MGS-B, C, and HV Series / Rating Table Low Voltage (MGS-B, C series) 50 Hz/1500 min-1/380-415 V 60 Hz/1800 min-1/380 V MGS-B Model MGS2700 Engine S16R2-PTAW MGS2500 S16R-PTAA2 MGS2000 S16R-PTA2-S Stand-by (kVA) Prime Code: P (kVA) Prime Continuous Code: CP (kVA) (kVA) KT84 2500 2500 2290 2275 2235 2220 2000 2000 1680 1675 1600 1600 1500 1500 1250 1050 1000 880 780 690 580 515 - 2250 2250 2035 2020 2030 2015 1800 1810 1600 1600 1450 1450 1362.5 1362.5 1125 1000 885 800 700 625 530 480 - 2250 2250 2000 2000 1935 1925 1735 1735 1390 1390 1287.5 1287.5 1055 900 770 750 665 560 500 450 - KT83 L51L7 KT83 L51L7 7PF 7PE MGS1500 S16R-PTA-S L51M6 L50V1 7PD MGS1400 S12R-PTA2-S 7PD L50V1 7PD MGS1200 S12R-PTA-S 7PB L50L8 7PC MGS1000 S12H-PTA-S H6K H6J MGS0900 S12A2-PTA2-S MGS0700 S6R2-PTAA-S MGS0650 S6R2-PTA-S MGS0500 S6R-PTA-S S6A3-PTAA-S MGS0450 S6A3-PTA-S MGS-C Alternator L51V9 H6J H6G H6H H6G H5F H5F H5E H5E H5D H5C High Voltage (MGS-HV series) 1900 1900 1550 1550 1130 1140 950 900 685 550 500 385 Voltage Range: 50 Hz 190-220 V & 380 V-440 V Stand-by: Code: S Applicable for supplying emergency power at varying load in the event of normal utility power interruption. Fuel stop power in accordance with ISO15550, ISO3046/1, JIS8002-1, DIN6271 and BS5514. Prime: Code: P Applicable for supplying emergency power at varying load in the event of normal utility power interruption. ;+10% overload in accordance with ISO3046/1. Overload power in accordance with ISO15550, ISO3046/1, JIS8002-1, DIN6271 and BS5514. Prime: Code: CP Applicable for supplying power with varying load instead of the utility for an unlimited time. ;+10% overload is allowed in accordance with ISO3046/1. Prime power in accordance with ISO8528. Continuous: Code: C Applicable for supplying power continuously. Continuous power in accordance with ISO8528, ISO15550, ISO3046/1, JISB8002-1 and BS5514. Conditions: Engine ratings are based on SAE J1349 standard conditions and also apply at ISO3046/1, DIN6271 & BS5514 standard conditions. Fuel rates: based on ASTM D975, BS2869 and on fuel oil of 35° API (16°C or 60°F) gravity having a LHV of 42,780 kJ/kg (18,390 Btu/Ib.) when used at 29°C (85°F) and weighing 838.9 g/liter (7.001 lbs./U.S. gal.). 50 Hz/1500 min-1 MGS-B Model Engine MGS2500 S16R-PTAA2 MGS2000 S16R-PTA2-S S16R-PTA-S MGS1500 S16R-PTA MGS1400 S12R-PTA2-S S12R-PTA-S MGS1200 S12R-PTA MGS1000 S12H-PTA-S MGS0900 S12A2-PTA2-S MGS0500 S6R-PTA-S S6R-PTA S6A3-PTAA-S MGS0450 S6A3-PTA-S Alternator Stand-by (kW) Prime Code: P (kW) 73PF 2000 2000 1900 1900 1700 1700 1415 1420 1265 1265 1070 860 620 500 480 - 1800 1810 1730 1730 1550 1550 1280 1280 1145 1145 970 785 560 460 435 - L51M68 73PF L51M68 73PF L51S58 73PD L51S58 73PD L50V18 73PD L50L78 73PD L50L78 73PD H6K H6J H6G H6G H5F H5E H5E H5C MGS-C Prime Continuous Code: CP (kW) (kW) 1800 1720 1640 1650 1470 1470 1220 1220 1080 1080 920 740 520 430 410 - 1240 1250 920 920 830 580 455 345 Model Engine MGS2700HV MGS2500HV MGS2000HV MGS1500HV MGS1400HV MGS1200HV MGS1000HV 16R2-PTAW S16R-PTAA2 S16R-PTA2-S S16R-PTA-S S12R-PTA2-S S12R-PTA-S S12H-PTA-S Stand-by (kVA) 3.3 kV 6.6 kV 2500 2500 2250 2250 2200 2200 2000 2000 1575 1600 1475 1475 1225 1225 Prime Code: P (kVA) 11 kV 2500 2250 2200 2000 1600 1475 1225 10 kV 2500 2250 2200 2000 1600 1475 1225 3.3 kV 6.6 kV 2250 2250 2010 2010 2000 2000 1810 1810 1450 