Common DC Bus Selection Guide Common DC Bus Applications Introduction Contents Overview this page Typical Common DC Bus Configuration this page Non-Regen Bus Supplies 3 Line Regeneration Solutions 8 Choppers & Dynamic Brakes 15 DC Input Drives 21 Power Components 21 Reference Materials 27 Overview An increasing number of drive systems in a wide range of industrial applications and power ranges are being configured today in a common DC bus configuration. This drive system configuration provides users with significant advantages such as; design flexibility, higher efficiency, and cost savings. A common rectifier can supply power to the DC bus for all the DC-AC inverters instead of individual rectifiers in the stand-alone AC drives. The power sharing on the DC bus is possible for applications where some inverters may be motoring while others in the same process may be simultaneously generating power. The power generating inverters feed power through the DC bus to the motoring inverters. This results in less power usage from the rectifier unit. Cost savings are realized through the use of application rated system components such as reactors, braking units, contactors, etc. This reduces the number of parts used on the drive system as well as assembly, wiring, wiring costs, number of failures and spare parts. PowerFlex® Common Bus products provide a wide range of modular solutions for the common DC bus application. Refer to page 27 for product details. Typical Common Bus Configuration Common DC Bus Main Switch or Input Contactor Line Reactor Three-Phase Source Fusing Common DC Bus SCR Bus Supply Fusing Inverters Three-Phase Motor 2 Three-Phase Motor Three-Phase Motor Common DC Bus Applications Non-Regen Bus Supplies PowerFlex 20S SCR Bus Supply Catalog Number Explanation Position Number 1-3 20S 4 5-7 8 9 10 D 400 N E N b c d e f a a Product Code Type 20S SCR Bus Supply 7 7 SCR Bus Supply available through Drive Systems only. b Voltage Rating Standards Compliance Code Input Voltage Ph. DC Output D 400/480V ac 3 540…650V dc F 600/690V ac 3 675…930V dc PowerFlex SCR DC Bus Supply conforms to the following: Conformity to: c Rating Approvals & Standards UL Listed 9 UL 508C c-UL Listed 9 CAN/CSA-C22.2 No. 14-M91 CE Compliant ✶ 9 EN61800-3, EN50178 Code Output 400 400A, 400/480V 600 600A, 400/480V 1K0 1000A, 400/480/600/690V ✶ SCR Bus Supply will meet the essential requirements for CE compliance provided an externally mounted line reactor and HF filter is used. d Enclosure Code Rating Conformal Coating N Open/IP00 No Description e PowerFlex SCR Bus Supplies are single-direction power converters for the front-end of common DC bus drive systems. The supplies convert incoming three-phase AC line voltage to a common DC bus voltage and current. The SCR Bus Supply offers the following features: y Six-pulse, full-wave, three-phase SCR bridge rectifier unit. y Built-in AC line and DC bus fuses (400 & 600A units). Rectifier branch fuses, snubber circuit and DC bus feedback fuses (1,000A units). All fuses feature trip indicator switches. y Overtemperature sensor located in the heat sink for thermal protection of the SCR bridge rectifier. y RC snubber circuit for dampening and linearity of overvoltages. y MOV snubber circuit for surge protection. y Precharge Board with enable contactor. y Stand alone and master-slave configurations (1,000A units only). A maximum of four slave units may be connected in parallel. Documentation & Shipping Carton Code User Manual Carton E English Yes f Configuration Code Type N Stand Alone M Master (1000A Only) ✶ S Slave (1000A Only) ✶ ✶ PowerFlex SCR Bus Supply units with Master and Slave configurations are available for 480 and 690 volts, but only with a 1000A output current rating. 3 Common DC Bus Applications Non-Regen Bus Supplies Product Selection Specifications Common to All SCR Bus Supply Units PowerFlex SCR Bus Supplies Voltage Description 400A, Stand Alone 400/480V 600/690V Cat. No. 20SD400NEN 600A, Stand Alone 20SD600NEN 1000A, Stand Alone 20SD1K0NEN 1000A, Master 20SD1K0NEM 1000A, Slave 20SD1K0NES Voltage Tolerance: –10% of minimum, +10% of maximum Frequency Tolerance: 47-63 Hz Displacement Power Factor: 0.92 lagging (entire load range) Efficiency: 99.5% at rated amps, nominal line volts. Line Transients: up to 6000 volts peak per IEEE C62.41-1991 Maximum Short Circuit Current Rating: 85 kA Cooling: Forced ventilation cooled by tangential blower below heat sink. 1000A, Stand Alone 20SF1K0NEN 1000A, Master 20SF1K0NEM Blower Power Consumption: 200 VA 1000A, Slave 20SF1K0NES Cooling Air: 600 m3/h Control Input Specifications HF Filter When this filter is used, the HF emission limits for class A, group 2 (EN55011) in the second environment (industrial supply network) according to the product standard EN61800-3 are met, and the Bus Supply fulfills CE conformity. Description Cat. No. 20S-RFC HF Filter, 690V AC Line Reactors A minimum reactance is required to limit peak currents in the AC line and the bridge circuit. This can be accomplished with a matched supply transformer or by adding a line reactor to ensure the requested minimum voltage drop over the total line impedance. The minimum voltage drop must be 3%. Line Reactor selection is based on the DC Amps sum of the connected drives and the supply transformer used. Refer to page 21 for selection information. Enable Contactor Coil: Single-Phase 115V ac, 30 VA (pickup), 4.5 VA (hold) Blower Current Consumption: Single-Phase 115V ac, 50/60 Hz, 1A Control Output Specifications Heat Sink Temperature Sensor: Sensor trips if heat sink temperature exceeds maximum temperature. Resistive Rating: 15A at 125V ac, 10A at NC Contact Output Rating 250V ac, 7A at 24V dc (max.): Inductive Rating: 10A at 125V ac, 6A at 250V ac Fuse Trip Indication Micro Switches F1-F11, NC Contact Output Rating (max.): Resistive Rating: 10A at 30 to 250V ac, 8A at 30V dc Enable Contactor K1, NC Contact Output Rating (max.): Resistive Rating: 10A at 24 to 230V ac, 3A at 30V dc Inductive Rating: L/R=25ms, 10A at 30 to 250V ac Inductive Rating: L2.2A at 24 to 230V ac Permitted Max. Capacitance This is the total DC Bus capacitance sum of for Connection to the DC the permitted drives to connect. Bus Supply: Approvals and Standards Compliance Specifications NFPA 70 - US National Electrical Code NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems. NEMA 