopping of
the fire pump (See NFPA 20 (2007), Paragraph
5.14.9.1), ASCO Power Technologies, LP assumes
no liability when Type D or E Shutdown Panels
are used in connection with fire pump control
equipment.
Approx. Shipping Weight
20 lbs (9 kg)
Note—Due to continual product enhancements, dimensions and specifications may change at any time
without notice. Contact the factory or local representative for current specifications.
(919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA
PD200-03 (04-02-07)