1450 1350 1350 1060 1100 10 kV 2250 2010 2000 1800 1450 1340 1100 Continuous (kVA) Prime Code: CP (kVA) 11 kV 2250 2005 2000 1800 1450 1340 1100 3.3 kV 6.6 kV 2250 2250 2000 2000 1900 1900 1700 1725 1380 1380 1280 1280 1050 1050 10 kV 2250 2000 1900 1725 1380 1270 1040 11 kV 2250 2000 1900 1725 1380 1270 1040 3.3 kV 6.6 kV 1900 1900 1560 1550 1140 1140 940 945 10 kV 1900 1540 1130 935 11 kV 1900 1540 1130 935 60 Hz/1800 min-1 Model Engine MGS2500HV MGS2000HV S16R-PTAA2 S16R-PTA2-S S16R-PTA-S S16R-PTA S12R-PTA2-S S12R-PTA-S S12R-PTA S12H-PTA-S MGS1500HV MGS1400HV MGS1200HV MGS1000HV Stand-by (kW) 3.3 kV 2000 1850 1575 1420 1270 1070 4.16 kV 2000 1920 1700 1420 1270 1070 6.6 kV 2000 1850 1575 1410 1260 1070 Continuous (kW) Prime Code: CP (kW) 13.8 kV 2000 1850 1575 1410 1260 1060 3.3 kV 1800 1650 1460 1225 1080 930 4.16 kV 1800 1650 1470 1230 1080 920 6.6 kV 1800 1640 1460 1220 1070 920 13.8 kV 1800 1640 1460 1220 1070 910 3.3 kV 1250 920 830 4.16 kV 1250 920 830 6.6 kV 1240 910 820 13.8 kV 1240 900 810 Notice: 60 Hz/1800 min-1/480 V MGS-B Model Engine MGS2500 S16R-PTAA2 MGS2000 S16R-PTA2-S S16R-PTA-S MGS1500 S16R-PTA MGS1400 S12R-PTA2-S S12R-PTA-S MGS1200 S12R-PTA MGS1000 S12H-PTA-S MGS0900 S12A2-PTA2-S MGS0500 S6R-PTA-S S6R-PTA S6A3-PTAA-S MGS0450 S6A3-PTA-S Alternator Stand-by (kW) Prime Code: P (kW) 7PF 2012 2010 1900 1900 1680 1700 1420 1420 1260 1260 1070 870 630 500 480 - 1820 1810 1730 1730 1550 1550 1280 1280 1150 1150 960 790 570 460 435 - L51M6 7PE L51M6 7PD L51S5 7PD L51S5 7PC L50L8 7PB L50L7 H6J L50L7 H6J H6H H5F H5F H5D K5D H5C H4F MGS-C Outputs are based on the following standard conditions -Ambient temperature: 40°C -Altitude above sea level: Below 1,000 meters For alternative voltages, overload requirements, extreme climate conditions, strict emissions requirements or additional rating requirements, please consult with your nearest Mitsubishi dealer. Specifications and some materials may be changed without notice. Prime Continuous Code: CP (kW) (kW) 1820 1800 1650 1650 1470 1470 1220 1220 1080 1080 920 740 540 430 410 - 1250 1250 910 920 830 620 460 345 Voltage Range: 60 Hz 200-240 V & 380 V-480 V 7 8 MU-G Series KU Diesel Series The MU-G Series is a fully customizable range of diesel generator sets dedicated to fulfilling every client’s requirement. With our comprehensive support from the design stage to after-sales service, you can select the most appropriate power generation system to meet your needs. The KU diesel engines were developed for those clients with major power demand requirements. With its high fuel efficiency, it minimizes the energy cost in the long term. Features Features (1) High outputs power from 3760 kW to 15400 kW (2) Low fuel cost due to high fuel efficiency (3) Long planned maintenance interval (4) Responsive load following (5) Extraordinary durability & reliability -Over 250 delivery record since 1985 -Max over 120000 operation hours including HFO operation (6) Wide fuel flexibility (Diesel, HFO, etc) (7) Low emission, low noise, and low vibration (1) Wide range of output from 735 kVA to 4500 kVA (2) A variety of control systems to suit all the user’s requirement (3) Appropriate for continuous operation with its excellent fuel efficiency (4) Compact yet powerful systems. The minimum space are required for installation (5) From low to high voltage