250 - Enclosures for Electrical Equipment IEC 146 - International Electrical Code. Input Ratings UL and cUL Listed to UL508C and CAN/CSA-C22.2 Description/Cat.No. 20SD400 20SD600 20SD1K0 20SF1K0 Nominal AC Input Voltage: 400/480V 600/690V Frequency: 47-63 Hz 47-63 Hz Operational AC Input Voltage: 187-528V 269-759V Input Current (Max. Cont. RMS): 355 521 843 843 Input kVA at Max. Cont. RMS Amps: 246/295 361/433 584/700 876/1007 The Bus Supply is designed to meet the following specifications: Marked for all applicable European Directives EMC Directive (89/336/EEC) Emissions: EN 61800-3 Adjustable Speed electrical power drives systems Part 3 Immunity: EN 61800-3 Second Environment, Restricted Distribution Low Voltage Directive (73/23/EEC) EN 50178 Electronic Equipment for use in Power Installations Output Ratings DC Bus Amps Continuous: 300 500 800 800 3 Sec. Every Minute: 450 750 1200 1200 Max. Continuous DC Bus Amps without Overload: 400 600 1000 1000 Power Dissipation - Watts at Max. Continuous Amps: 1200 1600 2700 2800 DC Bus Voltage: 4 AC Input Nominal Maximum 400V 540V 750V 480V 650V 750V 600V 810V 1080V 690V 930V 1080V Environmental Specifications Altitude: 1000 m (3300 ft.) max. without derating. Above 1000 m the derating for the output current is 1% per 100 m (330 ft). Ambient Operating Temperature without Derating: Open Type/IP00: 0 to 40°C (32 to 104°F) Above 40°C up to 50°C (122°F) maximum temperature the output Amps must be derated by 1% per °C (1.8% per °F). Storage Temperature (all): –40 to 70°C (–40 to 158°F) Relative Humidity: 5 to 95% non-condensing Shock: 15G peak for 11ms duration (±1.0 ms) Vibration: 0.152 mm (0.006 in.) displacement, 1G peak Common DC Bus Applications Non-Regen Bus Supplies Bus Supply Mounting Dimensions The dimensions and weights provided in the following drawing are for estimating purposes only. Contact your local Rockwell Automation Sales Office if certified drawings are required. 9.5 (0.37) 200 (7.87) B 35.0 (1.40) Dia. Lifting Holes 3.0 (1.20) Front View Side View A C 9.5 (0.37) D A B C D 400A Unit Type 535 (21.1) 404 (15.9) 580 (22.8) 276 (10.9) 30 kg (66 lb) Weight 600A 740 (29.1) 490 (19.3) 785 (30.9) 276 (10.9) 43 kg (95 lb) 1000A 740 (29.1) 490 (19.3) 785 (30.9) 276 (10.9) 67 kg (147 lb) Dimensions are in millimeters and (inches) 5 Common DC Bus Applications Non-Regen Bus Supplies PowerFlex 20T Diode Bus Supply Catalog Number Explanation Position Number 1-3 4 5-7 8 9 20T D 120 A E a b c d e a Product Code Type 20T Diode Bus Supply b Voltage Rating Code Input Voltage Ph. DC Output D 240…480V ac 3 325…650V dc E 500…600V ac 3 675…810V dc Standards Compliance c PowerFlex Diode DC Bus Supply conforms to the following: Conformity to: Rating Code Output Frame 120 120.0A 2 Approvals & Standards UL Listed 9 UL 508C c-UL Listed 9 CAN/CSA-C22.2 No. 14-M91 CE Compliant 9 EN61800-3, EN50178 d Enclosure Code Rating A NEMA Type 1/IP20 e Documentation & Shipping Carton Description Code User Manual Carton E English Yes PowerFlex Diode Bus Supplies are single-direction power converters for the front-end of common DC bus drive systems. The supplies convert incoming three-phase AC line voltage to a common DC bus voltage and current. The diode Bus Supply offers the following features: y Six-pulse, full-wave, three-phase diode bridge rectifier unit directly connected to the line input terminals. y Bus supply overtemperature sensors located in the heat sink for thermal protection of the diode bridge rectifier. y MOV circuit for surge protection connects to the three input phases. y Cooling fans powered by integral 24V DC supply. y DC bus snubber circuit for dampening and linearity of overvoltages. y Integral DC chokes, input filter capacitors and common mode capacitors compose an RFI filter meeting the requirements of EMC product standard 61800-3 for industrial environments. 6 Product Selection PowerFlex Diode Bus Supplies Voltage Description Cat. No. 240/480V 120A 20TD120AE 500/600V 120A 20TE120AE Common DC Bus Applications Non-Regen Bus Supplies Bus Supply Mounting Dimensions Specifications Input/Output Ratings AC Input Voltage Range 200-480V Unit 500-600V Unit Nominal AC Input Voltage: 240V 400V 480V 500V 600V Nominal DC Bus Voltage: 325V 540V 648V 675V 810V Continuous RMS AC Input Current: 105A 105A 105A 105A 105A Continuous DC Bus Current: 120A 120A 120A 120A 120A Voltage Tolerance: –10% of minimum, +10% of maximum. Frequency Tolerance: 47-63 Hz. Displacement Power Factor: 0.92 lagging (entire speed range) Efficiency: 99.5% at rated amps, nominal line volts. Line transients: up to 6000 volts peak per IEEE C62.41-1991 Heat Dissipation: 500 W The dimensions and weights provided in the following drawing are for estimating purposes only. Contact your local Rockwell Automation Sales Office if certified drawings are required. 15 (0.59) 5.8 (0.23) 222.0 (8.74) 192 (7.56) 5.5 (0.22) 200.0 (7.87) 342.5 (13.48) 320.0 (12.60) Max. Short Circuit Current Maximum short circuit current rating to Rating using Recommended match specified fuse/circuit breaker Fuse or Circuit Breaker Type: capability. Front View Side View Control Output Specifications Heat Sink Temperature Sensor: Contact Output Rating (max.): The two temperature sensors trip if heat temperature exceeds 85°C. Resistive Rating: 15A at 125V ac, 10A at 250V ac, 7A at 24V dc Inductive Rating: 10A at 125V ac, 6A at 250V ac Approvals and Standards Compliance The Bus Supply is designed to meet the following specifications: NFPA 70 - US National Electrical Code NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems. NEMA 250 - Enclosures for Electrical Equipment IEC 146 - International Electrical Code UL and cUL Listed to UL508C and CAN/CSA C2.2 No. 14-M91 Marked for all applicable European Directives EMC Directive (89/336/EEC) 5.5 (0.22) 8.0 (0.31) 151.0 (6.03) 111.0 (4.37) 71.0 (2.83) 50.5 (2.00) for Gland M50 16.5 (0.66) for Gland M16 141.0 (5.63) Approximate Shipping Weight 23 kg (50.7 lbs) 115.0 (4.59) Bottom View Dimensions are in millimeters and (inches) Emissions: EN 61800-3 Adjustable Speed electrical power drives systems Part 3 Immunity: EN 61800-3 Second Environment, Restricted Distribution Low Voltage Directive (73/23/EEC) EN 50178 Electronic Equipment for use in Power Installations Environmental Specifications Altitude: 1000 m (3300 ft.) max. without derating. Above 1000 m the derating