Product Description Low Suction Pressure Shutdown Alarm Panels Fire Pump Controllers • FTA200-D FTA200-E Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication and the SILENCE ALARM push-button. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM push-button has been pressed. Pressing the SILENCE ALARM push-button will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM push-button or until the abnormal condition has been corrected. A pressure switch for monitoring the suction pressure is mounted on the side of the enclosure. Description—Firetrol® FTA200 low suction pressure alarm and shutdown panels are designed to be used with electric and diesel engine driven fire pump controllers. They are intended for use where a local authority mandates pump shutdown in the event of low suction pressure. Approvals—These alarm panels have been approved by Factory Mutual. Standard Features—The following are included as standard with each controller: Type D - Type D panels provide audible and visible alarm indication for the following conditions: Supervisory Voltage Normal Pump Controller Voltage Failure Low Suction Pressure (Automatic Reset) Type E - Type E panels provide the same alarm indication as the Type D except that LOW SUCTION PRESSURE shutdown and alarm must be manually RESET when suction pressure is restored. Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. APPROVED Modifications—The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) Consult Factory for other style enclosures. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Operation on 220-240 Volts -BA Panel is supplied as standard for operation on 110-120 volts. 50 HZ Operation -GZ Controller is supplied to operate on 50 HZ incoming power. Dimensions and Shipping Weight Explanation of Catalog Number FTA200-D-GZ Alarm Panel Type Modification Code(s) Example - FTA200-D-GZ Type D Alarm Panel with modification to operate on 50 HZ incoming power. Information Required With Orders Catalog number of shutdown panel Catalog number of controller to be used with shutdown panel Modifications if any (give complete description) WARNING- Because NFPA 20 specifically prohibits the installation of any device in the suction piping which will restrict starting or stopping of the fire pump (See NFPA 20 (2007), Paragraph 5.14.9.1), ASCO Power Technologies, LP assumes no liability when Type D or E Shutdown Panels are used in connection with fire pump control equipment. Approx. Shipping Weight 20 lbs (9 kg) Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD200-03 (04-02-07)