available (6) Black start capability for uninterruptible power supply MU-G/50 Hz Stand-by (kVA) Model M16U-G M12U3-G M12U-G M8U-G M6U2-G M6U-G 1000 min-1 4280 4000 4290 3860 3200 3000 2140 2000 1760 1655 1600 1500 PTK PTA PTK PTA PTK PTA PTK PTA PTK PTA PTK PTA Prime (kVA) 750 min-1 3075 2820 2300 2115 1535 1410 1325 1235 1150 1055 1000 min-1 4100 3850 3900 3510 3075 2885 2050 1900 1650 1550 1540 1440 Continuous (C) (kVA) 750 min-1 2800 2560 2115 1920 1400 1275 1200 1125 1055 960 1000 min-1 3685 3450 3750 3375 2765 2590 1845 1725 1500 1405 1380 1300 750 min-1 2560 2300 1900 1730 1280 1150 1080 1015 960 865 Continuous (D) (kVA) 1000 min-1 3385 3170 3750 3375 2535 2375 1690 1585 1375 1290 1270 1190 750 min-1 2300 2075 1700 1555 1150 1035 970 915 865 775 Output (kW) KU44 M16U-G M12U3-G M12U-G M8U-G M6U2-G M6U-G PTK PTA PTK PTA PTK PTA PTK PTA PTK PTA PTK PTA 1200 min-1 900 min-1 4500 3865 4280 3570 3940 3650 3375 2900 3200 2675 2250 1930 2140 1785 1600 1500 1685 1450 1600 1340 Prime (kVA) 720 min-1 1200 min-1 900 min-1 2900 4335 3700 2660 4075 3455 3650 3340 2175 3250 2800 2000 3060 2600 1450 2165 1855 1330 2035 1725 1225 1515 1175 1400 1085 1625 1395 1000 1530 1300 Continuous (C) (kVA) 720 min-1 1200 min-1 900 min-1 2660 3900 3375 2420 3635 3115 3375 3125 2000 2920 2500 1815 2725 2335 1330 1950 1685 1200 1815 1560 1140 1400 1065 1275 1000 1460 1265 900 1365 1170 Continuous (D) (kVA) 720 min-1 1200 min-1 900 min-1 2400 3500 3000 2175 3275 2800 3375 3125 1815 2630 2280 1630 2455 2100 1210 1750 1520 1085 1635 1400 1035 1270 955 1200 900 1315 1140 815 1225 1090 720 min-1 2175 1960 1630 1470 1090 980 930 860 815 735 KU34 KU30B Voltage Renge : 60 Hz 200-240 V, 380-480 V, 3.3 kV, 4.16 kV, 6.6 kV, 13.8 kV ● 514 min-1 18KU44 15000 15400 16KU44 13350 13700 14KU44 11650 12000 12KU44 10000 10300 50 Hz 60 Hz 750 min-1 720 min-1 18KU34 9250 8900 16KU34 8200 7900 14KU34 7200 6900 12KU34 6150 5900 18KU30B 8100 7780 16KU30B 7200 6910 14KU30B 6300 6050 12KU30B 5400 5180 18KU30A 5880 5650 16KU30A 5230 5020 14KU30A 4570 4390 12KU30A 3920 3760 Model MU-G/60 Hz Stand-by (kVA) 60 Hz 500 min-1 Output (kW) Voltage Renge : 50 Hz 190-220 V, 380-440 V, 3.3 kV, 6.6 kV, 10 kV, 11 kV Model 50 Hz Model Mitsubishi Heavy Industries uses the following conditions to determine the rated output of generator sets : Stand-by: No overload, average load of approximately 70%, annual operation hours of approximately 500 hours; Prime: Overload of 10%, average load of approximately 80%, annual operation hours of approximately 3000 to 4000 hours, hours of operation at 80% or higher not exceeding 20% of annual operation hours; Continuous(C): Overload of 10%, average load of approximately 90 to 100%, unlimited annual operation; KU30A Voltage Renge : 50 Hz 3.3 kV, 6.6 kV, 10 kV, 11 kV 60Hz 3.3 kV, 4.16 kV, 6.6 kV, 13.8 kV *Based upon ISO3046 Standard Conditions & Configuration Continuous(D): Connection to utility grid, no overload, unlimited annual operation. Indicated output figures calculated in compliance with the standard ambient conditions specified by IS03046-1 (atmospheric pressure: 100 kPa, ambient temperature: 25°C, relative humidity: 30%, cooling water temperature at inlet of intake air cooler : 25°C) and based on generator efficienoy of 95% at operating speed between 750 min-1 and 1200 min-1 and efficiency of 94% at 720 min-1. ● 9 10