Synchronous Gen Parameters * Required * Want to submit data for a Synchronous Generator? Please Select... Only fill the data below if 'Yes' is s No Provide individual generator capability (All values requested here are for individual units) * Machine ID (e.g. ST, CT, CT1, CT2, ST2, etc.): Note: List all the machine IDs that these data corresponds (e.g. CT1, CT2). * MVA base: * Terminal voltage: * Nominal power factor: MVA KV Summer * Unit maximum net capacity output (unit CIR): * Unit gross energy output: * Unit reactive power capability at max gross energy output - leading: Winter MW MVAR Underexcited * Unit reactive power capability at max gross energy output - lagging: MVAR Overexcited Unit auxiliary load at max gross energy power output: * Where is the auxiliary load being connected? Please provide diagram illustrating aux load configuration. * Any additional comments on the capability (Aux Load): MW MVAR Please select... Load related to the operations of the plant (e.g. fans, pumps, etc.) Generator Parameters All reactances and resistance values in PU on Machine MVA Base * Combined turbine-generator-exciter inertia, H: * Speed damping coefficient, D: kWs/kVA 1 < H < 10 P.U. 0≤D<3 Generator Saturation * Generator saturation at 1.0 p.u. voltage, S (1.0): PU * Generator saturation at 1.2 p.u. voltage, S (1.2): PU 0 < S1.0 S1.0 < S1.2 Unsaturated Reactances * Direct axis synchronous reactance, Xd(i): PU * Direct axis transient reactance, X'd(i): PU * Direct axis sub-transient reactance, X"d(i): PU xd < 2.5 x'd < 0.5 x xd x"d < x'd * Quadrature axis synchronous reactance, Xq(i): PU * Quadrature axis transient reactance, X'q(i): PU * Quadrature axis sub-transient reactance, X"q(i): PU * Stator leakage reactance, Xl: * Negative sequence reactance, X2(i): * Zero sequence reactance, X0(i): PU PU PU Saturated Reactances * Saturated subtransient reactance, X"d(v): PU * Negative sequence reactance, X2(v): PU xq < xd x'q < xq x"q < x'q X"d(v) < X"d(i) * Zero sequence reactance, X0(v): Resistances * DC armature resistance, Ra: * Positive sequence resistance, R1: * Negative sequence resistance, R2: * Zero sequence resistance, R0: PU Ohms PU PU PU Time Constants * Direct axis transient open circuit, T'do: sec * Direct axis sub-transient open circuit, T"do: sec * Quadrature axis transient open circuit, T'qo: sec 1. < T(′do < 10.) 0.01667 < T"do < 0.2 0.2 ≤ T′qo ≤ 1.5 * Quadrature axis sub-transient open circuit, T"qo: sec 0.01667 ≤ T"qo ≤ 0.2 * Armature three-phase short circuit, Ta3: sec 0.025 ≤ Ta ≤ 0.1 Control Systems Select the appropriate dynamic model * Exciter * If any of the above models are not submitted, then explanation is required: * Governor: * If any of the above models are not submitted, then explanation is required: Please select.... Please select... * Power System Stabilizer (PSS): * If any of the above models are not submitted, then explanation is required: Please select... Additional Information: Synchronous Transformer * Want to submit data for a Generator Step-up Transformer Please select... Please complete all required information below. If you do not wish to submit a transformer for this turbine, please select "No" in the drop down above. Generator Step-Up (GSU) Transformer Form Note: Main Transformer information is requested in a separate * MVA base: Total Transformer Ratings (MVA) e.g. OA/FA1/FA2 MVA * Rating 1: * Rating 2: * Rating 3: * Select transformer windings: Impedances (All Values in PU on Transformer MVA base) MVA MVA MVA Please select... R * (a) High-side to low-side: * (b) High-side to tertiary: * (c) Low-side to tertiary: PU PU PU Winding Voltages (kV) * High-side: * Low-side: * Tertiary: KV KV KV Winding Connection Types (Delta, Wye, Wye Gnd, etc) * High-side: * Low-side: * Tertiary: * Tap position: Off-nominal Turns Ratio: Number of taps: Step size: Any additional comments on the transformer? Example: Specify machine ID jX X/R the data below if 'Yes' is selected on the left