for the output current is 1% per 100 m (330 ft). Ambient Operating Temperature without Derating: Open Type/IP00: 0 to 50°C (32 to 122°F) NEMA Type 1/IP20: 0 to 40°C (32 to 104°F) Storage Temperature (all): –40 to 70°C (–40 to 158°F) Relative Humidity: 5 to 95% non-condensing Shock: 15G peak for 11ms duration (±1.0 ms) Vibration: 0.152 mm (0.006 in.) displacement, 1G peak Permitted AC-Drives for connection to the DC-Bus Supply PowerFlex AC Drives with built-in precharge circuit, 1336 and GV3000 AC Drives 7 Common DC Bus Applications Line Regeneration Solutions 1336 REGEN Line Regeneration Package Catalog Number Explanation Position Number 1 2 3 1336R - VB a 4 5 180 - AA - HAB b c d e a Product Code Type 1336R 1336 REGEN b Drive Rating Code Input Voltage Ph. Hz VB 380…480V ac 3 50/60 c Rating Standards Compliance The 1336 REGEN conforms to the following: Conformity to: Code kW (Hp) 048 38.4 (48.2) 078 62.3 (78.2) 180 143.7 (180.4) Standard Product UL Listed 9 CSA Certified (c-UL) 9 d Enclosure Code Rating AA IP 20 (NEMA Type 1) AN IP 00 (Open) e Description The 1336 REGEN Line Regeneration Package can be configured to address the needs of two operating modes; the Regenerative DC Bus Supply mode and the Regenerative Brake mode. The selected operating mode will result in different implementation costs and hardware requirements. In the Regenerative Brake Mode the 1336 REGEN is used to remove braking energy from the DC bus and return it back to the three-phase AC utility. In many regenerative applications, the 1336 REGEN offers an energy-efficient alternative to dynamic brakes and chopper module/resistor combinations. In the Regenerative DC Bus Supply Mode, the 1336 REGEN supplies both motoring and regenerative current to one or more DC input drives. When the net power requirements of the attached common bus drives demand motoring power, energy flows from the utility to the common DC bus. When the net power requirements of the attached common bus drives demand regenerative power, energy flows from the common DC bus to the utility. 8 HIM Code Description HAB Blank - No Functionality HAP Programmer Only ✶ IP20 (NEMA Type 1) - Field must be specified. ✶ Common DC Bus Applications Line Regeneration Solutions Product Selection 1336 REGEN Bus Supply Example The 1336 REGEN Line Regeneration Package consists of: y A converter that transforms a three-phase AC input source into a DC output source. y A precharge unit that limits the inrush current and provides AC line voltage phase and magnitude information to the converter. When configured as a regenerative brake, a 3% 1321 line reactor will be required to limit current harmonics on the AC line and to provide impedance between the regenerative brake and the attached drives. When configured as a regenerative DC bus supply, a 10% line reactor and an EMI filter/3% reactor combination for high frequency noise attenuation will be required. The 3 or 10% 1321 line reactor and EMI filter are not included in the line regeneration package and must be ordered separately. 1336 REGEN Operating Mode Selection Application Requirements Regen DC Bus Supply Mode 3% Line Reactor AC Input 1336 REGEN Precharge EMI Filter 1336 REGEN Converter 10% Line Reactor 1336 REGEN Package (includes Converter & Precharge Module) Nominal Brake Rating Frame Input Amps IP00 (Open) No Enclosure Code Code 48.2 38.4 1336R-VB048-AN 1336R-VB048-AA C 78.2 62.3 1336R-VB078-AN 1336R-VB078-AA D 180.4 143.7 1336R-VB180-AN 1336R-VB180-AA Output kW Regen Brake Mode 1321 Line Reactors and EMI Filters X X High Power Factor ✶ X Equal Braking and Motoring HP ✶ X Less Braking Than Motoring HP ✶ X User Installed Options Single Drive Application ✶ X Human Interface Module Option Kits Intermittent Braking or Low Braking Duty Cycle ✶ X Refer to page 23. Description ✶ The Regenerative Bus Supply Mode can also be used for these applications, but will result in a more complex hardware configuration and a higher total system cost. Regenerative Bus Supply operation requires a custom Bulletin 1321 10% line reactor, while Regenerative Brake operation requires a standard Bulletin 1321 3% line reactor. The mode of operation is selected by a parameter setting in the 1336 REGEN Converter. 1336 REGEN Frame Designations AC Input kW Amp Rating IP20 (NEMA Type 1) General Purpose B Multiple Drive Applications 1336 REGEN Converter Rating DC Common Bus Drive DC Common Bus Drive Low Current Harmonics Frame Reference DC 1336 REGEN Precharge Rating AC Input kW Amp Rating B 38.4 48.2 38.4 48.2 C 62.3 78.2 62.3 78.2 D 143.7 180.4 143.7 180.4 Used with … Cat. No. IP 20 (NEMA Type 1) HIM Blank - No All Open Chassis and IP Functionality 20 (NEMA Type 1) converter ratings Programmer Only 1201-HAB 1201-HAP Option Cable Kit - Connect to HIM Cradle Port 0.33 Meters (1.1 Feet) All HIMs not mounted 1 Meter (3.3 Feet) on the converter 3 Meter (9.8 Feet) chassis 9 Meter (29.5 Feet) 1202-H03 1202-H10 1202-H30 1202-H90 Gasket & Enclosure Kits Description Gasket Kits for mounting 1336 REGEN Converter Units in User Supplied IP 54 or 65 (NEMA Type 12 or 4) Encl. 1336 REGEN Brake Example Enclosure Kits for 1336 REGEN Converter IP 20 (NEMA Type 1) Cat. No. Cat. No. Frame B 1336-RF4 Frame C 1336-RF5 Frame D 1336-RF6 Frame B 1336R-AA4 Frame C 1336R-AA5 Frame D 1336R-AA6 AC Drive AC Input Factory Installed Options DC 1336 REGEN Precharge 3% Line Reactor included in REGEN 1321-3R100-B part number 1336R-VB078 1336 REGEN Converter 1336R-VB078-AN Interface Options Cat. Code Description Used with … Human Interface Module, IP 20 (NEMA Type 1) Blank - No Functionality IP 00 (Open) and IP 20 (NEMA Type Programmer Only 1) Drives (Position e) -HAB -HAP 9 Common DC Bus Applications Line Regeneration Solutions Altitude Derating Specifications 100% Electrical 380-480V ac, Three-Phase, +10%/–15% Nominal, 48-62Hz 90-115V ac, Single-Phase, ±10% Nominal, 48-62Hz AC Input Voltage Range: 90% Control Output Specifications Heat SinkTemperature Sensor Contact Output Rating (max.): The two temperature sensors trip if heat temperature exceeds 85°C. Resistive Rating: 15A at 125V ac, 10A at 250V ac, 7A at 24V dc Inductive Rating: 10A at 125V ac, 6A at 250V AC Environmental Specifications Ambient Operating Temperature: IP00 (Open): 0-50°C IP20 (NEMA Type 1): 0-40°C Storage Temperature: All Ratings -40 to +85°C Relative Humidity: 5 to 95% non-condensing Shock: 15G peak for 11ms duration (±1.0 ms) Vibration: 0.152 mm (0.006 in.) displacement, 1G peak ESD Susceptibility, IP20 (NEMA Type 1) Only: 15 kV Protection AC Input Overvoltage Trip: Factory Set to +15% of Nominal Line Voltage Heatsink Over Temperature Trip: 100° C 1336R Converter Overcurrent Trip: Software Overcurrent Limit - Factory Set to 192% of AC Input Current Hardware Overcurrent Limit - Factory Set to 245% of AC Input Current Line Transients: Up to 6000 Volts Peak per ANSI C62.411991 Control Logic Noise Immunity: Showering Arc Transients Up to 1500 Volts Peak Power Ride-Thru: 6 ms at Full Load Control Logic Ride-Thru: 0.5 Sec. Minimum, 2 Sec. Typical Protection - Regenerative DC Bus Supply Mode Bus Overvoltage Trip: 670V dc at 380V ac Input, 850V dc at 480V ac Input Bus Undervoltage Trip: 430V dc at 380V ac Input, 520V dc at 480V ac Input Nominal Bus Voltage: 610V dc at 380V ac Input, 735V dc at 480V ac Input Regenerative DC Bus Supply Operation Only - 380480V AC Input Converter Precharge 10% Line Power Package Rating Converter Heat Sink Unit Reactor Line Filter Total 48A 141W 820W 15W 186W 173W 1335W 78A 193W 1110W 29W 258W 236W 1826W 180A 522W 2664W 58W 474W 317W 4035W Regenerative Brake Operation Only - 380-480V AC Input Rating Converter Converter Heat Sink Precharge Unit 3% Line Reactor Package Total 48A 141W 656W 15W 65W 78A 193W 888W 29W 84W 1194W 180A 522W 2131W 58W 168W 2879W 10 877W % of Rated Amps 80% 0 Altitude 1,000 (3,300) 2,000 (6,600) 3,000 (9,900) 4,000 m (13,200) (ft) Common DC Bus Applications Line Regeneration Solutions 1336 REGEN Converter Unit Mounting Dimensions The dimensions and weights provided in the following drawings are for estimating purposes only. Contact your local Rockwell Automation Sales Office if certified drawings are required. 1336 REGEN Converter Unit - Frames B and C A E Z C D Knockout Diameters ➊ Dual Knockout — 3 Places 28.6/34.9 (1.13/1.38) ➋ Single Knockout — 1 Place 22.2 (0.88) Shipping Weight B Frame — 22.7 kg (50 lbs.) C Frame — 38.6 kg (85 lbs.) Q F P B O N ➋ ➊ ➊ ➊ I J Front Side Bottom Mounting Holes (4) 7.0 (0.28) 7.0 (0.28) 12.7 (0.50) 12.7 (0.50) Frame Reference B A 276.4 (10.88) B 476.3 (18.75) C 225.0 (8.86) D 212.6 (8.37) E 461.0 (18.15) I 181.6 (7.15) J 167.1 (6.58) N 26.5 (1.04) O 163.6 (6.44) P 112.8 (4.44) Q 62.0 (2.44) Z 7.6 (0.30) C 301.8 (11.88) 701.0 (27.60) 225.0 (8.86) 238.0 (9.37) 685.8 (27.00) 181.6 (7.15) 167.1 (6.58) 26.5 (1.04) 182.7 (7.19) 119.2 (4.69) 68.4 (2.69) 7.6 (0.30) Dimensions are in millimeters and (inches) 11 Common DC Bus Applications Line Regeneration Solutions 1336 REGEN Converter Unit - Frame D A E C Z D Knockout Diameters ➊ Dual Knockout — 1 Place 34.9/50.0 (1.38/1.97) ➋ Dual Knockout — 2 Places 62.7/76.2 (2.47/3.00) ➌ Single Knockout — 3 Places 34.9 (1.38) F B Shipping Weight D Frame — 108.9 kg (240 lbs.) Q O P N ➊ ➋ ➌ ➌ I K J Front Mounting Slots (2) 7.0 (0.28) Bottom Side 7.0 (0.28) 12.7 (0.50) 12.7 (0.50) Frame Reference D A B C D E 381.5 1240.0 270.8 325.9 27.94 (15.02) (48.82) (10.66) (12.83) (1.10) F I 1216.2 198.1 (47.88) (7.8) J 131.6 (5.18) K 153.7 (6.05) L 169.4 (6.67) Dimensions are in millimeters and (inches) 12 M 204.5 (8.05) N 52.1 (2.05) O 144.0 (5.67) P Q Z 261.4 343.9 11.94 (10.29) (13.54) (0.47) L M Common DC Bus Applications Line Regeneration Solutions 1336 REGEN Precharge Unit - Frames B and C Knockout Diameters ➊ Dual Knockout — 3 Places 28.6/34.9 (1.125/1.375) Shipping Weight B and C Frame — 9.1 kg (20 lbs.) A C H D E CAT SER 1336R-VB048PRE-AN A LIS Mounting Slots (2) 7.0 (0.28) AC INPUT AC OUTPUT KW 38.4 38.4 DC OUTPUT – VOLTS 460 460 – A PH HZ 48.2 3 50/60 48.2 3 50/60 – – – L1 L2 TED 966X UL ® IN D CONT EQ LIS C ALLEN-BRADLEY REFER TO USER MANUAL FOR INSTALLATION ISNTRUCTIONS ® TED 966X UL ® IN D CONT EQ MADE IN U.S.A. L3 7.0 (0.28) 13 14 12.7 (0.50) R1 S1 T1 12.7 (0.50) F K G B ! DANGER RISK OF SHOCK REPLACE AFTER SERVICING R S T PE PE Interconnection Power Wiring Area Approx. 76.2 x 203.2 x 103.1 (3.00 x 8.00 x 4.06) (H x W x D) Mounting Hole Dia. (2) 7.0 (0.28) N I B and C J L M Bottom Side Front (Cover Removed) Frame Reference ➊ ➊ ➊ A B C D E F G H I J K L M N 203.2 (8.00) 355.6 (14.00) 184.2 (7.25) 152.4 (6.00) 25.4 (1.00) 254.0 (10.00) 317.5 (12.50) 12.7 (0.50) 28.45 (1.12) 50.8 (2.00) 279.4 (11.0) 60.45 (2.38) 33.02 (1.30) 59.44 (2.34) Dimensions are in millimeters and (inches) 13 Common DC Bus Applications Line Regeneration Solutions 1336 REGEN Precharge Unit - Frame D Knockout Diameters ➊ Dual Knockout — 2 Places 62.7/76.2 (2.47/3.00) ➋ Single Knockout — 1 Place 34.9 (1.38) Shipping Weight D Frame — 18.6 kg (41 lbs.) A D E CAT SER 1336R-VB180PRE-AN A LIS Mounting Slots (2) 7.0 (0.28) AC INPUT AC OUTPUT KW 118.7-143.7 118.7-143.7 DC OUTPUT – VOLTS 380-480 380-480 – A PH HZ 180.4 3 50/60 180.4 3 50/60 – – – 1 3 5 L1 L2 L3 12.7 (0.50) TED 966X UL ® IN D C ONT EQ LIS C ALLEN-BRADLEY REFER TO USER MANUAL FOR INSTALLATION ISNTRUCTIONS 7.0 (0.28) C H ® TED 966X UL ® IN D C ONT EQ MADE IN U.S.A. 13 14 R1 12.7 (0.50) S1 T1 F K G B TORQUE TERMINALS TO 275 LB-IN USE 75˚C WIRE ONLY ! DANGER RISK OF SHOCK REPLACE AFTER SERVICING S R T PE PE Interconnection Power Wiring Area Approx. 182.4 x 254.0 x 147.3 (7.18 x 10.00 x 5.80) (H x W x D) Mounting Hole Dia. (2) 7.0 (0.28) ➊ N ➋ O I Front (Cover Removed) Frame Reference D Side L M A B C D E F G H I J K L M N O 254.0 (10.00) 533.4 (21.00) 228.6 (9.00) 203.2 (8.00) 25.4 (1.00) 323.9 (12.75) 482.6 (19.00) 12.7 (0.50) 53.9 (2.12) 98.6 (3.88) 350.0 (13.82) 69.9 (2.75) 31.8 (1.25) 31.8 (1.25) 50.8 (2.00) Dimensions are in millimeters and (inches) 14 J Bottom Common DC Bus Applications Choppers & Dynamic Brakes Braking Solutions - Non-Regenerative Braking solutions protect against unnecessary drive shut-downs due to overvoltage conditions when operating in the regenerative mode. The non-regenerative braking products offering should be utilized in those processes when regenerative energy is dissipated on an occasional or periodic basis. Catalog Number Explanation Position 1-2 3 4 1336 - W B 009 a b c a 1336-WA, WB or WC Brake Chopper Module Product Code Type 1336 - W Brake Chopper Module b Voltage Rating Code Input Voltage A 230V ac B 380/415/460V ac C 575V ac c Continuous Amp Rating Code Voltage 018 070 Standards Compliance The 1336-WA, WB and WC conforms to the following: Conformity to: UL Listed 9 c-UL Listed 9 CE Compliant 9 Rating 375V dc, 18A 230V ac 115 375V dc, 70A 375V dc, 115A 009 750V dc, 9A 035 380/415/460V ac 110 750V dc, 35A 750V dc, 110A 009 935V dc, 9A 035 575V ac 085 935V dc, 35A 935V dc, 85A Description The 1336 Brake Chopper Module includes the following features: y Protective fuses sized to work in conjunction with a crowbar SCR. A sensing circuit within the chopper transistor voltage control isolates the chopper module from the DC bus when an abnormal condition is sensed. y Chopper transistor voltage control (hysteretic voltage comparator) regulates the voltage of the DC bus during regeneration. y A freewheel diode in parallel with the dynamic brake resistor allows any magnetic energy stored in the parasitic inductance of that circuit to be safely dissipated during turn off of the chopper transistor. y Chopper modules can be applied in parallel in a master-follower configuration if the individual current rating is insufficient for the application. y LED indicators: − “DC Power On” indicates when DC power has been applied to the chopper module. − “Brake On” flickers when the chopper module is operating (chopping). Product Selection Dynamic Brake, Chopper Only Kits Description 200-240V ac 380-480V ac 500-600V ac Chopper Rating Cat. No. 18A 1336-WA018 70A 1336-WA070 115A 1336-WA115 9A 1336-WB009 35A 1336-WB035 110A 1336-WB110 9A 1336-WC009 35A 1336-WC035 85A 1336-WC085 15 Common DC Bus Applications Choppers & Dynamic Brakes 1336-WA070, WB035 and WC035 Specifications 241.3 (9.50) Braking Torque & Duty Cycle: Refer to publication 1336-5.65. Input Power: DC power supplied from DC Bus. Brake Fault Contact: (1) N.C. contact, TTL compatible, closed when power is applied to the brake module, open when a brake fault or loss of power occurs. UL/CSA Rating: 1.0 Amps, 125V ac/1.0 Amps, 110V ac/2.0 Amps, 30V dc. 123.4 (4.86) 230.1 (9.06) A–B P\N 151076 REV 01 DC POWER BULLETIN 1336 BRAKING CHOPPER 1336-WB035 SER A 750 VDC 35.0 ADC (RMS) FOR USE WITH 460 VAC A.F. DRIVES CAT BRAKE ON INPUT 177.8 (7.00) 203.2 (8.00) MADE IN U.S.A. CE Certification: Low Voltage EN 60204-1. PREN 50178. (Front) (Side) Initial Contact Resistance: 100mOhms maximum. Operating Temperature: Chopper: -10°C to 40°C (14°F to 104°F) Resistor: -10°C to 50°C (14°F to 122°F) Storage Temperature: Chopper: -10°C to 40°C (14°F to 104°F) Resistor: -10°C to 50°C (14°F to 122°F) Humidity: 5 to 95% non-condensing Atmosphere: Non-corrosive/non-hazardous dust, vapor or gas. Altitude Derating: 1,000 meters (3,300 feet) maximum without derating. Enclosure Type: IP00 (Open) Watts Dissipated: WA018/WB009/WC009: 75W at 100% Duty Cycle WA070/WB035/WC035: 115W at 100% Duty Cycle WA115/WB110/WC085: 190W at 100% Duty Cycle Minimum Brake Resistance (based on peak amps): WA018 = 9.00 Ohms WA070 = 2.30 Ohms WA115 = 1.25 Ohms WB009 = 37.00 Ohms WB035 = 9.00 Ohms GND 1 2 E11 3 4 5 6 E12 5.6 (0.22) Dia. (4 places) 12.7 (0.50) Weight = 4.08 kg (9 .0 lbs) WB110 = 2.50 Ohms WC009 = 46.00 Ohms WC035 = 15.50 Ohms WC085 = 3.00 Ohms (Bottom) 1336-WA115, WB110 and WC085 290.6 (11.44) 239.8 (9.44) 279.4 (11.00) 1336 Chopper Mounting Dimensions DC POWER BULLETIN 1336 BRAKING CHOPPER 1336-WB110 SER A 750 VDC 110.0 ADC (RMS) 460 VAC A.F. DRIVES CAT BRAKE ON INPUT A–B P\N 151076 REV 01 The dimensions and weights provided in the following drawings are for estimating purposes only. Contact your local Rockwell Automation Sales Office if certified drawings are required. 228.6 (9.00) FOR USE WITH MADE IN U.S.A. 304.8 (12.00) 1336-WA018, WB009 and WC009 (Front) 241.3 (9.50) (Side) 104.4 (4.11) 230.1 (9.06) 5.6 (0.22) Dia. (4 places) BRAKE ON INPUT FOR USE WITH A–B P\N 74101-778-XX REV DC POWER BULLETIN 1336 BRAKING CHOPPER 1336-WB009 SER A 750 VDC 9.0 ADC (RMS) 460 VAC A.F. DRIVES CAT 38.1 (1.50) 177.8 (7.00) 203.2 (8.00) MADE IN U.S.A. (Front) (Side) GND Weight = 11.34 kg (25.0 lbs) 5.6 (0.22) Dia. (4 places) 12.7 (0.50) (Bottom) Weight = 3.18 kg (7.0 lbs) (Bottom) 16 Dimensions are in millimeters and (inches) Common DC Bus Applications Choppers & Dynamic Brakes AK DBU Dynamic Brake Unit Catalog Number Explanation Position Number 1-5 AK DBU a 6 7-9 10 11 F 300 N E b c d e a Product Code Type AKDBU Dynamic Braking Unit b Voltage Rating Code Input Voltage Full On Voltage F 600/690V ac 950/1090V dc c Rating Standards Compliance Code Peak Current 300 300A The AK DBU Dynamic Braking Unit conforms to the following: d Conformity to: Approvals & Standards UL Listed ✶ 9 UL 508C c-UL Listed ✶ 9 CAN/CSA-C22.2 No. 14-M91 CE Compliant 9 EN61800-3, EN50178 Enclosure Code Rating Conformal Coating N Open/IP00 No ✶ 600V rating only. e Documentation & Shipping Carton Code User Manual Carton E English Yes Description The AK DBU includes the following features: y 600/690V ac, 300A peak. y PWM chopper IGBT voltage control regulates the DC bus voltage during regeneration. y Overtemperature sensor located in the heat sink for thermal protection of the brake unit with N.C. output contact. − "DC Power On" indicates DC bus voltage greater than 50V dc. − "Brake On" indicates braking current flow. Product Selection AK DBU Dynamic Brake Units Description 950/1090V dc, 300A peak Voltage 600/690V Cat. No. AKDBUF300NE 17 Common DC Bus Applications Choppers & Dynamic Brakes Specifications AK DBU Dimensions Power Ratings Input Voltage: 600V 690V Peak Braking Power: 268 kW 305 kW Min. Brake Resistor Value permitted for Peak Braking Power: 3.2 ohm 3.7 ohm Max. Peak Braking Current with 150 sec. ON time at up to 300 Amp 25% Duty Cycle: Max. Mean RMS Braking Current: 150 Amp Heat Dissipation (Average) at 25% Duty Cycle: 170 W Power Consumption of the Control Circuits: 27 mA Max. DC Bus Voltage at DC+, DC- Terminals: DC 1150V PWM Switching Frequency: 0.67 kHz Capacitance of Internal Snubber: 4µF The dimensions and weights provided in the following drawing are for estimating purposes only. Contact your local Rockwell Automation Sales Office if certified drawings are required. 100.0 (4.00) Minimum BR2 NFPA 70 - US National Electrical Code NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems IEC 146 - International Electrical Code UL and cUL Listed to UL508C and CAN/CSA-C2.2 No. 14-M91 (600V ac only) Marked for all applicable European Directives EMC Directive (89/336/EEC) Emissions: EN 61800-3 Adjustable Speed electrical power drives systems Part 3 Immunity: EN 61800-3 Second Environment, Category C3 Low Voltage Directive (73/23/EEC) EN 50178 Electronic Equipment for use in Power Installations Environmental Specifications 1000 m (3300 ft.) max. without derating. Above 1000 m the derating for the nominal current is 1% per 100 m (330 ft). Degree of Protection: Open/IP00 Ambient Operating Temperature without derating: 0 to 40°C (32 to 104°F) For temperatures higher than 40°C up to a maximum 55°C (131°F), the maximum peak braking current must be derated by 1.5% per °C (0.8% per °F). Storage Temperature: –25 to 55°C (–25 to 131°F) Transportation Temperature: –25 to 70°C (–25 to 158°F), 70°C max. for 24 hours Relative Humidity: 5 to 95% non-condensing Shock: 15G peak for 11ms duration (±1.0 ms) Vibration: 0.152 mm (0.006 in.) displacement, 1G peak 89.0 (3.50) 5.0 (0.20) DC- DC+ BR1 350.0 (13.80) 356.0 (14.00) 310.0 (12.20) Front View Approvals and Standards Compliance 18 50.0 (2.00) 6.50 (0.26) Dia. PE The temperature sensor trips if heat sink temperature exceeds maximum. Heat Sink Temperature Sensor Resistive Rating: 15A at 125V ac, 10A at Contact Output Rating (max.): 250V ac, 7A at 24V dc Inductive Rating: 10A at 125V ac, 6A at 250V ac Altitude: 25.0 (1.00) 32.0 (1.30) Control Output Specifications The DBU is designed to meet the following specifications: 42.0 36.0 36.0 36.0 (1.65) (1.42) (1.42) (1.42) Side View Airflow 80.0 8.0 (3.15) (0.30) 100.0 (4.00) Minimum 215.0 (8.46) 5.0 (0.20) 157.0 (6.18) 225.0 (8.86) Weight = 10.0 kg (22.0 lbs) Required Cooling Airflow = 158 m3/h Dimensions are in millimeters and (inches) Common DC Bus Applications Choppers & Dynamic Brakes 1336-MOD-KA, KB or KC Heavy Duty Dynamic Braking Catalog Number Explanation Position Standards Compliance 1 2 3 1336 - MOD - K B 005 a b c The 1336-MOD-KA, KB and KC conforms to the following: a Conformity to: UL Listed 9 c-UL Listed 9 CE Compliant 9 Product Code Type 1336 - MOD - K Heavy Duty Dynamic Brake Unit b Voltage Rating Code Description The 1336-MOD-KA, KB and KC includes the following features: y All dynamic brakes are internally fused to protect brake components. y Self-contained NEMA Type 1 enclosed assembly y Master-Slave operation when more than one brake is needed to obtain the required braking load. y LED indicators: − “DC Power” indicates the drive DC bus voltage is greater than 40V DC. − “Brake On” when illuminated, indicates the brake is On. y Typical 100% braking torque for 20 seconds. y Typical 20% duty cycle. y A brake fault contact for all brake ratings has been included to provide a remote output signal to a PLC. If a loss of power or a brake malfunction occurs, the N.C. fault contact will open. A separate 115V ac power supply is required. Input Voltage A 230V ac B 380/415/460V ac C 500/575V ac c Brake Rating 7 Code Drive Voltage Brake Rating 200…240V ac 005 380…480V ac 3.7kW (5 Hp) Max. 500…600V ac 200…240V ac 010 380…480V ac 7.5kW (10 Hp) Max. 500…600V ac 380…480V ac 050 500…600V ac 37kW (50 Hp) Max. 7 Multiple chopper kits may be utilized together to obtain higher ratings. Refer to publication 1336-5.65 for further information. Product Selection Dynamic Brake, Complete Kits Description For 200-240V ac Drives Brake Rating 7 3.7 kW (5 Hp) Max. Cat. No. 1336-MOD-KA005 7.5 kW (10 Hp) Max. 1336-MOD-KA010 3.7 kW (5 Hp) Max. 1336-MOD-KB005 For 380-480V ac Drives 7.5 kW (10 Hp) Max. 1336-MOD-KB010 37 kW (50 Hp) Max. 1336-MOD-KB050 3.7 kW (5 Hp) Max. 1336-MOD-KC005 For 500-600V ac Drives 7.5 kW (10 Hp) Max. 1336-MOD-KC010 37 kW (50 Hp) Max. 1336-MOD-KC050 7 Multiple chopper kits may be utilized together to obtain higher ratings. Refer to Publication 1336-5.65 for information. 19 Common DC Bus Applications Choppers & Dynamic Brakes 1336-MOD-KA050, KB050 and KC50 Specifications 100% torque for 20 seconds (typical) Duty Cycle: 20% (typical) Input Power: DC power supplied from DC Bus. Customer supplied 115V ac, single-phase, 50/60 Hz required for KB050 & KC050 brake operation. Enable Signal: 50 mA, Fan Power: 600 mA Optional Brake Fault Contact: (1) N.C. contact, TTL compatible, closed when 115V ac is applied, open when a brake fault or loss of power occurs. Customer supplied 115V ac, 50 mA required for KA005, KB005, KC005, KA010, KB010 & KC010 optional brake fault contact monitoring. UL/CSA Rating: 0.6A at 125V ac, 0.6A at 110V ac, 2.0A at 30V ac. Initial Contact Resistance: 50 mΩ maximum. 14.3 (0.56) 17.3 (0.68) 592.3 (23.32) 609.6 (24.00) BULLETIN 1336 DYNAMIC BRAKE 1336ÐMODÐKC050 SER B 935 VDC. 10 ADC (RMS) FOR USE WITH 500/600 -10°C to 50°C (14°F to 122°F) Humidity: 5% to 95% non-condensing Atmosphere: NEMA Type 1 - Cannot be used in atmospheres having corrosive or hazardous dust, vapor or gas. DC POWER CAT INPUT Temperature: BRAKE ON AÐB P\N 151081 REV 01 Braking Torque: VAC BULL. 1336 A.F. DRIVES (OUTPUT) HEAT DISSIPATION 3750 WATTS MAXIMUM MADE IN U.S.A. 304.8 (12.00) Altitude Derating: 1,000 meters (3,300 feet) maximum without derating. Enclosure Type: KA005, KB005, KC005 - IP20 (NEMA Type 1) KA010, KB010, KC010 - IP20 (NEMA Type 1) KB050, KC050 - IP00 (Open) 8.4 (0.33) Dia. 6 Places 12.7 (0.50) 17.3 (0.68) 381.0 (15.00) 406.4 (16.00) 247.7 (9.75) 12.7 (0.50) Front View 1336-MOD-KA, KB and KC Mounting Dimensions The dimensions and weights provided in the following drawings are for estimating purposes only. Contact your local Rockwell Automation Sales Office if certified drawings are required. 1336-MOD-KA005-KA010, KB005-KB010 and KC005-KC010 14.3 (0.56) Dia. 7.1 (0.28) Dia 4 Places Side View Weight = 33.8 kg (75.0 lbs) 79.3 (3.12) Conduit Entry 28.5 (1.12) Dia. 50.8 (2.00) 50.8 (2.00) 152.4 (6.00) Bottom View 6.4 (0.25) Dimensions are in millimeters and (inches) 425.4 (16.75) 441.4 (17.38) FOR USE WITH 380/460 ADB P\N 151076 REV 01 BULLETIN 1336 DYNAMIC BRAKE CAT 1336-MOD-KB005 SER C INPUT 680-750 VDC. 2.5 ADC (RMS) DC POWER Side View BRAKE ON VAC BULL. 1336 A.F. DRIVES (OUTPUT) HEAT DISSIPATION 375 WATTS MAXIMUM MADE IN U.S.A. Front View 30.0 (1.18) 2 Places 133.4 (5.25) 193.5 (7.62) 9.7 (0.38) 174.5 (6.87) Bottom View Weight = 6.8 kg (15 .0 lbs) 50.8 (16.75) Conduit Entry 28.5mm (1.12") Dia. 20 50.8 (2.00) 50.8 (2.00) 46.0 (1.81) Common DC Bus Applications DC Input Drives/Power Components DC Input Drives For PowerFlex 700/700S DC Input Drives product solution, refer to the PowerFlex Family of Drives Catalog (publication D115-CA001). Power Components Line Reactor Selection for the SCR Bus Supply For line reactor specifications, refer to publication 1321-TD001. 400V, 50 Hz Line Reactor Selection Range of DC Amp Sum of Connected Drives and Supply Transformer Used ✶ DC Amp Sum 1000 kVA, 1250 kVA, 1600 kVA, 2500 kVA, 3000 kVA, of Connected 630 kVA, 5%, 800 kVA, 5%, 43 mH 35 mH 5.5%, 31 mH 6%, 27 mH 6%, 22 mH 6.5%, 16 mH 6.5%, 13 mH Drives (Amps) up to 203 204-255 256-319 320-407 408-509 510-635 636-763 764-938 120-150 120-154 120-160 151-203 155-203 161-203 204-255 - 204-255 - 204-255 - 120-165 120-168 120-173 120-176 Line Reactor Induct. (mH) 230 Cat. No. 7 1321-3R160-C 166-203 169-203 174-203 177-203 150 1321-3R160-B 204-206 204-209 204-219 204-224 185 1321-3R200-C 207-255 210-255 - - 220-255 225-255 110 1321-3R200-B 256-260 256-275 150 1321-3RB250-C 256-319 256-319 256-319 256-319 256-319 261-319 276-319 90 1321-3RB250-B 320-335 320-370 320-390 320-407 320-407 320-407 320-407 75 1321-3RB320-B 336-407 371-407 391-407 408-425 408-450 426-509 451-509 408-509 510-540 - 510-580 636-763 764-800 510-635 636-763 764-870 408-480 481-509 408-509 - 510-538 510-590 539-635 591-635 636-763 764-800 636-660 661-763 764-838 408-509 510-635 636-763 764-900 901-938 408-509 510-635 636-763 764-938 - 40 1321-3RB320-A 60 1321-3RB400-B 30 1321-3RB400-A 50 1321-3R500-B 25 1321-3R500-A 40 1321-3R600-B 20 1321-3R600-A 29 1321-3R750-B 15 1321-3R750-A ✶ The inductance value of the supply transformers includes 2.5 µH for 10 meter (131 feet) feeder cable. 7 The number in the catalog string represents the fundamental AC current rating of the reactor. 21 Common DC Bus Applications Power Components 480V, 60 Hz Line Reactor Selection Range of DC Amp Sum of Connected Drives and Supply Transformer Used ✶ DC Amp Sum 1000 kVA, 1250 kVA, 1600 kVA, 2500 kVA, 3000 kVA, of Connected 630 kVA, 5%, 800 kVA, 5%, 51 mH 41 mH 5.5%, 36 mH 6%, 32 mH 6%, 26 mH 6.5%, 19 mH 6.5%, 16 mH Drives (Amps) up to 203 204-255 256-319 320-407 408-509 510-635 636-763 764-938 120-140 120-144 120-150 120-155 120-160 120-165 120-170 Line Reactor Induct. (mH) 230 Cat. No. 7 1321-3R160-C 141-203 145-203 151-203 156-203 161-203 166-203 171-203 150 1321-3R160-B - - - - 204-209 204-214 204-218 185 1321-3R200-C 204-255 204-255 204-255 204-255 210-255 215-255 219-255 110 1321-3R200-B - - - - - - 256-260 150 1321-3RB250-C 256-290 256-319 256-319 256-319 256-319 256-319 261-319 90 1321-3RB250-B 291-319 - - - - - - 45 1321-3RB250-A - 320-340 320-360 320-380 320-407 320-407 320-407 75 1321-3RB320-B 320-407 341-407 361-407 381-407 - - - 40 1321-3RB320-A - - 408-420 408-450 408-490 408-509 408-509 60 1321-3RB400-B 408-440 408-509 421-509 451-509 491-509 - - 30 1321-3RB400-A - - - - 510-540 510-620 510-635 50 1321-3R500-B 510-560 510-535 510-600 510-635 541-635 621-635 - 25 1321-3R500-A - - - - - 636-700 636-763 40 1321-3R600-B - 636-680 636-763 636-763 636-763 701-763 - 20 1321-3R600-A - - - - - 764-840 764-938 29 1321-3R750-B - - - 764-938 764-938 841-938 - 15 1321-3R750-A ✶ The inductance value of the supply transformers includes 2.5 µH for 10 meter (131 feet) feeder cable. 7 The number in the catalog string represents the fundamental AC current rating of the reactor. 600V, 60 Hz Line Reactor Selection Range of DC Amp Sum of Connected Drives and Supply Transformer Used ✶ DC Amp Sum 1000 kVA, 1250 kVA, 1600 kVA, 2500 kVA, 3000 kVA, of Connected 630 kVA, 5%, 800 kVA, 5%, 78 mH 62 mH 5.5%, 55 mH 6%, 48 mH 6%, 38 mH 6.5%, 27 mH 6.5%, 21 mH Drives (Amps) up to 203 204-255 256-319 320-407 408-509 510-635 636-763 764-938 120-155 120-164 120-175 130-180 130-190 130-199 Induct. (mH) 230 Cat. No. 7 1321-3R160-C 156-203 165-203 176-203 181-203 191-203 200-203 - 150 1321-3R160-B - - 204-209 204-230 204-230 204-255 204-255 185 1321-3R200-C 204-255 204-255 210-255 204-255 210-231 - - 110 1321-3R200-B - - - - 256-270 256-295 256-319 150 1321-3RB250-C 1321-3RB250-B 256-280 256-319 256-319 256-319 261-319 296-319 - 90 281-319 - - - - - - 45 1321-3RB250-A - 320-340 320-360 320-390 320-407 320-407 320-407 75 1321-3RB320-B 320-407 341-407 361-407 391-407 - - - 40 1321-3RB320-A - - - - - - 408-425 105 1321-3RB400-C - - - 408-440 408-509 408-509 426-509 60 1321-3RB400-B 408-450 408-509 408-509 441-509 - - - 30 1321-3RB400-A 510-545 510-635 510-635 50 1321-3R500-B - 510-560 510-600 510-635 546-635 - - 25 1321-3R500-A - - - - - 636-740 636-763 40 1321-3R600-B - - - 636-750 636-763 741-763 - 20 1321-3R600-A - - - - - 764-640 764-938 29 1321-3R750-B - - - - 841-938 841-938 - 15 1321-3R750-A ✶ The inductance value of the supply transformers includes 2.5 µH for 10 meter (131 feet) feeder cable. 7 The number in the catalog string represents the fundamental AC current rating of the reactor. 22 140-203 Line Reactor Common DC Bus Applications Power Components 690V, 50 Hz Line Reactor Selection Range of DC Amp Sum of Connected Drives and Supply Transformer Used ✶ DC Amp Sum 1000 kVA, 1250 kVA, 1600 kVA, 2500 kVA, 3000 kVA, of Connected 630 kVA, 5%, 800 kVA, 5%, 123 mH 95 mH 5.5%, 86 mH 6%, 75 mH 6%, 59 mH 6.5%, 42 mH 6.5%, 33 mH Drives (Amps) up to 203 204-255 256-319 320-407 408-509 510-635 636-763 764-938 130-157 130-162 130-170 140-180 Line Reactor Induct. (mH) Cat. No. 7 2x150 1321-3R160-B‡ 186-203 230 1321-3R160-C - 150 1321-3R160-B 2x110 1321-3R200-B‡ 221-255 185 1321-3R200-C - 110 1321-3R200-B 2x90 1321-3RB250-B‡ 261-319 150 1321-3RB250-C - 90 1321-3RB250-B - 130-150 150-185 130-175 151-190 158-203 163-203 171--203 181-203 176-203 191-203 - - - - - - - - - 204-210 204-220 204-206 204-230 204-245 204-255 204-255 211-255 207-255 231-255 246-255 - - - - - - - - - 256-260 - 256-260 256-270 256-290 256-319 256-319 256-280 261-319 271-319 291-319 - - 281-319 - - - - - - 45 1321-3RB250-A - - - - 320-360 320-407 320-407 125 1321-3RB320-C 1321-3RB320-B - 320-360 320-380 320-407 361-407 - - 75 320-407 361-407 381-407 - - - - 40 1321-3RB320-A - - - - - 408-465 408-509 105 1321-3RB400-C - - 408-414 408-450 408-509 466-509 - 60 1321-3RB400-B - 408-500 415-509 451-509 - - - 30 1321-3RB400-A - - - - - 510-520 510-580 85 1321-3R500-C - - - 510-538 510-570 521-635 581-635 50 1321-3R500-B - - 510-540 539-635 571-635 - - 25 1321-3R500-A - - - - - - 636-650 65 1321-3R600-C 1321-3R600-B - - - - - 636-763 651-763 40 - - - - 661-763 - - 20 1321-3R600-A - - - - - - 764-780 48 1321-3R750-C - - - - - 764-850 781-938 29 1321-3R750-B - - - - - 551-938 - 15 1321-3R750-A ✶ The inductance value of the supply transformers includes 2.5 µH for 10 meter (131 feet) feeder cable. 7 The number in the catalog string represents the fundamental AC current rating of the reactor. ‡ Connect two reactors in series. Line Reactor and Filter Selection for 1336 REGEN Package 1321 Line Reactor - 380…480V ac 3% Line Reactor for Regenerative Brake Applications IP 00 (Open) No Enclosure Cat. No. 10% Line Reactor for DC Bus Supply Applications IP20 (NEMA Type 1) General Purpose Rated Amps Cat. No. IP 00 (Open) No Enclosure Rated Amps Cat. No. IP20 (NEMA Type 1) General Purpose Rated Amps Cat. No. Rated Amps 1321-3R55-B 48 1321-3RA55-B 48 1321-3LR048-B 48 1321-3LRA048-B 48 1321-3R100-B 78 1321-3RA100-B 78 1321-3LR078-B 78 1321-3LRA078-B 78 1321-3R200-B 180 1321-3RA200-B 180 1321-3LR180-B 180 1321-3LRA180-B 180 EMI Filters - 380… 480V ac Nominal Rating IP00 Open Style IP20 (NEMA Type 1) Cat. No. Cat. No. 48 1321-VB048FLT-AN 1321-VB048FLT-AA 78 1321-VB078FLT-AN 1321-VB078FLT-AA 180 1321-VB180FLT-AN 1321-VB180FLT-AA Amps 23 Common DC Bus Applications Power Components Line Reactor Dimensions The dimensions and weights provided in the following drawings are for estimating purposes only. Contact your local Rockwell Automation Sales Office if certified drawings are required. 1321 3% Line Reators Open Type (IP00) TOP SIDE END A D B C ® ® RL-20002 Manufactured By MTE Corp. Menomonee Falls, WI A1 CAT 1321-3R200-B PART# 0.11mH 200AMPS 1th=300A A2 B1 ® E66214 180-36 3 PHASE REACTOR 600V MAX 50/60 Hz B2 C1 C2 E G Mounting Hole NEMA Type 1 (IP20) C ® ® RL-20002 Manufactured By MTE Corp. Menomonee Falls, WI A1 A2 CAT 1321-3R200-B PART# 0.11mH 200AMPS 1th=300A B1 B2 ® E66214 180-36 3 PHASE REACTOR 600V MAX 50/60 Hz C1 C2 B B D D C F Important: Allow 152.4 (6.00) on all sides for proper heat dissipation. All Dimensions in Millimeters and (Inches) — All Weights in Kilograms and (Pounds) 24 Rating A B C D E F G Mounting Hole Shipping Weight 48A Open (IP 00) 229.0 (9.00) 118.0 (4.65) — 76.0 (3.00) 80.0 (3.15) — 187.0 (7.36) 9.50 (0.38) 12.2 (27) 78A Open (IP 00) 274.3 (10.80) 144.0 (5.67) — 92.0 (3.62) 93.0 (3.66) — 210.0 (8.27) 12.7 (0.50) 23.1 (51) 180A Open (IP00) 274.3 (10.80) 210.0 (8.27) — 92.0 (3.62) 112.0 (4.41) — 211.0 (8.31) 14.22 (0.56) 30.4 (67) 48/78A NEMA Type 1 (IP 20) — 330.0 (13.00) 330.0 (13.00) 279.0 (11.00) — 336.0 (13.23) — — 14.5/25.4 (32/56) 180A NEMA Type 1 (IP20) — 330.0 (13.00) 330.0 (13.00) 279.0 (11.00) — 336.0 (13.23) — — 32.7 (72) Common DC Bus Applications Power Components 1321 10% Line Reators Open Type (IP00) TOP A D E B C ® CAT 1321-3LR180-B PART# 0.430mH 180AMPS lth-270A 9730 RL-18004 Manufactured By MTE Corp. Menomonee Falls, WI R1 F R2 S1 END C E ® G SIDE ® E66214 180-36 3 PHASE REACTOR 600V MAX 50/60 Hz S2 T1 T2 J Mounting Hole 48A NEMA Type 1 (IP20) C ® ® RL-18004 Manufactured By MTE Corp. Menomonee Falls, WI R1 R2 CAT 1321-3LR180-B PART# 0.430mH 180AMPS lth-270A 9730 S1 S2 ® E66214 180-36 3 PHASE REACTOR 600V MAX 50/60 Hz T1 T2 B B D D H C 78/180A NEMA Type 1 (IP20) B D H Mounting Hole J Important: Allow 152.4 (6.00) on all sides for proper heat dissipation. All Dimensions in Millimeters and (Inches) — All Weights in Kilograms and (Pounds) Rating A B C D E F G H J Mounting Hole Shipping Weight 48A Open (IP00) 304.8 (12.00) 207.3 (8.16) 279.4 (11.00) 92.2 (3.63) 68.3 (2.69) 114.3 (4.50) 156.5 (6.16) — 215.9 (8.50) 9.7 x 19 (0.38 x 0.75) Slot 36.3 (80) 78A Open (IP00) 304.8 (12.00) 232.7 (9.16) 279.4 (11.00) 92.2 (3.63) 68.3 (2.69) 139.7 (5.50) 181.9 (7.16) — 215.9 (8.50) 9.7 x 19 (0.38 x 0.75) Slot 59.0 (130) 180A Open (IP00) 304.8 (12.00) 292.4 (11.51) 368.3 (14.50) 116.8 (4.60) 94.0 (3.70) 184.2 (7.25) 254.3 (10.01) — 317.5 (12.50) 14.22 (0.56) 136.0 (300) 48A NEMA Type 1 (IP20) — 330.2 (13.00) 330.0 (12.99) 279.0 (10.98) — — — 335.8 (13.22) — — 38.6 (85) 78A/180A NEMA Type 1 (IP20) — 609.6 (24.00) — 434.9 (17.12) — — — 432.0 (17.00) 467.0 (18.38) 11.2 x 17.6 (0.44 x 0.69) Slot 61.2/160.0 (135/353) 25 Common DC Bus Applications Power Components 1321 Power Line Filter Top All ratings are Open (IP00). 279.4 (11.00) 279.4 (11.00) 8.0 (0.32) Dia. 4 Places 254.0 (10.00) 26 304.8 (12.00) 330.2 (13.00) End Side Common DC Bus Applications Reference Materials Reference Materials The following reference documentation is available online at http://www.rockwellautomation.com/literature. For: 1336-WA/WB/WC Brake Chopper Module Refer to: Publication Number Installation Instructions 1336-5.65 1336-MOD-KA/KB/KC Heavy Duty Dynamic Braking Installation Instructions 1336-5.64 AK DBU Dynamic Braking Unit AK DBU Dynamic Braking Unit 600/690 VAC User Manual AKDBU-UM001… 20S SCR Bus Supply PowerFlex SCR Bus Supply User Manual 20S-UM001… 20T Diode Bus Supply PowerFlex Diode Bus Supply User Manual 20T-UM001… PowerFlex PowerFlex PowerFlex PowerFlex PowerFlex 700 User Manual 700 Series B User Manual 70/700 Reference Manual 700 Technical Data Dynamic Braking Resistor Calculator 20B-UM001… 20B-UM002… PFLEX-RM001… 20B-TD001… PFLEX-AT001… PowerFlex 700S Drive (Frames 1 through 6) PowerFlex PowerFlex PowerFlex PowerFlex PowerFlex 700S – Phase I Control User Manual 700S – Phase II Control User Manual 700S Reference Manual 700S Technical Data Dynamic Braking Resistor Calculator 20D-UM001… 20D-UM006… PFLEX-RM002… 20D-TD001… PFLEX-AT001… PowerFlex 700S Drive (Frames 9 through 11) PowerFlex PowerFlex PowerFlex PowerFlex PowerFlex PowerFlex 700S Installation Manual 700S – Phase I Control User Manual 700S – Phase II Control User Manual 700S Reference Manual 700S Technical Data Dynamic Braking Resistor Calculator PFLEX-IN006… 20D-UM001… 20D-UM006… PFLEX-RM002… 20D-TD001… PFLEX-AT001… PowerFlex 700 Drive* PowerFlex 700 Ser. B Drive* *Standard and Vector Control. 1336 REGEN Drive Line Regeneration Package User Manual 1336 REGEN-5.0 1321 Line Reactor & Isolation Transformers Line Reactor and Isolation Transformer Technical Data 1321-TD001… 27 PowerFlex is a registered trademark of Rockwell Automation, Inc. www.rockwellautomation.com Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA,Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium,Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong,Tel: (852) 2887 4788, Fax: (852) 2508 1846 Publication DRIVES-SG001B-EN-P – September, 2005 Supersedes DRIVES-SG001A-EN-P dated April, 2005 Copyright © 2005 Rockwell Automation, Inc.All rights reserved. Printed in USA.